Sei sulla pagina 1di 6

SAI COND

CHILLER TISTING REPORT


COSTOMER: DAIKIN SERIAL NO.
PROJECT: B 304 - 240 HP MUWMP BY2 MFG. NO:
CHILLER: NO. 1 DATE: 24 OCTBER 2008

DATA: PERFORMANCE TESTING RESULT HOURLY READING


STARTING 12 %LOAD 40%LOAD 70%LOAD 100%LOAD 1 2 3

COMP. AMP.
LINE. 1 59 88 139 153 145
LINE. 2
LINE. 3
COMP. VOLT.
LINE. 1 480 480 478 478 476
LINE. 2
LINE. 3

TEMP./ PRESS.
B1- INLET. EVAP. 25.5 24.5 22.5 16.2 14.2 12.1
B2- OUTLET. EVAP 24 22 19 11.3 9 6.5
B3- INLET. COND. 26 27 29.2 30.5 31 31.2
B4- OUTLET. COND. 27 30 32.7 35.6 36.3 36.4
B5- DISCH. TEMP 33 40.5 46 57 58.3 59
B7- HIGH PRESS. 14.9 15.5 16.3 17.3 19 19.1
B8- LOW PRESS. 7 5.7 5 4.3 4.2 4.2
FUNCTIONAL TEST
MECHANICAL DEVICES DESIGN ELECTRONIC DEVICES DESIGN TEST
SETTING COMP. 1 COMP. 2 PARAMETER COMP. 1
HIGH PRESSURE SW 22 BAR OK HIGH PRESS.TRANSDUCER 21 BAR OK
LOW “ “ 2.5 BAR OK LOW “ “ 2.8 BAR OK
DISCH. TEMP. SW 120 C DISCH. TEMP 90 C
ANTIFREEZE 5.5 C ANTIFREEZE 3.3 C OK
COND.FLOW SWITCH OFF MOTOR
COOLER FLOW SWITCH “
SAI COND
CHILLER TESTING REPORT
COSTOMER: DAIKIN SERIAL NO.
PROJECT: B 304 - 240 HP MUWMP BY2 MFG. NO:
CHILLER : NO. 2 DATE. 24 OCTBER 2008

DATA: PERFORMANCE TESTING RESULT HOURLY READING

COMP. AMP. STARTING 12 %LOAD 40%LOAD 70%LOAD 100%LOAD 1 2 3


LINE. 1
LINE. 2 60 88 140 152 146 146
LINE. 3
COMP. VOLT
LINE. 1
LINE. 2 480 479 480 478 478 478
LINE. 3
TEMP./ PRESS.
B1- INLET. EVAP. 24.7 21.1 19.3 15.8 13.2 12.9
B2- OUTLET. EVAP 19.2 18.6 16.7 11.2 8.9 6.9
B3- INLET. COND. 25.5 27.8 29.1 30.6 33 32
B4- OUTLET. COND. 26.6 30.6 32.5 34.5 37 36.5
B5- DISCH. TEMP 30.5 35.6 41.2 50.1 55.2 58.3
B7- HIGH PRESS. 14.8 18.4 16.6 17.2 17.7 17.3
B8- LOW PRESS. 6.2 5.3 4.5 4.3 4.2 4.1

FUNCTIONAL TEST
MECHANICAL DEVICES DESIGN ELECTRONIC DEVICES DESIGN COMP. 1
SETTING COMP. 1 COMP. 2 PARAMETER
HIGH PRESSURE SW 22 BAR OK HIGH PRESSURE TRANSDUCER 21 BAR OK
LOW “ “ 2.5 BAR OK LOW “ “ 2.8 BAR OK
DISCH. TEMP. SW 120 C DISCH. TEMP 90 C
ANTIFREEZE 6 ANTIFREEZE 3.3 C OK
COND.FLOW SWITCH OFF MOTOR
COOLER FLOW SWITCH “
SAI COND
CHILLER TESTING REPORT
CLIENT: DAIKIN COMPRESSOR. S/N. 8301002 MODEL/SERIAL NO:
PROJECT: B 299 MUWMP 180 BY2 CONDENSER. S/N. 1076036 MFG. NO: CO69J08 DOO97
CHILLER NO: 1 SINGLE COMP. EVAPORATOR.S/N. 3080223733 DATE: 3:30 PM 9/23/2008

DATA PERFORMANCE TESTING RESULT LOAD / HOURLY READING


25%LOAD 40%LOAD 70%LOAD 100%LOAD 1 2 3 4
COMP.AMP.
LINE. 1 119 136 207 228 223 215 215 218
LINE. 2 112 134 212 232 229 220 224 223
LINE. 3 113 135 218 234 228 219 221 221
COMP. VOLT
LINE. 1 458 458 458 458 458 458 458 458
LINE. 2 458 458 458 458 458 458 458 458
LINE. 3 459 459 459 459 459 459 459 459
TEMP./ PRESS.
B1. INLET. EVAP. 25 22.8 21.6 19.4 16.6 13.8 12.1 11.5
B2. OUTLET. EVAP. 23 19.8 17.8 15 11.8 9.0 7.3 6.7
B3. INLET. COND. 26.6 19.5 30.9 32.8 32.8 32 33 34
B4. OUTLET. COND. 28.6 32.3 34.5 37 37 36 36.7 37
B5. D/T. TEMP 48 50.9 52.7 57 61.5 64.5 65.3 67.3
B7. HIGH. PRESS. 16.5 17.9 20 20.2 20 19.3 19.9 20.0
B8. LOW. PRESS 7.6 6.7 5.5 5.0 4.7 4.4 4.1 3.8

DESIGN FUNCTIONAL TEST


MECHANICAL DEVICES SETTING COMP.NO.1 ELECTRONIC DEVICES PARAMETER COMP. 1
HIGH PRESSURE SW. 22 BAR OK HIGH PRESSURE TRANSDUCER 21 BAR OK
LOW PRESSURE SW. 2.5 BAR OK LOW PRESSURE TRANSDUCER 2.8 BAR OK
DISC.TEMP. SW 120 C OK DISC . TEMP 95 C OK
ANTIFREEZE 3.3 C OK ANTIFREEZE 3.3 C OK
COOLER FLOW SW. REMOVE JP. OK COND. FLOW SW. REMOVE JP. OK
SAI COND
CHILLER TESTING REPORT
CLIENT: DAIKIN COMPRESSOR. S/N. 8501001 MODEL/SERIAL NO:
PROJECT: B 299 MUWMP 180 BY2 CONDENSER. S/N. 1076037 MFG. NO. CO7OJ08/DOO98
CHILLER NO: 2 SINGLE COMP. EVAPORATOR. S/N. 3080223732 DATE: 10:30 AM 9/23/2008

DATA PERFORMANCE TESTING RESULT LOAD / HOURLY READING


25%LOAD 40%LOAD 70%LOAD 100%LOAD 1 2 3 4
COMP.AMP.
LINE. 1 102 120 185 208 207 206
LINE. 2 105 124 187 210 212 212
LINE. 3 102 123 189 211 211 211
COMP. VOLT
LINE. 1 458 457 457 457 455 455
LINE. 2 459 458 458 458 457 457
LINE. 3 458 458 458 458 457 457
TEMP./ PRESS.
B1. INLET. EVAP. 22.4 21.6 20.5 18.7 16.4 13.3 12.6 12.1
B2. OUTLET. EVAP. 21.7 17.5 15.8 13.6 11.4 8.4 7.7 7.3
B3. INLET. COND. 24.3 28.1 29.3 31.3 32.8 33 33.5 33.4
B4. OUTLET. COND. 26.4 31.2 33.2 35.8 27.3 37.4 37.9 38
B5. D/T. TEMP 29.7 37.4 40.7 45.7 51.4 56.5 56.9 56.9
B7. HIGH. PRESS. 14.1 15.7 17.4 18.3 18.1 18.4 18.5 18.5
B8. LOW. PRESS 7.2 6.3 5.1 4.8 4.5 4.3 4.3 4.2

DESIGN FUNCTIONAL TEST


MECHANICAL DEVICES SETTING COMP.NO.1 ELECTRONIC DEVICES PARAMETER COMP. 1
HIGH PRESSURE SW. 22 BAR OK HIGH PRESSURE TRANSDUCER 21 BAR OK
LOW PRESSURE SW. 2.5 BAR OK LOW PRESSURE TRANSDUCER 2.8 BAR OK
DISC.TEMP. SW 120 C OK DISC . TEMP 95 C OK
ANTIFREEZE 3.3 C OK ANTIFREEZE 3.3 C OK
COOLER FLOW SW. REMOVE JP. OK COND. FLOW SW. REMOVE JP. OK