4-1
Design Guidelines Handbook
How to use these tables
The following assumptions were made to
a) Determine the panels service surcharge
elaborate these tables:
load (governing local codes must be use for
each case).
a) Only 61.0 cm (2 ft) wide AAC reinforced
b) Determine the design span length, as shown
panels are considered.
in figure:
b) AAC cover for both compression and Panel Length, l
e) Flexure, shear, deformation, anchorage and c) Refer to design tables with service
cracking control have been all considered in surcharge distributed load to find the panel
calculating these tables. thickness.
Two different design tables are provided for
f) In order to perform deformation calculations, this purpose: One design table for GB3.3/
the following load proportions was used: 0.6 AAC class and one design table for
GB4.4/0.7 AAC class. When deciding the
Surcharge loads shown on tables are AAC class to use, its important to consider
assumed to be 60% dead load and 40% live the following facts:
load (self-weight of the panel is not included on
surcharge loads). u GB3.3/0.6 AAC class panels have lower
load bearing capacities than GB4.4, but
From the superimposed dead load, 50% is perform better under thermal or fire
assumed to be applied before the construction requirements.
of adjoining members and 50% after this
occurs. u GB4.4/0.7 AAC class panels have greater
load bearing capacities but lower thermal
g) Although the surcharge loads shown in and fire endurance properties although they
these tables are maximum allowable, when perform better under acoustic requirements.
distributed loads over 153 psi are required
(shaded in tables), Contecs Technical An example of how to look for an AAC panel
Department must be consulted to review is to determine the thickness of a panel
the calculations. needed to meet the following requirements:
Design tables for cases not fallen within the u Design length, ld = 10 ft
considerations shown above, are available
upon request to Contecs Technical u AAC class is GB4.4/0.7
Department.
u Service load = 90 psi
4-3
Design Guidelines Handbook
Table 4.2 Maximum service loads for Contec AAC reinforced panels
4-4
Design Guidelines Handbook
4.2 Masonry (see ACI 530-95, Section 5.1). In order to apply
this design philosophy, the following assumptions
are made:
Contec masonry construction consists of AAC wall
units (blocks), bonded together with thin-bed
u As explained above, AAC masonry is
adhesive mortar, to build load bearing and non-
considered as unreinforced masonry; therefore,
load bearing walls.
tensile resistance of masonry is taken into
consideration, and the contribution of
The masonry units manufactured by Contec are
reinforcing steel (if any, to control the effects of
solid, and therefore can be used for unreinforced
movements from temperature changes and
masonry construction. Design tables calculated
shrinkage) is neglected.
for Contec masonry products, to be used for
unreinforced wall construction are provided in this
u It is assumed that structural materials follow
section.
Hooke´s Law, i.e., deformations and strains are
linearly proportional to the loads and stresses.
4.2.1 Analysis and design
fundamentals u All materials are homogeneous and isotropic.
The distinction between walls and columns is The design methodology should also ensure that
relevant because of the specific requirements there is an adequate margin of safety against a
specified for columns by ACI 530-95. This chapter serviceability limit being reached. Normally, an
is intended to describe a design procedure for adequate margin may be assumed to exist when
masonry walls only. the design satisfies the requirements for allowable
stresses.
The design procedure is based upon allowable Strength limits for masonry walls are described
stress method, in which the effect of service loads briefly in the following sections.
on structural members permits an elastic analysis
4-5
Design Guidelines Handbook
w AXIAL COMPRESSION w BEARING
In all cases, a minimum eccentricity is used in As indicated by ACI 530-95 (Section 5.12.3),
order to account for construction imperfections. the allowable bearing stress is taken as 25%
The effect of the geometry of the element and of the specified compressive strength of
the stability of the material (buckling) is also masonry.
considered. For stress distribution within the wall due to the
application of concentrated loads, an angle of
w FLEXURE 45° is suggested by ACI 530/95. However, as
The allowable tensile stress is calculated based a general rule, for computing compressive
on the Modulus of Rupture of the material. A stress for walls laid in running bond pattern,
value of 80 psi for MOR is considered. Buckling concentrated loads with uniform spacing can
is also checked. be considered to have the same effect as
uniform loads along the entire length of the wall
w AXIAL-FLEXURE when their spacing is less than or equal to the
The combination of effects of axial and flexural width of bearing plus four times the wall
stresses is considered using the unity thickness and the distance of the first and last
interaction equation (ACI 530-95, Section concentrated load from the edge of the wall is
6.3.1). Buckling effect shall also be considered less than or equal to one half of the maximum
in calculation of allowable compressive stress. load spacing described.
The computed tensile stress shall not exceed
the allowable tensile stress. For allowable For openings in masonry, recommendations of
tensile stress, a value of 24 psi is considered. ACI 530-95 Masonry Designers Guide shall
be considered.
w SHEAR
ACI 530-95 (Section 6.5.2) specifies limits for It is important to notice that ACI 530-95 (Section
shear stresses acting on a masonry wall 5.6) states that, for beams and lintels providing
element. However, these stresses are defined support to unreinforced masonry elements,
for normal concrete and they are not applicable deflections due to dead plus live loads shall
for AAC masonry walls. Therefore, to define not exceed L/600 ratio nor 7.5 mm (0.3 in).
the allowable shear stresses, DIN 1053, 4.2.3 Design Tables
Masonry of Simplified Design is used.
4-6
Design Guidelines Handbook
This section includes design tables for AAC
unreinforced masonry walls, which are intended
to help the designer obtain the maximum
horizontal or vertical allowable service load to be
applied on them.
4-7
Design Guidelines Handbook
Table 4.3 Allowable axial surcharge loads for Contec AAC
unreinforced masonry (kips/ft).
Contec GP2/0.5 Block,
t = 6 in (nominal).
Wall height Eccentricity (in)
h' (ft) 0.00 0.25 t/10=0.59 0.75 t/6=0.98 1.25 1.50 1.75 2.00
3.0 6.101 5.190 4.276 3.950 3.553 3.188 2.908 2.186 1.648
3.5 6.040 5.153 4.251 3.929 3.535 3.174 2.896 2.186 1.648
4.0 5.971 5.111 4.222 3.904 3.515 3.158 2.883 2.186 1.587
4.5 5.894 5.062 4.189 3.876 3.492 3.140 2.867 2.186 1.254
5.0 5.809 5.008 4.151 3.844 3.466 3.119 2.850 2.041 1.016
5.5 5.716 4.947 4.110 3.808 3.437 3.095 2.830 1.687 0.839
6.0 5.616 4.881 4.064 3.769 3.405 3.069 2.495 1.417 0.705
6.5 5.507 4.809 4.014 3.725 3.370 3.040 2.126 1.208 0.601
7.0 5.390 4.730 3.959 3.678 3.331 2.950 1.833 1.041 0.518
7.5 5.266 4.645 3.899 3.626 3.288 2.570 1.597 0.907 0.451
8.0 5.133 4.553 3.834 3.570 3.242 2.259 1.404 0.797 0.397
8.5 4.992 4.455 3.764 3.510 3.090 2.001 1.243 0.706 0.351
9.0 4.844 4.351 3.689 3.444 2.757 1.785 1.109 0.630 0.313
9.5 4.687 4.239 3.609 3.374 2.474 1.602 0.995 0.565 0.281
10.0 4.523 4.121 3.523 3.128 2.233 1.446 0.898 0.510 0.254
4-8
Design Guidelines Handbook
Contec GP2/0.5 Block,
t = 7 in (nominal).
Wall height Eccentricity (in)
h' (ft) 0.00 0.25 0.50 t/10=0.69 1.00 t/6=1.15 1.50 1.75 2.00
3.0 7.162 6.227 5.470 5.010 4.401 4.159 3.681 3.403 2.675
3.5 7.107 6.194 5.445 4.989 4.384 4.145 3.669 3.393 2.675
4.0 7.045 6.156 5.415 4.964 4.365 4.128 3.656 3.381 2.675
4.5 6.976 6.113 5.382 4.936 4.343 4.108 3.641 3.368 2.675
5.0 6.901 6.064 5.344 4.904 4.319 4.086 3.623 3.353 2.675
5.5 6.818 6.010 5.302 4.869 4.291 4.062 3.604 3.337 2.675
6.0 6.729 5.951 5.256 4.830 4.261 4.035 3.583 3.319 2.457
6.5 6.633 5.887 5.206 4.787 4.228 4.005 3.559 3.298 2.093
7.0 6.530 5.817 5.151 4.741 4.192 3.972 3.534 2.911 1.805
7.5 6.420 5.742 5.092 4.691 4.153 3.937 3.506 2.536 1.572
8.0 6.304 5.661 5.029 4.637 4.110 3.899 3.366 2.229 1.382
8.5 6.181 5.575 4.961 4.579 4.065 3.858 2.982 1.974 1.224
9.0 6.050 5.483 4.888 4.517 4.016 3.814 2.660 1.761 1.092
9.5 5.913 5.386 4.810 4.451 3.963 3.766 2.387 1.581 0.980
10.0 5.769 5.282 4.727 4.380 3.907 3.546 2.154 1.427 0.884
4-9
Design Guidelines Handbook
Contec GP2/0.5 Block,
t = 8 in (nominal).
Wall height Eccentricity (in)
h' (ft) 0.00 0.25 0.50 t/10=0.69 1.00 t/6=1.31 1.50 1.75 2.00
3.0 8.218 7.267 6.468 5.741 5.301 4.764 4.491 4.172 3.896
3.5 8.167 7.237 6.444 5.723 5.285 4.752 4.480 4.163 3.887
4.0 8.110 7.203 6.417 5.701 5.267 4.737 4.467 4.151 3.877
4.5 8.047 7.164 6.385 5.677 5.246 4.720 4.451 4.138 3.866
5.0 7.978 7.120 6.351 5.649 5.222 4.701 4.435 4.123 3.853
5.5 7.903 7.071 6.312 5.619 5.196 4.680 4.416 4.107 3.839
6.0 7.822 7.018 6.270 5.585 5.167 4.656 4.395 4.089 3.823
6.5 7.735 7.960 6.223 5.548 5.136 4.631 4.372 4.069 3.806
7.0 7.642 7.897 6.173 5.508 5.102 4.603 4.347 4.048 3.787
7.5 7.543 6.830 6.119 5.465 5.065 4.573 4.320 4.025 3.767
8.0 7.438 6.757 6.061 5.419 5.025 4.540 4.291 3.999 3.327
8.5 7.328 6.680 5.999 5.369 4.982 4.505 4.260 3.972 2.947
9.0 7.211 6.598 5.932 5.316 4.936 4.467 4.226 3.782 2.629
9.5 7.088 6.511 5.862 5.259 4.887 4.427 4.190 3.395 2.359
10.0 6.959 6.418 5.787 5.198 4.835 4.384 4.152 3.064 2.129
4-10
Design Guidelines Handbook
Contec GP2/0.5 Block,
t = 10 in (nominal).
Wall height Eccentricity (in)
h' (ft) 0.00 0.25 0.50 0.75 t/10=0.98 1.25 1.50 t/6=1.64 2.00 2.25
3.0 10.321 9.353 8.849 7.771 7.200 6.646 6.98 5.971 5.461 5.154
3.5 10.275 9.328 8.468 7.753 7.185 6.634 6.187 5.961 5.452 5.147
4.0 10.224 9.299 8.444 7.733 7.168 6.619 6.174 5.949 5.442 5.138
4.5 10.168 9.266 8.417 7.711 7.148 6.602 6.160 5.936 5.431 5.128
5.0 10.107 9.230 8.837 7.685 7.126 6.584 6.143 5.921 5.419 5.117
5.5 10.041 9.189 8.353 7.657 7.102 6.563 6.125 5.904 5.404 5.104
6.0 9.971 9.144 8.316 7.626 7.076 6.540 6.105 5.886 5.389 5.090
6.5 9.896 9.096 8.276 7.592 7.047 6.515 6.084 5.886 5.372 5.075
7.0 9.816 9.044 8.233 7.556 7.015 6.488 6.060 5.844 5.354 5.059
7.5 9.731 8.987 8.186 7.516 6.981 6.459 6.035 5.820 5.334 5.041
8.0 9.642 8.927 8.136 7.474 6.945 6.428 6.008 5.795 5.313 5.022
8.5 9.548 8.863 8.083 7.429 6.906 6.395 5.979 5.768 5.290 5.002
4-11
Design Guidelines Handbook
Contec GP2/0.5 Block,
t = 12 in (nominal).
Wall height Eccentricity (in)
h' (ft) 0.00 0.25 0.50 0.75 1.00 t/10=1.18 1.50 1.75 t/6=1.97 2.25
3.0 12.417 11.444 10.533 9.756 9.086 8.655 7.988 7.533 7.176 6.763
3.5 12.373 11.422 110.514 9.740 9.072 8.643 7.978 7.524 7.168 6.755
4.0 12.324 11.397 10.493 9.722 9.056 8.628 7.966 7.513 7.58 6.747
4.5 12.272 11.369 10.469 9.701 9.038 8.612 7.952 7.501 7.147 6.737
5.0 12.216 11.337 10.442 9.678 9.018 8.594 7.936 7.487 7.134 6.726
5.5 12.156 11.302 10.413 9.653 8.996 8.574 7.919 7.472 7.120 6.713
6.0 12.091 11.264 10.380 9.625 8.972 8.552 7.900 7.455 7.105 6.700
6.5 12.023 11.222 10.345 9.594 8.946 8.528 7.880 7.437 7.088 6.685
7.0 11.951 11.177 10.306 9.561 8.917 8.502 7.858 7.417 7.070 6.669
7.5 11.875 11.129 10.265 9.526 8.886 8.474 7.834 7.396 7.051 6.652
8.0 11.795 11.077 10.221 9.488 8.853 8.444 7.808 7.373 7.030 6.633
8.5 11.711 11.022 10.174 9.448 8.818 8.412 7.780 7.348 7.008 6.613
9.0 11.622 10.963 10.124 9.404 8.780 8.377 7.751 7.322 6.984 6.592
9.5 11.530 11.901 10.071 9.359 8.740 8.341 7.720 7.294 6.959 6.570
10.0 11.434 11.836 10.016 9.311 8.698 8.303 7.687 7.265 6.932 6.546
4-12
Design Guidelines Handbook
Table 4.4 Maximum allowable lateral loads for Contec AAC
unreinforced masonry (psf).
Contec GP2/0.5 Block,
t = 6 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 167 167 180 176 192 185 205 194 218 203 231 213
3.5 123 123 132 130 142 136 151 143 160 150 170 156
4.0 94 94 101 99 109 105 116 110 123 115 130 120
4.5 75 75 80 79 86 83 92 87 97 91 103 95
5.0 61 61 65 64 70 67 74 70 79 74 84 77
5.5 50 50 54 53 58 56 62 58 65 61 69 64
6.0 42 42 45 45 49 47 52 49 55 51 58 54
6.5 36 36 39 38 41 40 44 42 47 44 50 46
7.0 31 31 33 33 36 35 38 36 41 38 43 40
7.5 27 27 29 29 31 30 33 32 35 33 37 34
8.0 24 24 26 25 28 27 29 28 31 29 33 30
8.5 21 21 23 22 24 24 26 25 28 26 29 27
9.0 19 19 20 20 22 21 23 22 25 23 26 24
9.5 17 17 18 18 20 19 21 20 22 21 23 22
10.0 15 15 17 16 18 17 19 18 20 19 21 20
4-13
Design Guidelines Handbook
Contec GP2/0.5 Block
t = 7 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 228 228 242 238 257 249 272 259 287 270 302 281
3.5 168 168 178 175 189 183 200 191 211 199 222 207
4.0 129 129 137 135 145 140 154 146 162 152 170 158
4.5 102 102 108 106 115 111 122 116 128 121 135 125
5.0 83 83 88 86 93 90 99 94 104 98 109 102
5.5 68 68 73 72 77 75 82 78 86 81 91 84
6.0 58 58 61 60 65 63 69 66 72 68 76 71
6.5 49 49 52 51 55 54 59 56 62 58 65 60
7.0 42 42 45 44 48 46 51 48 53 50 56 52
7.5 37 37 39 39 42 40 44 42 47 44 49 46
8.0 33 33 35 34 37 36 39 37 41 39 43 40
8.5 29 29 31 30 33 32 35 33 36 34 38 36
9.0 26 26 28 27 29 28 31 29 33 31 34 32
9.5 23 23 25 24 26 25 28 26 29 28 31 29
10.0 21 21 22 22 24 23 25 24 26 25 28 26
Contec GP4/0.7 Block
t = 7 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 229 229 244 239 258 250 273 261 288 271 303 282
3.5 168 168 179 176 190 184 201 192 212 200 223 208
4.0 129 129 138 135 146 141 154 147 163 153 171 159
4.5 102 102 109 107 116 112 122 117 129 121 136 126
5.0 83 83 89 87 94 91 99 95 105 99 110 102
5.5 69 69 73 72 78 75 82 78 87 82 91 85
6.0 58 58 62 61 66 63 69 66 73 69 77 71
6.5 50 50 53 52 56 54 59 56 62 59 66 61
7.0 43 43 46 45 48 47 51 49 54 51 57 53
7.5 38 38 40 39 42 41 45 43 47 44 49 46
8.0 33 33 35 35 37 36 39 38 41 39 44 41
8.5 29 29 31 31 33 32 35 33 37 35 39 36
9.0 26 26 28 27 30 29 31 30 33 31 35 32
9.5 24 24 25 25 27 26 28 27 30 28 31 29
10.0 21 21 23 22 24 23 25 24 27 25 28 26
4-14
Design Guidelines Handbook
Contec GP2/0.5 Block
t = 8 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 297 297 314 309 331 321 348 333 365 345 382 358
3.5 218 218 231 227 243 236 256 245 268 254 281 263
4.0 168 168 177 174 187 181 196 188 206 195 215 202
4.5 133 133 140 138 148 143 155 149 163 154 171 160
5.0 108 108 114 112 120 116 126 121 132 125 138 130
5.5 89 89 94 93 99 96 104 100 109 104 114 107
6.0 75 75 79 78 84 81 88 84 92 87 96 90
6.5 64 64 68 67 71 69 75 72 79 74 82 77
7.0 55 55 59 58 62 60 65 62 68 64 71 67
7.5 48 48 51 50 54 52 57 54 59 56 62 58
8.0 43 43 45 44 47 46 50 48 52 49 55 51
8.5 38 38 40 39 42 41 44 42 46 44 48 45
9.0 34 34 36 35 38 36 39 38 41 39 43 41
9.5 30 30 32 32 34 33 35 34 37 35 39 36
10.0 27 27 29 29 31 30 32 31 34 32 35 33
Contec GP4/0.7 Block
t = 8 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 298 298 315 310 332 323 349 335 366 347 383 359
3.5 220 220 232 229 245 238 257 246 270 255 282 264
4.0 169 169 178 176 188 182 197 189 207 196 217 203
4.5 134 134 141 139 149 144 156 150 164 155 171 161
5.0 109 109 115 113 121 117 127 122 133 126 139 130
5.5 90 90 95 94 100 97 105 101 110 104 115 108
6.0 76 76 80 79 84 82 89 85 93 88 97 91
6.5 65 65 68 67 72 70 76 73 79 75 83 78
7.0 56 56 59 58 62 60 65 63 69 65 72 67
7.5 49 49 52 51 54 53 57 55 60 57 63 59
8.0 43 43 46 45 48 47 50 48 53 50 55 52
8.5 38 38 40 40 43 41 45 43 47 44 49 46
9.0 34 34 36 36 38 37 40 38 42 40 44 41
9.5 31 31 33 32 34 33 36 34 38 36 39 37
10.0 28 28 29 29 31 30 32 31 34 32 36 33
4-15
Design Guidelines Handbook
Contec GP2/0.5 Block
t = 10 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 464 464 485 479 506 494 528 509 549 524 570 540
3.5 341 341 357 353 373 364 388 375 404 386 419 397
4.0 262 262 274 270 286 279 298 288 310 296 322 305
4.5 207 207 217 214 226 221 236 228 245 234 255 241
5.0 168 168 176 174 184 179 191 185 199 190 207 196
5.5 139 139 146 144 152 148 158 153 165 157 171 162
6.0 117 117 123 121 128 125 133 129 139 133 144 136
6.5 100 100 105 103 109 107 114 110 118 113 123 116
7.0 87 87 90 89 94 92 98 95 102 98 106 100
7.5 76 76 79 78 82 80 86 83 89 85 93 88
8.0 67 67 70 69 73 71 75 73 78 75 81 77
8.5 59 59 62 61 64 63 67 65 70 67 72 69
9.0 53 53 55 54 57 56 60 58 62 60 65 61
9.5 47 47 50 49 52 50 54 52 56 54 58 55
10.0 43 43 45 44 47 46 49 47 51 48 52 50
Contec GP4/0.7 Block
t = 10 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 466 466 487 481 508 496 530 512 551 527 572 542
3.5 343 343 359 354 375 366 390 377 406 388 421 399
4.0 264 264 276 272 287 281 299 289 311 298 323 306
4.5 209 209 218 216 228 222 237 229 247 236 256 243
5.0 170 170 177 175 185 181 193 186 200 191 208 197
5.5 141 141 147 145 153 150 160 154 166 159 172 163
6.0 118 118 124 122 129 126 134 130 140 134 145 137
6.5 101 101 106 104 110 108 115 111 119 114 124 117
7.0 88 88 91 90 95 93 99 96 103 99 107 101
7.5 76 76 80 79 83 81 87 84 90 86 93 89
8.0 67 67 70 69 73 72 76 74 79 76 82 78
8.5 60 60 62 62 65 64 68 66 70 67 73 69
9.0 54 54 56 55 58 57 61 59 63 60 65 62
9.5 48 48 50 50 52 51 55 53 57 54 59 56
10.0 44 44 45 45 47 46 49 48 51 49 53 50
4-16
Design Guidelines Handbook
Contec GP2/0.5 Block
t = 12 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 668 668 693 686 719 704 744 722 770 741 795 759
3.5 492 492 510 505 529 518 548 532 567 545 585 559
4.0 377 377 391 387 406 398 420 408 435 418 449 428
4.5 299 299 310 307 321 315 333 323 344 331 355 339
5.0 242 242 252 249 261 255 270 262 279 269 288 275
5.5 201 201 208 206 216 212 223 217 231 222 239 228
6.0 169 169 175 174 182 178 188 183 194 187 201 192
6.5 144 144 150 148 155 152 161 156 166 160 171 164
7.0 125 125 129 128 134 131 139 135 143 138 148 141
7.5 109 109 113 112 117 115 121 118 125 120 129 123
8.0 96 96 99 98 103 101 107 103 110 106 114 109
8.5 85 85 88 87 91 90 95 92 98 94 101 96
9.0 76 76 79 78 82 80 84 82 87 84 90 86
9.5 68 68 71 70 73 72 76 74 79 76 81 77
10.0 62 62 64 63 66 65 69 67 71 68 73 70
Contec GP4/0.7 Block
t = 12 in (nominal), e is eccentricity for axial load only.
Wall height Axial Load (kips/ft)
h' (ft) 0.00 0.25 0.50 0.75 1.00 1.25
e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6 e = t/10 e = t/6
3.0 671 671 696 689 722 707 748 726 773 744 799 762
3.5 494 494 513 508 532 521 551 535 569 548 588 561
4.0 380 380 394 390 408 400 423 410 437 421 451 431
4.5 301 301 312 309 323 317 335 325 346 333 357 341
5.0 244 244 253 251 263 257 272 264 281 271 290 277
5.5 202 202 210 208 218 213 225 219 233 224 240 230
6.0 171 171 177 175 183 180 190 184 196 189 202 193
6.5 146 146 151 150 157 153 162 157 167 161 173 165
7.0 126 126 131 129 135 133 140 136 145 139 149 143
7.5 110 110 114 113 118 116 122 119 126 122 130 125
8.0 97 97 101 100 104 102 108 105 111 107 115 110
8.5 86 86 89 88 93 91 96 93 99 95 102 98
9.0 77 77 80 79 83 81 86 83 88 85 91 87
9.5 69 69 72 71 74 73 77 75 80 77 82 78
10.0 63 63 65 64 67 66 70 68 72 69 74 71
4-17