110/30 kV power transformer Unit REQUIRED GUARANTEE

D
Technical performances
Manufacturer - Name
Country of origin - country
Type - Three phase
oil
IEC standards - IEC 60076,
60354
Rated power ONAN MVA 20
Rated voltage kV/kV 110/30
Maximum working voltage kV/kV 145/36
Nominal frequency Hz 50
Connection symbol - YNd11
Short-circuit voltage in middle position % 12
Insulation - uniform
Cooling mode - ONAN/ONAF
Temperature rise (Rated power, 40 ° C maximum
ambient temperature)
oil (Upper level) °C 50
Winding °C 60
Indoor / outdoor power frequency withstand kV 230/275
voltage, primary winding
Indoor / outdoor power frequency withstand kV 70/82
voltage, secondary winding
Internal / external shock wave withstand voltage, kV 550/650
primary winding
Internal / external shock wave withstand voltage, kV 170/200
secondary winding
Noise level (in no load / at 100% load) dB (A) 66
Idle current % In 0,2
No load losses kW
Current at no load A
Nominal power losses (ONAN) kW
Nominal power losses (ONAF) kW
Losses in the core W/kg
Short-circuit current (3s): kA 31,5
Homopolar impedance Ω/ph
Connection mode
Primary side overhead
Secondary side cables
Dimensions
Length mm
Depth mm
Height mm
Weight
Total kg
of transport kg
of oil kg
Tap changers
Type - In resistance
load
Rated current A
110/30 kV power transformer Unit REQUIRED GUARANTEE
D
Technical performances
Current assigned for permissible short duration
Maximum kA 31,5
3 seconds kA 10
On-load tap-changer adjustment range - +-15%
+-12x1,25
Mode of installation - HV side
Duration of the life of the switches cycles 200.000
Automatic tension control
Manufacturer -
Type -
Manufacturing place -
Tension Umax % of Un
Tension Umin % of Un
Max current x In
Sensitivity -%,+%
Response time sec
Maximum temperatures:
Normal maximum oil rise °C 50
Medium ONAN rise windings °C 55
Medium ONAF rise windings °C 55

maximum hot spot temperature at room °C 98


temperature and nominal power
maximum hot spot temperature in case of °C 140
emergency overload

Coupling
(a) HV windings Star
(b) LV windings Triangle
(d) Coupling YNd11

Short-circuit current at the terminals


110kV busbar kA 31,5
30 kV busbar kA 25

Type of control local, remote


control
Compensation of the line drop yes
Automatic control, voltage yes, 110V,
50Hz
Local control panel yes
Distance between local control panel and m drawing
transformer
Nominal / Maximum DC Voltage V 110 V/125 V
Help required for commissioning Control Yes
Special conditions of bid
i) HV side 110kV : 250/400/1A
Core 1 / Core 2 / Core 3 60VA / 5P20
i) LV side 30kV : 300/600/1A
Core 1 / Core 2 / Core 3 60VA / 5P20
110/30 kV power transformer Unit REQUIRED GUARANTEE
D
Technical performances
Creepage distance mm/KV 20
Cooling
Number of Chillers (Coolers) according to
study
Chiller losses (% of total losses at CMR) % 50
Standby Chiller One Fan per
Chiller
General
Type of conservation system Air cell
Maximum noise level dB (A) 78
Service conditions
External type of cooling - Air
maximum altitude m 2000
Maximum temperature of air °C 35