ALL-TEST Pro, LLC

Motor System Trouble-Shooting


This motor tripped twice and stopped running. It was tested with an ohm meter and meg-ohm
meter and pronounced OK. The motor was hooked directly to line power and it ran. The plant
concluded the drive was faulty, and replaced it. The motor would not run. It was then replaced
and sent to a motor shop for evaluation.

25 HP Inverter Grade Motor


Tested with DMM and Meg-Ohm meter
P1-2 P1-3 P2-3 Dev
Resistance 0.717 0.701 0.703 2.2%
Impedance ? ? ? ?
Inductance ? ? ? ?
Phase Angle ? ? ? ?
I/F ? ? ? ?
Ins. >99 Megohms

123 Spencer Plain Road P.O. Box 1139 Old Saybrook, CT 06475, USA
Phone: (860) 399-4222 Fax: (860) 399-3180 Email: info@alltestpro.com Web Site: www.alltestpro.com
ALL-TEST Pro, LLC

The motor shop had an ALL-TEST IV PRO 2000 and re-tested the motor prior to repair process-

25 HP Inverter Grade Motor


The same motor tested with ALL-
ALL-TEST IV PRO 2000
in the motor shop
P1-2 P1-3 P2-3 Dev
Resistance 0.717 0.701 0.703 2.2%
Impedance 86 156 159 81.0%
Inductance 34 31 31 9.7%
Phase Angle 73 73 71 2
I/F -40 -39 -39 1
Ins >99 Megohms
Shorted turns detected, later visually confirmed.
MCA would have saved 1- 1-1/2 days in resolving this
problem. Cost in your plant to lose 1 ½ days?

Diagnosing motor system faults where drives are in the circuit can be difficult and only using a
digital multi-meter and insulation to ground tester will cause you to miss common motor faults-
turn to turn and coil to coil shorts; particularly at the end turns of the stator windings.

©2006 ALL-TEST Pro, LLC April 2006