Sei sulla pagina 1di 10

Motor Protection—Basic Explanation

OVERLOAD PROTECTION Fast Acting Fuses


Overcurrents To offer overload protection, a protective device, depending on its
An overcurrent exists when the normal load current for a circuit is application and the motor’s service factor (S.F.), should be sized at
exceeded. It can be in the form of an overload or short-circuit. 115% or less of motor F.L.A. for 1.0 S.F. or 125% or less of motor
When applied to motor circuits an overload is any current, flowing F.L.A. for 1.15 or greater S.F. However, as shown in Curve 2, when
within the normal circuit path, that is higher than the motor’s normal fast-acting, non-time-delay fuses are sized to the recommended
full load amperes (F.L.A.). A short-circuit is an overcurrent which level the motors inrush will cause nuisance openings.
greatly exceeds the normal full load current of the circuit. Also, as
its name infers, a short-circuit leaves the normal current carrying 1,000 Motor Starting Current
(inrush)
path of the circuit and takes a “short cut” around the load and
back to the power source. Motors can be damaged by both types Non-Time-Delay Fuse
of currents. Sized to Protect Motor
Single-phasing, overworking and locked rotor conditions are 100
just a few of the situations that can be protected against with the
careful choice of protective devices. If left unprotected, motors will
continue to operate even under abnormal conditions. The exces-

TIME IN SECONDS
sive current causes the motor to overheat, which in turn causes the 10
motor winding insulation to deteriorate and ultimately fail. Good
motor overload protection can greatly extend the useful life of a
motor. Because of a motor’s characteristics, many common over-
current devices actually offer limited or no protection. 1

Fuse Opens
Motor Starting Currents
When an AC motor is energized, a high inrush current occurs.
Typically, during the initial half cycle, the inrush current is often .1
higher than 20 times the normal full load current. After the first half-
cycle the motor begins to rotate and the starting current subsides
to 4 to 8 times the normal current for several seconds. As a motor
.01
reaches running speed, the current subsides to its normal running
1

100
10

1,000
level. Typical motor starting characteristics are shown in Curve 1.
CURRENT IN AMPERES
1,000 Motor Starting Current
(Inrush) Curve 2

A fast-acting, non-time-delay fuse sized at 300% will allow the


motor to start but sacrifices the overload protection of the motor.
100 As shown by Curve 3 below, a sustained overload will damage the
motor before the fuse can open.

1,000 300% Overload


TIME IN SECONDS

10
Non-Time-Delay Fuse
Sized to Allow
Motor to Start
100
1 Motor Starting Current
(Inrush)
TIME IN SECONDS

Motor Damage Curve


10
.1

1
.01
1

100

1,000
10

CURRENT IN AMPERES
.1
Curve 1

Because of this inrush, motors require special overload pro-


tective devices that can withstand the temporary overloads associ-
ated with starting currents and yet protect the motor from sus- .01
tained overloads. There are four major types. Each offers varying
1

10

100

1,000

degrees of protection.
CURRENT IN AMPERES
Curve 3

98
Motor Protection—Basic Explanation
MCP’S and Thermal Magnetic Breakers Overload Relays
Magnetic only breakers (MCP’s) and thermal magnetic breakers Overload relays, or heaters, installed in motor starters are usually
are also unsatisfactory for the protection of motors. Once again to the melting alloy or bi-metallic type. When properly sized and
properly safeguard motors from overloads, these devices should maintained, the relay can offer good overload protection. When
be sized at 115% or less of motor F.L.A. for 1.0 S.F. or 125% or operating properly, overload relays allow the motor to start, but
less of motor F.L.A. for 1.15 or greater S.F. When sized this close when a sustained overload occurs the overload relays cause the
to the F.L.A. the inrush causes these breakers to open needlessly. contacts to open (Curve 6).
Curve 4 shows an MCP opening from motor inrush and an
1,000 300% Overload
unaffected 15 amp thermal magnetic circuit breaker (the minimum
standard size).
Overload Relay
1,000 Motor Starting Current
(inrush) 100 Motor Damage Curve

MCP Level Set at


the Minimum
100

TIME IN SECONDS
Thermal-Magnetic 10
Circuit Breaker
(15 Amp)
TIME IN SECONDS

10
1

1
.1

.1
.01
MCP
1

100
10

1,000
Opens
CURRENT IN AMPERES
.01
1

Curve 6
10

1,000
100

CURRENT IN AMPERES However, if the overload relays are oversized or if the contacts
Curve 4
fail to open for any reason (i.e., welded contacts), the motor is left
unprotected. Also, overload relays cannot offer any protection for
To allow the motor to start, the MCP must be sized at about short-circuits, and in fact must be protected by fuses or circuit
700-800% of the F.L.A. and the thermal magnetic breaker must be breakers under short-circuit conditions Curve 7 .
sized at about 250% of F.L.A. Curve 5 clearly shows that breakers
1,000 300% Overload
sized to these levels are unable to protect motors against over-
loads.
Overload Relay
1,000 300% Overload
100 Motor Damage Curve
Thermal Magnetic
Circuit Breaker
(15 Amp)
100
TIME IN SECONDS

Motor Starting Current 10


(Inrush)

Motor Damage Curve


TIME IN SECONDS

10
1
MCP Level Set to Allow
Motor to Start

1
.1

.1
.01
1

10

100

1,000

CURRENT IN AMPERES
.01
Curve 7
1

100
10

1,000

CURRENT IN AMPERES

Curve 5

99
Motor Protection—Basic Explanation
Dual-Element Fuses Motor Overload Protection
The dual-element fuse is unaffected by the motor inrush current Given a motor with 1.15 service factor or greater, size the FRN-R or
(Curve 8), but opens before a sustained overload can reach the FRS-R fuse at 125% of the motor full load current or the next smaller
motor damage curve (Curve 9). available fuse size. With a motor having a service factor of less than
1.15, size these same fuses at 115% of the motor’s F.L.A. or the
1,000 Fusetron® Dual-Element
Time-Delay Fuse
next smaller size.
(FRN-R-1flꭧ)
Motor Backup Overload Protection
Motor Starting Current By using the following “backup” method of fusing, it is possible
100 (Inrush)
to have two levels of overload protection. Begin by sizing the over-
load relays according to the manufacturers directions. Then, size
the fuse at 125%-130% or the next larger size. With this combina-
TIME IN SECONDS

tion you have the convenience of being able to quickly reset the
10
overload relay after solving a minor problem, while the fuses
remain unopened. However, if the overload relays are sized too
large, if the contacts fail to open for any reason or the heaters lose
calibration, the fuses will open before the motor damage curve is
1
reached.
Typically LPN-RK_SP, and LPS-RK_SP or FRN-R, and FRS-R
fuses have sufficient delay and thermal capacity to be sized for
motor backup overload protection.
.1
Curve 10 below shows the backup protection available with
this method.

.01 1,000 300% Overload


1

10

1,000
100

Overload Relay
CURRENT IN AMPERES
Curve 8 Motor Damage Curve
100

The NEC® allows dual-element fuses to be used by themselves Fails to Fusetron® Dual-Element
Open Time-Delay Fuse Sized
for both overload and short-circuit protection, (see NEC® sections for “Back Up” Protection
(FRN-R-1°Ω¡º)
TIME IN SECONDS

430.36, 430.37, 430.55, 430.57, & 430.90). Curve 9 shows that the 10
dual-element fuse offers excellent overload protection of motors.

1,000 300% Overload


1
Fusetron® Dual-Element
Time-Delay Fuse
(FRN-R-1flꭧ)
100
Motor Damage Curve
.1
TIME IN SECONDS

10
.01
1

10

100

1,000

CURRENT IN AMPERES
1
Curve 10

.1

.01
1

10

100

1,000

CURRENT IN AMPERES

Curve 9

100
Motor Circuit Branch Circuit Protection
Is Resettability of Value?
Motor Circuits – Choice of Overcurrent Protection 3. Circuit breakers must be periodically tested to verify they
Motor circuits have unique characteristics and several functions, mechanical operate and electrically tested to verify they still are
such as short-circuit protection, overload protection and automat- properly calibrated within specification. The circuit breaker manu-
ic/remote start/stop, that may be required. Sometimes the com- facturers recommend this. Typically circuit breakers should be
ment is made that users prefer circuit breakers because they can mechanically operated at least every year and electrically tested
be reset. Let’s examine the choice of either circuit breakers or cur- every 1 to 5 years, depending on the service conditions. Modern
rent-limiting fuses for motor branch circuit protection. current-limiting fuses do not have to be maintained or electrically
In the case to be examined, fuses and circuit breakers tested to verify they still will operate as intended. The terminations
(includes magnetic only circuit breakers which are called MCPs or of both circuit breakers and fusible devices need to be periodically
motor circuit protectors) are sized with the intent to provide only checked and maintained to prevent thermal damage. Plus fuse
short-circuit and ground fault protection for the motor branch circuit clips should be periodically inspected and if necessary maintained.
protection per 430.52. Other means, such as overload relays, pro-
4. After a circuit breaker interrupts a fault, it may not be suitable for
vide the motor overload protection. Typical thermal magnetic circuit
further service. UL489, the product standard for molded case circuit
breakers can only be sized for motor branch circuit protection (typi-
breakers, only requires a circuit breaker to interrupt two short-circuit
cally 200% - 250% of motor current) because if they are sized clos-
currents at its interrupting rating. Circuit breakers that are rated 100
er, the motor starting current trips the circuit breaker’s instanta-
amperes or less do not have to operate after only one short-circuit
neous mechanism. Magnetic only circuit breakers (MCPs) are
operation under “bus bar” short-circuit conditions. If the fault current
intentionally not provided with overload capability; they only oper-
is high, circuit breaker manufacturers recommend that a circuit
ate on short-circuit currents. There are some fuses such as the
breaker should receive a thorough inspection with replacement, if
FRS-R and LPS-RK fuses that can be sized close enough for motor
necessary. How does one know a circuit breaker’s service history or
running overload protection or backup motor running protection.
what level of fault current that a circuit breaker interrupts?
But for the discussion in this section, assume current-limiting fuses
With modern current-limiting fuses, if the fuse interrupts a fault,
are sized only for motor short-circuit and ground fault protection.
new factory calibrated fuses are installed in the circuit. The origi-
It is important to note that in this protection level being dis-
nal level of superior short-circuit protection can be there for the life
cussed, a circuit breaker or fuses should only open if there is a
of the motor circuit.
fault on the motor circuit. A separate overload protective device,
such as an overload relays, provides motor overload protection 5. After a fault, the electrician has to walk back to the storeroom to
per 430.32. Here are some important considerations: get new fuses; that is if spare fuses are not stored adjacent to the
equipment. This does require some additional down time.
1. OSHA regulation 1910.334(b)(2) Use of Equipment states
However, if fuses opened under fault conditions, there is a fault
Reclosing circuits after protective device operation. After a cir- condition that must be remedied. The electrician probably will be
cuit is deenergized by a circuit protective device, the circuit going back to the storeroom anyway for parts to repair the fault. If
may not be manually reenergized until it has been determined properly selected current-limiting fuses are used in the original cir-
that the equipment and circuit can be safely energized. The cuit, the starter will not sustain any significant damage or loss of
repetitive manual reclosing of circuit breakers or reenergizing overload calibration.
circuits through replaced fuses is prohibited. NOTE: When it With circuit breaker protection on motor circuits, after a fault
can be determined from the design of the circuit and the over- condition, it may be necessary to repair or replace the starter, so a
current devices involved that the automatic operation of a trip to the storeroom may be necessary. And if the starter is not
device was caused by an overload rather than a fault condition, significantly damaged, it may still need to be tested to insure the
no examination of the circuit or connected equipment is needed let-through energy by the circuit breaker has not caused the loss
before the circuit is reenergized. of starter overload calibration. Also, the circuit breaker needs to be
So the speed of reclosing a circuit breaker after a fault is not evaluated for suitability before placing it back into service. Who is
an advantage. The law requires that if the condition is a fault (that qualified for that evaluation? How much time will that take?
is the only reason the circuit breaker or fuses should open on a
In summary, resettability is not an important feature for motor
motor circuit), then the fault must be corrected prior to replacing
branch circuit (short-circuit) protection and resettability of the
fuses or resetting the circuit breaker.
branch circuit protective device is not a benefit for motor circuits.
2. The typical level of short-circuit protection for the motor starter As a matter of fact, resettability of the motor branch circuit overcur-
provided by circuit breakers and MCPs is referred to as Type 1. rent protective device may encourage an unsafe practice. The
This is because most circuit breakers are not current-limiting. So, function of motor branch circuit protection is fault protection: short-
for a loadside fault, the starter may sustain significant damage circuit and ground fault protection. Faults do not occur on a regu-
such as severe welding of contacts and rupturing of the heater ele- lar basis. But when a fault does occur, it is important to have the
ments. Or the heater / overload relay system may lose calibration. very best protection. The best motor branch circuit protection can
This is an acceptable level of performance per UL508, which is the be judged by (1) reliability - its ability to retain its calibration and
product standard for motor starters. Current-limiting fuses can be speed of operation over its lifetime, (2) current-limiting protection -
selected that can provide Type 2 “no damage” short-circuit protec- its ability to provide Type 2 “no damage” protection to the motor
tion for motor starters. starter, and (3) safety - its ability to meet a facility’s safety needs.
Consequently, with circuit breaker protection, after a fault con- Modern current-limiting fuses are superior to circuit breakers for
dition, significant downtime and cost may be incurred in repairing or motor branch circuit protection.
replacing the starter. With properly selected fuses for Type 2 pro- After a heavy fault on a motor branch circuit, you may need to
tection, after the fault is repaired, only new fuses need to be inserted (1) replace the fuses or (2) reset the circuit breaker and replace the
in the circuit; the starter does not have to be repaired or replaced. starter (and maybe the circuit breaker, too).

101
Motor Protection — Voltage Unbalance/Single-Phasing
Historically, the causes of motor failure can be attributed to: The NEMA standard for electric motors and generators rec-
Overloads 30% ommends that the maximum voltage unbalance be limited to 1%.
Contaminants 19% When the voltages between the three phases (AB, BC, CA)
Single-phasing 14% are not equal (unbalanced), the current increases dramatically in
Bearing failure 13% the motor windings, and if allowed to continue, the motor will be
Old age 10% damaged.
Rotor failure 5% It is possible, to a limited extent, to operate a motor when the
Miscellaneous 9% voltage between phases is unbalanced. To do this, the load must
100% be reduced.

From the above data, it can be seen that 44% of motor failure Voltage Unbalance Derate Motor to These
problems are related to HEAT. in Percent Percentages of the Motor’s Rating*
Allowing a motor to reach and operate at a temperature 10°C 1% 98%
above its maximum temperature rating will reduce the motor’s 2% 95%
expected life by 50%. Operating at 10°C above this, the motor’s 3% 88%
life will be reduced again by 50%. This reduction of the expected 4% 82%
life of the motor repeats itself for every 10°C. This is sometimes 5% 75%
referred to as the “half life” rule. *This is a general “rule of thumb”, for specific motors consult the motor
Although there is no industry standard that defines the life of manufacturer.
an electric motor, it is generally considered to be 20 years.
The term, temperature “rise”, means that the heat produced in Some Causes of Unbalanced Voltage Conditions
the motor windings (copper losses), friction of the bearings, rotor • Unequal single-phase loads. This is why many consulting
and stator losses (core losses), will continue to increase until the engineers specify that loading of panelboards be balanced to
heat dissipation equals the heat being generated. For example, a ± 10% between all three phases.
continuous duty, 40°C rise motor will stabilize its temperature at • Open delta connections.
40°C above ambient (surrounding) temperature. • Transformer connections open - causing a single-phase
Standard motors are designed so the temperature rise pro- condition.
duced within the motor, when delivering its rated horsepower, and • Tap settings on transformer(s) not proper.
added to the industry standard 40°C ambient temperature rating, • Transformer impedances (Z) of single-phase transformers
will not exceed the safe winding insulation temperature limit. connected into a “bank” not the same.
The term, “Service Factor” for an electric motor, is defined as: • Power factor correction capacitors not the same. . .or off the
“a multiplier which, when applied to the rated horsepower, indi- line.
cates a permissible horsepower loading which may be carried
under the conditions specified for the Service Factor of the motor.” Insulation Life
“Conditions” include such things as operating the motor at The effect of voltage unbalance on the insulation life of a typical T-
rated voltage and rated frequency. frame motor having Class B insulation, running in a 40°C ambient,
loaded to 100%, is as follows:
Example: A 10 H.P. motor with a 1.0 S.F. can produce 10
H.P. of work without exceeding its temperature rise requirements. Insulation Life
A 10 H.P. motor with a 1.15 S.F. can produce 11.5 H.P. of work Voltage Service Factor Service Factor
without exceeding its temperature rise requirements. Unbalance 1.0 1.15
Overloads, with the resulting overcurrents, if allowed to con- 0% 1.00 2.27
tinue, will cause heat build-up within the motor. The outcome will 1% 0.90 2.10
be the eventual early failure of the motor’s insulation. As stated 2% 0.64 1.58
previously for all practical purposes, insulation life is cut in half for 3% — 0.98
every 10°C increase over the motor’s rated temperature. 4% — 0.51

Voltage Unbalance Note that motors with a service factor of 1.0 do not have as
When the voltage between all three phases is equal (balanced), much heat withstand capability as does a motor that has a service
current values will be the same in each phase winding. factor of 1.15.
Older, larger U-frame motors, because of their ability to dissi-
pate heat, could withstand overload conditions for longer periods
of time than the newer, smaller T-frame motors.

102
Motor Protection — Voltage Unbalance/Single-Phasing
Insulation Classes Two motor overload protective devices provide adequate pro-
The following shows the maximum operating temperatures for dif- tection against balanced voltage overload conditions where the
ferent classes of insulation. voltage between phases is equal. When a balanced voltage over-
Class A Insulation 105°C load persists, the protective devices usually open simultaneously.
Class B Insulation 130°C In some cases, one device opens, and shortly thereafter, the sec-
Class F Insulation 155°C ond device opens. In either case, three-phase motors are protect-
Class H Insulation 180°C ed against balanced voltage overload conditions.
Three-phase motors protected by two overload protective
How to Calculate Voltage Unbalance and the Expected Rise in Heat devices are not assured protection against the effect of single-phas-
ing. For example, when the electrical system is WYE/DELTA or
Phase A
DELTA/WYE connected, all three phases on the secondary side of
248 Volts the transformer bank will continue to carry current when a single-
phasing caused by an open phase on the primary side of the trans-
Phase B 236 Volts
former bank occurs. As will be seen later, single-phasing can be
230 Volts considered to be the worst case of unbalanced voltage possible.
Phase C
Open 115% of Normal Current

Step 1: Add together the three voltage readings:


248 + 236 + 230 = 714V 230% of Normal Current

Step 2: Find the “average” voltage. MOTOR

714 115% of Normal Current


= 238V
3
Step 3: Subtract the “average” voltage from one of the voltages Two motor overload protective devices cannot assure protection
against the effects of PRIMARY single-phasing. The middle line
that will indicate the greatest voltage difference. In this example: current increase to 230% is not sensed.
248 – 238 = 10V
Step 4: Diagram of a WYE/DELTA transformation with one primary phase open.
greatest voltage difference The motor is protected by two overload devices. Note that one phase to
100 ≈
average voltage the motor is carrying two times that of the other two phases. Without an
10 overload device in the phase that is carrying two times the current in the
= 100 ≈ = 4.2 percent voltage unbalance
238 other two phases, the motor will burn out.
Step 5: Find the expected temperature rise in the phase winding
with the highest current by taking. . . The National Electrical Code®, Section 430.36 requires that
2 ≈ (percent voltage unbalance)2 when fuses are used for motor overload protection, a fuse shall be
In the above example: inserted in each phase. Where thermal overload devices, heaters,
2 ≈ (4.2)2 = 35.28 percent temperature rise. etc. are used for motor overload protection, Table 430.37 requires
one be inserted in each phase. With these requirements, the num-
Therefore, for a motor rated with a 60°C rise, the unbalanced ber of single-phasing motor burnouts are greatly reduced, and are
voltage condition in the above example will result in a temperature no longer a serious hazard to motor installations. The following fig-
rise in the phase winding with the highest current of: ure shows three overload protective devices protecting the three-
60°C ≈ 135.28% = 81.17°C phase motor.

The National Electrical Code


The National Electrical Code®, in Table 430.37, requires three over-
load protective devices, one in each phase, for the protection of all
three-phase motors. Three- 3Ø
Prior to the 1971 National Electrical Code ®, three-phase Phase MOTOR
Source
motors were considered to be protected from overload (overcur-
rent) by two overload protective devices. These devices could be
in the form of properly sized time-delay, dual-element fuses, or
overload heaters and relays (melting alloy type, bimetallic type,
magnetic type, and solid-state type.)
N.E.C. REQUIREMENT
Three-phase motors require
Motor Overload Devices three motor overload protective devices

Since 1971, The National Electrical Code® has required three overload
protective devices for the protection of three-phase motors, one in each
phase.
Three- 3Ø
Phase MOTOR
Source

Diagram showing two overload devices protecting a three-phase motor.


This was acceptable by the National Electrical Code® prior to 1971.

103
Motor Protection — Voltage Unbalance/Single-Phasing
Motor Branch Circuit, Short-Circuit and Ground Fault Protection For lightly loaded three-phase motors, say 70% of normal full-
When sized according to NEC® 430.52, a 3-pole common trip cir- load amperes, the phase current will increase by the square root of
cuit breaker or MCP can not protect against single-phasing dam- three (√3) under secondary single-phase conditions. This will result
age. in a current draw of approximately 20% more than the nameplate
It should be emphasized, the causes of single-phasing can- full load current. If the overloads are sized at 125% of the motor
not be eliminated. However, motors can be protected from the nameplate, circulating currents can still damage the motor. That is
damaging effects of single-phasing through the use of proper why it is recommended that motor overload protection be based
overcurrent protection. upon the actual running current of the motor under its given load-
Dual-element, time-delay fuses can be sized at or close to the ing, rather than the nameplate current rating.
motor’s nameplate full-load ampere rating without opening on nor-
mal motor start-up. This would require sizing the fuses at 100- Single-Phasing Causes Are Numerous
125% of the motors full-load current rating. Since all motors are not One fact is sure: Nothing can prevent or eliminate all types of sin-
necessarily fully loaded, it is recommended that the actual current gle-phasing.
draw of the motor be used instead of the nameplate rating. This is There are numerous causes of both primary and secondary
possible for motor’s that have a fixed load, but not recommended single-phasing. A device must sense and respond to the resulting
where the motor load varies.* increase in current when the single-phasing condition
Thus, when single-phasing occurs, FUSETRON® FRS-R and occurs…and do this in the proper length of time to save the motor
FRN-R and LOW-PEAK ® LPS-RK_SP and LPN-RK_SP dual- from damage.
element, time-delay fuses will sense the overcurrent situation and The term “single-phasing” is the term used when one phase
respond accordingly to take the motor off the line. of a three-phase system opens. This can occur on either the pri-
For motor branch-circuit protection only, the following sizing mary side or secondary side of a distribution transformer. Three-
guidelines † per 430.52 of the National Electrical Code ® are phase motors, when not individually protected by three time-delay,
allowed. dual-element fuses, or three overload devices, are subject to dam-
Normal Maximum aging overcurrents caused by primary single-phasing or sec-
• Dual-element, time- 175% 225% ondary single-phasing.
delay fuses
• Non-time-delay fuses 300% 400% Single-Phasing on Transformer Secondary – Typical Causes
and all Class CC fuses 1. Damaged motor starter contact–one pole open. The number of
• Inverse-time circuit 250% 400% for motors contact kits sold each year confirms the fact that worn motor
breaker 100 amperes starter contacts are the most common cause of single-phas-
or less. ing. Wear and tear of the starter contacts can cause contacts
300% for motors to burn open, or develop very high contact resistance, result-
more than ing in single-phasing. This is most likely to occur on automati-
100 amperes. cally started equipment such as air conditioners, compressors,
• Instantaneous only trip** 800%†† 1300%††† fans, etc.
circuit breakers 2. Burned open overload relay (heater) from a line-to-ground fault
(sometimes referred to as MCPs. on a 3 or 4 wire grounded system. This is more likely to occur
These are motor circuit protectors, on smaller size motor starters that are protected by non-
not motor protectors.) current-limiting overcurrent protective devices.
† See NEC® 430.52 for specifics and exceptions. 3. Damaged switch or circuit breaker on the main, feeder, or
†† 1100% for design E motors motor branch circuit.
††† 1700% for design E motors & energy efficient design B motors 4. Open fuse or open pole in circuit breaker on main, feeder, or
*When sizing to the actual running current of the motor is not practical, an motor branch circuit.
economic analysis can determine if the addition of one of the electronic
5. Open cable or bus on secondary of transformer terminals.
“black boxes” is financially justified. These electronic “black boxes” can
sense voltage and current unbalance, phase reversal, single-phasing, etc. 6. Open cable caused by overheated lug on secondary side con-
**Instantaneous only trip breakers are permitted to have time-delay. This could nection to service.
result in more damaging let-through current during short-circuits. 7. Open connection in wiring such as in motor junction box
(caused by vibration) or any pull box. Poor connections, par-
Note: When sized according to table 430.52, none of these over- ticularly when aluminum conductors are not properly spliced to
current devices can provide single-phasing protection. copper conductors, or when aluminum conductors are insert-
ed into terminals and lugs suitable for use with copper con-
Single-Phasing ductors or copper-clad conductors only.
The term single-phasing, means one of the phases is open. A 8. Open winding in motor.
secondary single-phasing condition subjects an electric motor to 9. Open winding in one phase of transformer.
the worst possible case of voltage unbalance. 10. ANY open circuit in ANY phase ANYWHERE between the
If a three-phase motor is running when the “single-phase” secondary of the transformer and the motor.
condition occurs, it will attempt to deliver its full horsepower
…enough to drive the load. The motor will continue to try to drive
the load…until the motor burns out…or until the properly sized
overload elements and/or properly sized dual-element, time-delay
fuses take the motor off the line.

104
Motor Protection — Voltage Unbalance/Single-Phasing
Hazards of Secondary Single-Phasing for a Three-Phase Motor NORMAL CONDITION SINGLE-PHASING CONDITION
When one phase of a secondary opens, the current to a motor in
the two remaining phases theoretically increases to 1.73 (173%) WYE-Connected Motor
times the normal current draw of the motor. The increase can be
as much as 2 times (200%) because of power factor changes.
Where the motor has a high inertia load, the current can approach
locked rotor values under single-phased conditions. Three proper-
ly sized time-delay, dual-element fuses, and/or three properly
sized overload devices will sense and respond to this overcurrent.

SINGLE-PHASING ON SECONDARY

NORMAL CONDITION SINGLE-PHASING CONDITION


Assume
the contacts
17.3A 17.3A 0A on one phase
10A 10A 10A (173%)
(173%) are worn out
resulting in
an open
circuit.

17.3A
10A

A
A

10

.3

0A
10

17
A
Assume
the contacts
on one phase FLA = 10 Amperes
10A 10A 10A 17.3A 17.3A 0A are worn out
(173%) (173%) resulting in
an open (WYE-Connected Motor) Diagram showing the increase in current in the
circuit.
two remaining phases after a single-phasing occurs on the secondary of
a transformer.
A

5.
5.
8A

.6

8A
8A

11
5.

5.8A 5.8A

Delta-Connected Motor
FLA = 10 Amperes

(Delta-Connected Motor) Diagram showing the increase in current in the


two remaining phases after a single-phasing occurs on the secondary of
a transformer.

105
Motor Protection — Voltage Unbalance/Single-Phasing
SINGLE-PHASING ON SECONDARY Single-Phasing on Transformer Primary – Typical Causes
1. Primary wire broken by:
NORMAL CONDITION SINGLE-PHASING CONDITION a. Storm – wind
b. Ice – sleet – hail
c. Lightning
d. Vehicle or airplane striking pole or high-line
e. Falling trees or tree limbs
f. Construction mishaps
2. Primary wire burned off from short-circuit created by birds or
animals.
3. Defective contacts on primary breaker or switch – failure to
make up on all poles.
4. Failure of 3-shot automatic recloser to make up on all 3 poles.
Contact Open 5. Open pole on 3-phase automatic voltage tap changer.
6. Open winding in one phase of transformer.
6.5A 6.5A 6.5A 11.2A 11.2A 0A 7. Primary fuse open.

Hazards of Primary Single-Phasing for a Three-Phase Motor


Probably the most damaging single-phase condition is when one
phase of the primary side of WYE/DELTA or DELTA/WYE trans-
8A

4A
3.

3.

former is open. Usually these causes are not within the control of
8A

8A
3.

7.

the user who purchases electrical power. When primary single-


phasing occurs, unbalanced voltages appear on the motor circuit,
3.8A 3.8A causing excessive unbalanced currents. This was covered earlier
in this bulletin.
When primary single-phasing occurs, the motor current in one
Delta-connected three-phase motor loaded to only 65% of its rated secondary phase increases to 230% of normal current. Normally,
horsepower. Normal FLA = 10 amperes. Overload (overcurrent) protection the overload relays will protect the motor. However, if for some rea-
should be based upon the motor’s actual current draw for the underload- son the overload relays or controller fail to function, the LOW-
ed situation for optimum protection. If load varies, overload protection is PEAK ® or FUSETRON ® dual-element fuses properly sized to
difficult to achieve. Temperature sensors, phase failure relays and cur- provide backup overload protection will clear the motor from the
rent differential relays should be installed. power supply.

When a motor is single-phased, the current in the remaining Effect of Single-Phasing on Three-Phase Motors
two phases increases to 173% of normal current. Normally the The effects of single-phasing on three-phase motors varies with
overload relays will safely clear the motor from the power supply. service conditions and motor thermal capacities. When single-
However, should the overload relays or controller fail to do so, phased, the motor temperature rise may not vary directly with the
LOW-PEAK® or FUSETRON® time-delay, dual-element fuses, prop- motor current. When single-phased, the motor temperature rise
erly sized to provide back-up overload protection, will clear the may increase at a rate greater than the increase in current. In
motor from its power supply. some cases, protective devices which sense only current may not
If the overload relays were sized at 12 amperes, based upon provide complete single-phasing protection. However, PRACTI-
the motor nameplate F.L.A. of 10 amperes, they would not “see” CAL experience has demonstrated that motor running overload
the single-phasing. However, if they were sized at 8 amperes (6.5A devices properly sized and maintained can greatly reduce the
x 1.25 = 8.13 amperes), they would “see” the single-phasing con- problems of single-phasing for the majority of motor installations. In
dition. some instances, additional protective means may be necessary
when a higher degree of single-phasing protection is required.
Generally, smaller horsepower rated motors have more thermal
capacity than larger horsepower rated motors and are more likely
to be protected by conventional motor running overload devices.

106
Motor Protection — Voltage Unbalance/Single-Phasing
SINGLE-PHASING ON PRIMARY
Delta-Connected Motor; FLA = 10 Amperes

NORMAL CONDITION

10A
5.8A 5.8A
5.8A 5.8A

10A

5.8A 5.8A
10A

WYE PRIMARY DELTA SECONDARY

SINGLE-PHASING CONDITION

Open by Wind Storm


11.5A (115%)

23A (230%)

11.5A (115%)

WYE PRIMARY DELTA SECONDARY

(Delta-Connected Motor) Diagram showing how the phase currents to a three-phase motor increase when a single-phasing occurs on the primary. For
older installations where the motor is protected by two overload devices, the phase winding having the 230% current will burn up. However, properly sized
overload relays or LOW-PEAK® or FUSETRON® dual-element, time-delay fuses will clear the motor from the power supply.

SINGLE-PHASING ON PRIMARY
Wye-Connected Motor; FLA = 10 Amperes

NORMAL CONDITION
10A
5.8A
5.8A
10A
10A 10A

10A
5.8A
10A

WYE PRIMARY DELTA SECONDARY

SINGLE-PHASING CONDITION

Open by Wind Storm


11.5A (115%)

23A (230%) 11.5A


23A

11.5A
11.5A (115%)

(Wye-Connected Motor) Diagram showing how the phase currents to a three-phase motor increase when a single-phasing occurs on the primary. For older
installations where the motor is protected by two overload devices, the phase winding having the 230% current will burn up. However, properly sized over-
load relays or LOW-PEAK® or FUSETRON® dual-element, time-delay fuses, will clear the motor from the power supply.

107

Potrebbero piacerti anche