Power autotransformer 220//110/30 kV Unit REQUIRED GUARANTEE

D
Technical performances
Manufacturer - Name
Country of origin - country
Type / Isolation - Three-phase /
- Mineral Oil
Manufacturing place
IEC standards - IEC 60076, 60354
Installation - External
Transformation ratio (median socket) kV / kV / 220 / 110 / 30
kV
Neutral speed - Firmly grounding
Nominal frequency Hz 50
Insulation - uniform
Cooling mode - ONAN/ONAF/
ONAF
Rated power MVA 20/60/60
Temperature rise (Rated power, 40 ° C maximum
ambient temperature)
oil (Upper level) °C 50
Winding °C 60
Primary insulation level: 1050
Resistance to impact voltage (line) kV peak 460
95

Resistance to industrial frequency (line) kV eff


Resistance to impact voltage (neutral) kV peak 650
275
95
Secondary insulation level:
Resistance to impact voltage (line) kV peak 650
Resistance to industrial frequency (line) kV eff 275
Resistance to impact voltage (neutral) kV peak 95
Tertiary insulation level: kV peak 170
Resistance to impact voltage (line) kV peak 70
Momentary induced voltage withstand (line)
Noise level (in no load / at 100% load) dB (A) < 65
Idle current % In 0,2
No load losses kW < 75
Current at no load A
Nominal power losses (ONAN) kW
Nominal power losses (ONAF) kW
Losses in the core W/kg
Short-circuit current (3s): kA 31,5
Homopolar impedance Ω/ph
Connection mode
Primary side - overhead
Secondary side - overhead
Tertiary side - cable
Dimensions
Length mm
Power autotransformer 220//110/30 kV Unit REQUIRED GUARANTEE
D
Technical performances
Depth mm
Height mm
Weight
Total kg
of transport kg
of oil kg
Paint
Tropical/anti-rust type - Yes
Layers - 3
On-load tap changer - 17 position 220kV
± 8 x 1.88% at
vacuum break
Current assigned for permissible short duration
Maximum kA
31,5
3 seconds kA 10
On-load tap-changer adjustment range - 17 positions 220
kV ± 8 x
1.88%with
vacuum cut-off
Mode of installation - HV side
Duration of the life of the switches cycles 200.000
Temperatures on a continuous rated load:
Winding °C 62
Oil °C 57
Hot point °C 72
Supply voltage for accessories (fans, controls, Vac 400/230
heating, etc.)
maximum hot spot temperature at room °C 98
temperature and nominal power
maximum hot spot temperature in case of °C 140
emergency overload
Coupling
Coupling - YNa0d11
Short-circuit current at the terminals
220kV busbar kA According to the
calculation
110kV busbar kA According to the
calculation
30kV busbar kA According to the
calculation
Type of control - local, remote
control
Compensation of the line drop Yes / no yes
Automatic control, voltage Yes / no yes, 110V, 50Hz
Local control panel Yes / no yes
Distance between local control panel and m drawing
transformer
Nominal / Maximum DC Voltage V 110 V/125 V
Supply voltage for accessories (fans, controls, V 400/230
Power autotransformer 220//110/30 kV Unit REQUIRED GUARANTEE
D
Technical performances
heating, etc.)
Supply voltage for accessories (fans, controls, Hz 50
heating, etc.)
Heating element with thermostat, located in the Yes / no Yes
control cabinet
Lighting, located in the control cabinet Yes / no Yes
High voltage supplied current transformers (220
kV and 110 kV side)
Number of transformers (per phase) - 2
Report - 400-800:1 A
Power and precision class - 30VA / 10P30
Neutral high voltage powered current transformers
Number of transformers (per phase) - 2
Report - 100:1 A
Power and precision class - 15VA / 10P20

Cooling
Number of Chillers (Coolers) according to study
Chiller losses (% of total losses at CMR) % 50
Standby Chiller One Fan per
Chiller
General
Type of conservation system Air cell
Maximum radio-electrical disturbances μV (@ 500
1.0 MHz)
Heating under continuous nominal load (40 ° C
ambient)
External type of cooling - Air
maximum altitude m 2000
Maximum temperature of air °C 40
Winding °C 62
Oil °C 57
Hot point °C 72