Tripped

On

19.5°
6.40[162.6]

21.5°

5.96[151.4]
ø0.20[5.1]

17.9°

5.66[143.8]

5.20[132.1]
4.99[126.7]
Off

3.69[93.7]

2.12[53.8]

2.04[51.8]
1.20[30.5]
0.74[18.8]
1.91[48.5] 1.38[35.1]

0.44[11.2]
2.87[72.9] 1.38[35.1] 1.38[35.1]

3.24[82.3]

1.06[26.9]
3.44[87.4]

0.43[10.9]
3.74[95.0]

4.36[110.7]

Detail A
0.08[2.0]

A
0.69[17.5]

0.63[15.9] 4.12[104.6]

Note: Part No.: Schneider Electric United States


- Drawings Not To Scale North American Division
- Drawings Subject to Change Without Notice Boston One Campus
- Dimensions are inches next to [Millimeters] HDL36040 800 Federal Street
Andover, MA 01810, USA
Phone:+1 8773425173
Email: CCC@us.schneider-electric.com
Technical Information: Specification:
General Application: Provides overload and short circuit protection Description: PowerPact H-frame Thermal Magnetic Circuit Breaker
For Use With: Industrial Enclosures and Switchboards Number of Poles: 3-Pole
Approvals: UL Listed - CSA Certified - IEC Rated Ampere Rating: 40A
Mounting Type: Unit Mount Voltage Rating: 600VAC/250VDC
Terminal Type: Line: Lug - Load: Lug Interrupting Rating: 25kA at 240VAC - 18kA at 480VAC - 14kA at 600VAC - 20kA at 250VDC
Wire Size: #14-3/0 AWG(Al/Cu) Circuit Breaker Rating: 80% Rated
Weight: 5 Pounds Fixed AC Magnetic Trip: Hold: 400A - Trip: 850A
Depth: 4.36 Inches
Height: 6.40 Inches
Width: 4.12 Inches