1756-IF16 (Single Ended Current) with 1492-AIFM16-F-5

1756-IF16
1492-ACABLE 1 UB
1492-AIFM16-F-5 1492-HWACAB 1 UB TC-IAH161
0 C1-TB1 3 Red 2
IN-0
1 C2-TB1 2 Brown 4
IN-1
2 C3-TB1 1 Black 6
IN-2
3 C4-TB1 14 White 8
IN-3
2-Wire Transmitter 4 C5-TB1 15 White/Black 12
IN-4
5 C6-TB1 16 White/Brown 14
+ IN-5
Transmitter 6 C7-TB1 17 White/Red 16
IN-6
7 C8-TB1 18 White/Orange 18
IN-7
RTN + iRTN C9-TB1 4 Orange 10
RTN
RTN + iRTN C10-TB1 6 Yellow
8 Green 8
RTN + iRTN C15-TB1 10 Blue 28
RTN
RTN + iRTN C16-TB1 19
J1-1 A17-TB1
6
8 C1-TB2 12 Violet 20
IN-8
9 C2-TB2 13 Gray 22
IN-9
10 C3-TB2 25 White/Black/Brown 24
IN-10
11 C4-TB2 24 White/Gray 26
IN-11
12 C5-TB2 23 White/Violet 30
IN-12
13 C6-TB2 22 White/Blue 32
IN-13
14 C7-TB2 20 White/Yellow 34
IN-14
15 C8-TB2 21 White/Green 36
IN-15
RTN + iRTN C9-TB2 1
4 iRTN-0
RTN + iRTN C10-TB2 3
iRTN-1
5
iRTN-2
RTN + iRTN C15-TB2 7
iRTN-3
RTN + iRTN C16-TB2 9
- Power Supply + RTN
+V B1-TB1 11
iRTN-4
+V0F B2-TB1 13
iRTN-5
2 15
+V1F B3-TB1 iRTN-6
17
+V2F B4-TB1 iRTN-7
19
iRTN-8
+V3F B5-TB1 21
iRTN-9
+V4F B6-TB1 23
iRTN-10
25
+V5F B7-TB1 iRTN-11
27
+V6F B8-TB1 RTN
29
iRTN-12
+V7F B9-TB1 31
iRTN-13
VCOM B10-TB1 33
iRTN-14
VCOM B11-TB1 35
iRTN-15
7
VCOM B17-TB1
VCOM B18-TB1
1 Cables are available in 0.5m, 1.0m, 2.5m, and 5.0m J1-2 A18-TB1
standard lengths (005=0.5m, 010=1.0m, 025=2.5m, +V B1-TB2
050=5.0m). Custom length cables are also available. +V8F B2-TB2
2 LED provides blown fuse indication. When the +V9F B3-TB2
fuse is blown the leakage current through the LED is
+V10F B4-TB2
2mA nominal.
3 Terminals starting with A are the lower row of +V11F B5-TB2
terminals, B terminals are the middle row, C +V12F B6-TB2
terminals are the upper row. TB1 is the left terminal
block, TB2 is the right terminal block. +V13F B7-TB2
+V14F B8-TB2
4 Function of DIP switch required by some PLC
analog modules to short unused channels to +V15F B9-TB2
common when closed. Factory Position: Open. VCOM B10-TB2
(Refer to your PLC manual for details). VCOM B11-TB2
5 Follow your PLC Analog User Manual for proper
shield grounding instructions. VCOM B17-TB2
6 To tie V COM to RTN, add a jumper between VCOM B18-TB2
terminals J1-1 and J1-2. SHIELD A1-TB1 SH
5
7 Terminals B10-TB1 through B18-TB1 and B10-TB2
through B18-TB2 can be used for field wire SHIELD A8-TB1
convenience connections. NOTE: they are SHIELD A1-TB2
connected together (commoned) on the AIFM.
8 RTN terminals are internally connected on SHIELD A8-TB2
41170-515 (2)
the 1756-IF16.
3