Warning Daikin products are manufactured for export to numerous countries throughout the world.

Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product PCXSPH1732A
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Use only those parts and accessories supplied or specified by Daikin.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Dealer
Lot 60334, Persiaran Bukit Rahman Putra 3,
Taman Perindustrian Bukit Rahman Putra,
47000 Sungai Buloh, Selangor Darul Ehsan, Malaysia
www.daikinmalaysia.com

Head office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan.

Specifications, designs and other content appearing in this brochure are current as of August 2017 but subject to change without notice. c All rights reserved
The solution for light commercial sector
Providing the ideal solution for all kinds of small commercial space such as shops, restaurant and
small offices. The Sky Air series offers a complete comfort solution that puts you in total control.

Capacity kW 50 60 71 100 125 140


Ceiling Cassette Type
(3x3)

Indoor unit FCRN50AXVL FCRN60AXVL FCRN71AXVL FCRN100AXVL FCRN125AXVL9


Outdoor unit RR50AGXVL RR60AGXVL RR71AGXVL RR100AGXVL RR125AGXTL9

Duct Connection
Standard Static
Pressure Type
Indoor unit FDMRN50AXVL FDMRN60AXVL FDMRN71AXVL FDMRN100AXVL FDMRN125AXVL9 FDMRN140AXVL9
Outdoor unit RR50AGXVL RR60AGXVL RR71AGXVL RR100AGXVL RR125AGXTL9 RR140AGXTL9

Ceiling Suspended
Type

Indoor unit FDMRN50DXV1 FDMRN60DXV1 FHRN100AXVL FHRN140AXVL FHRN140AXVL9


Outdoor unit RN50CAXV1 RN60CAXV1 RR100AGXVL RR140AGXVL RR140AGXTL9

Floor Standing
Type

Indoor unit FHRN50DXV1 FHRN60DXV1 FVRN71AXVL FVRN100AXVL FVRN125AXVL9 FVRN140AXVL9


Outdoor unit RN50CAXV1 RN60CAXV1 RR71AGXVL RR100AGXVL RR125AGXTL9 RR140AGXTL9

Outdoor Unit

Outdoor Unit

RR50AGXVL RR60AGXVL RR71AGXVL RR100AGXVL RR125AGXTL9 RR140AGXTL9

01 02
4-way air flow Compact body and quiet operation
Ceiling Cassette This unit promotes even air distribution covering every
corner of the room by combining 4-ways air discharge
and large discharge area.
Indoor units as an aerodynamically designed Diffuser
Turbo Fan.

Type

Draft resistance has been reduced by incorporating into


Fine square panels a single unit, an impeller and a diffuser to control air flow
3x3: FCRN50/60/71/100AXVL, 125AXVL9 Panel size is same for all models. It is easy to maintain a inside the unit. The Diffuser Turbo Fan is both quiet
neat appearance when multiple units are installed. during operation and compact.

3x3:

950mm

950mm

Wired controller: Wireless controller: Optimal comfort and convenience assured by air discharge modes (FCRN series only)
BRC51A62 BRC52A62 To increase the comfort level of the air conditioned area, the system is built-in with 3 different types of air flow pattern
* optional * supplied with panel
to suit different requirements.

1 2 3
Air direction in Air direction in draft Air direction in ceiling
standard setting prevention setting soiling prevention setting
For gentle drafts. Select this setting to eliminate Recommended for location with
direct drafts which can lead to light colour ceiling that must be
discomfort. kept spotless.

COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES OPTIONS OTHERS

The default setting for air swing pattern is 1. The air swing pattern can be selected through the wireless remote
Network Interface Module (NIM)

control.
Two selectable temperature

Pre-charged for up to 7.5m

External command control


Drain pump mechanism
Weekly scheduled timer

Washable saranet filter

Anti corrosion treated


Switchable fan speed

Auto random restart

Fresh-air intake kit


Programme “Dry”

Group control by

heat exchangers
Timer selector
Swing pattern

Self diagnosis
Auto swing

using BAG

Two selectable temperature sensors


sensor

Both indoor unit and wired remote controller (option) contain temperature-sensors. Temperature sensing can be set at
the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be
set during commissioning by the technicians.
* Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
*1 *1
** Wireless remote controller does not have a temperature-sensor.
*1 Applicable when wired controller is used.

03 04
Switchable fan speed Indoor unit on/off switch Drain pump is equipped as standard accessory with 700mm lift
High/Medium/Low/Quiet The unit can be conveniently started manually in the This unit comes with a condensate water drain pump which can pump water up to 700mm higher from drain pipe
event the wireless remote controller is misplaced or the outlet. Safety float is incorporated to monitor water level.
High setting provides maximum reach while low setting wireless remote controller batteries are not charged.
minimises drafts.

Extra protection
Timer selector This unit covered with insulation material acts as extra
protection when installed under very high humidity 700mm
Operation starts when the preset time of the ‘on’ timer
environment to prevent condensation.
elapses and stops when the preset time of the ‘off’ timer
elapses.

Powerful operation
New powerful operation boosts airflow to maximum
volume for a 20-minute period with highest fan
speed. After this, the unit automatically returns to its
previous settings.

Easy maintenance
Easy installation

Quick and easy to install Panel-hook mechanism Easier to maintain


The condition of the drain pan and drain water can be Just open the
Just 246mm high. Installable in tight ceiling spaces. This feature enables the installer to work with both
checked by removing the drain plug and intake grille. intake grille!
hands as the panel can be hung on the unit.

Drain plug
*246mm Simple step to change fan motor
• Without removing panel, it can be
easily accessed and service to
* 246mm high with FCRN50/60/71
fan motor
* 288mm high with FCRN125/140
• Reduced troubleshooting and Self-diagnosis function
servicing time This intelligent feature helps to detect faults or
All models can be installed without using lifter because • Simple steps: malfunctioning in the system and give user a warning by
of the light weight. control box  fan cover  blower fan  fan motor blinking of the LED light or display error code on wired
controller.
Detachable corner
For the ease and flexibility of installation, this unit is Position of connecting pipe and drain hose
designed with 4 detachable corners where installer is In order to create more space for installer to work on
able to fit their hand in to adjust hanging hook and connection pipe of indoor unit, the connection pipe of Options required for specific operating environments
perform drain leakage check. gas and liquid are located further from each other and
purposely not align to hanging hook.
To enhance the convenience of installation, drain hose Fresh air intake kit
location is relocated to another side of cassette unit (not
Using this kit*, a duct can be fitted to increase the intake
same side with connection pipe).
of outdoor air.

Easy accessible control box Knock-out hole


Control box of this unit can be accessed directly from
the intake grille for ease of installation and servicing The built-in knock-out hole are available for fresh air
process. intake or branch duct.

Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

05 06
Duct Connection
Thin, lightweight indoor unit makes delivery and installation easy
With a height of only 261mm, installation is possible even in buildings with narrow ceiling spaces.

Standard Static
Pressure Type
261mm

Flexibility in system design Two selectable temperature sensors


The unit offers fan motor that can operate up to 3 Both indoor unit and wired remote controller (option)
speeds, thus providing choices of external static contain temperature-sensors. Temperature sensing can
pressure for designing ducting system. be set at the unit or, to further improve comfort level,
closer to the target area at the wired remote control.
This feature must be set during commissioning by the
Double protection drainage system technicians.
The primary drain pan is designed with high thermal
* Temperature-sensor on indoor unit must be used when the air
insulation material and moulded in gradient for better conditioner is controlled from another room.
condensate water drainage. The extra secondary drain ** Wireless remote controller does not have a temperature-sensor.
pan “built in” to the standard unit offers extra protection
FDMRN50/60/71/100AXVL, 125/140AXVL9 against possible water leaking problems.
(standard static) Switchable fan speed
High/Medium/Low

High setting provides maximum reach while low setting


minimises drafts.

Primary drain pan


Polystyrene (PS) with
High Impact Polystyrene
(HIPS) cover
Secondary drain pan
with insulation

Wired controller: Wireless controller: Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
BRC51A62 BRC52A62 When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air
* supplied with unit * optional conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation
grilles should be installed on the partitioning wall or under the door between the rooms.

COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES OTHERS


Network Interface Module (NIM)
Two selectable temperature

Pre-charged for up to 7.5m

External command control


Weekly scheduled timer

Washable saranet filter

Anti corrosion treated


Switchable fan speed

Auto random restart


Programme “Dry”

heat exchangers
Group control by
Timer selector

Self diagnosis

using BAG
sensor

*1 *1

*1 Applicable when wired controller is used.

07 08
Far and high air flow Switchable fan speed
Ceiling Suspended Far air flow distance with high air flow ensuring the
spaces of the room to be cooled down rapidly to the set
temperature.
High/Medium/Low

High setting provides maximum reach while low setting

Type Two selectable temperature sensors


minimises drafts.

Timer selector
Both indoor unit and wired remote controller (option) Operation starts when the preset time of the ‘on’ timer
contain temperature-sensors. Temperature sensing can elapses and stops when the preset time of the ‘off’ timer
be set at the unit or, to further improve comfort level, elapses.
closer to the target area at the wired remote control.
This feature must be set during commissioning by the
technicians.
* Temperature-sensor on indoor unit must be used when the air
conditioner is controlled from another room.
FHRN100AXVL ** Wireless remote controller does not have a temperature-sensor.

Easy Installation

Installation flexibility for freedom of design


FHRN140AXVL9 Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints.

Easy Maintenance

Easy-clean surfaces Ease of maintenance


It is easy to wipe dirt off the surfaces of the unit. For all maintenance tasks, access is from bottom
surface.

Wired controller: Wireless controller:


BRC51A62 BRC52A62
* optional * supplied with unit

COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES OTHERS


Network Interface Module (NIM)
Two selectable temperature

Pre-charged for up to 7.5m

External command control


Weekly scheduled timer

Washable saranet filter

Anti corrosion treated


Switchable fan speed

Auto random restart


Programme “Dry”

heat exchangers
Group control by
Timer selector

Self diagnosis

using BAG
sensor

*1 *1

*1 Applicable when wired controller is used.

09 10
Floor Standing Auto-swing mode
This unit uses its automatic horizontal swing louver to spread
comfortable air flow to cool every corner of the room. Its
Timer selector
Operation starts when the preset time of the ‘on’ timer
elapses and stops when the preset time of the ‘off’ timer

Type
vertical louvers are adjusted manually to match different elapses.
interior spaces and partition as well as to avoid direct airflow.
Powerful operation
New powerful operation boosts airflow to maximum
volume for a 20-minute period with highest fan
speed. After this, the unit automatically returns to its
previous settings.

Indoor unit on/off switch


The unit can be conveniently started manually in the
event the wireless remote controller is misplaced or the
FVRN71/100AXVL, 125/140AXVL9 wireless remote controller batteries are not charged.
Auto horizontal swing Manual setting of
vertical airflow louvers

Easy maintenance
User-friendly controls
The unit comes with a stylish black control panel with
white LED light for clear display. It comes with a keylock
Safety clip
function to prevent setting change from unauthorised The safety clip feature allows users to remove the
personnel. washable saranet filter with ease during maintenance.
At the same time, it also acts as a safety feature to
Off state On state prevent the users from reaching into the electrical and
White display lights up to
indicate modes and mechanical components.
temperature settings when
switched on

Keylock icon displayed


when activated
Safety clip
Keylock function:
Activation / deactivation of
keylock by pressing
“SWING” and “TURBO”
together for 5 seconds

Wired controller: Wireless controller:


BRC51A62 BRC52A62 Far air flow
* optional * supplied with unit
The Daikin floor standing is able to achieve air flow distance as far as Additionally, this unit is incorporated Space for water drain pump
25m (size 160) which is about the size of a basketball court. with infrared sensor for usage with There is a space in the unit below the fan that allows
wireless controller which is supplied users to install an external condensate water pump.
V_r (m/s)
with the unit. Thus, it can be * The condensate water drain pump is separately purchased and field
controlled using wireless controller installed.
Global
2.44

1.22
for greater flexibility.
0.00

Two selectable temperature sensors


25m

Both indoor unit and wired remote controller (option)


contain temperature-sensors. Temperature sensing can be
COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES OTHERS set at the unit or, to further improve comfort level, closer to
the target area at the wired remote control. This feature
Network Interface Module (NIM)

must be set during commissioning by the technicians.


Two selectable temperature

Pre-charged for up to 7.5m

External command control


Weekly scheduled timer

Washable saranet filter

Anti corrosion treated


Switchable fan speed

Auto random restart


Programme “Dry”

Group control by

* Temperature-sensor on indoor unit must be used when the air


heat exchangers
Timer selector

Self diagnosis
Auto swing

conditioner is controlled from another room.


using BAG
sensor

** Wireless remote controller does not have a temperature-sensor

Switchable fan speed


High/Medium/Low
*1 *1 Piping Condensate
water
High setting provides maximum reach while low setting Floor standing unit drain pump
*1 Applicable when wired controller is used.
minimizes drafts.

11 12
Outdoor unit
Controller

Wireless controller BRC52A62

1 “Glow-in-the-dark” on/off 6 Vertical auto-swing


1 switch 7 Selectable mode:
6
2 Cool, Dry, Fan
2 Fan speed selection:
7
8 Low, Medium, High, Auto 8 Turbo function
3
9 3 Temperature setting: 9 Quiet function
4
Up & down 10 On timer setting
10 5
4 Sleep mode function 11 Real time clock
11
5 Off timer setting

RR50/60AGXVL RR71AGXVL RR100AGXVL


RR125/140AGXTL9
Wired controller BRC51A62
Fitted with wide inlet fan Pre-charged for up to 7.5 metres 1
Fully shaped aerodynamic propellers are designed to Model Max. piping length, m Max. piping elevation, m 1 Real time clock and day 7 Turbo function
push air with a large wing surface, providing both high
blow volume and quiet operation with turbulence.
RR50A 30 15
2
display 8 Cool, Dry, Fan mode
RR60A 7 3
2 Temperature operate in 9 Delay timer (1 or 2 hours)
RR71A 50 25 8
4
˚C and ˚F
10 7-days programmable timer
RR100A
9 3 Swing function
10 5 11 Low, Medium, High, Auto
RR125A 50 30 4 Quiet function
11 6 fan speed
RR140A 5 Sleep function
6 On/off switch

Wide inlet fan Wired controller BRC51A62 can directly be connected to the unit’s main board to start operating without extra setting
or modification. It also has a built-in temperature sensor that enables temperature sensing closer to target area for
improved comfort (no settings required to activate the handset temperature sensor).
Durability
• The unit is covered with corrosion-proof galvanized steel to enhance its durability.
• Heat exchange fins are provided with anti-corrosion treatment.

IR receiver on wired handset


received the signal

Signal sent from


wireless handset

13 14
Network controls Network controls

Simple system that provides flexibility of controls Sequential control by Sequential Network Interface Module (S-NIM)
Control two units of air conditioner in a master and slave system, operating at alternate sequence of preset hours
Control Pattern Remote Controls
(3/4/5/7/9/11/12 hours), controlled by a single BRC51A62 controller.
The S-NIM controls consist of:
• Mainboard
• Control panel (BRC51A62)
• S-NIM controller
Group control by Network For simultaneous control • Communication bus
Interface module (NIM) of up to 16 indoor units NIM NIM NIM NIM
The S-NIM is suitable in environment requiring 24-hours air conditioning, such as server room, room containing critical
electronics equipment, laboratories, telecommunication towers, railway switching centre and 24-hours shoplets. It also
extends the operating lifetime of existing air conditioning units.

Preset Switching
Time: 3 hours

Sequential control by For sequential control of


Sequential Network 2 indoor units at alternate
Interface Module (S-NIM) sequence of pre-set hour S-NIM S-NIM
S-NIM S-NIM

ON OFF

Operation and surveillance


is carried out using the
Control by external contact signal from the
command using BAG operation control box in BAG BAG BAG
the building surveillance
(security) room.
BMS

After 3 hours

Group control by Network Interface Module (NIM)


The NIM group controls consist of:• Mainboard S-NIM S-NIM
• Mainboard
• Control panel (BRC51A62)
• NIM controller OFF ON

• Communication bus

NIM utilizes master-slave configurations. One master can control up to 15 slave


units in a group. The master unit operates in conjunction with a control panel. Any
settings done via the control panel connected to the master overwrite the settings
of its slave units. Slave units can be operated with or without control panel. If a
slave unit is operating with a control panel, its settings can be changed without
following its master’s.
• DIP switch setting for group and unit address
• Automatic detection of control panel
• Error codes and error unit’s ID indication on control panel
• Supported configurations of NIM: When the operating unit is faulty, the standby unit automatically takes over. Other features of S-NIM:
• Auto restart feature with last state settings.
Master Slave • Error indication via error code display on the control panel.
NIM controller BRC51A62 • Pre-set operation hours via DIP switch.
BRC52A62 • Maximum point to point distance of 1000m.

15 16
Specification Specification

Ceiling cassette 3x3 Floor standing


50 60 71 100 125 71 100 125 140
Indoor unit FCRN50AXVL FCRN60AXVL FCRN71AXVL FCRN100AXVL FCRN125AXVL9 Indoor unit FVRN71AXVL FVRN100AXVL FVRN125AXVL9 FVRN140AXVL9
Model Outdoor unit RR50AGXVL RR60AGXVL RR71AGXVL RR100AGXVL RR125AGXTL9 Model
Outdoor unit RR71AGXVL RR100AGXVL RR125AGXTL9 RR140AGXTL9
Decorative panel BC50F2XWA
Btu/hr 29000 36000 48000 56000
Nominal cooling capacity
Btu/hr 18500 24000 29500 36000 48000 Nominal cooling capacity
kW 5.42 7.03 8.65 10.55 14.07 kW 8.50 10.55 14.07 16.41
Nominal total input power W 1730 2400 3130 3700 5100 Nominal total input power W 3130 3800 5000 6240
Nominal running current A 7.9 11.0 14.3 16.8 14.8 Nominal running current A 13.7 17.3 14.5 18.8
EER W/W 3.13 2.93 2.76 2.85 2.76
Power Supply
EER W/W 2.72 2.78 2.81 2.63
V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/3/60
Airflow (H/M/L/Q) cfm 730/620/510/360 840/700/560/440 890/760/620/490 1120/1030/890/760 1120/1030/890/760 Power Supply V/Ph/Hz 220/1/60 220/1/60 220/3/60 220/3/60
Sound pressure level (H/M/L/Q) dB(A) 39/35/33/30 41/38/36/34 43/40/38/37 48/45/41/37 49/46/42/38 Airflow (H/M/L/Q) cfm 675/625/530 1035/945/845 1035/935/835 1170/1085/985
Indoor Unit mm 246x840x840 246x840x840 246x840x840 288x840x840 288x840x840 Indoor Sound pressure level (H/M/L) dB(A) 44/42/39 49/47/44 50/48/46 54/53/51
Dimensions (HxWxD)
unit With decoration panel mm 301x950x950 301x950x950 301x950x950 343x950x950 343x950x950
unit Dimensions (HxWxD) mm 1850x600x270 1850x600x350 1850x600x350 1850x600x350
Unit kg 22 22 22 25 25
Machine weight Machine weight kg 42 45 48 51
Decoration panel kg 27 27 27 30 30
Sound pressure level dB(A) 50 50 57 61 66 Sound pressure level dB(A) 57 61 66 66
Outdoor
Dimensions (HxWxD) mm 651x855x328 651x855x328 753x855x328 852x1030x400 852x1030x400
Outdoor
unit Dimensions (HxWxD) mm 753x855x328 852x1030x400 852x1030x400 852x1030x400
Machine weight kg 43 43 57 71 87 unit
Machine weight kg 57 71 87 101
Liquid (Flare) Inch ø1/4" ø1/4" ø3/8" ø3/8" ø3/8"
Piping connections Liquid (Flare) Inch ø3/8" ø3/8" ø3/8" ø3/8"
Gas (Flare) Inch ø1/2" ø5/8" ø5/8" ø5/8" ø5/8"
Piping connections
Max. Interunit piping length m 30 30 50 50 50 Gas (Flare) Inch ø5/8" ø5/8" ø5/8" ø3/4"
Max. Installation level difference m 15 15 25 30 30 Max. Interunit piping length m 50 50 50 50
Max. Installation level difference m 25 30 30 30

Duct connection standard static pressure type Ceiling suspended


100
125 140 160
50 60 71 100 125 140
Indoor unit FDMRN50AXVL FDMRN60AXVL FDMRN71AXVL FDMRN100AXVL FDMRN125AXVL9 FDMRN140AXVL9 Model Indoor
Indoorunit
unit FHRN100AXVL
FHRN125AXVL FHRN140AXVL9
FHRN160AXVL
Model Model
Outdoor unit RR50AGXVL RR60AGXVL RR71AGXVL RR100AGXVL RR125AGXTL9 RR140AGXTL9 Outdoor
Outdoorunit
unit RR100AGXVL
RR125AGXVL RR140AGXTL9
RR160AGXTL
Btu/hr 18500 23500 29000 36000 48000 56000 Btu/hr 35000 56000
Nominal cooling capacity Nominal coolingcapacity
Nominal cooling capacity Btu/hr 35000 56000
kW 5.42 6.89 8.50 10.55 14.07 16.41 kW 10.26 16.41
Nominal total input power W 1730 2400 3330 4000 5520 6590 kW 10,26 16,41
Nominal total input power W 3800 6240
Nominal running current A 7.9 11.0 15.3 18.2 15.6 19.5 Nominal total input power W 3800 6240
EER W/W 3.13 2.87 2.55 2.64 2.55 2.49
Nominal running current A 17.3 18.8
Nominal running current A 17,3 18,8
Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/3/60 220/3/60 EER W/W 2.70 2.63
EER
Power Supply W/W
V/Ph/Hz 2,70
220/1/60 2,63
220/3/60
Airflow (H/M/L/Q) cfm 590/520/320 690/570/440 900/830/640 1250/980/780 1540/1280/1100 1580/1330/1180
External static pressure (H/M/L) Pa 50 50 100 100 100 100 Power Supply
Airflow (H/M/L) V/Ph/Hz
cfm 220/1/60
1107/999/751 220/3/60
1550/1380/1000
Indoor
Sound pressure level (H/M/L) dB(A) 40/38/33 42/40/39 47/45/42 50/47/43 51/48/46 52/50/47 Indoor
Indoor Sound pressure level (H/M/L) dB(A) 49/46/43 56/54/51
unit
Dimensions (HxWxD) mm 261x1065x411 261x1200x411 378x929x541 378x1045x541 378x1299x541 378x1499x541 unit Airflow (H/M/L) cfm 1107/999/751 1550/1380/1000
unit Dimensions (HxWxD) mm 235x1903x680 285x1903x680
Machine weight kg 24 26 42 44 50 56
Sound pressure
Machine weight level (H/M/L) dB(A)
kg 49/46/43
52 56/54/51
70
Sound pressure level dB(A) 50 50 57 61 66 66
Outdoor Dimensions (HxWxD) mm 235x1903x680 285x1903x680
Dimensions (HxWxD) mm 651x855x328 651x855x328 753x855x328 852x1030x400 852x1030x400 852x1030x400 Sound pressure level dB(A) 61 66
unit Outdoor
Machine weight kg 43 43 57 71 87 101 Machine weight
Dimensions (HxWxD) kg
mm 52
852x1030x400 70
852x1030x400
Liquid (Flare) Inch ø1/4" ø1/4" ø3/8" ø3/8" ø3/8" ø3/8" unit
Piping connections Outdoor Machine
Sound pressure
weight level dB(A)
kg 7161 10166
Gas (Flare) Inch ø1/2" ø5/8" ø5/8" ø5/8" ø5/8" ø3/4"
Dimensions (HxWxD) Liquid (Flare) mm
Inch 852x1030x400
ø3/8" 852x1030x400
ø3/8"
Max. Interunit piping length m 30 30 50 50 50 50 Piping connections
Max. Installation level difference m 15 15 25 30 30 30 Machine weight Gas (Flare) Inch
kg ø5/8"
71 ø3/4"
101
Max. Interunit piping length Liquid (Flare) m
Inch 50
ø3/8" 50
ø3/8"
Piping connections
Max. Installation level difference Gas (Flare) m
Inch 30
ø5/8" 30
ø3/4"
Max. Interunit piping length m 50 50
Max. Installation level difference m 30 30

Rated cooling capacities are based on the following conditions: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; piping length: 7.5m

17 18