UNIT-2 Boiler Walkdown Points & Defects

status
1 Furnace temp probe (R) feedback is hunting C&I Not done
2 ID Fan-2B IGV operation is sluggish above 60% command C&I Not done
3 ID Fan-2A tripped on differential protection Elec Not done
4 APH-2A taking more current (16 Amps) Mech Not done
6 ID Fan-2B motor NDE side ferrule joint oil leakage. Mech Not done
8 Drum LHS local level gauge bottom drain line got chocked . Mech Not done
9 Drum RHS local level gauge leakage . Mech Not done
10 A&C elevation LHS SA damper motor cable dressing to be done , now kept tied Elec Not done
11 PRDS to HFO atomizing drain line leakage Mech Not done
12 All drain lines & vent lines insulation,supporting work pending Mech Not done
13 MS to PRDS MOV passing & its MIV passing Mech Not done
14 MS to PRDS line drain line insulation & supporting work not completed Mech Not done
15 HFO tracing line cladding work pending. Mech Not done
16 FW 30% CV feedback,upstream MOV feedback not getting in DCS C&I Not done
17 FW line insulation work pending(main line&drain line) Mech Not done
18 Approach should be given for hot SA damper local operation(A&B) Mech Not done
19 Gun cleaning HFO atomising line insulation work pending (E elevation). Mech Not done
20 Approach to be provided for FW sampling line valve operation(nr NRV) Mech Not done
21 CRH drain and eco drain line insulation & support work pending Mech Not done
22 APH gas dampers local scale and pointer damaged Mech Not done
23 Eco hopper area(rear OFA) unsafe platform,proper supports to be given Mech Not done
26 Right side MS drain MIV & MOV chocked Mech Not done
27 APH sootblowing line vent line flange leakage Mech Not done
28 Boiler feed pump header pressure(LAC40CP001) not showing in dcs C&I Not done
30 APH right side hotspot detection not working(4 thermocouple failed) C&I Not done
31 ID-2B lube oil filter oil leakage C&I Not done
34 APH-2B guide bearing oil indicator not available Mech Not done
35 Left side frequently APH sootblower tripping [motor over load]. Mech/Elec Not done
36 Boiler stopvalve right close feedback not coming in DCS C&I Not done
37 Drum RHS hydrastep not working. C&I Not done
38 SH gas damper-2 feedback bad quality(not commissioned) C&I Not done
A&C elevation secondary & central air damper feedback in DCS showing erratic
39 value(command&feedback not matching) C&I Not done
40 CRH drain leftside MOV not operating from DCS. C&I Not done
42 APH I/L air temp#3(HLD10CT373) showing erratic value C&I Not done
43 Drum level transmitter(all 4) showing different value in DCS(-38,-55,-184,416)
C&I Not done

44 Boiler drain MOVs not working:front WW MV5;right WW MV5,MV3,MV8;rear WW MV4 C&I Not done
Deaerator tank temp readings not matching,LBD04CT001,LBD04CT002 showing
45 different values C&I Not done
Windbox&OFA outside swirl damper and straight damper proper scale adjustment
46 work pending. Mech Not done
48 Insulation for pent house at bottom side of boiler drum (LHS &RHS) pending Mech Not done
49 All safety valve body insulation pending Mech Not done
51 Boiler drum TV to be installed on both side. Mech Not done
52 Drum level Hydra step bottom side second isolation valve missing. Mech Not done
53 Drum level Hydra step direction (LHS) to be reversed and setright. Mech Not done
54 Sonic sencer erection work pending. Mech Not done
55 MS line Safety valve exhaust pipe proper supporting to be provided. Mech Not done
56 Soot blower line insulation work pending. Mech Not done
57 Soot blower line temporary supporting to be removed. Mech Not done
58 MS Drain line proper supporting & insulation to be provided. Mech Not done
60 Scrap material to be removed / House keeping to be done. Mech Not done
61 supporting Beam nut & bolt erection work pending. Mech Not done
62 Insulation to be provided around furnace pressur measurment tapping on both side. Mech Not done
63 Supporting bracing fouling with super heater spray line. Mech Not done
64 Scrap material to be removed arround furnace temprature probe area. Mech Not done
65 Super heater temporary support to be removed & permanent support to be provided. Mech Not done
66 Drain line supporting to be removed at 52meter Mech Not done
67 column support bolt to be provided (42 mtr RHS) Mech Not done
68 Column support bolt to be tighten. Mech Not done
69 Scrap material(scoffolding) to be removed at 37 mtr elevation Mech Not done
71 Supporting beam proper alignment to be done (rear side sootblower line). Mech Not done
72 SH & RH Temperature controle damper MOV canopy to be provided. Mech Not done
73 SH & RH Temperature controle damper local indicator to be provided. Mech Not done
74 Soot blower line drain (RHS) to be rooted as per Drg Mech Not done
75 Economiser vent line insulation work pending. Mech Not done
76 Damaged grating to be replaced. Mech Not done
78 Economiser bottom casing area unsafe platform to be made ready at 34.0mtr. Mech Not done
81 RH spray block valve insulation work pending at 24meter. Mech Not done
82 All coal pipe burner openinig to be arrest (gratings opening). Mech Not done
83 All Coal pipe insulation work pending. Mech Not done
84 Fouling Coal pipe supports to be rectify Mech Not done
85 Welding machine shed to be removed at 16 meter. Mech Not done
86 Atamoizing steam steam line insulation cladding work pending. Mech Not done
87 ATT to be complete. Mech Not done
88 House keeping at zero meter pending. Mech Not done
89 Drum level transmitter modified condensate pot erection work pending. Mech Not done
90 Pending MOV & Damper commissioning pending work to be complete[MOV &Damper list]. Mech Not done
MS & HRH ,CRH,FW line damaged insulation rework to be done [Thermowell
93 checking &hanger supporting work removed insulation] Mech Not done
94 FW drain after NRV line insulation supporting work pending. Mech Not done
95 Damaged Expension bellow to be replace. Mech Not done
Seal air fan discharge Duct supporting tie rod fouling with gratings[Hot air gate &
97 cold air gate approach gratings). Mech Not done
98 Seal air fan bearing cooling water flange leakage. Mech Not done
99 Flue gas duct & SA duct Scuffolding to be remove & clading patch work to be done. Mech Not done
100 Concrete flooring work not completed (right sideK4B2 column at 16 mtr) Mech Not done
Approach to be provide for local operation mill inlet seal air MOV at present cable try
101 & handrail fouling for local operation Mech Not done
Instrument & service air line temporary supports to be removed & permanent
102 supports to be provide (rear side16 mtr) . Mech Not done
Approach to be provide for instrument & service air isolation valve operation Boiler
103 right side 12 mtr. Mech Not done
Mill A-F hot air and cold air gate operation approach and walkway to be given
104 provided Mech Not done
Bunker O/L gate and feeder O/L gate grating to be extended for maintenance
105 purpose.currently given grating are too small to carry out any maintnce work Mech Not done
106 PA fan to seal air fan MOV (Damper) supporting welding work pending. Mech Not done
107 APH-A damaged radial seal to be replace (work inprogress) Mech Not done
108 Furnace temperature probe Top cover plate to be provided on the tailend side[RHS]. Mech Not done
109 Funace temp Flexible hose damaged[RHS]. Mech Not done
FD,PA & ID Duct supportings (cold & Hot) ,(Hot PA )Mill inlet duct supportings
110 welding work &plate bend to be remove. Mech Not done
Wind box damper Not done
C Elevation Left damper local indicator scale Not available. Mech Not done
111
C Elevation Right damper local indicator scale damaged. Mech Not done
D elevation rightside damper link cotter pin missed & local scale damaged. Mech Not done
112 D elevation Left side damper actuator fouling with cantral air damper approach
ladder. Mech Not done
E elevation Rightside actuator erection work pending & Local scale damaged,
113 Central air damper approach ladder fouling Mech Not done
E elevation left side actuator link cotter pin & actuator earthing pending. Mech Not done
OFA front sid elevation Right side Damper link cotter pin to be erect & Actuator
114
earthing to be done,Power cable and DCS feedback cable gland sealing to be done. Mech Not done
OFA front sied elevation Leftside Damper link cotter pin to be erect & Actuator
115
earthing to be done. Mech Not done
116 A Elevation left side damper actuator terminal box bolt to be tighten. Mech Not done
B elevation Right side control cable dressing to be done & Local indicator scale &
117 needle not available. Mech Not done
B elevation left side Local indicator scale & needle not available. Mech Not done
F elevation Right side damper actuator fouling with Handrail & local indicator scale
118
not available , Mech Not done
OFA rear side elevation Right side damper local indicator damaged,Manhole approachMech to be provide. Not done
119
OFA rear side elevation left side damper local indicator damaged, Manhole approach to Mech
be provide. Not done
120 Swas sytem to be made ready mech /C&I Not done
UNIT-2 Boiler Area Defects List

Leakage in MS to Aux PRDS pressure transmitter impulse line at panel and root valve
1 Not done
(20 mtr floor)
2 APRDS line to APH soot blower drain line flange leakage (Rear side of APH) Not done
3 Main steam RHS drain line chocked near MS stop valve. Not done
5 ID fan 2B, lube oil filter DP switch not resetting. Not done
6 HFO atomizing spray area two welding leakages in drain lines. Not done
7 Drum Right side Hydra step having leakage. Not done
8 MS to PRDS MOV at Drum Elevation Remote/Local switch broken condition. Not done
9 APH 2B GB oil indicator not available. Not done
10 HRH line RH outlet pressure Instrument line having leakage. Not done
11 HRA Drain MOV passing. Not done
12 DC scanner air fan NRV flap is passing. Not done
Both Scanner air fan Suction filter to be cleaned, Discharge pressure reading very
13 Not done
less value.
14 Return Heavy oil pressure (EG170CP001) is not reading any value. Not done
15 HFO return oil pre Tr meter (EG 170 cp 001) is not reading. Not done
FD fan 2B, drain valve passing of cooling water return line from oil cooler of lub oil
16 Not done
station.
17 APH 2A, soot blower steam line insulation incomplete. Not done
19 Lub oil leakage from APH-2A Main Drive shaft below support Bearing. Not done
20 HFO Supply pressure Switch PN (EG1101CP201) is not Resetting. Not done
APH 2A Lub oil Leakage from coupling of main drive shaft below support bearing of
21 Not done
APH
22 HFO supply pressure switch (EG 1101 cp 201) is not resetting. Not done
23 A4 LDO atomizing MIV wheel broken Not done
24 Soot blowing line MIV & MOV passing at drum elevation (platen SH to SB) Not done
Flue Gas leakage from furnace RHS Front & Rear side at 34 mts elev at RH Spray CV
25 Not done
area.
26 RH Spray water line support work pending at 34 mts elevation
Sl No. Description Remark
FD fan -2B
1 FD fan-2B Lube oil pump -1&2 its motor side abnormal sound.
2 FD fan-2B Discharge damper local indicator scale needle broken.
3 Lube oil tank temperature gauge not erected.
4 After cooler Lube oil temperature gauge not working.
5 Lube oil tank heater commissioning pending.
Vibration monitor panel no 6 showing danger indication in panel.[ 3&4 Replaced with
6 other fan for trial run]
7 House keeping in FD-2A area pending
8 ECW line painting work balance [cooler inlet &outlet].
9 Cooler outlet line [ECW] tapping to be provide for temp gauge.
10 Lube oil panel door locking system damaged.
11 FD fan discharge pressure guage indicator not erected.
12 Junction box panel near actuator to be properly clamped.
FD fan -2A
1 Lube oil tank temperature gauge not working.
2 After cooler Lube oil temperature gauge not damaged.
3 Lube oil tank heater commissioning pending.
4 House keeping in FD-2B area pending
5 Cooler outlet line [ECW] tapping to be provide for temp gauge.
6 ECW line painting work balance [cooler inlet &outlet].
7 FD fan discharge pressure guage indicator not erected.
8 Control oil pressure guage indicator oil leakage.
ID 2A fan
1 ID fan- 2A lube oil temperature gauge damaged.
2 ID fan discharge duct insulation work not completed (chimney connection point).
3 Lube oil tank heater commissioning pending.
4 Lube oil filter DPI not provided.
5 ECW line permanent supporting & painting work balance [cooler inlet &outlet].
6 House keeping surrouding fan area pending.
7 Cable conduit for vibration probe not available [Motor DE].
8 Neutral box bolts missing.
9 Power cable clampping damaged.
10 Power cable trench to be cleaned.

ID 2Bfan
1 Space heater cable dressing work pending
2 ID fan-2B inlet & outlet damper not commissioned.
3 ID fan discharge duct common [chimney connected point] insulation work not completed.
4 ESP inlet gate actuator commissioning work pending.
5 Lube oil tank heater commissioning pending.
6 Lube oil filter DPI not provided.
7 Cooler cooling water line flushing work pending.
8 Lube Oil coolers ECW line not connected.
9 ECW line painting work balance [cooler inlet &outlet].
10 Vibration monitor panel support frame insert plate or anchoring to be done
11 ID fan discharge duct temporary scaffolding to be removed.
12 Insulation to be completed on the scaffolding area.
13 Permanent canopy to be provide for cooling fan.

PA fan -2A
1 PA fan -A motor lube oil tank temperature guage damaged.
2 Filter DPI not erected.
3 Lube oil tank heater commissioning (fan side & motor side) work pending.
4 Lube oil Flow switch not erected.
5 lube oil Tank heater not commissioned.
6 Lube oil cooler return cooling water line drain to be provide.
7 Cooler outlet line [ECW] tapping to be provide for temp gauge.
8 ECW line painting work not completed.
9 Return oil tank temperature not erected.

PA fan -2B
1 Lube oil return oil temperature gauge not erected.
2 Lube oil Tank temp gauge damaged
Fan side lube oil system
1 Lube oil return temperature gauge & lube oil tank temperature guage not erected.
2 Lube oil control cabinet box cover to be provide.
3 After TCV temperature gauge damaged (needle broken)

Scanner airfan AC&DC


1 House keeping work surround AC & DC air fan.
2 AC scanner air fan discharge pressure guage needle broken.
3 Cable gland sealing work pending
4 Scanner air fan discharge flap through air passing.
5 DC Local panel door glass broken.
6 Scanner air line 'D' Elevation two valve passing, 'E' elevation two line valve not erected.

APH-2A
Support bearing Lube oil cooler cooling water discharge Temperature guage tapping &
1 drain point to be provide.
2 Guide bearing lube oil cooler cooling water line painting & supporting work pending.
3 Guide bearing motor terminal box bolt erection work pending.
4 support bearing Lube oil flow indicator to be provide in viewable area.
APH-2B
1 Guide bearing lube oil discharge line flange joint bolt & nut erection pending.
2 Guide Bearing Lube oil pump discharge line after cooler valve handle broken.
3 APH auxillary motor coupling guard erection work pending.
4 Gear box oil circulation motor terminal box bolt missed & cable gland sealin to be done
Gear box oil circulation discharge line pressure guage to be erect properly (as APH-A ,at
5 present pressure not visible).
6 oil leakage from view glass elbow [support bearing].
HFO & LDO system
1 LDO line temperature & pressure guage erection work pending.
2 HFO line temperature & pressure guage not erected.
3 Automizing line[steam & service air] tempearture & pressure guage erection work pending.
Furnace temperature probe
1 Furnace temp probe RHS local/remote selection switch not provided.
2 Local position feedback indication damaged[RHS].

seal air system punch list


1 Seal air fan 2A suction Damper through DCS commissioning work pending.
2 Seal air fan Discharge NRV flange leakage.
Seal air fan outlet discharge pressure gauge not erected (Individual fan discharge and
3 common discharge header as per P&ID).
4 House keeping on surround area pending.
UNIT-2 Turbine walk down Points & Defects
16.01.11 status
1 Auxiliary steam header safety valve floating Auxiliary steamNot done
2 Insulation of Auxiliary steamheader connected pipings Auxiliary steamNot done
3 Deaerator floor area scrap material removal and house keeping D/A floor Not done
4 Atomising steam line and Mill fire fighting line at D/A floor jammed with concrete, to be cleared D/A floor Not done
5 Aux. steam to Deaerator line insulation to be completed Auxiliary steamNot done
6 Aux. steam to Deaerator bypass MOV line support to be aligned properly Auxiliary steamNot done
7 Extraction # 4 to deaerator line jammed with concrete, to be cleared D/A floor Not done
8 Extraction # 4 to Deaerator line support at D/A floor to be corrected Extraction # 4 Not done
9 Extraction # 4 to Deaerator line insulation to be completed Extraction # 4 Not done
10 Instrument air line at Deaerator floor to be supported properly Instrument Air Not done
11 Condensate lineto deaerator jammed with concrete, to be cleared D/A floor Not done
12 Condensate line at Deaerator floor, elbow support to corrected and temparary support to be removed Condensate lineNot done
13 HPH Drip to Deaerator line temparary support removal at Deaerator floor HPH drip line Not done
14 Drum CBD line to CBD tank, Approach to be provided to CV and MOV CBD line Not done
15 Drum CBD line to CBD tank, insulation to be completed CBD line Not done
16 CBD tank PI to be provided CBD tank Not done
17 CBD tank drains to be routed out properly CBD tank Not done
18 CBD tank drain to IBD tank line no clearance with wall, to be cleared Deaerator floorNot done
19 Deaerator drain line jammed with concrete Deaerator floorNot done
20 TD BFP A suction line at deaerator floor jammed with concrete, to be cleared Feed water Not done
21 TD BFP A&B suction line at deaerator floor, temparary supports to be removed D/A floor Not done
22 Deaerator vents to be routed out properly Deaerator Not done
23 Extraction # 4 to Deaerator 6" line check valve not of proper rating Deaerator Not done
24 Deaerator filling line NRV bolts not of proper size, to be replaced D/A fill line Not done
25 CRH to HPH # 2 line welding to be completed Extraction # 2 Not done
26 HRH drip to Deaerator NRV bolts not of proper size, to be replaced HPH drip line Not done
27 CBD tank to Deaerator line MOV and NRV all bolts to be provided CBD vent to D/ANot done
28 LPH # 6 safety valve exhaust piping supports to be provided LPH Not done
29 HPH # 1,2 & 3 steam side drains to be supported properly HPH Not done
30 HPH # drip temparary supports to be removed HPH Not done
31 HPH # guage glass draining provision to be given HPH Not done
32 HPH # 1 O/L feed water line to economiser, clearance to be provided with wall Feed water Not done
33 TD BFP # A & B steam drain lines to be supported properly TDBFP Not done
34 Gland steam lines of TD BFP # A & B to be supported properly, temparary lines to be removed TDBFP Not done
35 HIP gland steam line insulation to be competed Gland steam Not done
36 LPBP valve # 1 spray line flange joint bolts to be provided LPBP valve # 1Not done
37 LPBP warm up line to be supported properly LPBP Not done
38 MS, CRH, HRH and Extraction steam lines insulation completion at Turbine end Steam lines Not done
39 Scrap material removal and house keeping at 6.9m elevation Not done
40 LPH # 7A to 8A drip line temporary supports removal LPH Not done
41 LP Turbine # A & B Gland steam line MIV's Approach to be provided Gland steam Not done
42 Stator water, H₂ cooler drain header drain line size to be increased Not done
43 LP Condenser vacuum breaker valve sealing line to completed vac breaker v/vNot done
44 TD BFP ehaust duct permanent supports erection to be completed, temparary supports to be removed TD BFP Not done
45 LPH # 5 & 6 sliding support to be made free LPH Not done
46 Openings in 6.9 m floor to be covered Not done
47 MS stop vale drain to gland steam line temparary supports to be removed Not done
48 Gland steam drains to be supported properly Gland steam Not done
49 All drain lines MIV and CV approach to be provided Drain lines Not done
50 LP Drain header to be completed Not done
51 CRH drain CV fouling with MS stop valve drains CRH Not done
52 TD BFP # B Booster pump discharge line fouling with ECW line Not done
53 LP Flash tank area platform to be provided below the control valves Not done
UNIT-2 Turbine Area Defects List
16.01.11 status
1 Leakage in MS line Left side Drain after CV near HP Flash tank Not done
2 CRH to TDBFP – B drain line leakage (6.9 mtr level). Not done
3 Leakage in Relief valve of Boiler fill MOV Not done
4 Boiler fill pump relief valve flange joint welding leakage Not done
5 Pin hole leakage in CRH to TDBFP header steam drain line. Not done
6 Leakage in CRH to TDBFP-B drain line flange. Not done
7 CRH to PRDS line vent valve is passing at Deaerator floor. Not done
8 Extr-4 to PRDS dummy pipe having welding leakage at 24 m elevation. Not done
9 Both TDBFP changeover valves upstream flange leakage Not done
10 TDBFP-B mech seal cooling water supply line welding leakage at 13.7 m elevation. Not done
11 Enlargement tank LLD vent valve passing (hydrogen leakage). Not done
12 LP Bypass A & B spray nozzle valves and CV’s inspection to be done (suspected to be chocked). Not done
13 Turbine Bearing NO.7 Jacking oil pressure reading less value. Not done
14 DC JOP local panel resistor got burnt. Not done
15 AC JOP not starting from DCS . Not done
16 H2 Purity Analyzer tapping line having leakage at 6.9 mtr. Not done
17 TDBFP – A CRH steam supply MOV gland leakage. Not done
18 LP Bypass B Spray CV gland leakage Not done
19 CRH steam supply MOV to PRDS flange leakage. Not done
20 HP Exhaust pipe drain valve -1, 2 not operating. Not done
21 HP Exhaust pipe drain valve -3 not operating. Not done
22 Boiler outlet SH steam prs-3 (LBA10CP007) is not reading any value in DCS. Not done
23 LP Bypass valve (HP Cond) behind steam prs (LBB10CP008) is not reading any value in DCS. Not done
24 LP Bypass valve (LP Cond) behind steam prs (LBB20CP008) is not reading any value in DCS . Not done
25 Turbine IP 1st stage pressure (1, 2, 3) are not reading any value in DCS. Not done
26 Gen. stator water conductivity readings to be made availiable in DCS. Not done
27 CW pump-3 Motor DE X vib reading to be made available in DCS. Not done
28 LP casing spray water prs (LCC11CP001) is in bad quality. Not done
29 Third stage DSH water prs (LCC50CP001) is in bad quality. Not done
30 Hotwell make up CV to be commissioned. Not done
31 Hotwell make up Pump-2 to be commissioned from DCS. Not done
32 HP Byp Valve behind stm tmp -1 (LBA10CT004) is in Bad quality . Not done
33 RH inlet stm prs (LBC13CP001) is reading less value . Not done
34 No approach provided for HP Cond Vacuum breaker MOV. Not done
35 No approach provided for HRH drain header MIV. Not done
36 Deaerator pegging MOV not operating from DCS. Not done
37 LP Bypass Valve front Drain Valve not operating. Not done
38 Extraction-3 front Drain Valve instrument air supply not connected. Not done
39 HP Exhaust steam Header pipe pressure (LBA11CP005) is not reading only value in DCS. Not done
40 Extraction -1 Drain Pneumatic valve not operating. Not done
41 RH outlet Steam pressure 2(LBB11CP002) is reading less value. Not done
42 CEP-2A Suction strainer got chocked. Not done
43 CEP outlet manifold prs-1(LCA21CP001) is not reading. Not done
44 EOP and DC SOP current reading not available in DCS. Not done
45 SOVP to be made ready. Not done
BOILER STEAM BLOW OUT MOV/DAMPERS/GATES /CONTROL VALVES
SL NO DESCRIPTION STATUS KKS REMARKS
1 Eco recirculation valve OK 10HAG10AA231
2 Eco recirculation valve-2 OK 10HAG10AA232
3 SH OUTLET MOV (LEFT) OK 1HAH10AA231
4 SH OUTLET MOV (RIGHT) OK 1HAH20AA231
5 EBD-2 OK 1HAN31AA232
6 EBD-1 OK 1HAN31AA233
7 CBD OK 1HAN20AA231
8 Bottom water wall hdr drain NOT OK 1HAN30AA230
9 Bottom water wall hdr drain OK 1HAN30AA231
10 Bottom water wall hdr drain OK 1HAN30AA232
11 Bottom water wall hdr drain OK 1HAN30AA233
12 Bottom water wall hdr drain OK 1HAN30AA234
13 Bottom water wall hdr drain OK 1HAN30AA235
14 Bottom water wall hdr drain OK 1HAN30AA236
15 Bottom water wall hdr drain OK 1HAN30AA237
16 Bottom water wall hdr drain OK 1HAN30AA238
17 Bottom water wall hdr drain OK 1HAN30AA239
18 Bottom water wall hdr drain OK 1HAN30AA240
19 Bottom water wall hdr drain OK 1HAN30AA241
20 Bottom water wall hdr drain OK 1HAN30AA242
21 Bottom water wall hdr drain OK 1HAN30AA243
22 Bottom water wall hdr drain OK 1HAN30AA244
23 Bottom water wall hdr drain OK 1HAN30AA245
24 Bottom water wall hdr drain OK 1HAN30AA246
25 Bottom water wall hdr drain NOT OK 1HAN30AA247
26 Bottom water wall hdr drain OK 1HAN30AA248
27 Bottom water wall hdr drain OK 1HAN30AA249
28 Bottom water wall hdr drain OK 1HAN30AA250
29 Bottom water wall hdr drain OK 1HAN30AA251
30 Bottom water wall hdr drain NOT OK 1HAN30AA252
31 Bottom water wall hdr drain OK 1HAN30AA253
32 Bottom water wall hdr drain OK 1HAN30AA254
33 Bottom water wall hdr drain OK 1HAN30AA255
34 Bottom water wall hdr drain NOT OK 1HAN30AA256
35 Bottom water wall hdr drain OK 1HAN30AA257
36 Bottom water wall hdr drain OK 1HAN30AA258
37 Bottom water wall hdr drain OK 1HAN30AA259
38 Bottom drain hdr to IBD OK 1HAN31AA231
39 Aux steam line to bottom ww hdr NOT OK 1HAD10AA134 Not commissioned
40 Startup vent OK 1HAH10AA231
41 Startup vent OK 1HAH10AA232
42 Startup vent OK 1HAH20AA233
43 Startup vent OK 1HAH20AA234
44 Main steam line drain OK 1HAN50AA233
45 Main steam line drain OK 1HAN50AA234
46 Primary SH inlet hdr drain OK 1HAN50AA232
47 HRA bottom ring hdr drain OK 1HAN50AA231
48 RH inlet hdr pipe drain(CRH) OK 1HAN90AA231
49 RH inlet hdr pipe drain(CRH) OK 1HAN90AA232
50 RH outlet hdr drain(HRH) OK 1HAN90AA233
51 RH outlet hdr drain(HRH) OK 1HAN90AA234
52 1st DSH inlet isolation valve OK 1HAM20AA231
53 1st DSH outlet isolation valve OK 1HAM20AA232
54 1st DSH inlet isolation valve OK 1HAM30AA231
55 1st DSH outlet isolation valve OK 1HAM30AA232
56 2nd DSH inlet isolation valve OK 1HAM20AA233
57 2nd DSH outlet isolation valve OK 1HAM20AA234
58 2nd DSH inlet isolation valve OK 1HAM30AA233
59 2nd DSH outlet isolation valve OK 1HAM30AA234
60 RH spray Inlet isolation valve(Left) OK 1HAM50AA231
61 RH spray Outlet isolation valve(Left) OK 1HAM50AA232
62 RH spray Inlet isolation valve(Right) OK 1HAM60AA231
63 RH spray Outlet isolation valve(Right) OK 1HAM60AA232 28
64 Drum to CBD blow down OK 1HAN10AA130
65 Drum to IBD blow down OK 1HAN11AA130
66 From CBD vent to D/A NOT OK 1HAN40AA130 Not commissioned
67 APH-A Soot blower mov 1HCB15AT001 Local operation is OK
68 APH-B Soot blower mov 1HCB15AT002 Local operation is OK
69 LDO RECIRULATION MOV OK
70 HFO RECIRULATION MOV OK
71 Back Washing MOV NOT OK 1HAH20AA233 Not commissioned

SL NO DESCRIPTION STATUS KKS REMARKS


72 CBD CONTROL VALVE OK
73 LDO RETURN LINE CONTROL VALVE OK
74 HFO RETURN CONTROL VALVE OK
75 HFO SUPPLY CONTROL VALVE OK
76 HFO ATOMISING CONTROL VALVE OK
77 LDO ATOMISING CONTROL VALVE OK
78 RH Temp Control Damper -1 OK
79 RH Temp Control Damper -2 OK
80 RH Temp Control Damper -3 OK
81 SH temp Control Damper -1 OK
82 SH temp Control Damper -2 NOT OK
83 SH temp Control Damper -3 OK
84 SH temp Control Damper -4 NOT OK
85 SH 1st DSH Temp CV (Primary) OK
85 SH 1st DSH Temp CV (Primary) OK
85 SH 1st DSH Temp CV(Secondary) OK
85 SH 1st DSH Temp CV(Secondary) OK
86 RH DSH Temp CV -A OK
87 RH DSH Temp CV -B OK
88 30% Line FRS CV NOT OK Feedback not coming in DCS
IBD Pre CV OK

SL NO DESCRIPTION STATUS KKS REMARKS


89 Left ESP outlet Gate - 1 OK
90 Left ESP outlet Gate - 2 OK
91 Left ESP inlet Gate - 1 OK
92 Left ESP inlet Gate - 2 OK
93 Right ESP outlet Gate - 1 OK
94 Right ESP outlet Gate - 2 NOT OK Gear box problem
95 Right ESP inlet Gate - 1 OK
96 Right ESP inlet Gate - 2 OK
97 IDF - A Blade Actuator(IGV) OK
98 IDF - A inlet Gate OK
99 IDF - A oulet Gate OK
100 IDF - B Blade Actuator (IGV) OK
101 IDF - B inlet Gate OK
102 IDF - B outlet Gate NOT OK
103 FDF - A Blade Actuator (BP) OK
104 FDF - A outlet Damper OK
105 FDF - B Blade Actuator (BP) OK
106 FDF - B outlet Damper OK
107 APH - A SA inlet Damper OK
108 APH - B SA inlet Damper OK
109 Left Hot SA Damper (APH - A) OK
110 Right Hot SA Damper (APH - B) OK
111 APH - A gas inlet Damper - 1 OK
112 APH - A Gas inlet Damper - 2 OK
113 APH - B gas inlet Damper - 1 OK
114 APH - B Gas inlet Damper - 2 OK
115 PAF-A Outlet Damper OK
116 PAF-B Outlet Damper OK
117 APH - A PA inlet Damper OK
118 APH - B PA inlet Damper OK
119 Left Hot PA Damper (APH - A) NOT OK Power supply problem
120 Right Hot PA Damper (APH - B) OK
121 Left Cold PA Damper OK
122 Right Cold PA Damper OK
123 SAF-A Inlet IGV NOT OK
124 SAF-B Inlet IGV OK

SL NO DESCRIPTION STATUS KKS REMARKS


Wind box Secondary hot air damper
124 C - LEFT OK
Wind box Secondary hot air damper
125 C - RIGHT OK
Wind box Secondary hot air damper
126 D - LEFT OK
Wind box Secondary hot air damper
127 D - RIGHT OK
Wind box Secondary hot air damper
128 E - LEFT NOT OK Cmd/Feedback mismatch
Wind box Secondary hot air damper
129 E - RIGHT OK
Wind box Secondary hot air damper
130 A - LEFT OK
Wind box Secondary hot air damper
131 A - RIGHT OK
Wind box Secondary hot air damper
132 B - LEFT OK
Wind box Secondary hot air damper
133 B - RIGHT OK
Wind box Secondary hot air damper
134 F - LEFT NOT OK Cmd/Feedback mismatch
Wind box Secondary hot air damper F
135 - RIGHT OK
136 Wind box Cental air damper C - LEFT OK
Wind box Cental air damper C-
137 RIGHT OK Abnormal sound
Wind box Cental air damper D -
138 LEFT NOT OK Cmd/Feedback mismatch
Wind box Cental air damper D-
139 RIGHT OK
140 Wind box Cental air damper E - LEFT OK
Wind box Cental air damper E -
141 RIGHT NOT OK Abnormal sound
142 Wind box Cental air damper A - LEFT OK
Wind box Cental air damper A -
143 RIGHT NOT OK Cmd/Feedback mismatch
144 Wind box Cental air damper B - LEFT OK
Wind box Cental air damper B -
145 RIGHT OK
146 Wind box Cental air damper F - LEFT NOT OK Cmd/Feedback mismatch
Wind box Cental air damper F -
147 RIGHT OK
148 FRONT OFA damper -LEFT OK
149 FRONT OFA damper -RIGHT OK
150 REAR OFA damper -LEFT OK
151 REAR OFA damper -RIGHT OK
UNIT-2 TURBINE AREA MOV LIST

Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks

1LBD82AA630 MFPT A EXHAUSE PIPE DRAIN VALVE ON/OFF


1 17/17 OK

1LBD83AA630 MFPT B EXHAUSE PIPE DRAIN VALVE ON/OFF


2 17/17 OK

1LBD45AA330 4 SECT EXTRACTION TO AUX. STEAM MOV REG


3 OK

1LBD71AA130 4 SECT EXTRACTION TO MFPT A MOV ON/OFF


4 95/95

1LBD72AA130 4 SECT EXTRACTION TO MFPT B MOV ON/OFF


5 95/95

1LBD40AA331 4 SECT EXTRACTION TO DEAERATOR MOV REG


6 OK

1LBD50AA330 5 SECT EXTRACTION MOV REG


7 Extraction OK
System
1LBD60AA330 6 SECT EXTRACTION MOV REG
8 OK

1LBD20AA130 2 SECT EXTRACTION MOV REG


9 OK

1LBD40AA330 4 SECT EXTRACTION MOV REG


10 OK

1LBD10AA130 1 SECT EXTRACTION MOV REG


11 OK

1LBD30AA130 3 SECT EXTRACTION MOV REG


12 OK

1LBD80AA330 MFPT A EXHAUSE VALVE ON/OFF


13 47/47

1LBD81AA330 MFPT B EXHAUSE VALVE ON/OFF


14 50/50

1LBG15AA130 AUX. STEAM TO AIR PREHEATER SOOTBLOWER MOV ON/OFF


15 67/67 OK

1LBG30AA130 AUX. STEAM TO FUEL OIL AREA STEAM MOV ON/OFF


16

1LBG14AA130 AUX. STEAM TO BOILER IGNITOR ATMOZING MOV ON/OFF


17 67/67 OK

1LBG16AA130 AUX. STEAM TO COAL MILL FIRE FIGHTING STEAM MOV ON/OFF
18 48/48 OK

1LBG17AA130 AUX. STEAM TO BEPT A STEAM MOV ON/OFF


19 90/90 OK

1LBG17AA131 AUX. STEAM TO BEPT B STEAM MOV ON/OFF


20 Aux . Steam 91/91 OK
system
Checked
Open/Clos Along
e time with
SL NO Aux . Steam KKS Code
SYSTEM DESCRIPTION Type (sec) DEC Remarks
system AUX. STEAM TO DEAERATOR REGULATING VALVE FRONT OK
1LBG12AA130 ON/OFF
21 MOV 107/107 OK
( Relate
d to
1LBG10AA130 UNIT 1 AUX. STEAM HEADER CONNECTING MOV ON/OFF
22 163/163 UNIT-1 )

1LBG12AA131 AUX. STEAM TO DEAERATOR BYPASS MOV REG


23 OK

1LBG19AA130 COLD REHEAT STEAM TO AUX. STEAM HEADER MOV ON/OFF


24 99/99 OK
COLD REHEAT STEAM TO AUX. STEAM HEADER BYPASS
1LBG19AA230 REG
25 MOV OK

1LBG20AA130 MAIN STEAM TO AST REG


26 OK
AUX. STEAM SOURCE SHUT-OFF VALVE OF TURBINE GLAND
1MAW10AA230 ON/OFF
27 STEAM 79/79 OK
CRH. AUX. STEAM SOURCE SHUT-OFF VALVE OF TURBINE
1MAW10AA231 ON/OFF
28 GLAND STEAM 54/54 OK

1MAW01AA230 GLAND STEAM CONDENSER TPO HOTWELL DRAIN VALVE ON/OFF


29
PRESS. REGULATING VALVE FRONT MOV. OF TURBINE
1MAW20AA230 ON/OFF
30 GLAND HP.. STEAM SOURCE 20/20 OK
PRESS. REGULATING VALVE FRONT MOV. OF TURBINE
1MAW10AA232 ON/OFF
31 GLAND STEAM LP. STEAM SOURCE 80/80 OK
SELF-SEALING STEAM OVERFLOW STATION REGULATING
1MAW30AA232 ON/OFF
32 VALVE BYPASS VALVE 129/129 OK
Gland steam PRESS REGULATING VALVE BYPASS VALVE OF TURBINE
1MAW10AA233 ON/OFF
33 system GLAND LP. STEAM SOURCE 20/20 OK
SELF-SEALING STEAM OVERFLOW STATION TO NO.8 LP
1MAW30AA230 ON/OFF
34 HEATER MOV. VALVE 120/120 OK
SELF-SEALING STEAM OVERFLOW STATION TO CONDENSER
1MAW30AA231 ON/OFF
35 MOV. VALVE 141/141 OK

1XAM12AA230 INLET STEAM VALVE OF BFPT A GLAND ON/OFF


36 12 OK

1XAM10AA230 OUTLET STEAM VALVE OF BFPT A GLAND ON/OFF


37 12

1XAM13AA230 INLET STEAM VALVE OF BFPT B GLAND ON/OFF


38 14/14 OK

1XAM11AA230 OUTLET STEAM VALVE OF BFPTB GLAND ON/OFF


39 14/14 OK

1LBA50AA200 HP BYPASS WARM UP PIPE MOV ON/OFF


40 25/25

1LBC15AA230 CRH TO BFPT A STEAM MOV ON/OFF


41 80/80 OK
Main Steam ,
RH ,Bypass
system
Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks
Main Steam ,
RH ,Bypass 1LBC16AA230 CRH TO BFPT B STEAM MOV ON/OFF
42 80/80 OK
system
1LAC20AA230 TURBINE PREHEATING VALVE ON/OFF
43 20/20 OK

1LAC20AA290 TURBINE PREHEATING THROTTLE VALVE REG


44 OK

1LCB40AA130 HOT WELL MAKE-UP WATER VALVE BYPASS MOV REG


45 OK
NO.5 LP HEATER OUTLET TO CIRCULATING DISCHARGE PIPE
1LCA36AA130 ON/OFF
46 MOV 100/100 OK

1LCG10AA660 CEP RECIRCULATION CONTROL VALVE BACK MOV REG


47 OK

1LCG10AA661 CEP RECIRCULATION CONTROL VALVE BYPASS MOV REG


48 OK

1LCA11AA400 CP. A INLET MOV ON/OFF


49 34/34 OK

1LCA12AA400 CP. B INLET MOV ON/OFF


50 34/34 OK

1LCA21AA130 CP. A OUTLET MOV ON/OFF


51 98/98 OK

1LCA22AA130 CP. B OUTLET MOV ON/OFF


52 100/100 OK

1LCA30AA130 GLAND STEAM CONDENSER INLET MOV ON/OFF


53 100/100 OK

1LCA30AA131 GLAND STEAM CONDENSER OUTLET MOV ON/OFF


54 111/111 OK

1LCA31AA130 GLAND STEAM CONDENSER BYPASS MOV ON/OFF


55 105/105 OK

1LCA32AA230 DEAERATOR WATER LEVEL CTRL BYPASS MOV REG


56 OK

1LCA30AA132 NO.8 LP HEATER INLET MOV ON/OFF


57 87/87 OK

1LCA30AA133 NO.7 LP HEATER OUTLET MOV ON/OFF


58 97/97 OK

1LCA33AA130 NO.7&8 LP HEATER BYPASS MOV ON/OFF


59 98/98 OK

1LCA30AA134 NO.6 LP HEATER INLET MOV ON/OFF


60 101/101 OK

1LCA30AA135 NO.6 LP HEATER OUTLET MOV ON/OFF


61 102/102 OK

1LCA34AA130 NO.6 LP HEATER BYPASS MOV ON/OFF


62 102/102 OK
Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks

1LCA30AA136 NO.5 LP HEATER INLET MOV ON/OFF


63 90/90 OK

1LCA30AA137 NO.5 LP HEATER OUTLET MOV ON/OFF


64 97/97 OK

1LCA35AA130 NO.5 LP HEATER BYPASS MOV ON/OFF


65 100/100 OK
CONDENSATE WATER TO ATTEMPERATOR OF TURBINE
1LCC52AA230 ON/OFF
66 GLAND STEAM SYSTEM REGULATING VALVE FRONT MOV 12 OK
CONDENSATE WATER TO ATTEMPERATOR OF TURBINE
1LCC52AA231 REG
67 Condensate GLAND STEAM SYSTEM REGULATING VALVE BYPASS MOV OK
system THIRD DESUPERHEATER(HP CONDENSER) OF LP BYPASS
1LCC31AA230 ON/OFF
68 SPRAY WATER REGULATING VALVE FRONT MOV 20/20
THIRD DESUPERHEATER(LP CONDENSER) OF LP BYPASS
1LCC32AA230 ON/OFF
69 SPRAY WATER REGULATING VALVE FRONT MOV 20/20
ATTEMPERATING WATER OF DRAIN FLASH TANK II CONTROL
1LCC70AA230 ON/OFF
70 VALVE FRONT MOV 17/17 OK
ATTEMPERATING WATER OF DRAIN FLASH TANK I CONTROL
1LCC60AA230 ON/OFF
71 VALVE FRONT MOV 17/17 OK

1LDF17AA001 POLISHING DEMINERALIZER INLET MOV REG


72 Not commissioned

1LDF17AA002 POLISHING DEMINERALIZER OUTLET MOV REG


73 Not commissioned

1LDF17AA003 POLISHING DEMINERALIZER BYPASS MOV REG


74 Not commissioned
AUX STEM TO BOILER IGITER ATOMISING TEMP
1LCC41AA230 ON/OFF
75 REGULATING VALVE FRONT MOV
AUX STEM TO BOILER IGITER ATOMISING TEMP
1LCC41AA231 REG
76 REGULATING VALVE BYPASS MOV

1LCC42AA230 MAIN STEAM TO AST TEMP REGULATING VALVE FRONT MOV ON/OFF
77

1LCC42AA231 MAIN STEAM TO AST TEMP REGULATING VALVE BYPASS MOV REG
78
CONDENSATE WATER TO PULVERIZER FOR FIRE FIGHTNING
1LCC43AA230 ON/OFF
79 STEAM TEMP REGULATIG VALVE FRONT MOV
CONDENSATE WATER TO PULVERIZER FOR FIRE FIGHTNING
1LCC43AA231 REG
80 STEAM TEMP REGULATIG VALVE BYPASS MOV
CONDENSATE WATER TO ATTEMPERATION OF AUX STEAM TO
1LCC51AA230 ON/OFF
81 GLAND STEAM VALVE 15/15 OK
OK
CONDENSATE WATER TO ATTEMPERATION OF AUX STEAM TO ( Comm
1LCC51AA231 REG
82 GLAND STEAM BYPASS VALVE
on to
CONDENSATE WATER TO FUEL OIL AREA STEAM Both
1LCC80AA231 ON/OFF
83 TEMP.REGULATING VALVE BYPASS MOV 15/16 Units )
Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks

1LCC42A230 MAIN STEAM AUX STEAM TEMP REG VALVE FRONT MOV ON/OFF
84
OK
1LCC42A231 MAIN STEAM AUX STEAM EMP REG VALVE BYPASS MOV REG ( Comm
85 on to
CONDENSATE WATER TO FUEL OIL AREA STEAM Both
1LCC80AA230 ON/OFF
86 TEMP.REGULATING VALVE FRONT MOV 15/16 Units )

1LCC31AA630 THIRD DESUPERHEATER(HP CONDENSER) BYPASS MOV REG


87

1LCC32AA630 THIRD DESUPERHEATER(HP CONDENSER) BYPASS MOV REG


88

1LCC61AA630 ATTEMPERATING WATER OF DRAIN FLASH TANK I CONTROL REG


89 VALVE BYPASS MOV
ATTEMPERATING WATER OF DRAIN FLASH TANK II CONTROL
1LCC71AA630 REG
90 VALVE BYPASS MOV OK

1LAC40AA001 BOILER FEED PUMP HEADER PIPE PRESS CONTROL VALVE REG
91 OK

1LAF10AA130 BOILER FILL MOV ON/OFF


92 20/20 OK

1LAA30AA130 TDBFBP A INLET MOV ON/OFF


93

1LAA20AA130 TDBFBP B INLET MOV ON/OFF


94

1LAA10AA130 MBFBP INLET MOV ON/OFF


95 146/146 OK

1LAC10AA132 FEED CONTROL STATION REGULATING VALVE FRONT MOV ON/OFF


96

1LAC71AA133 FEED CONTROL STATION REGULATING VALVE BACK MOV ON/OFF


97 OK

1LAC10AA130 TDFP A OUTLET MOV ON/OFF


98

1LAC20AA130 TDFP B OUTLET MOV ON/OFF


99 130/130 OK

Feedwater 1LAC30AA130 MBFP OUTLET MOV ON/OFF


100 143/143 OK
System
1LAC40AA130 NO.3 HP HEATER INLET MOV ON/OFF
101 263/263 OK

1LAC40AA131 NO.3 HP HEATER OUTLET MOV ON/OFF


102 263/263 OK

1LAC41AA130 NO.3 HP HEATER BY-PASS MOV ON/OFF


103 OK

1LAC50AA130 NO.2 HP HEATER INLET MOV ON/OFF


104 OK
Feedwater
System

Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks

1LAC50AA131 NO.2 HP HEATER OUTLET MOV ON/OFF


105 OK

1LAC51AA130 NO.2 HP HEATER BY-PASS MOV ON/OFF


106 OK

1LAC60AA130 NO.1 HP HEATER INLET MOV ON/OFF


107 OK

1LAC60AA131 NO.1 HP HEATER OUTLET MOV ON/OFF


108 OK

1LAC61AA130 NO.1 HP HEATER BY-PASS MOV ON/OFF


109 OK
110 1LAC70AA131 MAIN FEED WATER MOV (100% line ) ON/OFF OK
111 1LFA13AA130 HP CONDENSER VACCUM ISOLATION VALVE 1 ON/OFF OK
112 1LFA13AA131 HP CONDENSER VACCUM ISOLATION VALVE 2 ON/OFF OK
113 Vacuum 1LFA14AA130 LP CONDENSER VACCUM ISOLATION VALVE 1 ON/OFF OK
114 System 1LFA14AA131 LP CONDENSER VACCUM ISOLATION VALVE 2 ON/OFF OK
115 1LFA11AA130 HP CONDENSER VACCUM BREAKER VALVE ON/OFF OK
116 1LFA12AA130 LP CONDENSER VACCUM BREAKER VALVE ON/OFF OK
117 1LEC10AA630 DEAERATOR DRAIN VALVE BYPASS MOV REG OK
118 1LEC41AA230 DEAERATOR EXHAUST VALVE 1 ON/OFF Integral type
119
Deaerator Integral type
1LEC41AA231 DEAERATOR EXHAUST VALVE 2 ON/OFF
120 System 1LEC41AA232 DEAERATOR EXHAUST VALVE 3 ON/OFF Integral type
121 1LEC41AA233 DEAERATOR EXHAUST VALVE 4 ON/OFF Integral type
122 10PGB06AA102 ECWP1 DISCHARGE MOV ON/OFF OK
123 10PGB07AA102 ECWP2 DISCHARGE MOV ON/OFF OK
124 10PGB01AA101 ECW OVER HEAD TANK I/L MOV ON/OFF OK
125
ECW System OK
10PCB60AA330 MDBFP COOLER O/L CONTROL VALVE ON/OFF
126 10PGB06AA101 ECWP1 SUCTION MOV ON/OFF OK
127 10PGB07AA101 ECWP2 SUCTION MOV ON/OFF No Actuator
128 10PCB01AA101 ACW P-1 DISCHARGE MOV ON/OFF OK
129 10PCB02AA101 ACWP2 DISCHARGE MOV ON/OFF OK
130 ACW System 10PCB03AA101 ACWP3 DISCHARGE MOV ON/OFF OK
131 10PCB06AA101 ACWP RECIRCULATION VALVE REG OK
132 10PCB07AA101 ACW SUPPLY UNIT-1 ON/OFF Not commissioned
133 00PAB01AA101 CWP1 DISCHARGE VALVE (1A) ON/OFF OK
134 00PAB02AA101 CWP2 DISCHARGE VALVE (1B) ON/OFF OK
135 00PAB03AA101 CWP 5 DISCHARGE VALVE (Common) ON/OFF OK
136 00PAB04AA101 CWP 3 DISCHARGE VALVE (2A) ON/OFF OK
137 00PAB05AA101 CWP 4 DISCHARGE VALVE(2B) ON/OFF Not commissioned
138 00PAB06AA101 CW DUCT INTERCONNECTION VALVE UNIT1 ON/OFF OK
139 CW System 00PAB06AA101 CW DUCT INTERCONNECTION VALVE UNIT2 ON/OFF Actuator card problem
140 10PAB11AA101 CW TO CONDENSER I/L VALE1 ON/OFF Actuator problem
141 10PAB12AA101 CW TO CONDENSER I/L VALE2 ON/OFF Actuator problem
142 10PAB13AA101 CW O/L VALVE1 FROM CONDENSER ON/OFF Actuator problem
Checked
Open/Clos Along
e time with
SL NO SYSTEM KKS Code DESCRIPTION Type (sec) DEC Remarks
143 10PAB14AA101 CW O/L VALVE2FRO M CONDENSER ON/OFF Actuator problem
144 CONDENSER TUBE CLEANING FILTER VALVE1 ON/OFF Not commissioned
145 CONDENSER TUBE CLEANING FILTER VALVE2 ON/OFF Not commissioned
146 CONDENSER TUBE CLEANING DEBRIS FILTER VALVE1 Not commissioned
147 CONDENSER TUBE CLEANING DEBRIS FILTER VALVE2 Not commissioned