Sei sulla pagina 1di 95

Revision History

02/06/2007 Initial Release


05/06/2007 Added disclaimer
13/06/2007 Corrected errors in Partial volume calculation for Enclosures. Added calculation of top-down and bottom up when
02/07/2007 Corrected error in volume calculation for cylindrical hoppers.
03/07/2007 Corrected spherical vessel to show L/D always 1. Changed all L/D calculation formulae to allow calculating L/D<1
02/11/2007 Updated comments to reflect TIA Task Group modification of limits on Threshold Mass Equation
12/02/2008 Updated High Strength Dust solver cell formula per comments received. No change in results.
21/04/2008 Added notes in L/D tab to explain top-mounted vent application.
08/07/2008 Added guidance in Dust Enclosures tab describing duct diameter used for calculation and maximum 1.5 times are
29/07/2008 Changed L/D tab note 3) to correctly state that total enclosure volume is used for vent sizing with a single vent, no
Added new Note 4) to address multiple vents along central axis and renumbered subsequent notes.
Added check of Bottom-Up vs Top-Down total enclosure volume
Added check of calculated vent area versus effective area (cross-section for round or square enclosures)
29/10/2008 Revised L_D tab description of top-Down and Bottom-Up calculations to clarify.
Added a check for zero length above top-mounted vent in L_D tab so it eliminated div/zero error in Aeff calculation
26/11/2008 Corrected Partial Volume formula in Dust-Bldgs tab so Av4 equals Av3 when fill fraction is greater than 1 (was alr
Modified Partial Volume formula in Annex Vent Panel Inertia tab to highlight that Av3 is not used in that method
Added YES/NO selection for evenly distributed vents in High Str Gas and Dust Building tabs. Enclosure tabs use
01/06/2009 Add conditional restraint to VDI High Strength Gas equation. If Pstat is <0.1 bar, the second term in the equation

Throughout this document,


1. Green highlighted cells are for input
2. Yellow highlighted cells are calculated from other inputs
3. Purple highlighted cells are for copying and pasting from the L/D tab into the other tabs using Paste-Sp
4. Red highlighted cells appear in some places when a calculated value is out of allowed bounds. This is
22/01/2013 Add 2012 Equations with Rota calculation of Lambda based on Radius (as in original paper)
on of top-down and bottom up when vent is in side (pick longest L/Dhe). Added spherical vessel L/D. Corrected calculation of vented volu

n formulae to allow calculating L/D<1, but with warning format.


old Mass Equation
change in results.

culation and maximum 1.5 times area for vent ducts


for vent sizing with a single vent, no matter where vent is placed.
red subsequent notes.

ound or square enclosures)

ated div/zero error in Aeff calculation for top-down propagation.


fill fraction is greater than 1 (was already correct in Dust-Enclosures tab)
hat Av3 is not used in that method
st Building tabs. Enclosure tabs use L/D tab for input, but building tabs otherwise assume venting at one end of longest dimension.
bar, the second term in the equation is set equal to zero (not allowed to be negative)

nto the other tabs using Paste-Special-Values


is out of allowed bounds. This is not yet universal.
as in original paper)
calculation of vented volume to be entire section volume, not Veff (Veff is only used to determine the worst case L/D to the vent location)

ongest dimension.
L/D to the vent location)
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the methods

NFPA 68-2007 Evaluate L/D for Equipment Shapes

Calculate the Vent Area for each section of the Enclosure or for the whole enclosure
Notes:
1) The original printed version of the annex inserts the incorrect diameter of the conical hopper top into the eq
2) Placing a single vent somewhere along the central axis does not change the volume to be vented, but changes the
3) When a single vent is used, the volume to use in the vent area equations is the entire enclosure volume, no
4) When multiple vents are placed along the central axis, the volume to use in the vent area equations is the s
5) When subdividing along original central axis, at the point the section Length equals Dhe, then L/D=1.
6) Closer placement of vents does not reduce L/D or change the orientation of the axis, since the subdivision
7) When vents are placed such that L/D is less than or equal to 2, there is no further reduction in required vent area/se
8) For Dust Collectors, if the Volume between bags is considered, then look at a top-down height and calculate a sma

Rectangular Vessels with 1 Vent at end of section (no hopper extension)

Length 2 meters The longest distance from one end of the vessel to the opposite end of the vent.
Width 1 2 meters (Measured along central axis)
Width 2 2 meters
Volume 8 cubic meters

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). With only one vent, enter the longest distance from one end of the vessel to the
opposite end of the vent.

H 2 meters
Aeff 4 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape

p 8 meters
Dhe 2 meters

L/D 1 L/D can not be less than 1, by definition

Summary Block for Copying values


Length (H) 2 meters
Volume (V) 8 cubic meters
Area (Aeff) 4 square meters
Diameter (Dhe) 2 meters

Rectangular Vessels with Rectangular Hopper Extension


Calculate L/D for Bottom-up Flame Propogation
Volume above Top of Vent (not included in Effective Volume for L/D)
Length 1 meters The distance from the top of the vessel to the top of the vent.
Width a2 1.8 meters Dimension of straight side
Width b2 1.5 meters Dimension of opposite straight side
Volume 2.7 cubic meters Volume of Rectangular Section above the vent
If the Vent is mounted horizontally on the top of vessel, then B47 should be set to zero.
Length 3 meters The distance from the top end of the vent to the top end of the Rectangular Hopper.
Width a2 1.8 meters Dimension of straight side
Width b2 1.5 meters Dimension of opposite straight side
Volume 8.1 cubic meters Volume of Rectangular Section
If no Hopper, then B57 should be set to zero.
Height h 2 meters The distance from the top to the bottom of the the Rectangular Hopper
Width a1 0.5 meters Dimension of Rectangular Hopper bottom (same side as B48)
Width b1 0.3 meters Dimension of Rectangular Hopper bottom (same side as B49)
Volume 2.33 cubic meters Volume of Rectangular Hopper Section

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). With only one vent, enter the longest distance from one end of the vessel to the
opposite end of the vent.

H 5 meters
Veff 10.43 cubic meters
Aeff 2.086 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape above the hopper

Aspect 1.2 ratio a/b This uses the aspect ratio of the above rectangular section
Side a 1.5821504 meters
Side b 1.3184587 meters
p 5.8012183 meters
Dhe 1.4383186 meters

L/D 3.4762813 Bottom-up L/D can not be less than 1, by definition

Calculate L/D for Top-down Flame Propogation


If the Vent is mounted horizontally on the top of vessel, then B81 should be set to zero.
Length 2.5 meters The distance from the top of the vessel to the bottom of the vent (estimated 2.5 from picture)
Width a2 1.8 meters Dimension of straight side
Width b2 1.5 meters Dimension of opposite straight side
Volume 6.75 cubic meters Volume of Rectangular Section above the vent
Volume below Bottom of Vent (not included in Effective Volume for L/D)
Length 1.5 meters The distance from the bottom of the vent to the top of the Rectangular Hopper.
Width a2 1.8 meters Dimension of straight side
Width b2 1.5 meters Dimension of opposite straight side
Volume 4.05 cubic meters Volume of Rectangular Section
If no Hopper, then B91 should be set to zero.
Height h 2 meters The distance from the top to the bottom of the the Rectangular Hopper
Width a1 0.5 meters Dimension of Rectangular Hopper bottom (same side as B82)
Width b1 0.3 meters Dimension of Rectangular Hopper bottom (same side as B83)
Volume 2.33 cubic meters Volume of Rectangular Hopper Section
The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). With only one vent, enter the longest distance from one end of the vessel to the
opposite end of the vent.

H 2.5 meters
Veff 6.75 cubic meters
Aeff 2.7 sq meters If vent is mounted on top, sets Aeff=a2*b2

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape above the hopper

Aspect 1.2 ratio a/b This uses the aspect ratio of the above rectangular section
Side a 1.8 meters
Side b 1.5 meters
p 6.6 meters
Dhe 1.6363636 meters

L/D 1.5277778 Top-Down L/D can not be less than 1, by definition

Determine Worst-Case (either Top-Down or Bottom-up) for L/D (H/Dhe), Total Volume is the same
L/D(max) 3.4762813 Bottom-up

Summary Block for Copying values


Length (H) 5 meters Check Volume Calculation Top-Down
Volume (V) 13.13 cubic meters 13.13 cubic meters
Area (Aeff) 2.086 square meters
Diameter (Dhe) 1.4383186 meters

Cylindrical Vessels with 1 Vent at end of section (no hopper extension)

Length 4.5 meters


Diameter 2.01 meters
Volume 14.278892 cubic meters

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). This assumes all venting at one end.

H 4.5 meters
Aeff 3.1730871 sq meters
The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape

Dhe 2.01 meters

L/D 2.238806 L/D can not be less than 1, by definition


Summary Block for Copying values
Length (H) 4.5 meters
Volume (V) 14.278892 cubic meters
Area (Aeff) 3.1730871 square meters
Diameter (Dhe) 2.01 meters

Cylindrical Vessels with Conical Hopper Extension


Calculate L/D for Bottom-up Flame Propogation
Volume above Top of Vent (not included in Effective Volume for L/D)
Length 2 meters The distance from the top of the vessel to the top of the vent.
Diam 1 1.8 meters Diameter of larger cylindrical cross-section
Volume 5.0893801 cubic meters Volume of Cylindrical Section
If the Vent is mounted horizontally on the top of vessel, then B149 should be set to zero.
Length 2 meters The distance from the top of the vent to the top end of the Conical Hopper.
Diam 1 1.8 meters Diameter of larger cylindrical cross-section
Volume 5.0893801 cubic meters Volume of Cylindrical Section
If no Hopper, then B157 should be set to zero.
Height h 2 meters The distance from the top to the bottom of the the Conical Hopper
Diam 2 0.5 meters Diameter at bottom of Conical Hopper
Volume 2.2985986 cubic meters Volume of Cylindrical Hopper Section

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). With only one vent, enter the longest distance from one end of the vessel to the
opposite end of the vent.

H 4 meters
Veff 7.3879787 cubic meters
Aeff 1.8469947 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape above the hopper

Dhe 1.5335145 meters

L/D 2.6083875 Bottom-Up L/D can not be less than 1, by definition

Calculate L/D for Top-down Flame Propogation


If the Vent is mounted horizontally on the top of vessel, then B179 should be set to zero.
Length 3.5 meters The distance from the top of the vessel to the bottom of the vent (estimated from picture)
Diam 1 1.8 meters Diameter of larger cylindrical cross-section
Volume 8.9064152 cubic meters Volume of Cylindrical Section
Volume below Bottom of Vent (not included in Effective Volume for L/D)
Length 0.5 meters The distance from the bottom of the vent to the top end of the Conical Hopper.
Diam 1 1.8 meters Diameter of larger cylindrical cross-section
Volume 1.272345 cubic meters Volume of Cylindrical Section
If no Hopper, then B187 should be set to zero.
Height h 2 meters The distance from the top to the bottom of the the Conical Hopper
Diam 2 0.5 meters Diameter at bottom of Conical Hopper
Volume 2.2985986 cubic meters Volume of Cylindrical Hopper Section

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). With only one vent, enter the longest distance from one end of the vessel to the
opposite end of the vent.

H 3.5 meters
Veff 8.9064152 cubic meters
Aeff 2.54469 sq meters If vent mounted on top, sets Aeff=PI/4*(Diam 1)^2

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape above the hopper

Dhe 1.8 meters

L/D 1.9444444 Top-Down L/D can not be less than 1, by definition

Determine Worst-Case (either Top-Down or Bottom-up) for L/D (H/Dhe), Total Volume is the same
L/D(max) 2.6083875 Bottom-Up

Summary Block for Copying values


Length (H) 4 meters Check Volume Calculation Top-Down
Volume (V) 12.477359 cubic meters 12.477359 cubic meters
Area (Aeff) 1.8469947 square meters
Diameter (Dhe) 1.5335145 meters

Spherical Vessels with 1 Vent

Diameter 2 meters
Volume 4.1887902 cubic meters

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). This assumes all venting at one end.

H 2 meters
Aeff 2.0943951 sq meters

Set Dhe = D in order that L/D=1

Dhe 2 meters

L/D 1 L/D = 1 for sphere, by definition


Summary Block for Copying values
Length (H) 2 meters
Volume (V) 4.1887902 cubic meters
Area (Aeff) 2.0943951 square meters
Diameter (Dhe) 2 meters
ny implied warranty or guarantee.

verify that the methods and equations are consistent with the controlling NFPA standard.

cal hopper top into the equations.


e vented, but changes the effective worst/case L/D correction.
re enclosure volume, no matter where the vent is placed.
nt area equations is the section volume (Veff).

s, since the subdivision is only virtual walls, not real ones.


on in required vent area/section volume.
height and calculate a smaller Dhe, larger L/D for the bag section.

nd of the vent.
ctangular Hopper.

estimated 2.5 from picture).

ular Hopper.
lation Top-Down (Volume must be same)
estimated from picture)
lation Top-Down (Volume must be same)
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the methods

NFPA 68-2007 Gases in Buildings - Low Strength Method


Low Strength Method limited to Su of 60 and KG of 130

Room Dimensions
Length 7.5 meters Example Data Su KG
Width 3 meters Acetone 54
Height 4 meters Isopropanol 41 83
Volume 90 cubic meters Methanol 56 75
Ethanol 78
Internal Surface Area for Flat Walls and Ceiling
Floor 22.5 meters
Roof 22.5 meters
Walls 84 meters
As 129 square meters

Material Alcohol/Methanol (Methanol worse than acetone) Su is the Fundamental Burning Velocity, KG is the Deflagr
Su 56 cm/sec from NFPA-68 annex If KG not available, estimate from Su as below and enter a
KG 75 bar-m/sec from NFPA-68 annex
Basis is KG = 100, Su=4

Calculate C factor, in bar^(0.5) KG 121.73913 bar-m/sec estimated from NFPA-68


C = 1.57 x 10 (Su) + 1.57 x 10 (Su) + 0.0109
-5 2 -4

C factor 0.0689272

Calculate Low Inertia Vent Area

Pred is the maximum pressure developed during the explosion and must be less

Pred
Assumed 100 psf = 0.04788 bar US 100 psf
Pred 0.04788 bar Metric = 0.0478803 bar

Av 40.635282 square meters

Pstat (max)
Pstat is the static release pressure of the vent and must be at least 0.024 bar (0.35 psi) bar less than Pred

Pstat 0.02388 bar This is the largest allowable Pstat, it can be less than this.
The specific value of Pstat is not used in this correlation.

Check for L/D less than 3 (Quiescent)


The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central
axis flame length). This assumes all venting at one end.
H 7.5 meters
Aeff 12 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the
general shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape
p 14 meters
Dhe 3.4285714 meters

L/D 2.1875 If L/D exceeds 3, vents must be placed along longest dimension

Inertia Correction for Materials with KG < 130 bar-m/sec and Panel Mass < 40 kg/m^2

Correction for inertia is limited to KG < 130 bar-m/sec and panel mass < 40 kg/m^2. If actual panel mass is less than MT, then
is larger than the exterior wall of the room, one can either include roof area for venting or increase the containing walls and floo
them stronger.
n 1 number of panels

Mformula 429.90299 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above. If greater than 40 kg/m^2, consult an exp

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
M 40 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter here and e
Metric = 39.1 kg/m^2

ΔA 0 sq meters If M < MT, then there is no area correction for inertia


Av 40.6 sq meters

Buildings do not generally have vent ducts, so this is not included here.
ny implied warranty or guarantee.

verify that the methods and equations are consistent with the controlling NFPA standard.

Velocity, KG is the Deflagration Index.


m Su as below and enter at left:

Basis is KG = 100, Su=46 for propane

estimated from NFPA-68

xplosion and must be less than the room wall strength.


mass is less than MT, then no correction is needed. If Av
e containing walls and floor Pred values, that is make

40 kg/m^2, consult an expert

US units, enter here and enter metric units at left


Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the methods

NFPA 68-2007 Gases in Buildings - High Strength Method

Room Dimensions
Length 6.91896 meters Example Data Su KG
Width 6.30936 meters Acetone 54
Height 4.48056 meters Isopropanol 41 83
Volume 195.5953 cubic meters Methanol 56 75
Ethanol 78
Internal Surface Area for Flat Walls and Ceiling Hydrogen 550
Floor 43.654209 meters
Roof 43.654209 meters If KG not available, estimate from Su as below and enter a
Walls 118.54056 meters
As 205.84898 square meters Basis is KG = 100, Su=4

Material Propane
Su 0 cm/sec from NFPA-68 annex
KG 100 bar-m/sec from NFPA-68 annex KG 0 bar-m/sec estimated from NFPA-68

Pred
Pred is the maximum pressure developed during the explosion and must be less than the room wall strength.
The high strength method is intended for use at building design pressures of greater than 0.1 bar.

Assumed 313 psf = 0.15 bar US 313 psf


Pred 0.1 bar Metric = 0.1498652 bar

Pstat
Pstat is the static release pressure of the vent and must be > 0.1 bar and at least 0.05 bar less than Pred

Assumed 209 psf = 0.10 bar US 209 psf


Pstat 0.05 bar Metric = 0.1000697 bar

Cubical Vessel, Low Inertia Vent Area

A0=[(0.127 Log KG - 0.0567)*Pred^(-0.582) + 0.175 Pred^(-0.572)*(Pstat-0.1)]V^(2/3)


A0= 25.3921 Sq.Meters
where Limits
KG= 100 Bar M/sec <550
Pred= 0.1 Bar <2
Pstat= 0.05 Bar <0.5 If Red, Pstat is <0.1 and the formula is being used outside VDI bound
V= ### Cu.Meters <1000 When Pstat is <0.1, that part of formula is set to "zero"

Determine L/D
The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central axis
flame length). This assumes all venting at one end.
H 6.91896 meters
Aeff 28.269466 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the general
shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape
p 21.57984 meters
Dhe 5.2399769 meters

L/D 1 If Red, L/D has been set to "1" by entering a YES above.

L/D Correction
If L/D exceeds 2, a vent area correction is added

ΔA=A0* [KG (L/D-2)^2]/750


ΔA= 0.0000 Sq.Meters
where Limits
A0= 25.3921
KG= 100 Bar M/sec
L/D= 1 No Dimensions
A1=A0 + ΔA
A1= 25.3921 Sq.Meters

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to KG limit of the basic equation (i.e. KG=5

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
exterior wall of the room, one can either include roof area for venting or increase the containing walls and floor Pred values, th
n 1 number of panels

Mformula 1580.7337 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above. If greater than 40 kg/m^2, consult an exp

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
M 40 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter here and e
Metric = 39.1 kg/m^2

ΔA 0 sq meters If M < MT, then there is no area correction for inertia


Av 25.3921 sq meters
Buildings do not generally have vent ducts, so this is not included here.
ny implied warranty or guarantee.

verify that the methods and equations are consistent with the controlling NFPA standard.

This tab does not use the L/D tab for input values. Unless noted below, it is assumed that all venting is put on
the wall at the end of the longest dimension. If venting will be evenly distributed along the longest dimension,
such that L/D is evaluated as 1, enter YES in the cell below:
YES

m Su as below and enter at left:

Basis is KG = 100, Su=46 for propane

om NFPA-68 annex
estimated from NFPA-68

g used outside VDI bounds


ormula is set to "zero"
basic equation (i.e. KG=550 bar-m/sec)

n no correction is needed. If Av is larger than the


s and floor Pred values, that is make them stronger.

40 kg/m^2, consult an expert

US units, enter here and enter metric units at left


at all venting is put on
e longest dimension,
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the m

NFPA 68-2007 Gases in Enclosures - High Strength Method


Example Data
Enclosure Section Dimensions Acetone
(see L_D Tab to calculate these terms) Isopropanol
Methanol
Length (H) 4.5 meters Ethanol
Volume (V) 14.27889 cubic meters V<1000 (This is total volume, not Veff) Hydrogen
Area (Aeff) 3.173087 square meters
Diameter (Dhe) 2.01 meters If KG not available, estimat

KG is the deflagration index


Pred is the maximum pressure developed during the vented explosion
Pstat is the static release pressure of the vent panel
Su
Material Hydrogen KG

KG 550 bar-m/sec KG<550


Pred 0.19252 bar 0.1 bar<Pred<2 bar US 313
Pstat 0.1 bar 0.1 bar<Pstat<(Pred-0.05) and Pred<0.5 Metric = 0.1498652

Cubical Vessel, Low Inertia Vent Area

A0=[(0.127 Log KG - 0.0567)*Pred^(-0.582) + 0.175 Pred^(-0.572)*(Pstat-0.1)]V^(2/3)


A0= 4.4731 Sq.Meters Vent Area can not exceed cross-section (Aeff)

L/D Correction

L/D 2.238806 L/D<5


If L/D exceeds 2, a vent area correction is added

ΔA=A0* [KG (L/D-2)^2]/750


ΔA= 0.1871 Sq.Meters

A1=A0 + ΔA
A1= 4.6602 Sq.Meters Vent Area can not exceed cross-section (Aeff)

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to KG limit of the basic equation (i.e. KG=5

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
the room, one can either include roof area for venting or increase the containing walls and floor Pred values, that is make them
n 1 number of panels
Mformula 5.99021 kg/m^2
MT 5.99021 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
M 40 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter he
Metric = 39.1 kg/m^2 If greater than 40 kg/m^2, consult an e

ΔA 0.729949 sq meters If M < MT, then there is no area correction for inertia
Av 5.3901 sq meters Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect


As the vent duct increases Pred, a pseudo-value P'red is used in the initial equations.
This section iterates to the value of P'red and vent area that will achieve the overall Pred goal.

Calculate Duct hydraulic diameter


Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 2.6197213 meters

Rectangular Duct Y
Aspect 1.5 ratio a/b
Side a 2.8434505 meters
Side b 1.8956337 meters
p 9.4781683 meters
Rectangular Duct Dhe 2.2747604 meters

Chosen Duct Dhe 2.27476 meters


Chose correct relation between P'red and Pred
Lduct 2.1 meters
Duct L/Dhe) 0.923174 For Lduct<3 meters and L/Dhe<4
P'red= 0.1925197 bar
Enter Design Goal for Pred with Duct
PredGoal= 0.3 bar For Lduct of 3 to 6 meters or L/Dhe > 4
P'red= 0.01672 bar
P'red= 0.19252 bar

User must MANUALLY Copy the value of P'red above into the initial entry for Pred at cell B22 and
VERIFY that the same chosen P'red value is valid at cell B95 (This could change if the vent area gets much larger as a
t any implied warranty or guarantee.

user should verify that the methods and equations are consistent with the controlling NFPA standard.

Example Data Su KG
54
Isopropanol 41 83
56 75
78
550

If KG not available, estimate from Su as below and enter at left:

Basis is KG = 100, Su=46 for propane

0 cm/sec from NFPA-68 annex


0 bar-m/sec estimated from NFPA-68

psf
bar

he basic equation (i.e. KG=550 bar-m/sec)

hen no correction is needed. If Av is larger than the exterior wall of


ed values, that is make them stronger.
ensity is in US units, enter here and enter metric units at left
than 40 kg/m^2, consult an expert

area gets much larger as a result)


Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the

NFPA 68-2012 Gases in Enclosures - Low Strength Method

Room Dimensions
Length 7.3152 meters This tab does not use the L/D tab for input values. Unless
Width 7.3152 meters the wall at the end of the longest dimension. If venting wil
Height 3.6576 meters such that L/D is evaluated as 1, enter YES in the cell below
Volume 195.72604 cubic meters No

Internal Surface Area for Flat Walls and Ceiling


Floor 53.512151 meters
Roof 53.512151 meters
Walls 107.0243 meters
As 214.0486 square meters

Area for Rectangular Building


L1 3.6576 meters Enter smallest dimension here
L2 7.3152 meters Enter next smallest dimension here
Cross Section Aeff 26.756076 square meters
Wetted Perimeter 21.9456 meters
Dhe 4.8768 meters

Enter Appropriate Building Values For Enclosure Dimensions below (Copy and Paste Special - Values)
Longest dimension is length
Two smallest dimensions determine Area (cross-sectional area)
Wetted Perimeter is the sum of linear dimensions around the cross-section
Diameter (Dhe) is 4 x Area/Wetted Perimeter

Example Data
Enclosure Section Dimensions Acetone
(see Above to calculate these terms) Isopropanol
Methanol
Length (H) 7.3152 meters Methane
Volume (V) 195.72604 cubic meters V<1000 (This is total volume, not Veff) Hydrogen
Area (Aeff) 26.756076 square meters Propane
Diameter (Dhe) 4.8768 meters
Internal Surface (As) 214.0486 square meters

Pred is the maximum pressure developed during the vented explosion


Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel

Basic Enclosure and Vent Information

Pred 0.6 bar-g If Pred > 0.5 bar, use High Strength Method
Pstat 0 bar-g NOT USED in LOW STRENGTH
P0 0 bar-g intial pressure in the enclosure
Cd 0.7 vent flow discharge coefficient, taken as 0.7. Can be increased to 0.8 when the vent is esse
Pa 0.013 ambient pressure outside the vent = 0.013 bar-g

Material Propane
Su 0.46 m/sec
Pmax 7.9 bar-g US
Xst 0.055 stoichimetric volume fraction fuel in air Metric =
µu 1.80E-05 unburned gas-air mixture dynamic viscosity = 1.8E-05 kg/m-sec for gas concentrations less
au 343 unburned gas-air mixture sound speed = 343 m/sec for gas concentrations less than 5 vol%
ρu 1.2 unburned gas-air mixture mass density = 1.2 kg/m3 for gas concentrations less than 5 vol%
γb 1.15 ratio of specific heats for burned gas-air mixture = 1.1 to 1.2 depending on the gas mixture
Gu 230.1 unburned gas-air mixture sonic flow mass flux = 230.1 kg/m2-sec for an enclosure at ambien

Determination of Turbulent Flame Enhancement Factor, l

GUESS Av 15.59409 square meters GUESS of Vent Area that must be iterated (Dv is used to determine l
Difference 0.0000 square meters Use Solver to achieve difference of GUESS and Panel Inertia Correct

Note that pressure terms in formula for uv are in absolute units, while the standard approach is to use ga
Default Parameters
q 0.39
β1 1.23
β2 0.0487 m/sec

Evaluation of l0

Ref 7.48E+04

j1 3.1331

uv 312.7832 m/sec

Diameter of vent is iterated (av/pi)^0.5


Rev 4.65E+07

j2 1.8467

l0= 5.7858

Surface Area of Obstructions Correction to l

Surface area of obstructions includes:


1. The surface of conduits, pipes and such over 1/2 inch diameter
2. The surface area of structural columns, beams and joists
3. The surface area of stairways and railings
4. The surface area of equipment with characteristic dimension in the range of 2 to 20 inches (5.1 to 51 c

Aobs 0 square meters


Aobs/As 0
If Aobs> 0.4 As, l is increased. Otherwise l1 = l0

l1= 5.7858

L/D Correction to l IF(UPPER(LEFT(i11))="Y",1,…..) - This artificially sets L/D to 1 if venting is p

L/D 1.5000 L/D<5


If L/D exceeds 2.5, a correction is made to l .

l= 5.7858

Low Pressure, Low Inertia Vent Area

Determine C Deminimus value of C

C-demin = 0.0593507

C= 0.0564317
Determine Av0
Use original S-W equation, and also changing t

Av0= 15.5941 Sq.Meters Vent Area can not exceed cross-section (Aeff)

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:

Vgas 100 volume of gas at ambient pressure which could escape from the credible event, cubic meter

Xr= 9.289422
P= 0.0759494

If Xr is less then P, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3

Av1= 15.5941 square meters

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to Su limit of the basic equation (i.e. Su =

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
room, one can either include roof area for venting or increase the containing walls and floor Pred values, that is make them str
n 1 number of panels

Mformula 2500.228 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
The amount of vent area increase depends on the mode of opening, either hinged or translating.

M 10 kg/m^2 US 2 lb/sq ft If panel density is in US units, enter


Hinged Vent N YES/NO Metric = 9.8 kg/m^2 If greater than 40 kg/m^2, consult a

FSH 1

Av 15.5941 sq meters If M < MT, then there is no area correction for inertia
Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect


As the vent duct increases Pred, a pseudo-value P'red is used in the initial equations.
This section iterates to the value of P'red and vent area that will achieve the overall Pred goal.

Calculate Duct hydraulic diameter


Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 4.4558963 meters

Rectangular Duct Y
Aspect 1.5 ratio a/b
Side a 4.8364382 meters
Side b 3.2242921 meters
p 16.121461 meters
Rectangular Duct Dhe 3.8691505 meters

Chosen Duct Dhe 3.8691505 meters


Chose correct relation between P'red and Pred
Lduct 2.1 meters
Duct L/Dhe) 0.5427548 For Lduct<3 meters and L/Dhe<4
P'red= 0.1202357 bar
Enter Design Goal for Pred with Duct
PredGoal= 0.2 bar For Lduct of 3 to 6 meters or L/Dhe > 4
P'red= 0.0076265 bar
P'red= 0.1202357 bar

User must MANUALLY Copy the value of P'red above into the initial entry for Pred at cell B22 and
VERIFY that the same chosen P'red value is valid at cell B95 (This could change if the vent area gets much larger as a
ny implied warranty or guarantee.

er should verify that the methods and equations are consistent with the controlling NFPA standard.

b for input values. Unless noted below, it is assumed that all venting is put on
dimension. If venting will be evenly distributed along the longest dimension,
enter YES in the cell below:

Example Data Su Pmax


0.54
Isopropanol 0.41
0.56
0.4 7.8
3.12 6.8
0.46 7.9
0.8 when the vent is essentially an entire wall/side of the enclosure

313 psf
0.1498652 bar
r gas concentrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
nding on the gas mixture
or an enclosure at ambient temperatures

(Dv is used to determine l and is taken as Av0.5)


and Panel Inertia Corrected Vent Area = 0

dard approach is to use gauge values.


2 to 20 inches (5.1 to 51 cm)

ts L/D to 1 if venting is provided well distributed


ation, and also changing to not use Pred^0.5 below

redible event, cubic meters

basic equation (i.e. Su = 3 m/sec)

n no correction is needed. If Av is larger than the exterior wall of the


ues, that is make them stronger.

ensity is in US units, enter here and enter metric units at left


than 40 kg/m^2, consult an expert

ea gets much larger as a result)


Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the

NFPA 68-2012 Gases in Enclosures - Low Strength Method


Example Data
Enclosure Section Dimensions Acetone
(see L_D Tab to calculate these terms) Isopropanol
Methanol
Length (H) 7.3152 meters Methane
Volume (V) 195.72604 cubic meters V<1000 (This is total volume, not Veff) Hydrogen
Area (Aeff) 26.756076 square meters Propane
Diameter (Dhe) 4.8768 meters
Internal Surface (As) 214.0486 square meters NEED TO DETERMINE THIS IN L/D TAB, NOT DONE YET

Pred is the maximum pressure developed during the vented explosion


Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel

Basic Enclosure and Vent Information

Pred 0.6 bar-g If Pred > 0.5 bar, use High Strength Method
Pstat 0 bar-g NOT USED in LOW STRENGTH
P0 0 bar-g intial pressure in the enclosure
Cd 0.7 vent flow discharge coefficient, taken as 0.7. Can be increased to 0.8 when the vent is esse
Pa 0.013 ambient pressure outside the vent = 0.013 bar-g

Material Propane
Su 0.46 m/sec
Pmax 7.9 bar-g US
Xst 0.055 stoichimetric volume fraction fuel in air Metric =
µu 1.80E-05 unburned gas-air mixture dynamic viscosity = 1.8E-05 kg/m-sec for gas concentrations less
au 343 unburned gas-air mixture sound speed = 343 m/sec for gas concentrations less than 5 vol%
ρu 1.2 unburned gas-air mixture mass density = 1.2 kg/m3 for gas concentrations less than 5 vol%
γb 1.15 ratio of specific heats for burned gas-air mixture = 1.1 to 1.2 depending on the gas mixture
Gu 230.1 unburned gas-air mixture sonic flow mass flux = 230.1 kg/m2-sec for an enclosure at ambien

Determination of Turbulent Flame Enhancement Factor, l

GUESS Av 15.594089 square meters GUESS of Vent Area that must be iterated (Dv is used to determine l
Difference 0.0000 square meters Use Solver to achieve difference of GUESS and Panel Inertia Correct

Note that pressure terms in formula for uv are in absolute units, while the standard approach is to use ga
Default Parameters
q 0.39
β1 1.23
β2 0.0487 m/sec
Evaluation of l0

Ref 7.48E+04

j1 3.1331

uv 312.7832 m/sec

Diameter of vent is iterated (av/pi)^0.5

Rev 4.65E+07

j2 1.8467

l0= 5.7858

Surface Area of Obstructions Correction to l

Surface area of obstructions includes:


1. The surface of conduits, pipes and such over 1/2 inch diameter
2. The surface area of structural columns, beams and joists
3. The surface area of stairways and railings
4. The surface area of equipment with characteristic dimension in the range of 2 to 20 inches (5.1 to 51 c

Aobs 0 square meters


Aobs/As 0
If Aobs> 0.4 As, l is increased. Otherwise l1 = l0

l1= 5.7858
L/D Correction to l

L/D 1.5000 L/D<5


If L/D exceeds 2.5, a correction is made to l .

l= 5.7858

Low Pressure, Low Inertia Vent Area

Determine C Deminimus value of C

C-demin = 0.0593507

C= 0.0564317

Determine Av0

Av0= 15.5941 Sq.Meters Vent Area can not exceed cross-section (Aeff)

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:

Vgas 100 volume of gas at ambient pressure which could escape from the credible event, cubic meter

Xr= 9.289422
P= 0.0759494

If Xr is less then P, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3
Av1= 15.5941 square meters

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to Su limit of the basic equation (i.e. Su =

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
room, one can either include roof area for venting or increase the containing walls and floor Pred values, that is make them str
n 1 number of panels

Mformula 2500.228 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
The amount of vent area increase depends on the mode of opening, either hinged or translating.

M 10 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter


Hinged Vent N YES/NO Metric = 39.1 kg/m^2 If greater than 40 kg/m^2, consult a

FSH 1

Av 15.5941 sq meters If M < MT, then there is no area correction for inertia
Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect


As the vent duct increases Pred, a pseudo-value P'red is used in the initial equations.
This section iterates to the value of P'red and vent area that will achieve the overall Pred goal.

Calculate Duct hydraulic diameter


Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 4.4558963 meters

Rectangular Duct Y
Aspect 1.5 ratio a/b
Side a 4.8364382 meters
Side b 3.2242921 meters
p 16.121461 meters
Rectangular Duct Dhe 3.8691505 meters
Chosen Duct Dhe 3.8691505 meters
Chose correct relation between P'red and Pred
Lduct 2.1 meters
Duct L/Dhe) 0.5427548 For Lduct<3 meters and L/Dhe<4
P'red= 0.1925197 bar
Enter Design Goal for Pred with Duct
PredGoal= 0.3 bar For Lduct of 3 to 6 meters or L/Dhe > 4
P'red= 0.01672 bar
P'red= 0.1925197 bar

User must MANUALLY Copy the value of P'red above into the initial entry for Pred at cell B22 and
VERIFY that the same chosen P'red value is valid at cell B95 (This could change if the vent area gets much larger as a
ny implied warranty or guarantee.

er should verify that the methods and equations are consistent with the controlling NFPA standard.

Example Data Su Pmax


0.54
Isopropanol 0.41
0.56
0.4 7.8
3.12 6.8
0.46 7.9

NOT DONE YET

0.8 when the vent is essentially an entire wall/side of the enclosure

313 psf
0.1498652 bar
r gas concentrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
nding on the gas mixture
or an enclosure at ambient temperatures

(Dv is used to determine l and is taken as Av0.5)


and Panel Inertia Corrected Vent Area = 0

dard approach is to use gauge values.


2 to 20 inches (5.1 to 51 cm)
redible event, cubic meters
basic equation (i.e. Su = 3 m/sec)

n no correction is needed. If Av is larger than the exterior wall of the


ues, that is make them stronger.

ensity is in US units, enter here and enter metric units at left


than 40 kg/m^2, consult an expert
ea gets much larger as a result)
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the

NFPA 68-2012 Gases in Enclosures - High Strength Method

Room Dimensions
Length 7.3152 meters This tab does not use the L/D tab for input values. Unless
Width 7.3152 meters the wall at the end of the longest dimension. If venting wil
Height 3.6576 meters such that L/D is evaluated as 1, enter YES in the cell below
Volume 195.72604 cubic meters No

Internal Surface Area for Flat Walls and Ceiling


Floor 53.512151 meters
Roof 53.512151 meters
Walls 107.0243 meters
As 214.0486 square meters

Area for Rectangular Building


L1 3.6576 meters Enter smallest dimension here
L2 7.3152 meters Enter next smallest dimension here
Cross Section Aeff 26.756076 square meters
Wetted Perimeter 21.9456 meters
Dhe 4.8768 meters

Enter Appropriate Building Values For Enclosure Dimensions below (Copy and Paste Special - Values)
Longest dimension is length
Two smallest dimensions determine Area (cross-sectional area)
Wetted Perimeter is the sum of linear dimensions around the cross-section
Diameter (Dhe) is 4 x Area/Wetted Perimeter

Example Data
Enclosure Section Dimensions Acetone
(see Above to calculate these terms) Isopropanol
Methanol
Length (H) 7.3152 meters Methane
Volume (V) 195.72604 cubic meters V<1000 (This is total volume, not Veff) Hydrogen
Area (Aeff) 26.756076 square meters Propane
Diameter (Dhe) 4.8768 meters
Internal Surface (As) 214.0486 square meters

Pred is the maximum pressure developed during the vented explosion


Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel

Basic Enclosure and Vent Information

Pred 0.6 bar-g If Pred < 0.5 bar, use Low Strength Method
Pstat 0.1 bar-g 0.1 bar<Pstat<(Pred-0.05) and Pred<0.5
P0 0 bar-g intial pressure in the enclosure
Cd 0.7 vent flow discharge coefficient, taken as 0.7. Can be increased to 0.8 when the vent is esse
Pa 0.013 ambient pressure outside the vent = 0.013 bar-g

Material Propane
Su 0.46 m/sec
Pmax 7.9 bar-g US
Xst 0.055 stoichimetric volume fraction fuel in air Metric =
µu 1.80E-05 unburned gas-air mixture dynamic viscosity = 1.8E-05 kg/m-sec for gas concentrations less
au 343 unburned gas-air mixture sound speed = 343 m/sec for gas concentrations less than 5 vol%
ρu 1.2 unburned gas-air mixture mass density = 1.2 kg/m3 gas concentrations less than 5 vol% at
γb 1.15 ratio of specific heats for burned gas-air mixture = 1.1 to 1.2 depending on the gas mixture
Gu 230.1 unburned gas-air mixture sonic flow mass flux = 230.1 kg/m2-sec for an enclosure at ambien

Determination of Turbulent Flame Enhancement Factor, l

GUESS Av 15.955889 square meters GUESS of Vent Area that must be iterated (Dv is used to determine l
Difference 0.0000 square meters Use Solver to achieve difference of GUESS and Panel Inertia Correct

Note that pressure terms in formula for uv are in absolute units, while the standard approach is to use ga
Default Parameters
q 0.39
β1 1.23
β2 0.0487 m/sec

Evaluation of l0

Ref 7.48E+04

j1 3.1331

uv 312.7832 m/sec

Diameter of vent is iterated (av/pi)^0.5


Rev 4.70E+07

j2 1.8489

l0= 5.7928

Surface Area of Obstructions Correction to l

Surface area of obstructions includes:


1. The surface of conduits, pipes and such over 1/2 inch diameter
2. The surface area of structural columns, beams and joists
3. The surface area of stairways and railings
4. The surface area of equipment with characteristic dimension in the range of 2 to 20 inches (5.1 to 51 c

Aobs 89 square meters


Aobs/As 0.4157934
If Aobs> 0.4 As, l is increased. Otherwise l1 = l0

l1= 5.8843

L/D Correction to l IF(UPPER(LEFT(i11))="Y",1,…...) - This artificially sets L/D to 1 if venting is

L/D 1.5000 L/D<5


If L/D exceeds 2.5, a correction is made to l .

l= 5.8843

High Pressure, Low Inertia Vent Area

Determine d

d= 0.0151809
Determine Av0

Av0= 15.9559 Sq.Meters Vent Area can not exceed cross-section (Aeff)

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:

Vgas 100 volume of gas at ambient pressure which could escape from the credible event, cubic meter

Xr= 9.289422
P= 0.0759494

If Xr is less then P, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3

Av1= 15.9559 square meters

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to Su limit of the basic equation (i.e. Su =

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
room, one can either include roof area for venting or increase the containing walls and floor Pred values, that is make them str
n 1 number of panels

Mformula 2465.2265 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.
Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
The amount of vent area increase depends on the mode of opening, either hinged or translating.

M 10 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter


Hinged Vent N YES/NO Metric = 39.1 kg/m^2 If greater than 40 kg/m^2, consult a

FSH 1

Av 15.9559 sq meters If M < MT, then there is no area correction for inertia
Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect


As the vent duct increases Pred, a pseudo-value P'red is used in the initial equations.
This section iterates to the value of P'red and vent area that will achieve the overall Pred goal.

Calculate Duct hydraulic diameter


Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 4.5072908 meters

Rectangular Duct Y
Aspect 1.5 ratio a/b
Side a 4.8922219 meters
Side b 3.2614813 meters
p 16.307406 meters
Rectangular Duct Dhe 3.9137775 meters

Chosen Duct Dhe 3.9137775 meters


Chose correct relation between P'red and Pred
Lduct 2.1 meters
Duct L/Dhe) 0.536566 For Lduct<3 meters and L/Dhe<4
P'red= 0.1925197 bar
Enter Design Goal for Pred with Duct
PredGoal= 0.3 bar For Lduct of 3 to 6 meters or L/Dhe > 4
P'red= 0.01672 bar
P'red= 0.1925197 bar

User must MANUALLY Copy the value of P'red above into the initial entry for Pred at cell B22 and
VERIFY that the same chosen P'red value is valid at cell B95 (This could change if the vent area gets much larger as a
ny implied warranty or guarantee.

er should verify that the methods and equations are consistent with the controlling NFPA standard.

b for input values. Unless noted below, it is assumed that all venting is put on
dimension. If venting will be evenly distributed along the longest dimension,
enter YES in the cell below:

Obstacles (all)
Diam 2.38 inch
0.060452 m
Spacing 1.5 ft
0.4572 m
Totl Num 256
Totl Surf 177.8266 m2
1914.1095 ft2

Example Data Su Pmax


0.54
Isopropanol 0.41
0.56
0.4 7.8
3.12 6.8
0.46 7.9
0.8 when the vent is essentially an entire wall/side of the enclosure

313 psf
0.1498652 bar
r gas concentrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
ations less than 5 vol% at ambient temperatures
nding on the gas mixture
or an enclosure at ambient temperatures

Dv is used to determine l and is taken as Av0.5)


and Panel Inertia Corrected Vent Area = 0

dard approach is to use gauge values.


2 to 20 inches (5.1 to 51 cm)

ets L/D to 1 if venting is provided well distributed


redible event, cubic meters

basic equation (i.e. Su = 3 m/sec)

n no correction is needed. If Av is larger than the exterior wall of the


ues, that is make them stronger.
ensity is in US units, enter here and enter metric units at left
than 40 kg/m^2, consult an expert

ea gets much larger as a result)


Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the

NFPA 68-2012 Gases in Enclosures - High Strength Method


Example Data
Enclosure Section Dimensions Acetone
(see L_D Tab to calculate these terms) Isopropanol
Methanol
Length (H) 7.3152 meters Methane
Volume (V) 195.72604 cubic meters V<1000 (This is total volume, not Veff) Hydrogen
Area (Aeff) 26.756076 square meters Propane
Diameter (Dhe) 4.8768 meters
Internal Surface (As) 214.0486 square meters NEED TO DETERMINE THIS IN L/D TAB, NOT DONE YET

Pred is the maximum pressure developed during the vented explosion


Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel

Basic Enclosure and Vent Information

Pred 0.6 bar-g If Pred < 0.5 bar, use Low Strength Method
Pstat 0.1 bar-g 0.1 bar<Pstat<(Pred-0.05) and Pred<0.5
P0 0 bar-g intial pressure in the enclosure
Cd 0.7 vent flow discharge coefficient, taken as 0.7. Can be increased to 0.8 when the vent is esse
Pa 0.013 ambient pressure outside the vent = 0.013 bar-g

Material Propane
Su 0.46 m/sec
Pmax 7.9 bar-g US
Xst 0.055 stoichimetric volume fraction fuel in air Metric =
µu 1.80E-05 unburned gas-air mixture dynamic viscosity = 1.8E-05 kg/m-sec for gas concentrations less
au 343 unburned gas-air mixture sound speed = 343 m/sec for gas concentrations less than 5 vol%
ρu 1.2 unburned gas-air mixture mass density = 1.2 kg/m3 gas concentrations less than 5 vol% at
γb 1.15 ratio of specific heats for burned gas-air mixture = 1.1 to 1.2 depending on the gas mixture
Gu 230.1 unburned gas-air mixture sonic flow mass flux = 230.1 kg/m2-sec for an enclosure at ambien

Determination of Turbulent Flame Enhancement Factor, l

GUESS Av 15.95589 square meters GUESS of Vent Area that must be iterated (Dv is used to determine l
Difference 0.0000 square meters Use Solver to achieve difference of GUESS and Panel Inertia Correct

Note that pressure terms in formula for uv are in absolute units, while the standard approach is to use ga
Default Parameters
q 0.39
β1 1.23
β2 0.0487 m/sec
Evaluation of l0

Ref 7.48E+04

j1 3.1331

uv 312.7832 m/sec

Diameter of vent is iterated (av/pi)^0.5

Rev 4.70E+07

j2 1.8489

l0= 5.7928

Surface Area of Obstructions Correction to l

Surface area of obstructions includes:


1. The surface of conduits, pipes and such over 1/2 inch diameter
2. The surface area of structural columns, beams and joists
3. The surface area of stairways and railings
4. The surface area of equipment with characteristic dimension in the range of 2 to 20 inches (5.1 to 51 c

Aobs 89 square meters


Aobs/As 0.4157934
If Aobs> 0.4 As, l is increased. Otherwise l1 = l0

l1= 5.8843
L/D Correction to l

L/D 1.5000 L/D<5


If L/D exceeds 2.5, a correction is made to l .

l= 5.8843

High Pressure, Low Inertia Vent Area

Determine d

d= 0.0151809

Determine Av0

0.2248739

Av0= 15.9559 Sq.Meters Vent Area can not exceed cross-section (Aeff)

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:

Vgas 100 volume of gas at ambient pressure which could escape from the credible event, cubic meter

Xr= 9.289422
P= 0.0759494

If Xr is less then P, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3

Av1= 15.9559 square meters

Inertia Correction for Panel Mass < 40 kg/m^2


Based on the Task Group Activities, the inertia equations are applicable up to Su limit of the basic equation (i.e. Su =

Correction for inertia is limited to panel mass < 40 kg/m^2. If actual panel mass is less than MT, then no correction is needed.
room, one can either include roof area for venting or increase the containing walls and floor Pred values, that is make them str
n 1 number of panels

Mformula 2465.2265 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
The amount of vent area increase depends on the mode of opening, either hinged or translating.

M 10 kg/m^2 US 8 lb/sq ft If panel density is in US units, enter


Hinged Vent N YES/NO Metric = 39.1 kg/m^2 If greater than 40 kg/m^2, consult a

FSH 1

Av 15.9559 sq meters If M < MT, then there is no area correction for inertia
Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect


As the vent duct increases Pred, a pseudo-value P'red is used in the initial equations.
This section iterates to the value of P'red and vent area that will achieve the overall Pred goal.

Calculate Duct hydraulic diameter


Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 4.5072908 meters

Rectangular Duct Y
Aspect 1.5 ratio a/b
Side a 4.8922219 meters
Side b 3.2614813 meters
p 16.307406 meters
Rectangular Duct Dhe 3.9137775 meters

Chosen Duct Dhe 3.9137775 meters


Chose correct relation between P'red and Pred
Lduct 2.1 meters
Duct L/Dhe) 0.536566 For Lduct<3 meters and L/Dhe<4
P'red= 0.1925197 bar
Enter Design Goal for Pred with Duct
PredGoal= 0.3 bar For Lduct of 3 to 6 meters or L/Dhe > 4
P'red= 0.01672 bar
P'red= 0.1925197 bar

User must MANUALLY Copy the value of P'red above into the initial entry for Pred at cell B22 and
VERIFY that the same chosen P'red value is valid at cell B95 (This could change if the vent area gets much larger as a
ny implied warranty or guarantee.

er should verify that the methods and equations are consistent with the controlling NFPA standard.

Example Data Su Pmax


0.54
Isopropanol 0.41
0.56
0.4 7.8
3.12 6.8
0.46 7.9

NOT DONE YET

0.8 when the vent is essentially an entire wall/side of the enclosure

313 psf
0.1498652 bar
r gas concentrations less than 5 vol% at ambient temperatures
ntrations less than 5 vol% at ambient temperatures
ations less than 5 vol% at ambient temperatures
nding on the gas mixture
or an enclosure at ambient temperatures

Dv is used to determine l and is taken as Av0.5)


and Panel Inertia Corrected Vent Area = 0

dard approach is to use gauge values.


2 to 20 inches (5.1 to 51 cm)
redible event, cubic meters
basic equation (i.e. Su = 3 m/sec)

n no correction is needed. If Av is larger than the exterior wall of the


ues, that is make them stronger.

ensity is in US units, enter here and enter metric units at left


than 40 kg/m^2, consult an expert
ea gets much larger as a result)
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the methods

NFPA 68-2007 Dusts in Buildings

Room Dimensions This tab does not use the L/D tab for input values. Unless noted below, it is assu
Length 8.6 meters the wall at the end of the longest dimension. If venting will be evenly distributed a
Width 5 meters such that L/D is evaluated as 1, enter YES in the cell below:
Height 7.3 meters YES
Volume 313.9 cubic meters

KSt is the deflagration index


Pred is the maximum pressure developed during the vented explosion
Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel
Π is the ratio of Pred/Pmax

KSt 132 bar-m/sec


Pred 0.04788 bar Assumed 100 psf wall for this calculation
Pmax 9.1 bar
Pstat 0.0345 bar US 0.5 psig
Π 0.0052615 Pred/Pmax Metric = 0.0344738 barg

Av0 13.769331 sq meters

Check for L/D less than 2

The effective area, Aeff, shall be determined by dividing Veff by H (based on the longest central
axis flame length). This assumes all venting at one end.
H 8.6 meters
Aeff 36.5 sq meters

The effective hydraulic diameter, Dhe, for the enclosure shall be determined based upon the
general shape of the enclosure taken normal to the central axis.
Dhe = 4 * Aeff / p, Where p is the perimeter of the general shape
p 24.6 meters
Dhe 5.9349593 meters

L/D 1 If Red, L/D has been set to "1" by entering a YES above.
Av1 13.769331 sq meters

Building requires a factor of 1.7 on vent area

Av2 23.407863 sq meters

For Panel Mass > 40 kg/m^2, NFPA-68 recommends use of the Annex F (not included here)
Based on the Task Group Activities, the inertia equations are applicable up to KSt limit of the basic equation (i.e. KSt=

Inertia Correction for Panel Mass < 40 kg/m^2

n 1 number of panels

Mformula 2159.8515 kg/m^2


MT 40 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above. If greater than 40 kg/m^2, consult an exp
Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller.
The total mass of the panel, including insulaton, fasteners and restraint system is divided by the
open ventVent
Intended area.Panel Density
M 40 kg/m^2 US 2.5 lb/sq ft If panel density is in US units, enter here and e
Metric = 12.2 kg/m^2 If greater than 40 kg/m^2, consult an expert

Av3 23.407863 sq meters If M < MT, then there is no area correction for inertia

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:
Mf 148 gm Estimate Fill Fraction YES YES or NO
Afs 0.37 sq meters If YES Mf/Afs = 640 gm/m2 Assumed Dust on Floor of Operat
Cw 500 gm/m^3 Ms/Ass = 640 gm/m2 Worst Case allowed assumptions pe
H 7.3 meters Cw = 200 gm/m2
Ms 100 gm
Asur 20 sq meters Calculated from Inputs at Left
Ass 0.37 sq meters If NO Mf/Afs = 400 gm/m2
V 313.9 m^3 Ms/Ass = 270.27027 gm/m2
Cw = 500 gm/m2
Always Enter the mass of combustibles that could be released from equipment or storage below:
Me 4.8 kg
4800 gm

Xr 0.7187002 fill fraction

If Xr is less then Π, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3

Av4 22.131102 sq meters

Buildings do not generally have vent ducts, so this is not included here.
ny implied warranty or guarantee.

verify that the methods and equations are consistent with the controlling NFPA standard.

ess noted below, it is assumed that all venting is put on


will be evenly distributed along the longest dimension,
basic equation (i.e. KSt=800 bar-m/sec)

40 kg/m^2, consult an expert

US units, enter here and enter metric units at left


m^2, consult an expert
d Dust on Floor of Operational Room
se allowed assumptions per section 8.3.4
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the m

NFPA 68-2007 Dust in Equipment

Enclosure Section Dimensions


(see L_D Tab to calculate these terms)

Length (H) 1 meters


Volume (V) 2 cubic meters (This is total volume, not Veff)
Area (Aeff) 4 square meters
Diameter (Dhe) 1 meters

KSt is the deflagration index


Pred is the maximum pressure developed during the vented explosion
Pmax is the maximum pressure developed in a closed explosion test
Pstat is the static release pressure of the vent panel
Π is the ratio of Pred/Pmax

KSt 318 bar-m/sec


Pred 0.88 bar
Pmax 8.4 bar
Pstat 0.1 bar US 0.5 psig
Π 0.1047619 Pred/Pmax Metric = 0.0344738 barg

Av0= 0.1675141 sq meters Vent Area can not exceed cross-section (Aeff)

Check for L/D less than 2


(Use inputs above)

L/D (H/Dhe) 1 L/D<6 (8 for silos)

If L/D >2, increase vent area, else Av1=Av0


Av1= 0.1675141 sq meters Vent Area can not exceed cross-section (Aeff)

Turbulence Correction
Select as many options as applicable for the enclosure and this picks the highest correction.
Building? N YES/NO Correction factor of 1.7 if a building (occupiable)
Av2/Av1= 0

Flow-Created? N YES/NO
Inlet Air 20 m^3/sec
Inlet Pipe Diam 1m
Outlet Pipe Diam 1m
Vaxial 10 meter/sec
Vtangential 12.732395 meter/sec (0.5 Vtan_max)

Rotating Equip? N YES/NO


Rotational Radius 0.5 meter
Rotational Speed 1000 RPM
Vtangential 26.179939 meter/sec (0.5 Vtan_max)

Pick highest value of selected "YES" options above


Highest Av2/Av1= 0 No adjustment made if calculated Av2/Av1 is <1

If Velocities are less than 20 meters/sec, then Av2=Av1.

Av2= 0.1675141 sq meters Vent Area can not exceed cross-section (Aeff)

For Panel Mass > 40 kg/m^2, NFPA-68 recommends use of the Annex F (not included here)
Based on the Task Group Activities, the inertia equations are applicable up to KSt limit of the basic equation (i.e. KSt=

Inertia Correction for Panel Mass < 40 kg/m^2

n 1 number of panels

Mformula 0.5901206 kg/m^2


MT 0.5901206 kg/m^2 MT is minimum of 40 kg/m^2 or the formula above.

Vent area is increased if panel density exceeds the threshold or 40 kg/m^2, whichever is smaller. The total mass
of the panel, including insulaton, fasteners and restraint system is divided by the open vent area.
Intended Vent Panel Density
M 7.45 kg/m^2 US 0.75 lb/sq ft If panel density is in US units, en
Metric = 3.7 kg/m^2 If greater than 40 kg/m^2, consu

Av3 0.2058578 sq meters If M < MT, then there is no area correction for inertia
Vent Area can not exceed cross-section (Aeff)
Partial Volume Correction
Calculate the worst-case building partial volume fraction, Xr, from the following equation:
Mf 148 gm Estimate Fill Fraction YES YES or NO
Afs 0.37 sq meters If YES Mf/Afs = 640 gm/m2
Cw 500 gm/m^3 Ms/Ass = 640 gm/m2
H 1 meters Cw = 200 gm/m2
Ms 100 gm
Asur 20 sq meters Calculated from Inputs at Left
Ass 0.37 sq meters If NO Mf/Afs = 400 gm/m2
V 2 m^3 Ms/Ass = 270.27027 gm/m2
Cw = 500 gm/m2
Always Enter the mass of combustibles that could be released from equipment or storage below:
Me 4.8 kg
4800 gm

Xr 47.2 fill fraction

If Xr is less then Π, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av3

Av4= 0.2058578 sq meters Vent Area can not exceed cross-section (Aeff)

Vent Duct Effect

Enter a Guess for the final Avf. A suggestion is to start with about 20% greater than Av4.
Avf (guess)= 0.2058578 m^2
Calculate Duct hydraulic diameter
Only enter YES/NO for Round Duct, as Rectangular is the automatic other choice

Round Duct N YES/NO


Round Duct Dhe 0.5119632 meters Guidance
1. The duct area used in the Vent Duct Effect is that
Rectangular Duct Y 2. When duct area is larger than the vent area, actua
Aspect 1.5 ratio a/b 3. The actual duct area should be no more than 1.5
Side a 0.5556858 meters
Side b 0.3704572 meters
p 1.8522859 meters
Rectangular Duct Dhe 0.4445486 meters

Chosen Duct Dhe 0.4445486 meters

Enter Duct Configuration

Lduct 0 meters
epsilon 0.26 mm This is the roughness, used in friction factor.
K elbows 0
K hat 0

Calculate Friction Factor

f= 0.0172862

Iterate Vent Duct Effect


Use Solver to set "Guess-Calc Avf" to zero by changing Avf (guess) with constraints of Avf*Lduct/V < 1, and Avf < Aeff to get a
Multiple solutions are possible at or above the given constraints.
If Lduct is too large, there may not be a solution and you will have to look at increasing Pred.

(f*Lduct/Dhe)= 0 (straight duct sections)


K= 1.5 Solution Problems
E1= 0 1. If the Pred is too low, the cons
E2= 3.5923896 2. If the Duct length is too great,
Avf/Av4= 1 Suggestions to Solve
Avf = 0.2058578 m^2 Vent Area can not exceed cross-section (Aeff) 1. Increase Pred
2. Shorten duct
Guess-Calc Avf 0 Avf(guess) is cell B149 3. Change to round duct
4. Straighten duct

Constraint <1
Avf*Lduct/V 0 This is the ratio of the duct volume to the enclosure volume
Av/Aeff 0.0514644 This is the ratio of the duct area to the enclosure cross-section

Constraint Leff < RHS Constraint


Ldusty= 73.060145 meters (Pmax-Pred)*V/Av
Leff= 0 meters min(Lduct, Ldusty)
RHS Constraint= 13.979516 meters min(10000*D/Kst, 11000/Kst)
ithout any implied warranty or guarantee.

he user should verify that the methods and equations are consistent with the controlling NFPA standard.
Correction for Flow-Created Turbulence (uses the maximum Axial or Tangential Turbulence)
This would be typical for a cyclone
Av2/Av1= 0

Correction factor if Rotating Equipment


This would be typical for a grinder or hammermill
Av2/Av1= 0

it of the basic equation (i.e. KSt=800 bar-m/sec)

aller. The total mass


area.
If panel density is in US units, enter here and enter metric units at left
If greater than 40 kg/m^2, consult an expert

ion for inertia


YES or NO
Assumed Dust on Floor of Operational Room
Worst Case allowed assumptions per section 8.3.4
ed in the Vent Duct Effect is that equal to the vent area.
s larger than the vent area, actual Pred can be higher or lower.
rea should be no more than 1.5 times the vent area.

Lduct/V < 1, and Avf < Aeff to get a single solution.

Solution Problems
1. If the Pred is too low, the constraint of Av/Aeff is not met and Cells B183-187 will not be numbers
2. If the Duct length is too great, the constraint of Avf*Lduct/V is not met and the same thing will happen.
Suggestions to Solve
1. Increase Pred
2. Shorten duct
3. Change to round duct
4. Straighten duct
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the met

Determine Pred for "Inertialess" vents, including L/D, Turbulence, and Partial Volume
For Panel Mass > 40 kg/m^2, NFPA-68 recommends use of the Annex F (here)

Use: 1) Enter Input data and value slightly below desired Pred at B26
2) Use solver to set Target Cell M7 equal to desired Pred with Inertia, by changing cell B26

Enclosure Section Dimensions Final Value of Pred with Inertia Correction


(see L_D Tab to calculate these terms) Second Peak

Length (H) 2 meters


Volume (V) 2.4 cubic meters (This is total volume, not Veff)
Area (Aeff) 4 square meters
Diameter (Dhe) 2 meters

KSt is the deflagration index


Pred is the maximum pressure developed during the vented explosion
Pmax is the maximum pressure developed in a closed explosion test
Π is the ratio of Pred/Pmax
Pstat is the static release pressure of the vent panel

KSt 260 bar-m/sec


Pred 0.856099 bar Solver solution constrained > 0.01
Pmax 9.1 bar
Pstat 0.1 bar US 0.5 psig
Π 0.094077 Pred/Pmax Metric = 0.034474 barg

Av0= 0.166694 sq meters Vent Area can not exceed cross-section (Aeff)

Check for L/D less than 2


(Use inputs above)

L/D (H/Dhe) 1

If L/D >2, increase vent area, else Av1=Av0


Av1= 0.166694 sq meters Vent Area can not exceed cross-section (Aeff)
Turbulence Correction
Select as many options as applicable for the enclosure and this picks the highest correction.

Building? N YES/NO Correction factor of 1.7 if a building (occupiable)


Av2/Av1= 0

Flow-Created? N YES/NO For Flow-Created Turbulence, use the maximum Axial or Tangential Turbulence
Inlet Air 20 m^3/sec This would be typical for a cyclone
Inlet Pipe Diam 1m Av2/Av1= 0
Outlet Pipe Diam 1m
Vaxial 16.66667 meter/sec
Vtangential 12.7324 meter/sec (0.5 Vtan_max)

Rotating Equip? N YES/NO Correction factor if Rotating Equipment


Rotational Radiu 0.5 meter This would be typical for a grinder or hammermill
Rotational Speed 1000 RPM Av2/Av1= 0
Vtangential 26.17994 meter/sec (0.5 Vtan_max)

ighest Av2/Av1= 0 (picks highest value of selected "YES" options above)

If Velocities are less than 20 meters/sec, then Av2=Av1.


Minimum value of Av2/Av1 is 1.

Av2= 0.166694 sq meters Vent Area can not exceed cross-section (Aeff)

Partial Volume Correction


Calculate the worst-case building partial volume fraction, Xr, from the following equation:

Mf 148 gm Estimate Fill Fractio YES YES or NO


Afs 0.37 sq meters If YES Mf/Afs = 640 gm/m2 Assumed Dust on Floor of Operation
Cw 500 gm/m^3 Ms/Ass = 640 gm/m2
H 2 meters Cw = 200 gm/m2
Ms 100 gm
Asur 20 sq meters Calculated from Inputs at Left
Ass 0.37 sq meters If NO Mf/Afs = 400 gm/m2
V 2.4 m^3 Ms/Ass = 270.27 gm/m2
Cw = 500 gm/m2
Always Enter the mass of combustibles that could be released from equipment or storage below:
Me 4.8 kg
4800 gm

Xr 85.86667 fill fraction

If Xr is less then Π, then no venting is required


If Xr is greater than 1, partial volume does not apply and Av4=Av2 (Inertia correction is later)

Av4= 0.166694 sq meters Vent Area can not exceed cross-section (Aeff)

Annex F Alternate Inertia Correction

Vent Panel Characteristics


sv = 64 kg/m^2 Panel Shape changes Shape Factor, cs
n= 1 equal panels Square 1 Aspect ratio= 0.5
cs = 1 Enter from Right Round 0.886 Rectang 1.06066

m= 0 Enter from Right Vent Gravitational Coefficient, m


Horizontal panel, on top of vessel 1
Po = 1 bara Other Orientations 0
Pmax = 10.1 bara

2.4000 bara
Pred due to panel inertia = 1.4000 barg = 20.30 psig

4.0 - Determine inertia


1.0 -Correct Kst for pressure. param S 8.0 - Determine Pv 13.0 - Determine Pri for Gk< 1

Kst,v = 305.5 S = 0.13679 Pv = 0.010989 Pri =

5.0 - Determine Sk after 14.0 - Determine Pri for 1<


2.0 -Correct Kst for volume. vent deployment 9.0 - Determine f(Pv) Gk< 3
K = 261.1166 Sk = 0.13827 f(Pv) = 3.3149677 Pri =

6.0 - Determine vent param 10.0 - Determine exponent 15.0 - Determine Pri for 3
3.0 -Dpr, for inertialess vents G h < Gk

Dpr = 0.856099 barg G = 0.75672 h = 0.6114 Pri =

16.0 - Determine increase ove


7.0 - Determine vent param 11.0 - Determine Pvi (Pstat with vent pressure after
Gk inertia
) deployment Pri

Gk = 0.75349 Pvi = 1.7166569 bara Pri =


thout any implied warranty or guarantee.

user should verify that the methods and equations are consistent with the controlling NFPA standard.

anging cell B26

d with Inertia Correction 1.4000 bar


1.4000 bar
um Axial or Tangential Turbulence

med Dust on Floor of Operational Room


vent panel aspect ratio (short side/long side<1)

13.0 - Determine Pri for Gk< 1

2.4000

14.0 - Determine Pri for 1<


Gk< 3
2.3671

15.0 - Determine Pri for 3


< Gk

1.8561

16.0 - Determine increase over


vent pressure after
deployment Pri

2.4000 bara
Disclaimer - This spreadsheet is the personal work of Samuel Rodgers, given freely without any implied warranty or g
This is not authorized by any employer, by NFPA, or by any other organization.
Use of this spreadsheet is solely the responsibility of the user and the user should verify that the methods

Insert Prugh Le-Chatalier for Hybrid Mix from Loss Prevention

Question whether the shape of the curve can be estimated using the same Brandes method
Insert Hybrid Mixture estimation from Su.
ny implied warranty or guarantee.

verify that the methods and equations are consistent with the controlling NFPA standard.

Potrebbero piacerti anche