Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CONTROLS
INSTRUCTIONS
E2008 Lennox Industries Inc. 505103M Commercial Touch
Dallas, Texas, USA
11/08
Supersedes 01/2007 Screen Thermostat
3. Installer must be a trained, experienced ser-
Application vice technician.
The Lennox Commercial Touchscreen Thermo- 4. After installation is complete, check out prod-
stat provides electronic control of 24 Vac heating uct operation as provided in these instruc-
and cooling systems. See Table 1 for a descrip- tions.
tion.
Table 1. Thermostat Description CAUTION
Feature Description
Electrical Shock or Equipment Damage haz-
Powering S Battery only ard.
Methods
S Direction connection to a 24 Vac Can shock individuals or short equipment
transformer only. circuitry.
S Direct connection to a 24 Vac Disconnect power supply before installation.
transformer with battery backup.
System S Conventional (up to 2 heat, 2 cool Select Thermostat Location
Types stages) Select a location for the thermostat about 5 feet
S Heat Pump (up to 3 heat, 2 cool (1.5m) above the floor in an area with good air cir-
stages) culation at average temperature (see figure 1).
Changeover Manual or automatic changeover (se-
lectable)
System Set- Heat−Off−Cool−Auto
tings
YES NO
NO 5 FEET
MERCURY NOTICE (1.5 METERS)
11/08
*2P1108* 62-0227-02
Separate Wallplate from Thermostat Wiring
Separate the wallplate from the thermostat (see fig-
ure 2). IMPORTANT
− All wiring must agree with applicable codes, ordi-
WALLPLATE nances and regulations
WIRE HOLE
− Use 18 gauge thermostat wire. Shielded cable is
not required.
NOTES −
− Sensor wires must have a cable separate from
the thermostat control cable.
− Refer to Table 2 for terminal designation descrip-
tions.
− See figure 7 through 10 for wiring diagrams from
THERMOSTAT specific equipment applications.
M22267 1. Select conventional set of terminal identifica-
tions which correspond to the system type
Figure 2. − Separate Wallplate from Thermostat (conventional or heat pump (see figure 4).
Install Wallplate Lennox commercial equipment does not use
the heat pump system terminals.
Install the thermostat horizontally on the wall (see
HEAT PUMP
figure 3):
CONVENTIONAL
1. Pull the wires through the wire hole on the
wallplate.
2. Position the wallplate on the wall with the arrow Y2 Y2 RC
RC
L L R
pointing up. Level the wallplate for appearance A
R
O/B
A W
only. W1 W2 Y
Y
3. Use a pencil to mark the mounting holes. S1 S1 G G
S2 S2 C C
WA L L SCREW
TERMINALS
WIRES THROUGH WALL
AND WIRE SLOT Figure 4. Terminal Identifications for System
WALL ANCHORS (2) Type
2. Loosen screw terminals used for the applica-
tion.
3. Insert the wires into the terminal block and
tighten each screw terminal (see figure 5).
MOUNTING
HOLES
MOUNTING
SCREWS (2)
M19916
Terminal
Designation Description
Rc Power for cooling−connect to secon-
(see note 1) dary side of cooling system trans-
former.
R Power for heating−connect to secon-
(see note 1) dary side of heating system trans-
former.
Y Compressor output.
C Command wire from secondary side
(see note 2) of cooling system transformer.
W Heat relay.
WALL OPENING
G Fan relay.
SHADED AREA
W2 Second stage heat relay.
Y2 Second stage cooling. Figure 6. Restrict Wires to Shaded Area of Wire
Hole
O/B Changeover valve for heat pumps.
(see note 3) Terminal not used with Lennox com- Terminal A Wiring Details for Economizers
mercial equipment.
S Wire the A" terminal as shown in diagrams in
A Economizer/Time−of−Day (TOD) out-
(see note 4) put−powered via R terminal. figures 7, 8, 9 and 10.
S1 Optional outdoor or indoor remote S The A" signal is powered from the R" termi-
(see note 5) sensor. nal and energizes the economizer to signal
S2 Optional outdoor or indoor remote occupied status and drive the damper to the
(see note 5) sensor. set minimum position.
L Powers red LED behind plastic in
A2 THERMOSTAT UNIT TB1
upper right corner of the thermostat.
NOTES −
1 When used in a single−transformer system, leave
metal jumper wire in place between Rc and R. If used
on a two−transform system, remove metal jumper
wire between Rc and R.
2 Common wire is optional when thermostat is used
with batteries. When using separate transformer for
heating and cooling, the common must come from
the cooling transformer.
3 Lennox commercial heat pumps do not use this
terminal to energize the reversing valve. Thermostat
will always be conventional type.
4 Reference economizer literature for wiring details.
When set for economizer operation, the A terminal
provides the occupancy signal. (Power indicates oc-
cupied.)
5 Sensor wires must have a cable separate from
the thermostat control cable. Figure 7. Wire LG/LC/LH/SG/SC Units.
Page 3 62-0227—02
A2 UNIT TB1 SUBBASE SUBBASE
THERMOSTAT
SUBBASE
SUBBASE
20K Ohm
A2 UNIT TB1
THERMOSTAT
DONE
BATTERIES (3)
REMOVE
TAB
REMOVE DURING
INSTALLATION
PM
DONE
Powerup
Page 5 62-0227—02
3. The Setup Number displays to the lower−left
Advance Settings area of the screen. It is a four−digit code begin-
The thermostat has advanced settings to match the ning with zero. The current setting is dis-
HVAC system. These settings can be adjusted to played to the right.
match specific needs. Access to these settings is NOTE − To cycle through the Setup Numbers,
obtained as follows: press the up or down arrow.
1. From the main screen, press SYSTEM. Five
blank touch keys show on the bottom on the
screen between DONE and CANCEL. Installer Setup Numbers, Settings
2. Press and hold the two blank keys on either and Tests
side of the center blank key for approximately
five seconds (see figure 16).
Installer System Tests
Use setup numbers in table 3 setting up the thermo-
stat.
MO SA SU Use the Installer system test to test the heating,
In si de Se t To
cooling and fan (see table 4).
S Y ST E
M
EM
HEAT
Followin g
Sc h edu l e
CAUTION
OF F Equipment Damage hazard.
DO
N E CANC
Minimum compressor off time is bypassed
during installer system test.
Avoid cycling compressor quickly.
Page 7 62-0227—02
Table 3. Installer Setup Menu
Installer Installer Default
Setup No. Setup Name Setting All Settings Notes
0− Off
Minimum 2− 2 minutes
Only shown if system has cool stages. Set to
0580 Compressor 0 3− 3 minutes
0. Not needed for 3 phase systems.
Off Time 4− 4 minutes
5− 5 minutes
Heat Tempera-
0600 ture Range 90 40 to 90° F (4 to 32° C) Only shown if system has heat stages.
Stops
Cool Tempera-
0610 ture Range 50 50 to 99°F (10 to 37°C) Only shown if system has cool stages.
Stops
0640 Clock Format 12 12−12 Hour 24− 24 Hour
Extended Fan− 0−Off Not displayed with fan set to fossil or with cool−
0650 0
on time Heat 90− 90 seconds only systems.
Extended Fan− 0−Off
0660 0 Only shown if system has cool stages.
on time Cool 40− 40 seconds
Unlocked: All functions accessible.
0−Unlocked
Partial 1: Locks all but Holiday, Override, and
Keypad Lock- 1−Partial Lockout 1
0670 0 Up/Down.
out 2−Partial Lockout 2
Partial 2: Locks all but Holiday and Override.
3−Fully Locked
Full: Entire interface locked/non−functional.
Only shown if system has heat stages.
Only integral gains affected. Affects control
1−Less Aggressive operation in all control regimes (not just recov-
Temperature
0680 2 2−Standard ery or setpoint change).
Control Heat
3−More Aggressive More Aggressive stops signal prior to reaching
the setpoint. (For use with oversized equip-
ment.)
Only shown if system has cool stages.
Only integral gains affected. Affects control
1−Less Aggressive operation in all control regimes (not just recov-
Temperature
0690 2 2−Standard ery or setpoint change).
Control Cool
3−More Aggressive More Aggressive stops signal prior to reaching
the setpoint. (For use with oversized equip-
ment.)
Recovery Only shown if system has heat stages.
0685 Heat Ramp 5 0−20°F/hour 0 disables ramped recovery (step setpoint
Rate change at period start time).
Only shown if system has cool stages.
Recovery Cool
0695 3 0−20°F/hour 0 disables ramped recovery (step setpoint
Ramp Rate
change at period start time).
−3 (−1.5) −3°F(−1.5°C)
−2 (−1.0)− −2°F (−
1.0°C)
This offset applies to both the control tempera-
Temperature −1 (−0.5)− −1°F (−0.5°C)
0700 0 ture and to the display temperature for indoor
Display Offset 0 (0.0)−0°F (0.0°C)
sensor (and remote indoor sensor).
1 (0.5)−1°F (0.5°C)
2 (1.0)− 2°F (1.0°C)
3 (1.5)−3°F (1.5°C)
Resets all ISU parameters to default values
Restore Fac- 0 −No
0710 0 and resets the schedule to default Energy Star.
tory Defaults 1−Yes
Retains only calendar settings and time.
Page 9 62-0227—02
Table 4. Installer Tests Table 5. Energy Star Default Program Settings
Schedule Setpoints Fan
Period Time Setting
0−Off Heat Cool
Test
Test Cool 0 1−Cool Stage 1
1 08:00 70oF 75oF
2−Cool Stage 2 Occ1 Auto
am (21oC) (24oC)
Test 0−Off
Test Fan 0
2 1−Fan On 10:00 55oF 85oF
Unocc1 Auto
pm (10oC) (29.5oC)
0−Off
Test 1−Heat Stage 1 Occ2 a −−−−
Test Heat 0
3 2−Heat Stage 1 and 2
3− Heat Stage 1, 2 and 3 Unocc2a −−−−
Test Auxiliary 0−Auxiliary Heat Off a The thermostat default setting is two period only. To
0 use four periods, change the appropriate setup pa-
4 Heat 1−Auxiliary Heat On
rameter.
Test TOD/ 0−TOD/Economizer Off
0
8 Economizer 1−TOD/Economizer On
Outdoor or indoor temperature
NOTE − Press the Done button to exit the Installer sensor
System Test.
Allow outdoor or indoor temperature sensor to ab-
sorb the air for a minimum of five minutes before
taking a reading. See the Sensor instructions for
more information.
Off Both heating and cooling systems are off. Yes De−energized
Unoccupied
No De−energized
Cool Thermostat controls the cooling system.
Override − Energized
Auto Thermostat automatically changes be-
tween heat and cool operation, depending on in-
door temperature.
Allow outdoor or indoor temperature sensor to ab-
sorb the air for a minimum of five minutes before
Fan Settings taking a reading. See the Sensor instructions for
Auto Fan runs only when heating/cooling system more information.
is on. On−Fan runs continuously.
Troubleshooting
Table 5 shows default program settings. See Own-
er’s Guide for complete instructions to change the Table 7 lists symptoms, causes and actions to take
program. to remedy problems.
Page 11 62-0227—02
Table 7. Troubleshooting
Symptom Possible Cause Action
Heating equipment is not
a heat pump but System
Heating equipment is run- Set System Type (Installer Setup Number 0170) to
Type (Installer Setup
ning in the cool mode. match the installed heating and/or cooling equipment.
Number 0170) is set to
Heat Pump.
Heating equipment does
Heating equipment is not
not turn off and heat tem-
a heat pump but System
perature setting is set be- Set System Type (Installer Setup Number 0170) to
Type (Installer Setup
low room temperature match the installed heating and/or cooling equipment.
Number 0170) is set to
(Heat On is not in the dis-
Heat Pump.
play).
System Type (Installer
Cannot set the system Set System Type (Installer Setup Number 0170) to
Setup Number 0170) is
setting to Heat. set to Cool Only. match the installed heating and/or cooling equipment.
Shipping Temperature:
Specifications
−30°F to 150°F (−34.4°C to 65.6°C).
Electrical Ratings: Operating Relative Humidity (Non−condensing):
W (Heating) 20 − 30 Vac 0.02 − 1.0A 5% to 90%.
Y (Cooling) 20 − 30 Vac 0.02 − 1.0A Thermostat Dimensions: 3−3/4 in. (95mm) high x 6
G (Fan) 20 − 30 Vac 0.02 − 0.60A in. (152mm) wide x 1−3/8 in. (35mm) deep.
A (Economizer/TOD) 20 − 30 Vac 0.02 − 1.0A Accessories:
− X4148 Outdoor Sensor: 10K ohm NTC
Temperature Setting Range:
Heating: 40°F to 90°F (4.5°C to 32°C). − 47W36 Wall−Mount Remote Indoor Sensor 20K
Cooling: 50°F to 99°F (10°C to 37°C). ohm
Operating Ambient Temperature: − 47W37 Wall−Mount Remote Indoor Sensor 10K
0°F to 120°F (−18°C to 49°C). ohm