Sei sulla pagina 1di 6

June 2001 Bulletin 61.

2:1061DD

Type 1061DD Damper Control Drive Assembly


D The Type 1061DD drive assembly (figure 1) is The actuator is mounted on a fabricated steel pedestal
available from Fisher Service Company only as shown in figure 1. The pedestals are custom
fabricated for each application, so floor bolting costs
Damper control drives can be used for gas-stream are minimized. Fisher Service Company will measure
modulation applications, isolation service for utilities your application and will quote drives that bolt directly
and other industries, and many other similar to your existing mounting pads. Fisher Service
applications where damper control is needed. Company also offers linkage assemblies (figure 2) that
include lever, turnbuckles, and industrial-grade rod
This drive assembly is very flexible, with seven ends (which are superior in performance to a bolted
available sizes with torque output up to 19,800 NSm clevis construction). This design reduces lost motion
(175,000 lbfSin) and customized mounting positions to caused by wear of metal-to-metal contact and
match your requirements. improves controllability. The linkage includes left- and
right-handed adjustor threads that allow you to adjust
The damper control drives are part of Fisher’s Type the linkage without disconnecting it.
1061 pneumatic piston actuator family. Damper drives
use a standard Type 1061 double-acting pneumatic
piston actuator and a Type 3620JP electro-pneumatic Features
positioner. This combination has proven performance
as a rugged, accurate control valve actuator, and it D Minimum Deadband—Single-point linkage with
can provide you the same performance as a damper splined and clamped lever (see figure 3) minimizes
control drive. lost motion and improves control accuracy.

ACTUATOR

POSITIONER

LEVER

PEDESTAL

W6245-1/IL W6246-1/IL

Figure 1. Type 1061DD Damper Drive


D102022X012
Bulletin 61.2:1061DD
Specifications
Note Electrical Classification
Specifications shown here are the Refer to the Hazardous Area Classification bulletin
general specifications you need for the for specific approvals for the electro-pneumatic
Type 1061DD damper control drive. If positioner
you need more detailed specifications
on the Type 1061 actuator or the Type Output Shaft Diameters, mm (Inches)
3620JP positioner, refer to Bulletin Size 30: J 2.7(1/2 ), J 15.9 (5/8), J 19.1 (3/4),
61.1:1061 or 62.1:3610. J 22.2 (7/8), J 25.4 (1), and J 31.8 (1-1/4)
Sizes 40, 60, and 68: J 19.1 (3/4), J 22.2 (7/8),
Positioner Input Signal(1) J 25.4 (1), J 31.8 (1-1/4), J 38.1 (1-1/2), J 44.5
4 to 20 mA dc constant current with 30 V dc (1-3/4), and J 50.8 (2)
maximum compliance voltage. Split range is also Sizes 80 and 100: J 44.5 (1-3/4), J 50.8 (2), and
available, see Bulletin 62.1:3610 J 63.5 (2-1/2)
Size 130: J 76.2 (3) J 88.9 (3-1/2)
Positioner Output Signal(2)
Pneumatic pressure as required by the actuator up Maximum Shaft Rotation
to full supply pressure J 90 deg without travel stop or J 60 deg with
Positioner Supply Pressure(1) optional travel stop
Minimum Recommended: 0.3 bar (5 psig) above Stroking Time
actuator requirement
Dependent on actuator size, rotation, and positioner
Maximum: 10.3 bar (150 psig)
if used. If stroking time is critical, consult your Fisher
Actuator Cylinder Operating Pressure sales office.
Minimum Recommended: J 1.4 bar (20 psig) Travel Indication
without positioner or J 0.35 bar (5 psi) above
actuator requirement with positioner(3) Graduated scale and pointer located on actuator
Maximum Allowable: shaft
Sizes 30 and 60: 6.9 bar (100 psig)
Size 40: 10.3 bar (150 psig) Pressure Connections
Size 68: 5.9 bar (85 psig) 1/4-inch NPT female
Size 80: 10.3 bar (150 psig)
Size 100: 10.3 bar (150 psig) Positioner Conduit Connection
Size 130: 10.3 bar (150 psig) 1/2-inch NPT female
Actuator Sizes and Maximum Torque(3)
Approximate Weight
Size 30: Up to 282 NSm (2500 lbfSin)
Size 40: Up to 847 NSm (7500 lbfSin) Positioner: 3.6 kg (8 pounds)
Size 60: Up to 1130 NSm (10,000 lbfSin) Actuator:
Size 68: Up to 1540 NSm (13,600 lbfSin)
Size 80: Up to 5080 NSm (45,000 lbfSin) Actuator Size kg Lb
Size 100: Up to 6290 NSm (55,700 lbfSin) with 30 22 49
standard 63.5 mm (2-1/2 in) shaft 40 29 63
Size 130: Up to 19,800 NSm (175,000 lbfSin) 60 39 86
68 156 123
Also see figure 5. 80 122 246
100 135 298
Operative Temperature Limits(1) 130 299 660
Positioner: –40 to 80°C (–40 to 180°F)
Actuator with Standard Elastomers: –34 to 82°C
(–30 to 180°F)
- Continued -

2
Bulletin 61.2:1061DD
Specifications (Continued)
Dimensions Limit Switches: J Type 304 limit switch for one
Damper Drive Pedestal: To meet your through six single-pole, double-throw contacts (see
requirements. Specify the dimensions shown in separate bulletin), J GO(4) proximity switches for
figure 6 one or two single-pole, double-throw contacts, or
Actuator: See Bulletin 61.2:1061 J Micro-Switches or NAMCO switches for one or
Positioner: See Bulletin 62.1:3610 two single-pole, double-throw or double-pole,
double-throw contacts
Options Locking Mechanism: The locking mechanism is
Positioner: J Supply pressure gauge, J tire available for sizes J 30, J 40, J 60, and J 68
valves, or J plugs actuators.
Actuator: FlowScannert: Quick disconnect connections are
377 Series trip valves are available with available for use with the portable FlowScanner
J lock-in-last position, J fail-up, or J fail-down microprocessor-based diagnostic testing unit.
action (see separate bulletins)
Potentiometer: For remote rotation indication
1. This term is defined in ISA Standard S51.1.
2. For direct action, an increasing input signal extends actuator rod. For reverse action, an increasing input signal retracts actuator rod.
3. Actual actuator torque available depends on specific construction, degrees of rotation, and cylinder pressure. For information on torque
requirements of the valve being considered, contact your Fisher sales office.
4. The GO proximity switches are not available for size 80, 100 or 130 actuators.

D Compact Construction—Compared to similar


actuators, overall size is as much as 30% smaller.

D Longer Service Life—Rugged construction


provides stability, corrosion resistance, and protection
from deformation should overpressure occur.

D Accurate, Efficient, Vibration-Resistant


Operation—The positioner is an accurate, fast-
responding instrument that can withstand the
vibrations of most plant environments. Low
steady-state air consumption contributes to efficient
operation.

D Versatility—The positioner offers split-range


capabilities and adjustable zero and span. The
rangeability of the positioner zero and span permits
using a single range spring for all standard input
signals including split ranges. A6351/IL

D Easy Positioner Adjustments—With the


positioner cover removed, zero, span, and cross-over
adjustments, shown in figure, are easily accessible
and can be made with a screwdriver (figure 4). Figure 2. Linkage Assembly for Type 1061DD Damper Drive

D Stable Operation—Changes in supply pressure


have minimal effect on positioner operation.

3
Bulletin 61.2:1061DD

ACTUATOR ROD
CAM
FEEDBACK LEVER

POSITIONER

LEVER

OUTPUT
SHAFT

W3783-1/IL

Figure 3. Single-Point Actuator-Shaft Linkage with Splined and Clamped Lever

CROSSOVER
ADJUSTMENT

DIRECT/
REVERSE
PLATE

ZERO
ADJUSTMENT

COARSE SPAN
ADJUSTMENT
MINOR LOOP
GAIN
ADJUSTMENT
FINE SPAN
ADJUSTMENT

W4900-1/IL

Figure 4. Easy Adjustments for Positioner

4
Bulletin 61.2:1061DD

SIZE 40 SIZE 80 SIZE 130


150

ÇÇÇ
125
SIZE 100

ÇÇÇ
SIZE 30 SIZE 60
SUPPLY PRESSURE, PSIG

100
SIZE 68
85

65
50

0
2 4 6 8 12

0 10,000 20,000 30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 110,000 120,000 130,000 140,000 150,000 160,000
45,000 65,000 175,000
AVAILABLE TORQUE, INCH-POUNDS
NOTES:
1. CYLINDER PRESSURE EQUALS SUPPLY PRESSURE FOR AN ACTUATOR WITHOUT A
POSITIONER OR FOR A TYPE 3620JP POSITIONER AND ACTUATOR COMBINATION. WHEN
ANOTHER POSITIONER IS USED, ASSUME CYLINDER PRESSURE IS 90% OF SUPPLY PRESSURE.
2 FOR SIZE 100, DO NOT EXCEED 6290 NSm (55,700 LBFSIN) WITH STANDARD 63.5 mm (2-1/2 INCH)
OUTPUT SHAFT.
A2216-2 / IL

Figure 5. Available Actuator Torques at 0° and 90° Rotation

Ordering Information 3. Maximum supply pressure available


4. Damper and size with which the actuator will be
When ordering, please specify the product application used
and construction: 5. Required output rotation in degrees
6. Actuator torque required with actuator rod fully
retracted and with actuator rod extended
Positioner and Actuator Application 7. Stroking time requirements, if critical
1. Positioner type number 8. Seismic requirements, if critical
2. Maximum supply pressure available 9. Options:
3. Actuator size and type number
4. Input signal
Be sure to specify the Type 1061 actuator and Type
3620JP positioner type number. Refer to the
specifications table. Review the description to the right
Damper Application of each specification and in the referenced figures.
When ordering, specify: Specify the desired choice wherever there is a
selection to be made. Refer to Bulletin 61.2:1061 and
1. On-off or throttling service 62.1:3610 if you need more detailed information on
2. Input signal range specifications.

5
Bulletin 61.2:1061DD

254
(10-INCH)

mm
(INCH)

A6352/IL

SPECIFY THE DIMENSIONS (INCHES) SHOWN:


A BASE WIDTH _______
B BASE LENGTH _______
C MOUNTING HOLE LOCATION _______
D MOUNTING HOLE LOCATION _______
E MOUNTING HOLE DIAMETER _______
F LEVER HOLE DIAMETER _______
L LEVER LENGTH _______
S SIDE CLEARANCE _______
T TOP CLEARANCE _______
X LOCATION OF LEVER _______
Y LOCATION OF LEVER _______
Z LOCATION OF LEVER _______
ALSO SPECIFY OUTPUT TORQUE
REQUIRED IF KNOW (LBFSIN) _______

Figure 6. Dimensions

FlowScanner, Fisher, and Fisher-Rosemount are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
EFisher Controls International, Inc. 1994, 2001; All Rights Reserved

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

For information, contact Fisher:


Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461

6
Printed in U.S.A.

Potrebbero piacerti anche