Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Page No.1 of 12
1 INTRODUCTION
NSPCL, A Joint Venture of NTPC and SAIL, is setting up an expansion of the Bhilai
Power Project by 2x250 MW power generation at Bhilai, District Durg, Chhatisgarh. The
installed capacity of existing Power Plants (Power Plant 1-PP1 and Power Plant 2- PP2) in
Bhilai Steel Plant (BSP) is 110MW. The BSP load is 350 MW. In normal course, the Bhilai
Power Project (Power Plant 3, PP3 consisting of G1 and G2) will work in parallel with Bhilai
Steel Plant (BSP), existing Power Plants (PP1 and PP2) and PGCIL’s grid. PP3 will supply 240
MW to BSP. Around 40 MW are consumed by PP3 auxiliaries, the balance 220 MW will be
exported to the grid at 400 kV. But during contingency conditions, there is a possibility of BSP
together with PP1, PP2 and PP3 being islanded from grid. Under this islanding operation, PP3
shall be supplying power to Bhilai Steel Plant only through dedicated transmission lines
connecting Bhilai Steel Plant to Bhilai Power Project. This report focuses on the development of
a model of the electric power system in an expansion of the Bhilai Power Project by 2x250 MW
power generation in order to perform short circuit study conducted on power system data as per
TB-254-357-001- “Design Data, Load Flow and Island Mode of Operation Study” Report. The
results of study serve to establish sequence data files to be used in further stability studies.
SIMPOW, Power System Simulation Software is used for carrying out the Short Circuit studies.
A Short Circuit Study is critical for the safe, efficient, and economical operation of any
electrical distribution system. A Short Circuit Study will help to ensure that personnel and
equipment are protected by establishing proper short circuit current ratings. When an electrical
fault exceeds the interrupting rating of the protective device, the consequences can be
devastating, including injury, damaged electrical equipment, and costly downtime. Among the
most important tasks, when planning and operating power systems, are the short-circuit current
calculations (SCCs). Faults, i.e. short-circuits, can be minimized in the system through planning
and design, and well-performed maintenance and operation of the system, but cannot be totally
avoided. Protection settings and coordination and dimensioning of switchgear require accurate
and detailed SCCs because switches and breakers have to be designed to switch off short-
circuits in a safe way and in short time. Short-circuits can cause mechanical oscillations in
generators which can lead to oscillations in the power in the system, causing problems of
stability in the power transfer. In the worst case this can lead to a blackout of the system. One
last area to consider is that the installed equipment must be able to withstand the thermal and
mechanical effects of short-circuit currents. Hence, it is very essential to conduct fault level
calculation study for power system.
TB-254-357-005
Page No.2 of 12
4 Input Data
1. Input data for the study is as per Report No: TB-254-357-001.
2. Single line diagram is taken to indicate the overall network around Bhilai Steel Plant for
carrying out the short circuit studies.
The following load flow base cases [1] as described in Load Flow study were considered for
calculating the Short Circuit levels.
The power flow results for the above 3 cases are mentioned in Report No: TB-254-357-001.
6 Fault Studies
The power system is divided into several different voltage levels, where calculations are
made for short circuits on the 400 kV, 220kV and 132 kV levels. Three different cases are set up
in order to evaluate the system, so that the maximum and minimum currents can be determined.
Fault studies were carried out to determine fault levels under the below three cases.
Fault Cases
Case No. CASE Name
1 CASE 1
2 CASE 2
3 CASE 3
TB-254-357-005
Page No.3 of 12
1 BESCL220
2 BESCL400
3 MSD5Ͳ220
4 MSD6Ͳ220
5 BP1TG1Ͳ6
6 BP1TG2Ͳ6
7 BP1TG0Ͳ6
8 MSD1Ͳ132
9 MSD2Ͳ132
10 MSD3Ͳ132
11 MSD4Ͳ132
12 MSD5Ͳ132
13 MSD6Ͳ132
14 M4SEC1Ͳ1
15 M4SEC2Ͳ1
16 M4SEC1Ͳ6
17 M4SEC2Ͳ6
18 M2DR1Ͳ6
19 M2DR2Ͳ6
20 M2VADͲ11
21 M2SMSͲ11
22 M2SEC1Ͳ1
TB-254-357-005
Page No.4 of 12
23 M2SEC2Ͳ1
24 M2SEC1Ͳ6
25 M2SEC2Ͳ6
26 M2SEC3Ͳ6
27 M2SEC4Ͳ6
28 M6SEC1Ͳ1
29 M6SEC2Ͳ1
30 P2Ͳ1Ͳ132
31 P2Ͳ2Ͳ132
32 P2SEC1Ͳ6
33 P2SEC2Ͳ6
34 P2Ͳ21TͲ6
35 P2Ͳ22TͲ6
36 P2Ͳ23TͲ6
TB-254-357-005
Page No.5 of 12
The different cases analyzed are a number of network configurations that are of interest to
investigate. Three different cases are set up, where each case has a specific objective which is
important to examine.
7.1.1 Case 1
7.1.2 Case 2
Case 2 is set up at Islanded operation of 2X250 MW PP3, PP2, PP1 and BSP without grid
connection. PP3 generators are assumed to be operating at 1.05pu voltage in order to ensure
the voltages in the study system within the limits. Generator G1 is supplying 143 MW and
generator G2 is supplying 142 MW to meet the reduced load requirement in the absence of
export to grid. The short circuit current levels in the network are tabulated in Table.2. The short
circuit current values obtained in the study system are within the limits, i.e. less than 40kA for
one second.
The 3 phase to ground and single phase to ground fault currents at each of the 400kV, 220kV
and 132kV buses for case 2 are tabulated in Annexure B.
7.1.3 Case 3
Case 2 is set up at Islanded operation of 1X250 MW PP3, PP2, PP1 and BSP from grid
connection. Only one PP3 generator (G1) is assumed to be operating at 1.03pu voltage and
supplying 250 MW to BSP. The short circuit current levels in the network are tabulated in
Table.2. The short circuit current values obtained in the study system are within the limits, i.e.
less than 40kA for one second.
The 3 phase to ground and single phase to ground fault currents at each of the 400kV, 220kV
and 132kV buses for case 3 are tabulated in Annexure C.
.
TB-254-357-005
Page No.6 of 12
For each case, reported in Annexure A to C, the maximum fault current (fault KVA level) out of
the fault currents on the selected 36 buses is shown in bold letters. Similarly, the minimum fault
current (fault KVA level) out of the fault current on the selected 36 buses are shown in bold
italics for each operating scenario.
8 Conclusions
The short circuit studies were conducted for the various base operating conditions and
contingencies.
Maximum fault currents were then determined at M2DR1-6 bus for case 1,BP1TG1-6 bus
for case 2 and M2DR1-6 bus for case 3.
The fault levels at various buses of 400kV, 220kV and 132kV were found to be lower than
40 kA as stipulated in Technical Specifications. Out of the reported fault levels, the
minimum and maximum fault levels at the 400 kV, 220kV and 132kV buses in cases 1 to 3
are as shown below:
The study summarises the results of short circuit levels under various conditions.
9 References:
1. TB-254-357-001- “Design Data, Load Flow and Island Mode of Operation Study” Report.
TB-254-357-005
Page No.7 of 12
Annexure A
CASE 1
Annexure B
CASE 2
Annexure C
CASE 3