RC SERIES
REFRIGERATED CYCLING COMPRESSED AIR DRYER
150-3000 CFM
PART NUMBER:
02250195-402 R04
KEEP FOR
FUTURE
WARRANTY NOTICE REFERENCE
Failure to follow the instructions ©
COPYRIGHT 2012 SULLAIR
and procedures in this manual or, The information in this manual is current
as of its publication date, and applies to
misuse of this equipement will dryer serial number:
VOID its warranty!
0711SA0250
and all subsequent serial numbers.
AIR CARE SEMINAR TRAINING
Sullair Air Care Seminars are courses that provide hands-on instruction for the proper operation, maintenance,
and servicing of Sullair products. Individual seminars on Stationary compressors and compressor electrical
systems are offered at regular intervals throughout the year at Sullair’s corporate headquarters training facility
located at Michigan City, Indiana.
Instruction includes training on the function and installation of Sullair service parts, troubleshooting common
faults and malfunctions, and actual equipment operation. These seminars are recommended for maintenance,
contractor maintenance, and service personnel.
1-888-SULLAIR or
219-879-5451 (ext. 5623)
www.sullair.com
training@sullair.com
- Or Write -
Sullair
3700 E. Michigan Blvd.
Michigan City, IN 46360
Attn: Service Training Department.
TABLE OF CONTENTS
SECTION 1—SAFETY INSTRUCTIONS
7 1.1 SAFETY REGULATIONS:
7 1.2 ISSUES TO AVOID
7 1.3 RECEIVING AND INSPECTION
8 1.4 TRANSPORTATION
8 1.5 INSTALLATION LAYOUT REQUIREMENTS
8 1.6 ENVIRONMENTAL PROTECTION
SECTION 2—INTRODUCTION
9 2.1 CYCLING REFRIGERATED AIR DRYERS
SECTION 3—SPECIFICATIONS
11 3.1 PRODUCT PICTURE / PRODUCT FINAL ASSEMBLY DRAWING
12 3.2 PRODUCT MODELS AND SPECIFICATIONS
SECTION 6—MAINTENANCE
123 6.1 MAINTENANCE BY AN ENGINEER/TECHNICIAN
123 6.2 MAINTENANCE BY THE USER
124 6.3 RECOMMENDED MAINTENANCE
126 6.4 REPLACEMENT PARTS
SECTION 7—TROUBLESHOOTING
143 7.1 TROUBLESHOOTING TABLES
Section 1
SAFETY INSTRUCTIONS
7
NOTES
1.4 TRANSPORTATION heat radiated by the dryer. (About 18 watts
for each SCFM under ISO 7183-5 condition
1. Use care and caution when transporting the or 40 watt for each liter/sec under ISO 7183-
dryer. Avoid sudden jerks, tilting, dropping A condition).
and other physical abuse.
2. A forklift can be used to transport the dryer 1.6 ENVIRONMENTAL
provided the forks are long enough to sup- PROTECTION
port the full width or length. Caution must be
1. US/EU laws protect the environment against
used throughout the move.
refrigerant being released into the atmo-
sphere.
1.5 INSTALLATION LAYOUT
REQUIREMENTS 2. An annual leak control test at less than 5.0
gr/year should be performed by a qualified
1. The dryer must be installed horizontally. A engineer if the refrigerant dryer contains
minimum of at least 1 ½ feet clearance more than 4.4 lbs/ 2 kg of refrigerant. This
around the dryer is necessary to allow free control test has to be done twice a year if the
air circulation and easy access for servicing. dryer contains more than 66 lbs/30 kg.
2. The ambient temperature in the room 3. Prior to dryer disposal, the refrigerant must
should not exceed 120° F and should not be properly recovered by a qualified engi-
be below 40° F, taking into account the neer.
8
INTRODUCTION
Section 2
INTRODUCTION
2.1 CYCLING REFRIGERATED Water (moisture) is one of the greatest enemies of air
AIR DRYERS tools and piping. Left untreated in the compressed air
stream, this moisture will deteriorate the tools,
The Sullair Cycling Refrigerated air dryersare equipment and piping with corrosion, pipe scaling,
designed for full and partial load operations. They freezing and a host of other problems that will
use specially designed heat exchangers with diminish the life of your entire compressed air
integrated components to provide consistent system. With a Sullair refrigerant dryer, you can be
dewpoint and trouble-free service for years to come. assured of clean, dry air with consistent dewpoint
between 36-40°F / 2-4°C. The unique three-in-one
The dryers remove the moisture from the
heat exchanger combination - heats up the exiting
compressed air stream. By using basic refrigeration,
air, thereby eliminating the chances of freezing even
the hot saturated air is cooled in the highly efficient
in relatively cooler ambient conditions. Warm dry air
heat-exchangers and the moisture is condensed and
will not affect the piping nor the tools and the result is
removed. Additional filtration eliminates other
extended tool life. In addition, applications that
contaminants and particles.
require clean dry air can rely upon Sullair’s cycling
refrigerated air dryers to provide dry air at full or
partial load continuously.
9
NOTES
10
SPECIFICATIONS
Section 3
SPECIFICATIONS
Pay attention to the Minimum and Maximum operating conditions before installing and operating the dryer.
If your application does not match the above criteria, contact your Sullair distributor and they will be able to
provide the right dryer for your application.
11
SPECIFICATIONS SECTION 3
12
SECTION 3 SPECIFICATIONS
13
SPECIFICATIONS SECTION 3
14
PRODUCT DESCRIPTION
Section 4
PRODUCT DESCRIPTION
This refrigerated compressed air dryer has been 4.1.3 REFRIGERANT CIRCUIT PROTECTION
designed to remove water vapor from industrial
compressed air that is free of any aggressive 1. Overload protector:
contaminants like ammonia, gaseous acid, dust, rust, Single phase compressors are equipped
liquid condensate, any other chemical or mineral with an overload protector which is a current/
substances capable of attacking or clogging the heat temperature switch that reacts to the motor
exchanger(s). winding amps and temperature of the com-
pressor motor. When the switch detects a
The optional, water-cooled condenser is not high current or a high temperature condition
designed for use with seawater or water containing with the compressor motor it opens causing
aggressive contaminants. loss of voltage to the compressor. This
Please contact your factory representative for further switch automatically resets as the motor
questions on this issue. This dryer has been cools down to a factory preset temperature.
designed for indoor operation only. This cool down period can take as long as 8
hours.
The minimum and maximum values stated must be
observed, as well as the safety precautions 2. High/Low pressure safety switch:
described in this manual. Refrigerant circuits are protected against
excessive pressure by a safety switch that
stops the compressor in cases of high or low
4.1 PRODUCT FEATURES refrigerant pressure. If this safety switch has
tripped out on high refrigerant pressure, it
4.1.1 REFRIGERANT COMPRESSOR
has to be manually reset before the dryer
The refrigerant compressor is fully hermetically can be restarted. A low pressure trip will
sealed and requires no maintenance. automatically reset
4.1.2 CONDENSER 4.1.4 FILTER DRYER
1. Air cooled models: The refrigerant con- Total water removal in the refrigerant circuit is
denser is equipped with fans that are cycled achieved by a filter dryer who also traps any solid
on and off to maintain a minimum high side particles that may have migrated into the circuit
pressure. during assembly.
2. Water-cooled dryers Utilize a water control 4.1.5 CRANKCASE HEATER
valve piloted by a sensing bulb that reacts to
the high side refrigerant pressure control- 3-Phase dryers are equipped with an electric
ling the water flow Maintain a minimum high crankcase heater. The heater provides preliminary
side pressure. pre-heating of the refrigerant compressor to
evaporate liquid refrigerant possibly condensed in
the crankcase. This will prevent liquid shock that can
damage the compressor.
15
PRODUCT DESCRIPTION SECTION 4
16
PRINCIPLE OF OPERATION
Section 5
PRINCIPLE OF OPERATION
The refrigerant circuit can be divided in 3 parts: through the heat exchangers to eliminate
any dew point fluctuations commonly found
1. Low pressure section with an evaporator
in other cycling dryers. The glycol is stored in
(heat exchanger)
a stainless steel insulated tank with welded
2. High pressure section including: Condenser, liq- connections. The glycol flows through the
uid receiver, (if installed) and the filter dryer. pump to the Air-to-Glycol chamber located in
what is commonly termed as the heat
3. Control circuit including: Compressor, meter-
exchanger where it cools the compressed air
ing device, hot gas by-pass valve (if
by counter flow. From there, it travels to the
installed), fan pressure switch, safety high/
evaporator where heat is extracted out by
low pressure switch. Water cooled dryers are
the refrigerant. The heat saturated glycol
equipped with a water flow control valve.
then returns to the storage tank. A tempera-
ture probe in the tank monitors the tempera-
5.1 REFRIGERATION HEAT ture and turns off the compressor when the
EXCHANGER glycol reaches its set point. A float switch
inside the glycol tank shuts off the unit if the
1. There are two (2) basic sections, commonly
glycol level drops below the minimum height.
referred to as the high and low-pressure sec-
tions, in a refrigeration circuit. The high side 3. Refrigerant controls: High-low refrigerant
begins at the refrigerant compressor dis- cut-out switch senses high and low refriger-
charge port and ends at the expansion ant pressure at refrigerant compressor inlet
devise. The circuit leaving the expansion and outlet ports shutting the compressor
devise through the air to refrigerant heat down in the event of high refrigerant dis-
exchanger and up to the compressor suction charge pressures or low refrigerant suction
port is known as the low pressure circuit. The pressure.
compressor takes in low pressure refrigerant
4. Liquid line filter dryer: Filters refrigerant of
gas and compresses it to a high pressure
moisture and any foreign particles. Must be
and high temperature gas. The high temper-
replaced if the refrigerant system has been
ature gas passes into the refrigerant con-
opened causing exposure to atmospheric
denser where it is cooled and liquefied. The
pressures.
refrigerant then passes through the filter
dryer where moisture and any foreign parti- 5. Expansion device: Meters refrigerant flow in
cles are removed. The refrigerant then the evaporator.
passes through an expansion device where
6. Electronic drain valve: An electronic drain
the liquid refrigerant is throttled and a tem-
valve on the separator is designed to open
perature drop will occur as part of the liquid
and close automatically to drain away con-
turns into gas. The cold refrigerant gas and
densate.
liquid then enters the refrigerant-to-glycol
heat exchanger where it absorbs the heat 7. Crank case heater: A safety device which
from the glycol as it evaporates. The low- prevents refrigerant migration back to the
pressure refrigerant gas returns to the com- compressor during shutdown.
pressor for repetition of the process.
8. Air cooled models Cooling air flows from the
2. Glycol Side: The thermal mass is food safe front to the back of the dryer. Air must be
and environmentally friendly polypropylene drawn from a clean source in order to reduce
glycol solution. It is pumped continuously
17
PRINCIPLE OF OPERATION SECTION 5
dust and dirt accumulation on the condenser 2. Pre-separation: As the air is pre-cooled,
coils. some of the moisture condenses. During this
phase, all condensed moisture and oil is
9. Fan motor and compressor rotation: This unit
separated from the compressed air.
has been equipped with a phase sensing
controller. If the unit will not start please 3. Thermal Mass: The air then enters and is fur-
reverse any two of the three phases and ther cooled in the refrigeration air to glycol
restart the unit. Cooling air should exhaust chamber. The air stream is cooled to 35-39ºF
through the condenser coils away from the / 1.6-3.8ºC, reducing its dew point to this
fan motors. temperature.
4. Separation: As the air is cooled in the air to
5.2 COMPRESSED AIR HEAT glycol chamber, the moisture condenses into
EXCHANGER a liquid. At this point, all liquid, passing
through the separator is removed from the
AIR TO AIR SIDE
air stream and drained away with an elec-
1. Pre cooling: Warm, saturated compressed tronic drain
air enters the air-to-air heat exchanger,
5. Recuperation: The cold, dry air is reheated
where it is cooled by the outgoing cooled
by incoming warm air as it passes back
compressed air flowing in a counter flow
through the air to air heat exchanger in a
direction.
counter flow direction.
18
SECTION 5 PRINCIPLE OF OPERATION
19
PRINCIPLE OF OPERATION SECTION 5
20
SECTION 5 PRINCIPLE OF OPERATION
21
5.9 ED—RC 175 AND 200
22
PRINCIPLE OF OPERATION
SECTION 5
02250196-546 R02
5.9 ED—RC 175 AND 200
SECTION 5
KEY PART NO. DESCRIPTIONS QTY KEY PART NO. DESCRIPTIONS QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-CBL-0200-C CABINET LEG 4
2 SEE REF. TABLE CONDENSER 1 30 M-HP1-0200-C CABINET HORIZONTAL PROFILE 1 2
3 M-FMT-0200 FAN MOTOR 1 31 M-CFR-0200-C CABINET HORIZONTAL PROFILE 2 2
4 M-FAN-0200 FAN BLADE 1 32 M-CTC-6000 CABINET TOP CORNER 4
5 M-GRL-0200 FAN GRILL 2 33 M-CPS-6000 CABINET HANDLE 8
6 M-DRI-0200 DRIER-DEHYDRATOR 1 34 M-STU-3000 CABINET STUD AND NUT 12
7 M-EXC-0200 HEAT EXCHANGER 1 35 M-FAS-6000 CABINET FASTENER 12
8 M-WHC-0200 EVAPORATOR (WATER HEAT EXCHANGER) 1 36 M-NUT-1200 CAGE NUT AND SCREW 16
9 M-INL-0200 FLEXIBLE STEEL TUBE (INLET) 1 37 M-SCR-6000 SCREW TYPE 2 16
10 M-OTL-0200 FLEXIBLE STEEL TUBE (OUTLET) 1 38 M-CSR-0200-220/230-1-50/60 COMPRESSOR START RELAY 1
11 M-EXV-0200 EXPANSION VALVE 1 39 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
12 M-HPS-0200 HIGH PRESSURE SECURITY SWITCH 1 40 M-CNT-0250-230 CONTACTOR 1
13 M-FNS-0200 FAN ON/OFF SWITCH 1 41 M-WPC-3000 WATER PUMP CONTACTOR 1
14 M-WPS-3000 WATER PRESSURE SWITCH 1 42 M-CSC-0200-230-1-60 COMPRESSOR START CAPACITOR 1
15 M-LIN-3000 WATER PUMP 1 43 M-RUN-0200 RUN CAPACITOR 1
16 SEE REF. TABLE WATER TANK 1 44 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
17 M-MNS-1200 LEVEL INDICATOR 1 45 M-VEN-3000 VENT/RELIEF 1
18 M-WAG-3000 WATER GUAGE 1 46 M-SNS-0150 SENSOR PROBE 1
19 M-DGC-3000-230-1-60 DIGITAL CONTROLLER 1 47 M-DBV-0200 DRAIN BALL VALVE 1
20 SEE REF. TABLE COMPRESSOR ELECTRIC BOX 1 48 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 2
21 M-MNS-1200 MAIN SWITCH 1 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
22 M-TMR-3000 TIMER 1 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
23 M-SLV-250-230 SELENOID VALVE 1 51 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-0200-C CABINET FRONT 1 52 M-KEP-0200-230-1-60-C KIT FOR ELECTRICAL PANEL 1
25 M-CSI-0200-C CABINET SIDE 2 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRE-0200-C CABINET REAR 1 54 M-PWC-1200 POWER CONNECTOR 1
PRINCIPLE OF OPERATION
27 M-CTP-0200-C CABINET TOP 1 55 M-DCF-0200 DRAIN CONNECTION FITTING 1
28 M-CBA-0200-C CABINET BASE 1 56 M-ACF-0200 AIR CONNECTION FITTING 1
COMPRESSOR
DRYER PART POWER COMPRESSOR WATER PUMP
DECAL CFM COOLING COMPRESSOR CONDENSER WATER TANK OVERLOAD
NUMBER RATINGS ELECTRIC BOX CONTRACTOR
PROTECTOR
RC175 175 02250193-865 220V/1Ph/50Hz AIR COOLED M-CMP-200-220-1-50 M-CON-0175 M-WTA-0175 M-CEB-0200-220-1-50 M-COP-0200-220-1-50 M-WPC-3000
208-230V/3Ph/
RC175 175 02250193-821 AIR COOLED M-CMP-200-230-1-60 M-CON-0175 M-WTA-0175 M-CEB-0200-230-1-60 M-COP-0200-230-1-60 M-WPC-0250-230-1-60
60Hz
RC200 200 02250193-866 400V/3Ph/50Hz AIR COOLED M-CMP-200-220-1-50 M-CON-0200 M-WTA-0200 M-CEB-0200-220-1-50 M-COP-0200-220-1-50 M-WPC-3000
RC200 200 02250194-822 220V/1Ph/50Hz AIR COOLED M-CMP-200-230-1-60 M-CON-0200 M-WTA-0200 M-CEB-0200-230-1-60 M-COP-0200-230-1-60 M-WPC-0250-230-1-60
23
PRINCIPLE OF OPERATION SECTION 5
5.10 ED—RC 250
02250196-547 R02
24
5.10 ED—RC 250
SECTION 5
KEY PART NO. DESCRIPTIONS QTY KEY PART NO. DESCRIPTIONS QTY
1 SEE REF. TABLE COMPRESSOR 1 34 M-CPS-6000 CABINET HANDLE 8
2 M-CON-0325 CONDENSER 1 35 M-STU-6000 CABINET STUD AND NUT 12
3 SEE REF. TABLE FAN MOTOR 1 36 M-FAS-6000 CABINET FASTENER 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 37 M-NUT-1200 CAGE NUT AND SCREW 16
5 M-EXC-0125 HEAT EXCHANGER 2 38 M-SCR-6000 SCREW TYPE 2 16
6 M-WHC-0400 EVAPORATOR (WATER HEAT EXCHANGER) 1 39 SEE REF. TABLE TRANSFORMER 1
7 M-EXV-0250 EXPANSION VALVE 1 40 SEE REF. TABLE PHASE PROTECTION RELAY 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 41 M-CNT-0250-230 CONTACTOR 1
9 M-FNS-0400 FAN ON/OFF SWITCH 1 42 SEE REF. TABLE FAN CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 43 M-WPC-3000 WATER PUMP CONTACTOR 1
11 M-THS-6000 THERMOSTATIC SWITCH 1 44 SEE REF. TABLE SECONDARY CONTACT 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 45 SEE REF. TABLE WATER PUMP PROTECTOR 1
13 SEE REF. TABLE WATER PUMP 1 46 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WTA-0250 WATER TANK 1 47 SEE REF. TABLE FAN OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 48 SEE REF. TABLE COMPRESSOR START RELAY 1
16 M-WAG-3000 WATER GAUGE 1 49 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 SEE REF. TABLE DIGITAL CONTROLLER 1 50 SEE REF. TABLE COMPRESSOR START CAPACITOR 1
18 SEE REF. TABLE ON/OFF BUTTON 1 51 M-VEN-3000 VENT RELIEF 1
19 M-MNS-1200 MAIN SWITCH 1 52 M-SNS-0150 SENSOR PROBE 1
20 M-TMR-3000 TIMER 1 53 M-DBV-6000 DRAIN BALL VALVE 1
21 SEE REF. TABLE SELENOID VALVE 1 54 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 4
22 M-MMV-2400 MEMBRANE VALVE 1 55 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
23 M-MMM-6000 MEMBRANE 1 56 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
24 M-CFR-0400-C CABINET FRONT 1 57 M-WPB-3000 WATER PUMP BRACKET 1
25 M-CLE-0400-C CABINET SIDE-LEFT 2 58 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
26 M-CRI-0400-C CABINET SIDE-RIGHT 2 59 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5-2
27 M-CRE-0400-C CABINET REAR 1 60 M-PWC-1200 POWER CONNECTOR 1
28 M-CTO-0400-C CABINET TOP 1 61 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
PRINCIPLE OF OPERATION
29 M-CBA-0400-C CABINET BASE 1 62 M-CCK-0850 CONTACTOR CONNECTING KIT 3
30 M-CBL-0400-C CABINET LEG 4 63 M-CLP-1200 DRYER CLAMP 1
31 M-HP1-0400-C CABINET HORIZONTAL PROFILE 1 2 64 M-DFD-1200 DRAIN FIXING DEVICE 1
32 M-HP2-0400-C CABINET HORIZONTAL PROFILE 2 2 65 M-SCP-0400 CAPILLARY FOR SWITCH 1
33 M-CTC-6000 CABINET TOP CORNER 4 66 M-HLC-0400 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
COMPRESSOR
DRYER PART POWER ON-OFF
DECAL CFM COOLING COMPRESSOR FAN MOTOR WATER PUMP OVERLOAD
NUMBER RATINGS BUTTON
PROTECTOR
RC250 250 02250193-865 220V/1Ph/50Hz AIR COOLED M-CMP-0250-220-1-50 M-FMT-0325 M-PMP-0250-230-1-60 N/A N/A
RC250 250 02250193-821 230V/3Ph/60Hz AIR COOLED M-CMP-0250-230-3-60 M-FMT-0400-230 M-PMP-3000 M-ONB-3000 M-COP-0400-460-3-60
RC250 250 02250193-866 400V/3Ph/50Hz AIR COOLED M-CMP-0250-460-3-60 M-FMT-0400-460 M-PMP-3000 M-ONB-3000 M-COP-0250-460-3-60
RC250 250 02250193-822 460V/3Ph/60Hz AIR COOLED M-CMP-0250-460-3-60 M-FMT-0400-460 M-PMP-3000 M-ONB-3000 M-COP-0250-460-3-60
RC250 250 02250194-822 575V/3Ph/60Hz AIR COOLED M-CMP-0250-575-3-60 M-FMT-0400-575 M-PMP-3000 M-ONB-3000 M-COP-0250-460-3-60
25
PRINCIPLE OF OPERATION SECTION 5
5.11 ED—RC 325
02250196-548 R02
26
5.11 ED—RC 325
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-0325 CONDENSER 1 34 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 1 35 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-0200 HEAT EXCHANGER 2 37 M-NUT-1200 CAGE NUT AND SCREW 16
6 M-WHC-0400 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-0500 EXPANSION VALVE 1 39 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 1 41 M-CNT-0400 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-FCN-1000 FAN CONTACTOR 1
11 M-THS-0325 THERMOSTATIC SWITCH 1 43 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-SEC-1000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 45 M-WPP-1000 WATER PUMP PROTECTOR 1
14 M-WTA-0325 WATER TANK 1 46 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-FOP-3000 FAN OVERLOAD PROTECTOR 1
16 M-WAG-3000 WATER GAUGE 1 48 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 49 M-VEN-3000 VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-SNS-0150 SENSOR PROBE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-DBV-6000 DRAIN BALL VALVE 1
20 M-TMR-3000 TIMER 1 52 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 4
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
22 M-MMV-6000-24 MEMBRANE VALVE 2 54 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
23 M-MMM-2400 MEMBRANE 2 55 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-0400-C CABINET FRONT 1 56 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
25 M-CLE-0400-C CABINET SIDE-LEFT 2 57 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRI-0400-C CABINET SIDE-RIGHT 2 58 M-PWC-1200 POWER CONNECTOR 1
27 M-CRE-0400-C CABINET REAR 1 59 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CTO-0400-C CABINET TOP 1 60 M-CCK-0850 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBA-0400-C CABINET BASE 1 61 M-CLP-1200 DRYER CLAMP 1
30 M-CBL-0400-C CABINET LEG 4 62 M-DFD-1200 DRAIN FIXING DEVICE 1
31 M-HP1-0400-C CABINET HORIZONTAL PROFILE 1 2 63 M-SCP-0400 CAPILLARY FOR SWITCH 1
32 M-HP2-0400-C CABINET HORIZONTAL PROFILE 2 2 64 M-HLC-0400 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
02250196-549 R02
28
5.12 ED—RC 400
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-0325 CONDENSER 1 34 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 1 35 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-0200 HEAT EXCHANGER 2 37 M-NUT-1200 CAGE NUT AND SCREW 16
6 M-WHC-0400 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-0500 EXPANSION VALVE 1 39 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 1 41 M-CNT-0400 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-FCN-1000 FAN CONTACTOR 1
11 M-THS-0325 THERMOSTATIC SWITCH 1 43 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-SEC-1000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 45 M-WPP-1000 WATER PUMP PROTECTOR 1
14 M-WTA-0325 WATER TANK 1 46 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-FOP-3000 FAN OVERLOAD PROTECTOR 1
16 M-WAG-3000 WATER GAUGE 1 48 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 49 M-VEN-3000 VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-SNS-0150 SENSOR PROBE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-DBV-6000 DRAIN BALL VALVE 1
20 M-TMR-3000 TIMER 1 52 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 4
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
22 M-MMV-6000-24 MEMBRANE VALVE 2 54 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
23 M-MMM-2400 MEMBRANE 2 55 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-0400-C CABINET FRONT 1 56 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
25 M-CLE-0400-C CABINET SIDE-LEFT 2 57 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRI-0400-C CABINET SIDE-RIGHT 2 58 M-PWC-1200 POWER CONNECTOR 1
27 M-CRE-0400-C CABINET REAR 1 59 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CTO-0400-C CABINET TOP 1 60 M-CCK-0850 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBA-0400-C CABINET BASE 1 61 M-CLP-1200 DRYER CLAMP 1
30 M-CBL-0400-C CABINET LEG 4 62 M-DFD-1200 DRAIN FIXING DEVICE 1
31 M-HP1-0400-C CABINET HORIZONTAL PROFILE 1 2 63 M-SCP-0400 CAPILLARY FOR SWITCH 1
32 M-HP2-0400-C CABINET HORIZONTAL PROFILE 2 2 64 M-HLC-0400 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
02250196-551 R02
30
5.13 ED—RC 500
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CPS-6000 CABINET HANDLE 8
2 M-CON-0500 CONDENSER 1 34 M-STU-6000 CABINET STUD AND NUT 12
3 SEE REF. TABLE FAN MOTOR 1 35 M-FAS-6000 CABINET FASTENER 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-NUT-1200 CAGE NUT AND SCREW 16
5 M-EXC-0200 HEAT EXCHANGER 2 37 M-SCR-6000 SCREW TYPE 2 16
6 M-WHC-0500 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-TRF-6000 TRANSFORMER 1
7 M-EXV-0500 EXPANSION VALVE 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-CNT-0850-460-3-60 CONTACTOR 1
9 M-FNS-6000 FAN ON/OFF SWITCH 1 41 M-FCN-1200 FAN CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
11 M-THS-3000 THERMOSTATIC SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
13 SEE REF. TABLE WATER PUMP 1 45 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WTA-0500 WATER TANK 1 46 M-FOP-1200 FAN OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
16 M-WAG-3000 WATER GAUGE 1 48 M-SNS-6000 SENSOR PROBE 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 49 M-VEN-3000 VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-DBV-6000 DRAIN BALL VALVE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 6
20 M-TMR-3000 TIMER 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
22 M-MMV-6000 MEMBRANE VALVE 2 54 M-WPB-3000 WATER PUMP BRACKET 1
23 M-MMM-6000 MEMBRANE 2 55 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
24 M-CFR-0400-C CABINET FRONT 1 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CSD-0850-C CABINET SIDE 2 57 M-PWC-1200 POWER CONNECTOR 1
26 M-CRE-0500-C CABINET REAR 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CTO-0700-C CABINET TOP 1 59 M-CCK-0850 CONTACTOR CONNECTING KIT 3
28 M-CBA-0850-C CABINET BASE 1 60 M-CLP-1200 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-CBL-0850-C CABINET LEG 4 61 M-DFD-1200 DRAIN FIXING DEVICE 2
30 M-HP1-0850-C CABINET HORIZONTAL PROFILE 1 2 62 M-SCP-0850 CAPILLARY FOR SWITCH 2
31 M-HP2-0850-C CABINET HORIZONTAL PROFILE 2 2 63 M-HLC-0850 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
32 M-CTC-6000 CABINET TOP CORNER 4
COMPRESSOR
DRYER PART POWER KIT FOR
DECAL CFM COOLING COMPRESSOR FAN MOTOR WATER PUMP OVERLOAD
NUMBER RATINGS ELECTRICAL PANEL
PROTECTOR
RC500 500 02250193-826 230V/3Ph/60Hz AIR COOLED M-CMP-0700-230-3-60 M-FMT-0700-230-3-60 M-PMP-3000 M-COP-0850 M-KEP-0850-230-3-60
RC500 500 02250193-907 400V/3Ph/50Hz AIR COOLED M-CMP-0500-460-3-60 M-FMT-0700-400/460-3-50/60 M-PMP-3000 M-COP-0500 M-KEP-0850
RC500 500 02250193-966 460V/3Ph/60Hz AIR COOLED M-CMP-0500-460-3-60 M-FMT-0700-400/460-3-50/60 M-PMP-3000 M-COP-0500 M-KEP-0850
RC500 500 02250194-124 575V/3Ph/60Hz AIR COOLED M-CMP-0500-575-3-60 M-FMT-0700-575-3-60 M-PMP-3000-575-3-60 M-COP-0500 M-KEP-0850
31
PRINCIPLE OF OPERATION SECTION 5
5.14 ED—RC 700
02250196-553 R02
32
5.14 ED—RC 700
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CPS-6000 CABINET HANDLE 8
2 M-CON-0700 CONDENSER 1 34 M-STU-6000 CABINET STUD AND NUT 12
3 SEE REF. TABLE FAN MOTOR 2 35 M-FAS-6000 CABINET FASTENER 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-NUT-1200 CAGE NUT AND SCREW 16
5 M-EXC-0200 HEAT EXCHANGER 3 37 M-SCR-6000 SCREW TYPE 2 16
6 M-WHC-1200 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-TRF-6000 TRANSFORMER 1
7 M-EXV-0700 EXPANSION VALVE 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-CNT-0850-460-3-60 CONTACTOR 1
9 M-FNS-6000 FAN ON/OFF SWITCH 1 41 M-FCN-1200 FAN CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
11 M-THS-3000 THERMOSTATIC SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
13 SEE REF. TABLE WATER PUMP 1 45 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WTA-0700 WATER TANK 1 46 M-FOP-1200 FAN OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
16 M-WAG-3000 WATER GAUGE 1 48 M-SNS-6000 SENSOR PROBE 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 49 M-VEN-3000 VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-DBV-6000 DRAIN BALL VALVE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 6
20 M-TMR-3000 TIMER 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
22 M-MMV-6000 MEMBRANE VALVE 2 54 M-WPB-3000 WATER PUMP BRACKET 1
23 M-MMM-6000 MEMBRANE 2 55 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
24 M-CFR-0850-C CABINET FRONT 1 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CSD-0850-C CABINET SIDE 2 57 M-PWC-1200 POWER CONNECTOR 1
26 M-CRE-0850-C CABINET REAR 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CTO-0700-C CABINET TOP 1 59 M-CCK-0850 CONTACTOR CONNECTING KIT 3
28 M-CBA-0850-C CABINET BASE 1 60 M-CLP-1200 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-CBL-0850-C CABINET LEG 4 61 M-DFD-1200 DRAIN FIXING DEVICE 2
30 M-HP1-0850-C CABINET HORIZONTAL PROFILE 1 2 62 M-SCP-0850 CAPILLARY FOR SWITCH 2
31 M-HP2-0850-C CABINET HORIZONTAL PROFILE 2 2 63 M-HLC-0850 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
32 M-CTC-6000 CABINET TOP CORNER 4
COMPRESSOR
DRYER PART POWER KIT FOR
DECAL CFM COOLING COMPRESSOR FAN MOTOR WATER PUMP OVERLOAD
NUMBER RATINGS ELECTRICAL PANEL
PROTECTOR
RC700 700 02250193-827 230V/3Ph/60Hz AIR COOLED M-CMP-0700-230-3-60 M-FMT-0700-230-3-60 M-PMP-3000 M-COP-1600 M-KEP-0850-230-3-60
RC700 700 02250193-908 400V/3Ph/50Hz AIR COOLED M-CMP-0700-460-3-60 M-FMT-0700-400/460-3-50/60 M-PMP-3000 M-COP-0850 M-KEP-0850
RC700 700 02250193-967 460V/3Ph/60Hz AIR COOLED M-CMP-0700-460-3-60 M-FMT-0700-400/460-3-50/60 M-PMP-3000 M-COP-0850 M-KEP-0850
RC700 700 02250194-125 575V/3Ph/60Hz AIR COOLED M-CMP-0700-575-3-60 M-FMT-0700-575-3-60 M-PMP-3000-575-3-60 M-COP-0850 M-KEP-0850
33
5.15 ED—RC 700 WATER COOLED
34
PRINCIPLE OF OPERATION
SECTION 5
02250196-554 R02
5.15 ED—RC 700 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-CPS-1000 CABINET HANDLE 8
2 M-CON-0700-W CONDENSER 1 32 M-STU-3000 CABINET STUD AND NUT 12
3 M-DRI-1200 DRIER-DEHYDRATOR 1 33 M-FAS-3000 CABINET FASTENER 12
4 M-EXC-0200 HEAT EXCHANGER 3 34 M-NUT-3000 CAGE NUT AND SCREW 16
5 M-WHC-1000 EVAPORATOR (WATER HEAT EXCHANGER) 1 35 M-SCR-3000 SCREW TYPE 2 16
6 M-EXV-1000 EXPANSION VALVE 1 36 M-TRF-6000 TRANSFORMER 1
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-CNT-0700-460-3-60-A CONTACTOR 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 40 M-SEC-3000 SECONDARY CONTACT 1
11 M-PMP-0850-460-3-60 WATER PUMP 1 41 M-WPP-6000 WATER PUMP PROTECTOR 1
12 M-WTA-0700 WATER TANK 1 42 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
14 M-WAG-3000 WATER GAUGE 1 44 M-WVF-0700 WATER VALVE 1
15 M-DGC-3000 DIGITAL CONTROLLER 1 45 M-SNS-6000 SENSOR PROBE 1
16 M-ONB-3000 ON/OFF BUTTON 1 46 M-VEN-3000 VENT RELIEF 1
17 M-MNS-1600 MAIN SWITCH 1 47 M-DBV-6000 DRAIN BALL VALVE 1
18 M-TMR-3000 TIMER 1 48 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 6
19 M-SLV-2400-24 SELENOID VALVE 1 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
20 M-MMV-2400 MEMBRANE VALVE 3 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
21 M-MMM-2400 MEMBRANE 3 51 M-WPB-3000 WATER PUMP BRACKET 1
22 M-CFR-0850-C CABINET FRONT 1 52 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
23 M-CSD-0850-C CABINET SIDE 2 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
24 M-CRE-0700-C CABINET REAR 1 54 M-PWC-1200 POWER CONNECTOR 1
25 M-CTO-0700-C CABINET TOP 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
26 M-CBA-0850-C CABINET BASE 1 56 M-CCK-0850 CONTACTOR CONNECTING KIT 3
27 M-CBL-0-850-C CABINET LEG 4 57 M-CLP-1200 DRYER CLAMP 1
28 M-HP1-0850-C CABINET HORIZONTAL PROFILE 1 2 58 M-DFD-1200 DRAIN FIXING DEVICE 2
PRINCIPLE OF OPERATION
29 M-HP2-0850-C CABINET HORIZONTAL PROFILE 2 2 59 M-HLC-0850 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
30 M-CTC-3000 CABINET TOP CORNER 4
COMPRESSOR
DRYER PART
DECAL CAPACITY POWER RATING COOLING COMPRESSOR WATER PUMP OVERLOAD
NUMBER
PROTECTOR
RC700 700 CFM 02250193-856 230V/3PH/60HZ WATER COOLED M-CMP-0700-230-3-60-A M-PMP-3000 M-COP-1600
RC700 700 CFM 02250193-933 400V/3PH/50HZ WATER COOLED M-CMP-0700-460-3-60-A M-PMP-3000 M-COP-0850
RC700 700 CFM 02250193-998 460V/3PH/60HZ WATER COOLED M-CMP-0700-460-3-60-A M-PMP-3000 M-COP-0850
RC700 700CFM 02250194-152 575V/3PH/60HZ WATER COOLED M-CMP-0700-575-3-60-A M-PMP-3000-575-3-60 M-COP-0850
35
5.16 ED—RC 850 AIR COOLED
36
PRINCIPLE OF OPERATION
SECTION 5
02250196-555 R05
5.16 ED—RC 850 AIR COOLED
SECTION 5
Key Part Number Qty Description Key Part Number Qty Description
1 SEE REF. TABLE 1 COMPRESSOR 33 M-CHN-6000 8 CABINET HANDLE (NEW)
2 M-CON-1000 1 CONDENSOR 34 M-STU-6000 22 CABINET STUD AND NUT
3 SEE REF. TABLE 2 FAN MOTOR 35 M-FAS-6000 22 CABINET FASTENERS
4 M-DRI-1200 1 DRIER-DEHYDRATOR 36 M-NUT-1200 29 CAGE NUTS
5 M-EXC-6000 2 HEAT EXCHANGER 37 M-SCR-6000 16 SCREWS
6 M-WHC-1200 1 EVAPORATOR (WATER HEAT EXCHANGER) 38 SEE REF. TABLE 1 TRANSFORMER
7 M-EXV-6000 1 EXPANSION VALVE 39 M-PPR-6000 1 PHASE PROTECTION RELAY
8 M-HPS-6000 1 HIGH PRESSURE SECURITY SWITCH 40 M-CNT-1200 1 CONTACTOR
9 M-FNS-6000 2 FAN ON/OFF SWITCH 41 M-FCN-1200 2 FAN CONTACTOR
10 M-LPS-6000 1 LOW PRESSURE SWITCH 42 M-CNT-MP 1 WATER PUMP CONTACTOR
11 M-THS-3000 1 THERMOSTATIC SWITCH 43 M-SEC-3000 1 SECONDARY CONTACT
12 M-WPS-3000 1 WATER PRESSURE SWITCH 44 M-FOP-6000 1 WATER PUMP PROTECTOR
13 SEE REF. TABLE 1 WATER PUMP 45 M-COP-1200 1 COMPRESSOR OVERLOAD PROTECTOR
14 M-WTA-1000 1 WATER TANK 46 M-FOP-1200 2 FAN OVERLOAD PROTECTOR
15 M-LIN-3000 1 LEVEL INDICATOR 47 M-WST-3000 1 WATER PRESSURE SWITCH TIMER
16 M-WAG-3000 1 WATER GUAGE 48 M-SNS-6000 1 SENSOR PROBE
17 M-DGC-3000,460,3-60 1 RC CONTROLLER 49 M-VEN-3000 1 VENT/RELIEF
18 M-ONB-3000 1 ON/OFF BUTTON 50 M-DBV-6000 1 DRAIN BALL VALVE
19 M-MNS-1200 1 MAIN SWITCH 51 M-EHH-6000 2 ELBOW FOR HEAT EXCHANGER HOSE
20 M-TMR-3000 1 TIMER 52 M-CCP-6000 10 CONDUIT FOR CONTROL PANEL
21 M-SLV-6000-24 1 SELENOID VALVE 53 M-CCB-1600 1 CONDUIT FOR CONTROL BOX
22 M-MMV-6000 2 MEMBRANE VALVE 54 M-WPB-3000 1 WATER PUMP BRACKET
23 M-MMM-6000 2 MEMBRANE 55 SEE REF. TABLE 1 KIT FOR ELECTRICAL PANEL
24 M-CFR-1200 1 CABINET FRONT 56 M-FHH-6000 5 HIGH VOLTAGE FUSE HOLDER
25 M-CSD-1000 2 CABINET SIDE 57 M-PWC-1200 1 POWER CONNECTOR
26 M-CRE-1200-C 1 CABINET REAR 58 M-FHL-6000 2 LOW VOLTAGE FUSE HOLDER
27 M-CTO-1000 1 CABINET TOP 59 M-CCK-1600 4 CONTACTOR CONNECTION KIT
28 M-CBA-1000-C 1 CABINET BASE 60 M-CLP-1200 1 DRYER CLAMP
29 M-CBL-1200 4 CABINET LEG 61 M-DFD-1200 2 DRAIN FIXING DEVICE
PRINCIPLE OF OPERATION
30 M-HP1-1200 2 CABINET HORIZONTAL PROFILE 1 62 M-SCP-1200 2 CAPILLARY FOR SWITCH
31 M-HP2-1000 2 CABINET HORIZONTAL PROFILE 2 63 M-HLC-1200 2 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE
32 M-CTC-6000 4 CABINET TOP CORNER 64 M-ECP-1200 1 ELECTRICAL PANEL
COMPRESSOR
DRYER PART POWER KIT FOR
DECAL CFM COOLING COMPRESSOR FAN MOTOR WATER PUMP OVERLOAD
NUMBER RATINGS ELECTRICAL PANEL
PROTECTOR
RC 850 850 02250193-828 230V/3Ph/60Hz AIR COOLED M-CMP-0850-230-3-60 M-FMT-1200-400/460-3-50/60 M-PMP-3000 M-COP-1600 M-KEP-0850-230-3-60
RC 850 850 02250193-909 400V/3Ph/50Hz AIR COOLED M-CMP-1000-460-3-60 M-FMT-1200-400/460-3-50/60 M-PMP-3000 M-COP-0850 M-KEP-0850
RC 850 850 02250193-968 460V/3Ph/60Hz AIR COOLED M-CMP-1000-460-3-60 M-FMT-1200-400/460-3-50/60 M-PMP-3000 M-COP-0850 M-KEP-0850
RC 850 850 02250194-126 575V/3Ph/60Hz AIR COOLED M-CMP-1000-575-3-60 M-FMT-1200-575-3-60 M-PMP-3000-575-3-60 M-COP-0850 M-KEP-0850-575-3-60-C
37
5.17 ED—RC 850 WATER COOLED
38
PRINCIPLE OF OPERATION
SECTION 5
02250196-556 R02
5.17 ED—RC 850 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-CPS-1000 CABINET HANDLE 8
2 M-CON-0850-W CONDENSER 1 32 M-STU-3000 CABINET STUD AND NUT 12
3 M-DRI-1200 DRIER-DEHYDRATOR 1 33 M-FAS-3000 CABINET FASTENER 12
4 M-EXC-0200 HEAT EXCHANGER 4 34 M-NUT-3000 CAGE NUT AND SCREW 16
5 M-WHC-1000 EVAPORATOR (WATER HEAT EXCHANGER) 1 35 M-SCR-3000 SCREW TYPE 2 16
6 M-EXV-1000 EXPANSION VALVE 2 36 M-TRF-6000 TRANSFORMER 1
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-CNT-0700-460-3-60-A CONTACTOR 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 40 M-SEC-3000 SECONDARY CONTACT 1
11 M-PMP-0850-460-3-60 WATER PUMP 1 41 M-WPP-6000 WATER PUMP PROTECTOR 1
12 M-WTA-0850 WATER TANK 1 42 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
14 M-WAG-3000 WATER GAUGE 1 44 M-WVF-0700 WATER VALVE 1
15 M-DGC-3000 DIGITAL CONTROLLER 1 45 M-SNS-6000 SENSOR PROBE 1
16 M-ONB-3000 ON/OFF BUTTON 1 46 M-VEN-3000 VENT RELIEF 1
17 M-MNS-1600 MAIN SWITCH 1 47 M-DBV-6000 DRAIN BALL VALVE 1
18 M-TMR-3000 TIMER 1 48 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 8
19 M-SLV-2400-24 SELENOID VALVE 1 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
20 M-MMV-2400 MEMBRANE VALVE 4 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
21 M-MMM-2400 MEMBRANE 4 51 M-WPB-3000 WATER PUMP BRACKET 1
22 M-CFR-0850-C CABINET FRONT 1 52 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
23 M-CSD-0850-C CABINET SIDE 2 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
24 M-CRE-0700-C CABINET REAR 1 54 M-PWC-1200 POWER CONNECTOR 1
25 M-CTO-0700-C CABINET TOP 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
26 M-CBA-0850-C CABINET BASE 1 56 M-CCK-0850 CONTACTOR CONNECTING KIT 3
27 M-CBL-0850-C CABINET LEG 4 57 M-CLP-1200 DRYER CLAMP 1
28 M-HP1-0850-C CABINET HORIZONTAL PROFILE 1 2 58 M-DFD-1200 DRAIN FIXING DEVICE 2
PRINCIPLE OF OPERATION
29 M-HP2-0850-C CABINET HORIZONTAL PROFILE 2 2 59 M-HLC-0850 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
30 M-CTC-3000 CABINET TOP CORNER 4
COMPRESSOR
DRYER PART KIT FOR
DECAL CFM POWER RATING COOLING COMPRESSOR WATER PUMP OVERLOAD
NUMBER ELECTRICAL PANEL
PROTECTOR
RC 850 850 02250193-934 230V/3PH/60HZ WATER COOLED M-CMP-0850-230-3-60 M-PMP-3000 M-COP-1600 M-KEP-0850-230-3-60-C-W
RC 850 850 02250193-999 400V/3PH/50HZ WATER COOLED M-CMP-1000-460-3-60 M-PMP-3000 M-COP-0850 M-KEP-0850-C-W
RC 850 850 02250193-968 460V/3PH/60HZ WATER COOLED M-CMP-1000-460-3-60 M-PMP-3000 M-COP-0850 M-KEP-0850-C-W
RC 850 850 02250194-153 575V/3PH/60HZ WATER COOLED M-CMP-1000-575-3-60 M-PMP-3000-575-3-60 M-COP-0850 M-KEP-0850-C-W
39
5.18 ED—RC 1000 AIR COOLED
40
PRINCIPLE OF OPERATION
SECTION 5
02250196-557 R03
5.18 ED—RC 1000 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CPS-6000 CABINET HANDLE 8
2 M-CON-1000 CONDENSER 1 34 M-STU-6000 CABINET STUD AND NUT 12
3 SEE REF. TABLE FAN MOTOR 2 35 M-FAS-6000 CABINET FASTENER 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-NUT-1200 CAGE NUT AND SCREW 16
5 M-EXC-6000 HEAT EXCHANGER 2 37 M-SCR-6000 SCREW TYPE 2 16
6 M-WHC-1200 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-TRF-6000 TRANSFORMER 1
7 M-EXV-1200 EXPANSION VALVE 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-CNT-1200 CONTACTOR 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 41 M-FCN-1200 FAN CONTACTOR 2
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
11 M-THS-3000 THERMOSTATIC SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
13 SEE REF. TABLE WATER PUMP 1 45 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WTA-1000 WATER TANK 1 46 M-FOP-1200 FAN OVERLOAD PROTECTOR 2
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
16 M-WAG-3000 WATER GAUGE 1 48 M-SNS-6000 SENSOR PROBE 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 49 M-VEN-3000 VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-DBV-6000 DRAIN BALL VALVE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 2
20 M-TMR-3000 TIMER 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
22 M-MMV-6000 MEMBRANE VALVE 2 54 M-WPB-3000 WATER PUMP BRACKET 1
23 M-MMM-6000 MEMBRANE 2 55 M-KEP-1200-C KIT FOR ELECTRICAL PANEL 1
24 M-CFR-1200 CABINET FRONT 1 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CSD-1000 CABINET SIDE 2 57 M-PWC-1200 POWER CONNECTOR 1
26 M-CRE-1200-C CABINET REAR 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CTO-1000 CABINET TOP 1 59 M-CCK-1600 CONTACTOR CONNECTING KIT 3
28 M-CBA-1000-C CABINET BASE 1 60 M-CLP-1200 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-CBL-1200 CABINET LEG 4 61 M-DFD-1200 DRAIN FIXING DEVICE 2
30 M-HP1-1200 CABINET HORIZONTAL PROFILE 1 2 62 M-SCP-1200 CAPILLARY FOR SWITCH 2
31 M-HP2-1000 CABINET HORIZONTAL PROFILE 2 2 63 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
32 M-CTC-6000 CABINET TOP CORNER 4
DECAL CFM DRYER PART POWER COOLING COMPRESSOR FAN MOTOR WATER PUMP
NUMBER RATINGS
PRINCIPLE OF OPERATION
SECTION 5
02250196-558 R03
5.19 ED—RC 1000 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-CPS-6000 CABINET HANDLE 8
2 M-CON-1000-W CONDENSER 1 32 M-STU-3000 CABINET STUD AND NUT 12
3 M-DRI-1200 DRIER-DEHYDRATOR 1 33 M-FAS-6000 CABINET FASTENER 12
4 M-EXC-6000 HEAT EXCHANGER 4 34 M-NUT-6000 CAGE NUT AND SCREW 16
5 M-WHC-1200 EVAPORATOR (WATER HEAT EXCHANGER) 1 35 M-SCR-6000 SCREW TYPE 2 16
6 M-EXV-1000 EXPANSION VALVE 2 36 M-TRF-6000 TRANSFORMER 1
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-CNT-1200-460-3-60-A CONTACTOR 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 40 M-SEC-3000 SECONDARY CONTACT 1
11 SEE REF. TABLE WATER PUMP 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
12 M-WTA-1000 WATER TANK 1 42 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
14 M-WAG-3000 WATER GAUGE 1 44 M-WVF-3000 WATER VALVE 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 45 M-SNS-6000 SENSOR PROBE 1
16 M-ONB-3000 ON/OFF BUTTON 1 46 M-VEN-3000 VENT RELIEF 1
17 M-MNS-1200 MAIN SWITCH 1 47 M-DBV-6000 DRAIN BALL VALVE 1
18 M-TMR-3000 TIMER 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 8
19 M-SLV-6000-24 SELENOID VALVE 1 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
20 M-MMV-6000 MEMBRANE VALVE 4 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
21 M-MMM-6000 MEMBRANE 4 51 M-WPB-3000 WATER PUMP BRACKET 1
22 M-CFR-1000 CABINET FRONT 1 52 M-KEP-1200-W-C KIT FOR ELECTRICAL PANEL 1
23 M-CSD-1000 CABINET SIDE 2 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
24 M-CRE-1000 CABINET REAR 1 54 M-PWC-1200 POWER CONNECTOR 1
25 M-CTO-1000-W CABINET TOP 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
26 M-CBA-1000 CABINET BASE 1 56 M-CCK-1600 CONTACTOR CONNECTING KIT 3
27 M-CBL-1200 CABINET LEG 4 57 M-CLP-1200 DRYER CLAMP 1
28 M-HP1-1200 CABINET HORIZONTAL PROFILE 1 2 58 M-DFD-1200 DRAIN FIXING DEVICE 2
PRINCIPLE OF OPERATION
29 M-HP2-1200 CABINET HORIZONTAL PROFILE 2 2 59 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
30 M-CTC-6000 CABINET TOP CORNER 4
DRYER PART
DECAL CFM POWER RATING COOLING COMPRESSOR WATER PUMP
NUMBER
PRINCIPLE OF OPERATION
SECTION 5
02250196-559 R03
5.20 ED—RC 1200 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 33 M-CPS-6000 CABINET HANDLE 8
2 M-CON-1200 CONDENSER 1 34 M-STU-6000 CABINET STUD AND NUT 12
3 SEE REF. TABLE FAN MOTOR 2 35 M-FAS-6000 CABINET FASTENER 12
4 M-DRI-1200 DRIER-DEHYDRATOR 1 36 M-NUT-1200 CAGE NUT AND SCREW 16
5 M-EXC-6000 HEAT EXCHANGER 3 37 M-SCR-6000 SCREW TYPE 2 16
6 M-WHC-1200 EVAPORATOR (WATER HEAT EXCHANGER) 1 38 M-TRF-6000 TRANSFORMER 1
7 M-EXV-1200 EXPANSION VALVE 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 40 M-CNT-1200 CONTACTOR 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 41 M-FCN-1200 FAN CONTACTOR 2
10 M-LPS-6000 LOW PRESSURE SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
11 M-THS-3000 THERMOSTATIC SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
13 SEE REF. TABLE WATER PUMP 1 45 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WTA-1200 WATER TANK 1 46 M-FOP-1200 FAN OVERLOAD PROTECTOR 2
15 M-LIN-3000 LEVEL INDICATOR 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
16 M-WAG-3000 WATER GAUGE 1 48 M-SNS-6000 SENSOR PROBE 1
17 M-DGC-3000 DIGITAL CONTROLLER 1 49 M-VENT/RELIEF VENT RELIEF 1
18 M-ONB-3000 ON/OFF BUTTON 1 50 M-DBV-6000 DRAIN BALL VALVE 1
19 M-MNS-1200 MAIN SWITCH 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 3
20 M-TMR-2400 TIMER 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-SLV-6000-24 SELENOID VALVE 1 53 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
22 M-MMV-6000 MEMBRANE VALVE 2 54 M-WPB-3000 WATER PUMP BRACKET 1
23 M-MMM-6000 MEMBRANE 3 55 M-KEP-1200-C KIT FOR ELECTRICAL PANEL 1
24 M-CFR-1200 CABINET FRONT 1 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CSD-1200 CABINET SIDE 2 57 M-PWC-1200 POWER CONNECTOR 1
26 M-CRE-1200 CABINET REAR 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CTO-1200 CABINET TOP 1 59 M-CCK-1600 CONTACTOR CONNECTING KIT 3
28 M-CBA-1200 CABINET BASE 1 60 M-CLP-1200 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-CBL-1200 CABINET LEG 4 61 M-DFD-1200 DRAIN FIXING DEVICE 2
30 M-HP1-1200 CABINET HORIZONTAL PROFILE 1 2 62 M-SCP-1200 CAPILLARY FOR SWITCH 2
31 M-HP2-1200 CABINET HORIZONTAL PROFILE 2 2 63 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
32 M-CTC-6000 CABINET TOP CORNER 4
DECAL CFM DRYER PART POWER COOLING FAN MOTOR COMPRESSOR WATER PUMP
NUMBER RATINGS
PRINCIPLE OF OPERATION
SECTION 5
02250196-560 R03
5.21 ED—RC 1200 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-CPS-6000 CABINET HANDLE 8
2 M-CON-1200-W CONDENSER 1 32 M-STU-6000 CABINET STUD AND NUT 12
3 M-DRI-1200 DRIER-DEHYDRATOR 1 33 M-FAS-6000 CABINET FASTENER 12
4 M-EXC-6000 HEAT EXCHANGER 4 34 M-NUT-6000 CAGE NUT AND SCREW 16
5 M-WHC-1200 EVAPORATOR (WATER HEAT EXCHANGER) 1 35 M-SCR-6000 SCREW TYPE 2 16
6 M-EXV-1200 EXPANSION VALVE 2 36 M-TRF-6000 TRANSFORMER 1
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-CNT-1200 CONTACTOR 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 40 M-SEC-3000 SECONDARY CONTACT 1
11 SEE REF. TABLE WATER PUMP 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
12 M-WTA-1200 WATER TANK 1 42 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
14 M-WAG-3000 WATER GAUGE 1 44 M-WVF-3000 WATER VALVE 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 45 M-SNS-6000 SENSOR PROBE 1
16 M-ONB-3000 ON/OFF BUTTON 1 46 M-VEN-3000 VENT RELIEF 1
17 M-MNS-1200 MAIN SWITCH 1 47 M-DBV-6000 DRAIN BALL VALVE 1
18 M-TMR-2400 TIMER 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 3
19 M-SLV-6000-24 SELENOID VALVE 1 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
20 M-MMV-6000 MEMBRANE VALVE 4 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
21 M-MMM-6000 MEMBRANE 4 51 M-WPB-3000 WATER PUMP BRACKET 1
22 M-CFR-1200 CABINET FRONT 1 52 M-KEP-1600-W-C KIT FOR ELECTRICAL PANEL 1
23 M-CSD-1200 CABINET SIDE 2 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
24 M-CRE-1200 CABINET REAR 1 54 M-PWC-1200 POWER CONNECTOR 1
25 M-CTO-1200-W CABINET TOP 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
26 M-CBA-1200 CABINET BASE 1 56 M-CCK-1600 CONTACTOR CONNECTING KIT 3
27 M-CBL-1200 CABINET LEG 4 57 M-CLP-1200 DRYER CLAMP 1
28 M-HP1-1200 CABINET HORIZONTAL PROFILE 1 2 58 M-DFD-1200 DRAIN FIXING DEVICE 2
PRINCIPLE OF OPERATION
29 M-HP2-1200 CABINET HORIZONTAL PROFILE 2 2 59 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
30 M-CTC-6000 CABINET TOP CORNER 4
DRYER PART
DECAL CFM POWER RATING COOLING COMPRESSOR WATER PUMP
NUMBER
PRINCIPLE OF OPERATION
SECTION 5
02250196-561 R02
5.22 ED—RC 1600 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 32 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-1600 CONDENSER 1 33 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 2 34 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-2400 DRIER-DEHYDRATOR 1 35 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-6000 HEAT EXCHANGER 3 36 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-WHC-2000 EVAPORATOR (WATER HEAT EXCHANGER) 1 37 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-1600 EXPANSION VALVE 1 38 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 40 M-CNT-1600-460-3-60 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 41 M-FCN-6000 FAN CONTACTOR 2
11 M-THS-3000 THERMOSTATIC SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
14 M-WTA-1600 WATER TANK 1 45 M-COP-1600 COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 46 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
16 M-WAG-3000 WATER GAUGE 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 48 M-SNS-6000 SENSOR PROBE 1
18 M-ONB-3000 ON/OFF BUTTON 1 49 M-VEN-3000 VENT RELIEF 1
19 M-MNS-2400 MAIN SWITCH 1 50 M-DBV-6000 DRAIN BALL VALVE 5
20 M-TMR-3000 TIMER 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
21 M-SLV-6000-24 SELENOID VALVE 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
22 M-MMV-6000 MEMBRANE VALVE 2 53 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
23 M-MMM-6000 MEMBRANE 3 54 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-2000 CABINET FRONT 1 55 M-KEP-1600-C KIT FOR ELECTRICAL PANEL 1
25 M-CSD-2000 CABINET SIDE 2 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRE-2000 CABINET REAR 1 57 M-PWC-2400 POWER CONNECTOR 1
27 M-CTO-2000-w CABINET TOP 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CBA-2000 CABINET BASE 1 59 M-CCK-1600 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBL-6000 CABINET LEG 4 60 M-CLP-2400 DRYER CLAMP 1
30 M-HP1-2000 CABINET HORIZONTAL PROFILE 1 2 61 M-SCP-2000 CAPILLARY FOR SWITCH 2
31 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 62 M-HLC-2000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR FAN MOTOR WATER PUMP
PART NUMBER RATINGS
RC 1600 1600 CFM 02250193-912 400V/3PH/50HZ AIR COOLED M-CMP-1600-460-3-60 F-FMT-1600-460-3-60 M-PMP-3000
RC 1600 1600 CFM 02250193-971 460V/3PH/60HZ AIR COOLED M-CMP-1600-460-3-60 F-FMT-1600-460-3-60 M-PMP-3000
RC 1600 1600 CFM 02250194-129 575V/3PH/60HZ AIR COOLED M-CMP-1600-575-3-60 F-FMT-1600-575-3-60 M-PMP-3000-575-3-60
49
5.23 ED—RC 1600 WATER COOLED
50
PRINCIPLE OF OPERATION
SECTION 5
02250196-562 R02
5.23 ED—RC 1600 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 30 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-1600-W CONDENSER 1 31 M-CPS-6000 CABINET HANDLE 8
3 M-DRI-2400 DRIER-DEHYDRATOR 1 32 M-STU-6000 CABINET STUD AND NUT 12
4 M-EXC-6000 HEAT EXCHANGER 4 33 M-FAS-6000 CABINET FASTENER 12
5 M-WHC-2000 EVAPORATOR (WATER HEAT EXCHANGER) 1 34 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-EXV-1600 EXPANSION VALVE 1 35 M-SCR-6000 SCREW TYPE 2 16
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-TRF-6000 TRANSFORMER 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 38 M-CNT-1600 CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
11 SEE REF. TABLE WATER PUMP 1 40 M-SEC-3000 SECONDARY CONTACT 1
12 M-WTA-1600 WATER TANK 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 42 M-COP-1600 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WAG-3000 WATER GAUGE 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 44 M-WVF-1600 WATER VALVE 1
16 M-ONB-3000 ON/OFF BUTTON 1 45 M-SNS-6000 SENSOR PROBE 1
17 M-MNS-2400 MAIN SWITCH 1 46 M-VEN-3000 VENT RELIEF 1
18 M-TMR-3000 TIMER 1 47 M-DBV-6000 DRAIN BALL VALVE 5
19 M-SLV-6000-24 SELENOID VALVE 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
20 M-MMV-6000 MEMBRANE VALVE 5 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-MMM-6000 MEMBRANE 5 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
22 M-CFR-2000 CABINET FRONT 1 51 M-WPB-3000 WATER PUMP BRACKET 1
23 M-CSD-2000 CABINET SIDE 2 52 M-KEP-1600-W-C KIT FOR ELECTRICAL PANEL 1
24 M-CRE-2000 CABINET REAR 1 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CTO-2000-W CABINET TOP 1 54 M-PWC-2400 POWER CONNECTOR 1
26 M-CBA-2000 CABINET BASE 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CBL-2000 CABINET LEG 4 56 M-CCK-1600 CONTACTOR CONNECTING KIT 3
28 M-HP1-2000 CABINET HORIZONTAL PROFILE 1 2 57 M-CLP-2400 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 58 M-HLC-2000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR WATER PUMP
PART NUMBER RATINGS
RC 1600 1600 CFM 02250193-937 400V/3PH/50HZ WATER COOLED M-CMP-1600-460-3-60 M-PMP-3000
RC 1600 1600 CFM 02250194-102 460V/3PH/60HZ WATER COOLED M-CMP-1600-460-3-60 M-PMP-3000
RC 1600 1600 CFM 02250194-156 575V/3PH/60HZ WATER COOLED M-CMP-1600-575-3-60 M-PMP-3000-575-3-60
51
5.24 ED—RC 2000 AIR COOLED
52
PRINCIPLE OF OPERATION
SECTION 5
02250196-563 R03
5.24 ED—RC 2000 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 32 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-2400 CONDENSER 1 33 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 2 34 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-2400 DRIER-DEHYDRATOR 1 35 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-6000 HEAT EXCHANGER 4 36 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-WHC-2000 EVAPORATOR (WATER HEAT EXCHANGER) 1 37 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-2400 EXPANSION VALVE 1 38 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 40 M-CNT-2400 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 41 M-FCN-6000 FAN CONTACTOR 2
11 M-THS-3000 THERMOSTATIC SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
14 M-WTA-2000 WATER TANK 1 45 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 46 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
16 M-WAG-3000 WATER GAUGE 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 48 M-SNS-6000 SENSOR PROBE 1
18 M-ONB-3000 ON/OFF BUTTON 1 49 M-VEN-3000 VENT RELIEF 1
19 M-MNS-2400 MAIN SWITCH 1 50 M-DBV-6000 DRAIN BALL VALVE 5
20 M-TMR-3000 TIMER 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
21 M-SLV-6000-24 SELENOID VALVE 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
22 M-MMV-6000 MEMBRANE VALVE 5 53 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
23 M-MMM-6000 MEMBRANE 5 54 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-2000 CABINET FRONT 1 55 M-KEP-2400-C KIT FOR ELECTRICAL PANEL 1
25 M-CSD-2000 CABINET SIDE 2 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRE-2000 CABINET REAR 1 57 M-PWC-2400 POWER CONNECTOR 1
27 M-CTO-2000-W CABINET TOP 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CBA-2000 CABINET BASE 1 59 M-CCK-5000 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBL-6000 CABINET LEG 4 60 M-CLP-2400 DRYER CLAMP 1
30 M-HP1-2000 CABINET HORIZONTAL PROFILE 1 2 61 M-SCP-2000 CAPILLARY FOR SWITCH 2
31 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 62 M-HLC-2000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR FAN MOTOR WATER PUMP
PART NUMBER RATINGS
RC 2000 2000 CFM 02250193-913 400V/3PH/50HZ AIR COOLED M-CMP-2000-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 2000 2000 CFM 02250193-972 460V/3PH/60HZ AIR COOLED M-CMP-2000-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 2000 2000 CFM 02250194-130 575V/3PH/60HZ AIR COOLED M-CMP-2000-575-3-60 F-FMT-6000-575-3-60 M-PMP-3000-575-3-60
53
5.25 ED—RC 2000 WATER COOLED
54
PRINCIPLE OF OPERATION
SECTION 5
02250196-564 R03
5.25 ED—RC 2000 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 30 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-2400-W CONDENSER 1 31 M-CPS-6000 CABINET HANDLE 8
3 M-DRI-2400 DRIER-DEHYDRATOR 1 32 M-STU-6000 CABINET STUD AND NUT 12
4 M-EXC-6000 HEAT EXCHANGER 4 33 M-FAS-6000 CABINET FASTENER 12
5 M-WHC-2000 EVAPORATOR (WATER HEAT EXCHANGER) 1 34 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-EXV-2400 EXPANSION VALVE 1 35 M-SCR-6000 SCREW TYPE 2 16
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-TRF-6000 TRANSFORMER 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 38 M-CNT-2400 CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
11 SEE REF. TABLE WATER PUMP 1 40 M-SEC-3000 SECONDARY CONTACT 1
12 M-WTA-2000 WATER TANK 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 42 M-COP-1600 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WAG-3000 WATER GAUGE 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 44 M-WVF-2400 WATER VALVE 1
16 M-ONB-3000 ON/OFF BUTTON 1 45 M-SNS-6000 SENSOR PROBE 1
17 M-MNS-2400 MAIN SWITCH 1 46 M-VEN-3000 VENT RELIEF 1
18 M-TMR-3000 TIMER 1 47 M-DBV-6000 DRAIN BALL VALVE 5
19 M-SLV-6000-24 SELENOID VALVE 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
20 M-MMV-6000 MEMBRANE VALVE 5 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-MMM-6000 MEMBRANE 5 50 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
22 M-CFR-2000 CABINET FRONT 1 51 M-WPB-3000 WATER PUMP BRACKET 1
23 M-CSD-2000 CABINET SIDE 2 52 M-KEP-2400 KIT FOR ELECTRICAL PANEL 1
24 M-CRE-2000 CABINET REAR 1 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CTO-2000-W CABINET TOP 1 54 M-PWC-2400 POWER CONNECTOR 1
26 M-CBA-2000 CABINET BASE 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CBL-2000 CABINET LEG 4 56 M-CCK-5000 CONTACTOR CONNECTING KIT 3
28 M-HP1-2000 CABINET HORIZONTAL PROFILE 1 2 57 M-CLP-2400 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 58 M-HLC-2000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR WATER PUMP
PART NUMBER RATINGS
RC 2000 2000 CFM 02250193-938 400V/3PH/50HZ WATER COOLED M-CMP-2000-460-3-60 M-PMP-3000
RC 2000 2000 CFM 02250194-103 460V/3PH/60HZ WATER COOLED M-CMP-2000-460-3-60 M-PMP-3000
RC 2000 2000 CFM 02250194-157 575V/3PH/60HZ WATER COOLED M-CMP-2000-575-3-60 M-PMP-3000-575-3-60
55
5.26 ED—RC 2400 AIR COOLED
56
PRINCIPLE OF OPERATION
SECTION 5
02250196-565 R02
5.26 ED—RC 2400 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 32 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-2400 CONDENSER 1 33 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 2 34 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-2400 DRIER-DEHYDRATOR 1 35 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-6000 HEAT EXCHANGER 5 36 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-WHC-2400 EVAPORATOR (WATER HEAT EXCHANGER) 1 37 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-2400 EXPANSION VALVE 1 38 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 40 M-CNT-2400 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 41 M-FCN-6000 FAN CONTACTOR 2
11 M-THS-3000 THERMOSTATIC SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
14 M-WTA-2000 WATER TANK 1 45 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 46 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
16 M-WAG-3000 WATER GAUGE 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 48 M-SNS-6000 SENSOR PROBE 1
18 M-ONB-3000 ON/OFF BUTTON 1 49 M-VEN-3000 VENT RELIEF 1
19 M-MNS-2400 MAIN SWITCH 1 50 M-DBV-6000 DRAIN BALL VALVE 6
20 M-TMR-3000 TIMER 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 5
21 M-SLV-6000-24 SELENOID VALVE 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
22 M-MMV-6000 MEMBRANE VALVE 5 53 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
23 M-MMM-6000 MEMBRANE 5 54 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-3000 CABINET FRONT 1 55 M-KEP-6000 KIT FOR ELECTRICAL PANEL 1
25 M-CSD-3000 CABINET SIDE 2 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRE-3000 CABINET REAR 1 57 M-PWC-2400 POWER CONNECTOR 1
27 M-CTO-3000-W CABINET TOP 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CBA-3000 CABINET BASE 1 59 M-CCK-5000 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBL-6000 CABINET LEG 4 60 M-CLP-2400 DRYER CLAMP 1
30 M-HP1-3000 CABINET HORIZONTAL PROFILE 1 2 61 M-SCP-3000 CAPILLARY FOR SWITCH 2
31 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 62 M-HLC-3000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR FAN MOTOR WATER PUMP
PART NUMBER RATINGS
RC 2400 2400 CFM 02250193-914 400V/3PH/50HZ AIR COOLED M-CMP-2400-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 2400 2400 CFM 02250193-973 460V/3PH/60HZ AIR COOLED M-CMP-2400-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 2400 2400 CFM 02250194-131 575V/3PH/60HZ AIR COOLED M-CMP-2400-575-3-60 F-FMT-6000-575-3-60 M-PMP-3000-575-3-60
57
5.27 ED—RC 2400 WATER COOLED
58
PRINCIPLE OF OPERATION
SECTION 5
02250196-567 R02
5.27 ED—RC 2400 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 30 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-2400-W CONDENSER 1 31 M-CPS-6000 CABINET HANDLE 8
3 M-DRI-2400 DRIER-DEHYDRATOR 1 32 M-STU-6000 CABINET STUD AND NUT 12
4 M-EXC-6000 HEAT EXCHANGER 4 33 M-FAS-6000 CABINET FASTENER 12
5 M-WHC-2400 EVAPORATOR (WATER HEAT EXCHANGER) 1 34 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-EXV-2400 EXPANSION VALVE 1 35 M-SCR-6000 SCREW TYPE 2 16
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-TRF-6000 TRANSFORMER 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 38 M-CNT-3000-460-3-60 CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
11 SEE REF. TABLE WATER PUMP 1 40 M-SEC-3000 SECONDARY CONTACT 1
12 M-WTA-2400 WATER TANK 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 42 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WAG-3000 WATER GAUGE 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 44 M-WVF-2400 WATER VALVE 1
16 M-ONB-3000 ON/OFF BUTTON 1 45 M-SNS-6000 SENSOR PROBE 1
17 M-MNS-2400 MAIN SWITCH 1 46 M-VEN-3000 VENT RELIEF 1
18 M-TMR-3000 TIMER 1 47 M-DBV-6000 DRAIN BALL VALVE 6
19 M-SLV-6000-24 SELENOID VALVE 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 5
20 M-MMV-6000 MEMBRANE VALVE 5 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-MMM-6000 MEMBRANE 5 50 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
22 M-CFR-3000 CABINET FRONT 1 51 M-WPB-3000 WATER PUMP BRACKET 1
23 M-CSD-3000 CABINET SIDE 2 52 M-KEP-3000-W-C KIT FOR ELECTRICAL PANEL 1
24 M-CRE-3000 CABINET REAR 1 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CTO-3000-W CABINET TOP 1 54 M-PWC-2400 POWER CONNECTOR 1
26 M-CBA-3000 CABINET BASE 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CBL-6000 CABINET LEG 4 56 M-CCK-5000 CONTACTOR CONNECTING KIT 3
28 M-HP1-3000 CABINET HORIZONTAL PROFILE 1 2 57 M-CLP-2400 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 58 M-HLC-3000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR WATER PUMP
PART NUMBER RATINGS
RC 2400 2400 CFM 02250193-939 400V/3PH/50HZ WATER COOLED M-CMP-2400-460-3-60 M-PMP-3000
RC 2400 2400 CFM 02250194-104 460V/3PH/60HZ WATER COOLED M-CMP-2400-460-3-60 M-PMP-3000
RC 2400 2400 CFM 02250194-158 575V/3PH/60HZ WATER COOLED M-CMP-2400-575-3-60 M-PMP-3000-575-3-60
59
5.28 ED—RC 3000 AIR COOLED
60
PRINCIPLE OF OPERATION
SECTION 5
02250196-568 R02
5.28 ED—RC 3000 AIR COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 32 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-3000 CONDENSER 1 33 M-CPS-6000 CABINET HANDLE 8
3 SEE REF. TABLE FAN MOTOR 2 34 M-STU-6000 CABINET STUD AND NUT 12
4 M-DRI-3000 DRIER-DEHYDRATOR 1 35 M-FAS-6000 CABINET FASTENER 12
5 M-EXC-6000 HEAT EXCHANGER 5 36 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-WHC-3000 EVAPORATOR (WATER HEAT EXCHANGER) 1 37 M-SCR-6000 SCREW TYPE 2 16
7 M-EXV-3000 EXPANSION VALVE 1 38 M-TRF-6000 TRANSFORMER 1
8 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-FNS-6000 FAN ON/OFF SWITCH 2 40 M-CNT-3000 CONTACTOR 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 41 M-FCN-6000 FAN CONTACTOR 2
11 M-THS-3000 THERMOSTATIC SWITCH 1 42 M-WPC-3000 WATER PUMP CONTACTOR 1
12 M-WPS-3000 WATER PRESSURE SWITCH 1 43 M-SEC-3000 SECONDARY CONTACT 1
13 SEE REF. TABLE WATER PUMP 1 44 M-WPP-3000 WATER PUMP PROTECTOR 1
14 M-WTA-3000 WATER TANK 1 45 M-COP-3000 COMPRESSOR OVERLOAD PROTECTOR 1
15 M-LIN-3000 LEVEL INDICATOR 1 46 M-FOP-6000 FAN OVERLOAD PROTECTOR 2
16 M-WAG-3000 WATER GAUGE 1 47 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
17 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 48 M-SNS-6000 SENSOR PROBE 1
18 M-ONB-3000 ON/OFF BUTTON 1 49 M-VEN-3000 VENT RELIEF 1
19 M-MNS-2400 MAIN SWITCH 1 50 M-DBV-6000 DRAIN BALL VALVE 7
20 M-TMR-3000 TIMER 1 51 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 6
21 M-SLV-6000-24 SELENOID VALVE 1 52 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
22 M-MMV-6000 MEMBRANE VALVE 5 53 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
23 M-MMM-6000 MEMBRANE 5 54 M-WPB-3000 WATER PUMP BRACKET 1
24 M-CFR-3000 CABINET FRONT 1 55 M-KEP-3000-C KIT FOR ELECTRICAL PANEL 1
25 M-CSD-3000 CABINET SIDE 2 56 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
26 M-CRE-3000 CABINET REAR 1 57 M-PWC-3800 POWER CONNECTOR 1
27 M-CTO-3000-W CABINET TOP 1 58 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
28 M-CBA-3000 CABINET BASE 1 59 M-CCK-5000 CONTACTOR CONNECTING KIT 3
PRINCIPLE OF OPERATION
29 M-CBL-6000 CABINET LEG 4 60 M-CLP-3800 DRYER CLAMP 1
30 M-HP1-3000 CABINET HORIZONTAL PROFILE 1 2 61 M-SCP-3000 CAPILLARY FOR SWITCH 2
31 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 62 M-HLC-3000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR FAN MOTOR WATER PUMP
PART NUMBER RATINGS
RC 3000 3000 CFM 02250193-915 400V/3PH/50HZ AIR COOLED M-CMP-3000-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 3000 3000 CFM 02250193-974 460V/3PH/60HZ AIR COOLED M-CMP-3000-460-3-60 F-FMT-6000-460-3-60 M-PMP-3000
RC 3000 3000 CFM 02250194-132 575V/3PH/60HZ AIR COOLED M-CMP-3000-575-3-60 F-FMT-6000-575-3-60 M-PMP-3000-575-3-60
61
5.29 ED—RC 3000 WATER COOLED
62
PRINCIPLE OF OPERATION
SECTION 5
02250196-569 R02
5.29 ED—RC 3000 WATER COOLED
SECTION 5
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 30 M-CTC-6000 CABINET TOP CORNER 4
2 M-CON-3000-W CONDENSER 1 31 M-CPS-6000 CABINET HANDLE 8
3 M-DRI-5000 DRIER-DEHYDRATOR 1 32 M-STU-6000 CABINET STUD AND NUT 12
4 M-EXC-6000 HEAT EXCHANGER 6 33 M-FAS-6000 CABINET FASTENER 12
5 M-WHC-3000 EVAPORATOR (WATER HEAT EXCHANGER) 1 34 M-NUT-6000 CAGE NUT AND SCREW 16
6 M-EXV-3000 EXPANSION VALVE 6 35 M-SCR-6000 SCREW TYPE 2 16
7 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-TRF-6000 TRANSFORMER 1
8 M-LPS-6000 LOW PRESSURE SWITCH 1 37 M-PPR-6000 PHASE PROTECTION RELAY 1
9 M-THS-3000 THERMOSTATIC SWITCH 1 38 M-CNT-3000-460-3-60 CONTACTOR 1
10 M-WPS-3000 WATER PRESSURE SWITCH 1 39 M-WPC-3000 WATER PUMP CONTACTOR 1
11 SEE REF. TABLE WATER PUMP 1 40 M-SEC-3000 SECONDARY CONTACT 1
12 M-WTA-2400 WATER TANK 1 41 M-WPP-3000 WATER PUMP PROTECTOR 1
13 M-LIN-3000 LEVEL INDICATOR 1 42 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
14 M-WAG-3000 WATER GAUGE 1 43 M-WST-3000 WATER PRESSURE SWITCH TIMER 1
15 M-DGC-3000-460-3-60 DIGITAL CONTROLLER 1 44 M-WVF-2400 WATER VALVE 1
16 M-ONB-3000 ON/OFF BUTTON 1 45 M-SNS-6000 SENSOR PROBE 1
17 M-MNS-3800 MAIN SWITCH 1 46 M-VEN-3000 VENT RELIEF 1
18 M-TMR-3000 TIMER 1 47 M-DBV-6000 DRAIN BALL VALVE 7
19 M-SLV-6000-24 SELENOID VALVE 1 48 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 6
20 M-MMV-6000 MEMBRANE VALVE 7 49 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
21 M-MMM-6000 MEMBRANE 7 50 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
22 M-CFR-3000 CABINET FRONT 1 51 M-WPB-3000 WATER PUMP BRACKET 1
23 M-CSD-3000 CABINET SIDE 2 52 M-KEP-3000-W-C KIT FOR ELECTRICAL PANEL 1
24 M-CRE-3000 CABINET REAR 1 53 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
25 M-CTO-3000-W CABINET TOP 1 54 M-PWC-3800 POWER CONNECTOR 1
26 M-CBA-3000 CABINET BASE 1 55 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
27 M-CBL-6000 CABINET LEG 4 56 M-CCK-5000 CONTACTOR CONNECTING KIT 3
28 M-HP1-3000 CABINET HORIZONTAL PROFILE 1 2 57 M-CLP-3800 DRYER CLAMP 1
PRINCIPLE OF OPERATION
29 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 58 M-HLC-3000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
DRYER POWER
DECAL CAPACTIY COOLING COMPRESSOR WATER PUMP
PART NUMBER RATINGS
PRINCIPLE OF OPERATION
SECTION 5
02250195-273 R00
5.30 P&I—RC150-850
SECTION 5
KEY DESCRIPTION
1 COMPRESSOR
2 REFRIGERANT CONDENSER
3 FAN MOTOR
4 FAN MOTOR SWITCH
5 EVAPORATOR
6 AIR-AIR EXCHANGER
7 DEW POINT INDICATOR
8 EVAPORATOR
9 THERMO. EXP. VALVE
10 SUCTION ACCUMULATOR
11 LOW PRESSURE
12 ISOLATION VALVE
13 HIGH PRESSURE
14 SAFETY VALVE
15 RECEIVER
16 REFRIG. FILTER DRIER
17 AIR VENT
18 FLOAT SWITCH
19 COLD STORAGE TANK
PRINCIPLE OF OPERATION
20 SIGHT GLASS
21 AIR FILTER OPTIONAL
22 WATER PUMP
23 WATER PRESSURE SWITCH
NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR
P/N AND REVISION.
65
5.31 P&I—RC400-850
66
PRINCIPLE OF OPERATION
SECTION 5
02250195-279 R00
5.31 P&I—400-850
SECTION 5
KEY DESCRIPTION MODEL REFRIGERANT TYPE LB
1 COMPRESSOR RC400 ...
2 WATER CONDENSER RC500 ...
R134A
3 EVAPORATOR RC700 ...
4 AIR-AIR EXCHANGER RC850 ...
5 DEW POINT INDICATOR
6 EVAPORATOR
8 SUCTION ACCUMULATOR
9 LOW PRESSURE
10 ISOLATION VALVE
11 HIGH PRESSURE
12 SAFETY VALVE
13 RECEIVER
15 AIR VENT
16 FLOAT SWITCH
PRINCIPLE OF OPERATION
17 COLD STORAGE TANK
18 SIGHT GLASS
19 WATER PUMP
PRINCIPLE OF OPERATION
SECTION 5
02250195-281 R00
5.32 P&I—1000-3000
SECTION 5
KEY DESCRIPTION REFRIGERANT
MODEL LB
1 COMPRESSOR TYPE
8 SUCTION ACCUMULATOR
9 LOW PRESSURE
10 ISOLATION VALVE
11 HIGH PRESSURE
12 SAFETY VALVE
13 RECEIVER
15 AIR VENT
16 FLOAT SWITCH
PRINCIPLE OF OPERATION
17 COLD STORAGE TANK
18 SIGHT GLASS
20 WATER PUMP
PRINCIPLE OF OPERATION
SECTION 5
02250195-283 R00
5.34 P&I—RC1000-3000
SECTION 5
KEY DESCRIPTION REFRIGERANT
MODEL LB
TYPE
1 COMPRESSOR
RC1000 ...
2 WATER CONDENSER
9 HIGH PRESSURE
10 SAFETY VALVE
11 RECEIVER
13 AIR VENT
14 FLOAT SWITCH
PRINCIPLE OF OPERATION
16 SIGHT GLASS
17 WATER PUMP
PRINCIPLE OF OPERATION
SECTION 5
02250195-243 R00
5.35 ID—RC 150-200
SECTION 5
DRYER PART
POWER RATINGS COOLING DECAL
NUMBER
PRINCIPLE OF OPERATION
73
5.36 ID—RC 250-400
74
PRINCIPLE OF OPERATION
SECTION 5
02250195-244 R00
5.36 ID—RC 250-400
SECTION 5
A B
DECA DRYER PART POWER
COOLING (AIR (WATER C D E
L NUMBER RATINGS
CONNECTION) CONNECTION)
02250193-867 220V/1Ph/50Hz
02250193-823 230V/3Ph/60Hz
RC250 02250193-904 400V/3Ph/50Hz AIR COOLED 1 1/2” NPT-F N/A N/A N/A N/A
02250193-963 460V/3Ph/60Hz
02250194-121 575V/3Ph/60Hz
02250193-824 230V/3Ph/60Hz
02250193-905 400V/3Ph/50Hz
RC325 AIR COOLED 2” NPT-F N/A N/A N/A N/A
02250193-964 460V/3Ph/60Hz
02250194-122 575V/3Ph/60Hz
02250193-825 230V/3Ph/60Hz
02250193-906 400V/3Ph/50Hz
AIR COOLED 2” NPT-F N/A N/A N/A N/A
02250193-965 460V/3Ph/60Hz
02250194-123 575V/3Ph/60Hz
RC400
02250193-854 230V/3Ph/60Hz
02250193-930 400V/3Ph/50Hz 5.83” 40.15” 46.06”
WATER COOLED 2” NPT-F 1” NPT-F
02250193-996 460V/3Ph/60Hz 135mm 1020mm 1170mm
02250194-150 575V/3Ph/60Hz
PRINCIPLE OF OPERATION
WITHOUT PALLET SIZES WITH PALLET SIZES
R WEIGHT WEIGHT
RC250 1275 LB 1157 LB
29,33”*33,27”*50 34,25"*38,19"*57,48"
RC325 1245 LB 1224 LB
[745]*[845]*[1270] [870]*[970]*[1460]
RC400 1397 LB 1292 LB
75
PRINCIPLE OF OPERATION SECTION 5
5.37 ID—RC 500-850
02250195-245
76
5.37 RC 500-850
SECTION 5
DRYER PART POWER AIR WATER
DECAL A B C D COOLING G H
NUMBER RATINGS CONNECTION CONNECTION
02250193-826 230V/3Ph/60Hz
02250193-907 400V/3Ph/50Hz 34.25” 15.55” 10.4” 14.76”
RC 500 2” NPT-F
02250193-966 460V/3Ph/60Hz 870mm 395mm 255mm 375mm
02250194-124 575V/3Ph/60Hz
02250193-827 230V/3Ph/60Hz
02250193-908 400V/3Ph/50Hz 34.25” 15.55” 11.61” 14.17”
RC700 3” NPT-F AIR COOLED N/A N/A N/A
02250193-967 460V/3Ph/60Hz 870mm 395mm 295mm 360mm
02250194-125 575V/3Ph/60Hz
02250193-828 230V/3Ph/60Hz
02250193-909 400V/3Ph/50Hz 34.25” 15.55” 11.61” 14.17”
RC850 3” NPT-F
02250193-968 460V/3Ph/60Hz 870mm 395mm 295mm 360mm
02250194-126 575V/3Ph/60Hz
02250193-855 230V/3Ph/60Hz
02250193-932 400V/3Ph/50Hz 34.25” 15.55” 10.4” 14.76”
RC 500 2” NPT-F
02250193-997 460V/3Ph/60Hz 870mm 395mm 255mm 375mm
02250194-151 575V/3Ph/60Hz
02250193-856 230V/3Ph/60Hz
02250193-933 400V/3Ph/50Hz 34.25” 15.55” 11.61” 14.17” WATER 4.33” 4.33”
RC700 3” NPT-F 1” NPT-F
02250193-998 460V/3Ph/60Hz 870mm 395mm 295mm 360mm COOLED 110mm 110mm
02250194-152 575V/3Ph/60Hz
02250193-858 230V/3Ph/60Hz
PRINCIPLE OF OPERATION
02250193-934 400V/3Ph/50Hz 34.25” 15.55” 11.61” 14.17”
RC850 3” NPT-F
02250193-999 460V/3Ph/60Hz 870mm 395mm 295mm 360mm
02250194-153 575V/3Ph/60Hz
DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZES WITH PALLET SIZES
RC 500 807 lb 794 lb
29.33”*33.27”*50” 33.85”*48.03”*59.8”
RC 700 847 lb 835 lb
810mm*1165mm*1490mm 860mm*1220mm*1520mm
RC 850 952 lb 941 lb
77
PRINCIPLE OF OPERATION SECTION 5
5.38 ID—RC 1000-1200
02250195-246
78
5.38 ID—RC 1000-1200
SECTION 5
DRYER PART POWER (WATER
DECAL (DEPTH) COOLING C D E
NUMBER RATINGS CONNECTION)
02250193-829 230V/3Ph/60Hz
02250193-910 400V/3Ph/50Hz 31.89”
RC1000
02250193-969 460V/3Ph/60Hz 810mm
02250194-127 575V/3Ph/60Hz
AIR COOLED N/A N/A N/A N/A
02250193-827 230V/3Ph/60Hz
02250193-908 400V/3Ph/50Hz 45.87”
RC1200
02250193-967 460V/3Ph/60Hz 1165mm
02250194-125 575V/3Ph/60Hz
02250193-828 230V/3Ph/60Hz
02250193-909 400V/3Ph/50Hz 31.89” 6.3” 19.29” 25.19”
RC1000
02250193-968 460V/3Ph/60Hz 810mm 160mm 490mm 640mm
02250194-126 575V/3Ph/60Hz WATER
1”NPT-F
02250193-855 230V/3Ph/60Hz COOLED
02250193-932 400V/3Ph/50Hz 45.87” 6.3” 21.25” 29.13”
RC1200
02250193-997 460V/3Ph/60Hz 1165mm 160mm 540mm 740mm
02250194-151 575V/3Ph/60Hz
GROSS
DRYER NET WEIGHT WITHOUT PALLET SIZES WITH PALLET SIZES
WEIGHT
31.89”*45.87”*74.2” 34.64”*48.82”*76.38”
RC1000 1415 lb 1395 lb
810mm*1165mm*1885mm 879mm*1220mm*1940mm
PRINCIPLE OF OPERATION
45.87”*45.87”*74.2” 48.03”*48.03”*76.38”
RC1200 1735 lb 1715 lb
1165mm*1165mm*1885mm 1220mm*1220mm*1940mm
79
PRINCIPLE OF OPERATION SECTION 5
5.39 ID—RC 1600-2000
02250195-248
80
5.39 ID—RC 1600-2000
SECTION 5
DRYER PART POWER (WATER
DECAL COOLING B C
NUMBER RATINGS CONNECTION)
02250193-912 400V/3Ph/50Hz
RC 1600 02250193-971 460V/3Ph/60Hz
02250194-129 575V/3Ph/60Hz AIR
N/A N/A N/A
02250193-913 400V/3Ph/50Hz COOLED
RC2000 02250193-972 460V/3Ph/60Hz
02250194-130 575V/3Ph/60Hz
02250193-937 400V/3Ph/50Hz
RC 1600 02250193-102 460V/3Ph/60Hz
02250194-156 575V/3Ph/60Hz WATER 21.25” 29.13”
1 1/4” NPT-F
02250193-938 400V/3Ph/50Hz COOLED 540mm 740mm
RC2000 02250193-103 460V/3Ph/60Hz
02250194-157 575V/3Ph/60Hz
GROSS
DRYER NET WEIGHT WITHOUT PALLET SIZES WITH PALLET SIZES
WEIGHT
RC1600 2246 lb 2112 lb 45.87”*61.81”*74.8” 50.98”*64.17”*79.53”
RC2000 2712 lb 2403 lb 1165mm*1570mm*1985mm 1295mm*1630mm*2020mm
PRINCIPLE OF OPERATION
81
PRINCIPLE OF OPERATION SECTION 5
5.40 ID—RC 2400-3000
02250195-249
82
5.40 ID—RC 2400-3000
SECTION 5
DRYER PART POWER (WATER
DECAL COOLING B C
NUMBER RATINGS CONNECTION)
02250193-914 400V/3Ph/50Hz
RC2400 02250193-973 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-131 575V/3Ph/60Hz
02250193-939 400V/3Ph/50Hz
WATER 21.25” 29.13”
RC2400 02250193-104 460V/3Ph/60Hz 1 1/4” NPT-F
COOLED 540mm 740mm
02250194-158 575V/3Ph/60Hz
02250193-915 400V/3Ph/50Hz
RC3000 02250193-974 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-132 575V/3Ph/60Hz
02250193-940 400V/3Ph/50Hz
WATER 21.25” 29.13”
RC3000 02250193-105 460V/3Ph/60Hz 1 1/4” NPT-F
COOLED 540mm 740mm
02250194-159 575V/3Ph/60Hz
GROSS
DRYER NET WEIGHT WITHOUT PALLET SIZES WITH PALLET SIZES
WEIGHT
48.23”*78.74”*78.15”*1225mm* 50.98”*81.5”*79.53”
RC2400 2580 lb 2453 lb
2000mm*1985mm 1295mm*2070mm*2020mm
48.23”*86.22”*78.15”*1225mm* 50.98”*92.52”*79.53”
RC3000 2925 lb 2816 lb
2190mm*1985mm 1295mm*2350mm*2020mm
PRINCIPLE OF OPERATION
83
5.41 WIRING DIAGRAM—CONTROL CIRCUIT RC 150 (110/120-1-50/60-A, 208/230-1-50/60-A)
84
PRINCIPLE OF OPERATION
SECTION 5
02250195-313-1
5.41 WIRING DIAGRAM—CONTROL CIRCUIT RC 150 (110/120-1-50/60-A, 208/230-1-50/60-A)
SECTION 5
A01: CONTROL CIRCUIT TRANSFORMER
A10-1: RUNNING LAMP ON CONTROL PANEL (GREEN)
A10-2: REMOTE CONTROL RUNNING LAMP (GREEN)
A10-3: DUAL BUTTON CONTROL LAMP (GREEN)
A11-1: STAND-BY LAMP ON CONTROL PANEL (RED)
A11-2: REMOTE CONTROL STAND-BY LAMP (RED)
A20: DRAIN VALVE
K01: COMPRESSOR RELAY
EMR4: PHASE PROTECTION RELAY
F10: CONTROL CIRCUIT PROTECTION
F11: DRAIN VALVE PROTECTION
F12: FAN PROTECTION
F13: ALARM PROTECTION
K01: COMPRESSOR MOTOR RELAY
K10: FAN MOTOR RELAY
K20: DRAIN TIMER
K30: ALARM RELAY
K30-1: EKONOMIZER RELAY
K40: WATER MOTOR RELAY
RL1: ESD2 CONTACT
RL2: ESD2 ALARM CONTACT
S02-1: START BUTTON ON CONTROL PANEL
PRINCIPLE OF OPERATION
S02-2: REMOTE CONTROL START BUTTON
S03-1: STOP BUTTON ON CONTROL PANEL
S03-2: REMOTE CONTROL STOP BUTTON
S04: REMOTE CONTROL SWITCH
S10: FAN PRESSURE CONTROL
S11: HP-BP SECURITY CONTROL
S20: SECURITY THERMOSTAT
S30-1: FAN PROTECTOR I
S30-2: FAN PROTECTOR II
85
5.42 WIRING DIAGRAM—POWER CIRCUIT RC 150 (110/120-1-50/60-A, 208/230-1-50/60-A)
86
PRINCIPLE OF OPERATION
SECTION 5
02250195-313-2
5.42 WIRING DIAGRAM—POWER CIRCUIT RC 150 (110/120-1-50/60-A, 208/230-1-50/60-A)
SECTION 5
A: RUN WINDING
B: START WINDING
C: MOTOR PROTECTION
A01: CONTROL CIRCUIT TRANSFORMER
B01: MAIN TERMINAL BLOCK
F1: A01 PRIMARY PROTECTION
K01: COMPRESSOR CONTACTOR
K10: FAN CONTACTOR
K40: WATER MOTOR
M01: COMPRESSOR
M10: FAN MOTOR
M40: WATER MOTOR
S01: MAIN SWITCH
PRINCIPLE OF OPERATION
87
5.43 WIRING DIAGRAM—CONTROL CIRCUIT RC 200 (208/230-1-50/60-A)
88
PRINCIPLE OF OPERATION
SECTION 5
02250195-315-1
5.43 WIRING DIAGRAM—CONTROL CIRCUIT RC 200 (208/230-1-50/60-A)
SECTION 5
A01: CONTROL CIRCUIT TRANSFORMER
A10-1: RUNNING LAMP ON CONTROL PANEL (GREEN)
A10-2: REMOTE CONTROL RUNNING LAMP (GREEN)
A10-3: DUAL BUTTON CONTROL LAMP (GREEN)
A11-1: STAND-BY LAMP ON CONTROL PANEL (RED)
A11-2: REMOTE CONTROL STAND-BY LAMP (RED)
A20: DRAIN VALVE
K01: COMPRESSOR RELAY
EMR4: PHASE PROTECTION RELAY
F10: CONTROL CIRCUIT PROTECTION
F11: DRAIN VALVE PROTECTION
F12: FAN PROTECTION
F13: ALARM PROTECTION
K01: COMPRESSOR MOTOR RELAY
K10: FAN MOTOR RELAY
K20: DRAIN TIMER
K30: ALARM RELAY
K30-1: EKONOMIZER RELAY
K40: WATER MOTOR RELAY
RL1: ESD2 CONTACT
RL2: ESD2 ALARM CONTACT
S02-1: START BUTTON ON CONTROL PANEL
PRINCIPLE OF OPERATION
S02-2: REMOTE CONTROL START BUTTON
S03-1: STOP BUTTON ON CONTROL PANEL
S03-2: REMOTE CONTROL STOP BUTTON
S04: REMOTE CONTROL SWITCH
S10: FAN PRESSURE CONTROL
S11: HP-BP SECURITY CONTROL
S20: SECURITY THERMOSTAT
S30-1: FAN PROTECTOR I
S30-2: FAN PROTECTOR II
89
5.44 WIRING DIAGRAM—POWER CIRCUIT RC 200 (208/230-1-50/60-A)
90
PRINCIPLE OF OPERATION
SECTION 5
02250195-315-2
5.44 WIRING DIAGRAM—POWER CIRCUIT RC 200 (208/230-1-50/60-A)
SECTION 5
A: RUN WINDING
B: START WINDING
C: MOTOR PROTECTION
A01: CONTROL CIRCUIT TRANSFORMER
B01: MAIN TERMINAL BLOCK
F1: A01 PRIMARY PROTECTION
K01: COMPRESSOR CONTACTOR
K10: FAN CONTACTOR
K40: WATER MOTOR
M01: COMPRESSOR
M10: FAN MOTOR
M40: WATER MOTOR
S01: MAIN SWITCH
1: FAN MOTOR (BROWN)
2: FAN MOTOR (GRAY)
3: FAN MOTOR (BLACK)
PRINCIPLE OF OPERATION
91
5.45 WIRING DIAGRAM—CONTROL CIRCUIT RC 250 (208/230-1-50/60-A)
92
PRINCIPLE OF OPERATION
SECTION 5
02250195-316-1
5.45 WIRING DIAGRAM—CONTROL CIRCUIT RC 250 (208/230-1-50/60-A)
SECTION 5
A01: CONTROL CIRCUIT TRANSFORMER
A10-1: RUNNING LAMP ON CONTROL PANEL (GREEN)
A10-2: REMOTE CONTROL RUNNING LAMP (GREEN)
A10-3: DUAL BUTTON CONTROL LAMP (GREEN)
A11-1: STAND-BY LAMP ON CONTROL PANEL (RED)
A11-2: REMOTE CONTROL STAND-BY LAMP (RED)
A20: DRAIN VALVE
K01: COMPRESSOR RELAY
EMR4: PHASE PROTECTION RELAY
F10: CONTROL CIRCUIT PROTECTION
F11: DRAIN VALVE PROTECTION
F12: FAN PROTECTION
F13: ALARM PROTECTION
K01: COMPRESSOR MOTOR RELAY
K10: FAN MOTOR RELAY
K20: DRAIN TIMER
K30: ALARM RELAY
K30-1: EKONOMIZER RELAY
K40: WATER MOTOR RELAY
RL1: ESD2 CONTACT
RL2: ESD2 ALARM CONTACT
S02-1: START BUTTON ON CONTROL PANEL
PRINCIPLE OF OPERATION
S02-2: REMOTE CONTROL START BUTTON
S03-1: STOP BUTTON ON CONTROL PANEL
S03-2: REMOTE CONTROL STOP BUTTON
S04: REMOTE CONTROL SWITCH
S10: FAN PRESSURE CONTROL
S11: HP-BP SECURITY CONTROL
S20: SECURITY THERMOSTAT
S30-1: FAN PROTECTOR I
S30-2: FAN PROTECTOR II
93
5.46 WIRING DIAGRAM—POWER CIRCUIT RC 250 (208/230-1-50/60-A)
94
PRINCIPLE OF OPERATION
SECTION 5
02250195-316-2
5.46 WIRING DIAGRAM—POWER CIRCUIT RC 250 (208/230-1-50/60-A)
SECTION 5
A: RUN WINDING
B: START WINDING
C: MOTOR PROTECTION
A01: CONTROL CIRCUIT TRANSFORMER
A30: COMPRESSOR CRANCASE HEATER
B01: MAIN TERMINAL BLOCK
F1: A01 PRIMARY PROTECTION
K01: COMPRESSOR CONTACTOR
K10: FAN CONTACTOR
K40: WATER MOTOR
M01: COMPRESSOR
M10: FAN MOTOR
M40: WATER MOTOR
S01: MAIN SWITCH
1: FAN MOTOR (BROWN)
2: FAN MOTOR (GRAY)
3: FAN MOTOR (BLACK)
PRINCIPLE OF OPERATION
95
5.47 WIRING DIAGRAM—CONTROL CIRCUIT RC 250/3000 (230-3-50/60-A, 400/460-3-50/60-A)
96
PRINCIPLE OF OPERATION
SECTION 5
02250195-317-1
5.47 WIRING DIAGRAM—CONTROL CIRCUIT RC 250/3000 (230-3-50/60-A, 400/460-3-50/60-A)
SECTION 5
A01: CONTROL CIRCUIT TRANSFORMER S10-2: FAN PRESSURE CONTROL 2
A10-1: RUNNING LAMP ON CONTROL PANEL (GREEN) S11: HP-LP SECURITY CONTROL
A10-2: REMOTE CONTROL RUNNING LAMP (GREEN) S20: SECURITY THERMOSTAT
A10-3: DUAL BUTTON CONTROL LAMP (GREEN) S30-1: FAN PROTECTOR I
A11-1: STAND-BY LAMP ON CONTROL PANEL (RED) S30-2: FAN PROTECTOR II
A11-2: REMOTE CONTROL STAND-BY LAMP (RED)
A20: DRAIN VALVE
K01: FREE OF POTENTIAL CONTACT ON RELAY
EMR4: PHASE PROTECTION RELAY
F10: CONTROL CIRCUIT PROTECTION
F11: DRAIN VALVE PROTECTION
F12: FAN PROTECTION
F13: ALARM PROTECTION
K01: COMPRESSOR MOTOR RELAY
K10-1: FAN MOTOR RELAY 1
K10-2: FAN MOTOR RELAY 2
K20: TIMER DRAIN
K40: WATER POMP RELAY
K30: ALARM RELAY
K30-1: EKONOMIZER RELAY
P01: THERMAL PROTECTION OF COMPRESSOR
P10-1: THERMAL PROTECTION OF FAN 1
PRINCIPLE OF OPERATION
P10-2: THERMAL PROTECTION OF FAN 2
RL1: ESD2 CONTACT
RL2: ESD2 ALARM CONTACT
S02-1: START BUTTON ON CONTROL PANEL
S02-2: REMOTE CONTROL START BUTTON
S03-1: STOP BUTTON ON CONTROL PANEL
S03-2: REMOTE CONTROL STOP BUTTON
S04: REMOTE CONTROL SWITCH
S10-1: FAN PRESSURE CONTROL 1
97
5.48 WIRING DIAGRAM—POWER CIRCUIT RC 250/3000 (230-3-50/60-A, 400/460-3-50/60-A)
98
PRINCIPLE OF OPERATION
SECTION 5
02250195-317-2
5.48 WIRING DIAGRAM—POWER CIRCUIT RC 250/3000 (230-3-50/60-A, 400/460-3-50/60-A)
SECTION 5
A01-1: CONTROL CIRCUIT TRANSFORMER
A30-1/A30-2: COMPRESSOR CHANKASER HEATERS
B01: MAIN TERMINAL BLOCK
EMR4: PHASE PROTECTION RELAY
F1,F2: A01 PRIMARY PROTECTION
K01: COMPRESSOR CONTACTOR (24V)
K10-1: FAN CONTACTOR1 (24V)
K10-2: FAN CONTACTOR2 (24V)
K40: WATER MOTOR
M01-1/M01-2: COMPRESSORS (400V-440V)
M10-1: FAN MOTOR1 (400V-440V)
M10-2: FAN MOTOR2 (400V-440V)
P01: THERMAL PROTECTION OF
P10-1: OVER LOAD PROTECTOR 1
P10-2: OVER LOAD PROTECTOR 2
P40: WATER MOTOR PROTECTION
S01: MAIN SWITCH
PRINCIPLE OF OPERATION
99
5.49 WIRING DIAGRAM—RC 150-250 (115/220/1 50/60 AC)
100
PRINCIPLE OF OPERATION
SECTION 5
02250195-299 R00
5.49 WIRING DIAGRAM—RC 150-250 (115/220/1 50/60 AC)
SECTION 5
P Compressor overload protection
AL Alarm contact
PRINCIPLE OF OPERATION
A40-2 Compressor start capacitor
PT Thermostatic sensor
PRINCIPLE OF OPERATION
SECTION 5
02250195-300 R00-1
5.50 WIRING DIAGRAM—RC 250-400 (230/3 60 AC)
SECTION 5
A01 control circuit transformer
M01 compressors
PRINCIPLE OF OPERATION
P04 water motor protection
PRINCIPLE OF OPERATION
SECTION 5
02250195-300 R00-2
5.51 WIRING DIAGRAM—RC 250-400 (230/3 60 AC)
SECTION 5
F10 control circuit protection ZR1 timer relay
PRINCIPLE OF OPERATION
S30 fan protector
AL alarm contact
5.52 WIRING DIAGRAM—RC 250-400 (400/460/575/3 50/60 AC)
106
PRINCIPLE OF OPERATION
SECTION 5
02250195-969 R00-1
5.52 WIRING DIAGRAM—RC 250-400 (400/460/575/3 50/60 AC)
SECTION 5
A01 control circuit transformer
M01 compressors
PRINCIPLE OF OPERATION
P04 water motor protection
PRINCIPLE OF OPERATION
SECTION 5
02250195-969 R00-2
5.53 WIRING DIAGRAM—RC 250-400 (400/460/575/3 50/60 AC)
SECTION 5
F10 control circuit protection ZR1 timer relay
PRINCIPLE OF OPERATION
S30 fan protector
AL alarm contact
5.54 WIRING DIAGRAM—RC (500-1000) 230/60 AC
110
PRINCIPLE OF OPERATION
SECTION 5
02250195-968-1
5.54 WIRING DIAGRAM—RC (500-1000) 230/60 AC
SECTION 5
A01 control circuit transformer
M01 compressors
PRINCIPLE OF OPERATION
P01 thermal protection of compressor
PRINCIPLE OF OPERATION
SECTION 5
02250195-968 R00-2
5.55 WIRING DIAGRAM—RC (500/700/850/1000/1200/1600/2000/2400/3000) 460-3-60-A, 400-3-60-A
SECTION 5
F10 control circuit protection A20 drain timer supply
PRINCIPLE OF OPERATION
S15 water low pressure switch
PRINCIPLE OF OPERATION
SECTION 5
02250195-301 R00-1
5.56 WIRING DIAGRAM—RC 500-3000 (400/460/575/3 50/60 AC)
SECTION 5
A01 control circuit transformer
M01 compressors
PRINCIPLE OF OPERATION
P04 water motor protection
PRINCIPLE OF OPERATION
SECTION 5
02250195-301 R00-2
5.57 WIRING DIAGRAM—RC 500-3000 (400/460/575/3 50/60 AC)
SECTION 5
F10 control circuit protection A11-2 remote control stand-by lamp (red)
P04 thermal protection of water motor TH indiates high temperature in the circuit
PRINCIPLE OF OPERATION
S15 water low pressure switch
PRINCIPLE OF OPERATION
SECTION 5
02250195-971 R00-1
5.58 WIRING DIAGRAM—RC 700-3000 (400/460/575/3 50/60 AC)
SECTION 5
A01 control circuit transformer
M01 compressors
PRINCIPLE OF OPERATION
119
5.59 WIRING DIAGRAM—RC RC 700-3000 (400/460/575/3 50/60 AC)
120
PRINCIPLE OF OPERATION
SECTION 5
02250195-971 R00-2
5.59 WIRING DIAGRAM—RC 700-3000 (400/460/575/3 50/60 AC)
SECTION 5
F10 control circuit protection HP indicates high pressure
PRINCIPLE OF OPERATION
A11-1 stand-by lamp on control panel (red)
AL alarm contact
setting.
Press and buttons at the same time.
122
MAINTENANCE
Section 6
MAINTENANCE
6.1 MAINTENANCE BY AN 6.2 MAINTENANCE BY THE
ENGINEER/TECHNICIAN USER
1. Maintenance and repairs should only be per- 1. Keep the dryer clean.
formed when the air dryer is shut down and
2. In the case of dryers that contain more than
depressurized and when the main power
4 pounds of refrigerant, the dryer should be
switch is turned OFF.
regularly checked to be leak free by qualified
2. Use only the appropriate tools for mainte- refrigerant engineer. Refer to section “Envi-
nance and repair. ronmental protection” of this manual.
3. Before dismantling any part that has been 3. Every month - clean the air condenser with a
pressurized, disconnect the pressure brush or compressed air as soon as it’s dirty
sources and depressurize the system com- or clogged. Take extra care not to bend the
pletely. Shut off all valves and isolate the fins of the condenser heat exchanger. Do not
dryer. use wire brushes as these may bend the
fins, causing leaks.
4. Proceed carefully during maintenance and
repair. Prevent dirt from entering by covering 4. Every six months - check the correct opera-
parts and orifices with a clean cloth, paper or tion of the condenser drain trap. Replace
tape. timer or solenoid valve in case of clogging or
malfunctioning.
5. Receiver tanks should never be welded or
modified in any way. 5. Every six months - check and clean the drain
strainer by undoing the access screw and
6. Never leave tools, loose parts or cleaning
rinsing the filter with tap water to remove the
rags in or on the air dryer.
trapped dirt from the inside.
7. Before connecting the dryer back online,
6. Check the troubleshooting list in case of
check the setting of the control and safety
maintenance issues.
devices as well as the pressure and the tem-
perature of the compressed air circuit. 7. Check operating pressures, temperatures
and time settings after maintenance. If oper-
8. For dryers with water-cooled condensers -
ating and safety devices function properly,
End caps of water condenser can be disas-
the air dryer may be used.
sembled for cleaning with help of a water jet.
8. For water-cooled condensers - Use only
clean water when cleaning the condenser.
Water should be jet-streamed from the outlet
side to the inlet side.
123
MAINTENANCE SECTION 6
Semi-
Recommended Maintenance Activity Weekly Monthly Annual
Annual
Drain control X
124
NOTES
125
6.4 REPLACEMENT PARTS
126
MAINTENANCE
Component Name RC-0150-115-1-60-A RC-0150-220-1-50-A RC-0150-230-1-60-A RC-0175-220-1-50-A RC-0175-230-1-60-A
SECTION 6
Fan Overload Protector M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000
MAINTENANCE
Cabinette Horizontal profile 1 M-HP1-0200-C M-HP1-0200-C M-HP1-0200-C M-HP1-0200-C M-HP1-0200-C
MAINTENANCE
Component Name RC-0200-220-1-50-A RC-0200-230-1-60-A RC-0250-220-1-50-A RC-0250-230-3-60-A RC-0250-400-3-50-A
SECTION 6
Compressor Overload Protector M-COP-0200-220-1-50-A M-COP-0200-230-1-60-A M-COP-250-220-1-50-A M-COP-250-230-3-60-A M-COP-250-460-3-60-A
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0200-C M-HP2-0200-C M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C
129
130
MAINTENANCE
Component Name RC-0250-460-3-60-A RC-0250-575-3-60-A RC-0325-230-3-60-A RC-0325-400-3-50-A RC-0325-460-3-60-A
SECTION 6
Compressor Overload Protector M-COP-250-460-3-60-A M-COP-250--5753-60-A M-COP-325-230-3-60-A M-COP-325-400-3-50-A M-COP-325-460-3-60-A
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C
131
132
MAINTENANCE
Component Name RC-0400-230-3-60-A RC-0400-400-3-50-A RC-0400-460-3-60-A RC-0400-575-3-60-A RC-0500-230-3-60-A
SECTION 6
Compressor Overload Protector M-COP-400-230-3-60-A M-COP-400-400-3-50-A M-COP-400-460-3-60-A M-COP-400-575-3-60-A M-COP-500-230-3-60-A
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C M-HP2-0400-C M-HP2-0500-C
133
134
MAINTENANCE
Component Name RC-0500-400-3-50-A RC-0500-460-3-60-A RC-0500-575-3-60-A RC-0700-230-3-60-A RC-0700-400-3-50-A
SECTION 6
Fan Overload Protector M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0500-C M-HP2-0500-C M-HP2-0500-C M-HP2-0700-C M-HP2-0700-C
135
136
MAINTENANCE
Component Name RC-0700-460-3-60-A RC-0700-575-3-60-A RC-0850-230-3-60-A RC-0850-400-3-50-A RC-0850-460-3-60-A
SECTION 6
Fan Overload Protector M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0700-C M-HP2-0700-C M-HP2-0850-C M-HP2-0850-C M-HP2-0850-C
137
138
MAINTENANCE
Component Name RC-0700-460-3-60-A RC-0700-575-3-60-A RC-0850-230-3-60-A RC-0850-400-3-50-A RC-0850-460-3-60-A
SECTION 6
Compressor Overload Protector M-COP-700-460-3-60-A M-COP-700-575-3-60-A BELLİ DEĞİL M-COP-1000-400-3-50-A M-COP-1000-460-3-60-A
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0700-C M-HP2-0700-C M-HP2-0850-C M-HP2-0850-C M-HP2-0850-C
139
140
MAINTENANCE
Component Name RC-0850-575-3-60-A RC-1000-230-3-60-A RC-1000-400-3-50-A RC-1000-460-3-60-A RC-1000-575-3-60-A
SECTION 6
Fan Overload Protector M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000 M-FOP-3000
MAINTENANCE
Cabinette Horizontal profile 2 M-HP2-0850-C M-HP2-1000-C M-HP2-1000-C M-HP2-1000-C M-HP2-1000-C
141
NOTES
142
TROUBLESHOOTING
Section 7
TROUBLESHOOTING
7.1 TROUBLESHOOTING TABLES
Dryer is switched ON, 3-phase dryers: The Invert two phases 3-phase dryers are equipped
indicator light is lit but the connection has inverted with a phase controller to avoid
refrigerant compressor phases the fans from turning in the
does on turn ON (Dryer is opposite direction.
not functioning)
Refrigeration unit is not Check refrigeration Several factors can cause
functioning compressor compressor failure. A qualified
refrigeration technician needs to
check all the electrical and
refrigerant circuit and controls.
The refrigerant high The refrigerant safety The dryer is protected against
pressure protection has high pressure switch has excessively high refrigerant
tripped tripped. pressure. If the condenser
efficiency has reduced, the
switch will trip.
143
TROUBLESHOOTING SECTION 7
Dryer is switched ON, Excessive ambient Be sure that dryer is A high ambient temperature
indicator light is lit but the temperature working in temperatures may cause the refrigerant
refrigerant compressor lower than the design system to operate at higher than
does on turn ON (Dryer is conditions. Designed normal pressures. Results will
not functioning) conditions and correction be higher than normal
factors are described in evaporator temperature.
this manual . Important: adequate air
circulation around the dryer, and
proper ventilation in the
equipment room should
guarantee a low enough
ambient temperature.
Excessive compresser air Be sure that dryer is The dryer is designed for
inlet temperature. working in temperatures working into calculated
at or below design conditions (see description in
conditions. this manual). If conditions are
exceeded, the dryer will be
overflowed, dew point will go up
and protecting devices can
switch off.
144
SECTION 7 TROUBLESHOOTING
Dryer is switched ON, Clogged condenser fins Clear fins or water The clogged fins in the
indicator light is lit but the or clogged water condenser of all condenser will restrict the air
refrigerant compressor condenser. obstructions. passage and reduce the
does on turn ON (Dryer is refrigeration capacity,” causing
not functioning) Possible high crankcase high temperature in the
temperature evaporator. Same will occur if
water condenser is clogged with
Possible loss of phase
mud or dirt. Air condenser and
Possible low voltage water condenser should be
causing overload trip periodically checked and
cleaned. Protect water circuit by
Possible failed an adapted filter.
compressor
Too much compressed air Check actual flow through This dryer is designed for a
flow. the dryer. maximum air flow at design
conditions. If too much air is
pumped into the dryer, water
removal capacity may not be
sufficient, resulting in liquid
carryover downstream. Check
the rated output the air
compressor.
Faulty electrical wiring Inspect the circuit The compressor-on light should
be wired into the refrigerant
compressor circuit. See wiring
diagram in chapter “Drawings”
of this manual.
One electrical protection Reset the protection or The dryer is protected against
has tripped. replace the blown fuse. high amp draw by fuse and/or
overload relay that can trip in
case of need. Reset or replace
fuse once, but do not persist if it
trips again, request assistance
from a qualified refrigeration
contractor.
Dryer-on light is lit but fan Fan has to run if Check that compressed Fan operates automatically to
is not running. refrigerant high pressure air flows through the keep refrigerant pressure below
reaches upper set point. dryer. Check that fan the maximum value. The fan
blades are free to move. can stop if pressure is under the
recommended setting.
Check the fan pressure
switch.
When compressor starts, Compressor is slugging Be sure the pre-heating Refrigerant may move between
it vibrates a lot and liquid refrigerant at start- period of at least 4 hours receivers when refrigerant
makes mechanical noise. up. is respected for dryers compressor is stopped and not
equipped with a heated, especially if stopped for
crankcase heater. a long time. This migration may
cause liquid shock (slugging) in
valves specially on large dryers
containing more refrigerant.
145
TROUBLESHOOTING SECTION 7
Water downstream Inlet and outlet Check inlet and outlet This dryer is designed for air
connections are reversed. connections. flow in one direction only. Inlet
(compressed air?) and outlet directions are
identified on the dryer.
Drain system is clogged Restore a free flow of Drain system may be a timed
or inoperative. water condensate. Check solenoid valve, pneumatically
water evacuation. assisted or zero loss drain
which has to be adjusted in
accordance with values listed in
this the maintenance manual.
The Solenoid valve includes a
strainer that has to be
periodically checked and
cleaned. Membranes of
pneumatically assisted drain
have to be checked or replaced
every 6 months. Sullair zero
loss drain has to be cleaned
with soft water when needed.
Bypass system is open Check the valves Important: Bypass piping should
be installed around the dryer so
the dryer can be isolated for
service without shutting down
the air supply. During dryer
operation, valves must be set so
all air goes into the system.
Check tightness of the bypass
system.
Free moisture remains in Blow out the system Before the dryer is first started
pipe lines. all free moisture should be
blown out of the system.
Excessive air flow Check actual flow through This dryer is designed for a
the dryer. maximum air flow. If too much
air is pumped into the dryer,
water removal capacity may not
be sufficient, resulting in liquid
Carry-over downstream. Check
the rated flow of the air
compressor.
Excessive free moisture Check the separator and In some system there may be
drain system and an accumulation of free
compressor after cooler moisture in the line ahead of the
ahead of the dryer. dryer. If this moisture is pumped
into the dryer intermittently, the
water removal capacity may not
be sufficient. A water separator
should be installed in the line
before the dryer.
146
SECTION 7 TROUBLESHOOTING
Water downstream Excessive compressed Be sure that dryer is The dryer is designed for
air inlet temperature. working lower than working into calculated design
design conditions conditions. Should the
conditions be exceeded, the
dryer will be overflowed, dew
point will go up and protecting
devices can switch off.
Clogged condenser fins Clear fins of all The clogged fins in the
obstructions condenser will restrict air
passage and reduce refrigerant
capacity causing water
downstream. Fins should be
periodically checked and
cleaned.
Shortage of refrigerant Fix the leak and add a Loss of refrigerant will cause
charge of refrigerant. improper functioning. A
qualified, refrigeration specialist
should perform the necessary
repairs, or factory should be
contacted if the units is in
warranty.
147
TROUBLESHOOTING SECTION 7
High pressure drop Excessive compressed Check actual pressure This dryer is designed for a
air flow or too low air inlet and flow through the maximum air flow. If too much
pressure. dryer. air is pumped into the dryer,
water removal capacity may not
be sufficient, resulting in liquid
carry-over downstream. Check
the rated flow of the air
compressor.
Inlet pre-filter clogged Replace the element Dryers with 2 or more heat
exchangers are equipped with a
25 micron, protective pre-filter.
Check it regularly and replace
when pressure drop is too high.
Contact your Sullair Distributor
for spares.
Clogged heat exchanger Clean heat exchanger Dryer are supposed to be used
with a reverse air flow. with compressed air free of any
aggressive contaminants. Some
contamination may require extra
maintenance of the heat
exchanger. Contact your Sullair
Distributor.
148
SECTION 7 TROUBLESHOOTING
The unit will not run or Line disconnect switch is Close the start or If the dryer is not operating,
cycles off and on. open. disconnect switch check the disconnect switch or
circuit breaker to be certain it is
on.
Fuse or breaker is open Replace fuse or reset The fuse to the power line
breaker. should be checked and
replaced if needed. Never
replace a buRCt fuse with an
oversized fuse.
149
TROUBLESHOOTING SECTION 7
The unit will not run or Excessive compressed Design conditions and The dryer is designed for
cycles off and on. air inlet temperature. correction factors are working into calculated design
described in this manual conditions. Should the
Be sure that dryer is conditions be exceeded, the
working in ambient dryer will be overflowed, dew
temperatures below point will go up and protecting
design conditions. devices may trip.
Clogged condenser fins Clear fins of all The clogged fins in the
obstructions condenser will restrict the air
passage and reduce the
refrigeration capacity, causing
high temperature in the
evaporator. Fins should be
periodically checked and
cleaned.
Shortage of refrigerant Fix the leak and add a Loss of refrigerant will cause
charge of refrigerant. improper functioning. 3-phase
dryers are equipped with a
temperature switch which
maintains the amount of
refrigerant to maintain proper
cooling of the compressor. A
shortage of refrigerant may
cause suction line to become
very hot, causing the
temperature switch to trip. A
qualified refrigeration specialist
should perform the necessary
repairs, or the factory should be
contacted if the unit is in
warranty.
Err sign occurs on digital The dew point is too low Check refrigerant gas and If there is not enough refrigerant
temperature control or too high. make sure that the gas or if the working
device working conditions are temperature and inlet
within the correct range. temperatures are very high, the
dew point will increase.
150
HORIZONTAL CLOSE COUPLED PUMP
Section 8
HORIZONTAL CLOSE COUPLED PUMP
8.1 GENERAL INSTRUCTIONS the pump upon receipt. If units are flushed out prior
to storage, this inhibitor will be removed and proper
CENTRIFUGAL PUMPS care must be taken to prevent product deterioration
from improper storage.
1. Inspection of Equipment
For storage beyond 30 days, a corrosion inhibiting
2. Storage
protective fluid should be added to the internal pump
3. Placing Stored Pumps Into Service cavities. Fluids used in the pump should be selected
for compatibility with pump materials. This is very
4. Recommended Spare Parts
important when optional seal and gasket materials
When properly installed and given reasonable care have been used. Protective caps on the inlet and
and maintenance, centrifugal pumps should operate outlets should also be used. Caps alone are not
satisfactorily for many years. The C Series pumps sufficient protection.
use tight running clearances to build pressure.
Abrasive particles in high enough concentrations, 8.1.3 APPLICATION CONSIDERATIONS
can eventually open up the close clearances ELECTRICAL WIRING
between the impeller and the casing, thus reducing
pressure output. To avoid this, careful selection and All electrical equipment and wiring should conform to
use of a low resistance suction strainer should be Local and National Electrical Codes. Use the motor
considered. For critical services it is recommended manufacturer’s instructions for connecting the motor.
that you keep an identical pump for stand-by use. Note the correct rotation and wiring diagrams on the
assembly. Make sure the motor rotation and speed
8.1.1 INSPECTION OF EQUIPMENT matches that required for the pump. When making
electrical connections to motors provided with
Immediately upon receipt of the shipment, inspect
threaded stud electrical terminals, the recommended
the equipment for damage or missing components.
torque should be 13-16 inch-lbs. Applying torque in
Check the shipping manifest and report any damage
excess of this range may cause damage.
or shortage to the transportation company’s local
agent. Inspect the crate and any wrapping material CONSTRUCTION MATERIALS
before discarding. Parts or accessories are
While it is reasonable to assume that good
sometimes wrapped individually or fastened to the
judgement has been used in selecting all the
skid.
materials in the pump for compatibility with process
Put the instructions that came with the shipment in a fluids, actual conditions sometimes vary from original
safe place where they will be available to those who expectations. Also, typical material selection charts
will be using them for installation and service. do not consider all the temperature, pressure, and
fluid variables. The customer’s engineer should be
8.1.2 STORAGE consulted for final judgement on the best materials
If the pump is to be stored before use, it should be for critical process applications.
inspected as described in Section 8.1.1, recrated and VALVES
stored in a dry location. Standard shipping containers
are not suitable for outdoor storage. In some areas, it If a shutoff valve is necessary in the suction line, use
may be necessary to cover the pump’s exterior a gate, ball, butterfly, or other full port valve. Globe or
surface with oil or other rust inhibiting coating. All other flow restricting valves, can in some cases,
units are tested at the factory with a water/corrosion reduce pump flow or increase chances of cavitation.
inhibitor solution, some of which will remain inside A swing check valve in the suction line is
151
HORIZONTAL CLOSE COUPLED PUMP SECTION 8
recommended even when the pump inlet is only Pvp = Vapor pressure of the pumped fluid in PSIA.
slightly higher than the fluid source to aid in priming.
It should be the same size as the pump inlet or sized Hs = Static height of the pumped fluid above (+) or
based on reasonable fluid friction losses. below (-) the centerline of the pump.
A foot valve is recommended when lifting fluid from a Hf = All friction losses from the vessel to the pump.
sump. This will save wear and tear on any pump,
even those equipped with self priming equipment. P s – P vp
NPSH = 2.31 ------------------- + H s – H f
SPGR
A low resistance Suction Strainer is recommended
immediately ahead of the pump on any newly
constructed system. This is advisable due to the For boiling liquids, Ps and Pvp are equal. This item
probability that foreign material large enough to then becomes zero and can be omitted from the
damage pump clearances may remain, even though equation.
the piping has been flushed. NOISE
Valves in the outlet piping of a centrifugal pump Motors, bearings, and other rotating components add
should be closed, or nearly closed, when the pump is to noise, which sometimes create objectionable
started. This will reduce the start-up load on the harmonics.
pump and motor. Never start the pump with the
discharge valve fully open, unless system friction Careful pump installation can contribute to noise
losses are substantial enough to prevent the pump reduction. Proper alignment of the pump and driver is
from operating at “maximum flow,” otherwise essential. Adequate supports for the inlet and
cavitation or motor overload may occur. discharge piping is equally important. A degree of
noise reduction may be obtained when the pumping
Inlet valving should be fully open when starting any unit is supported free of building structures by the
pumping system. Without some fluid in the pump at use of vibration isolators, flexible piping and conduit
startup, the unit can gall and lock up the impeller. connections. To separate motor noise and vibration
Always fill the pump and vent it of air for best pump from the fluid and piping structure, using a flexible
life. Violent pump failure will result from continued elastomer-coupled (long coupled) configuration is
operation with the inlet valve closed. very desirable.
NPSH (NET POSITIVE SUCTION HEAD) FREEZING
The NPSH required varies with every size and When ambient temperatures drop below the freezing
capacity of pump. The NPSH required by your unit point of the fluid, consideration should be given to
can be obtained from the performance curves or from heating, insulating, or draining the pump. If you
your MTH representative. choose to drain the pump, first remove the drain
If the NPSH available is not equal to or greater than plugs and drain the suction and discharge lines.
that required by the pump, it must be increased or a Carefully blow out the pump with compressed air to
different pump selected. The usual method for clear all internal cavities of fluid.
increasing NPSH is to raise the static head on the 8.1.4 RECOMMENDED SPARE PARTS
pump inlet, (HS). By definition, NPSH means: “Net
Positive Suction Head” above the vapor pressure of FOR ROUTINE MAINTENANCE:
the pumped liquid, available at the centerline of the
Only a complete set of “O” ring gaskets and a
pump. It should always be given in feet of pumped
mechanical seal are recommended. Should
liquid. The NPSH is actually a measurement of the
additional components show wear, they are available
amount of energy available in the pumped liquid to
from stock at the factory (see the C Series price
produce the required absolute entrance velocity in
brochure).
the pump. If a pump requires more energy (or NPSH)
than is available at a given capacity, the pressure at FOR SERVICING A PUMP THAT DOES NOT
the inlet will fall below the vapor pressure of the PRODUCE RATED CAPACITY OR HEAD :
pumped liquid and fluid vaporization and loss of
“O” ring gaskets, impeller, mechanical seal, and
performance will result.
pump casing.
Ps = Pressure in the suction vessel in PSIA.
152
SECTION 8 HORIZONTAL CLOSE COUPLED PUMP
153
HORIZONTAL CLOSE COUPLED PUMP SECTION 8
The following tools and equipment are needed for 6. Penetrating oil.
disassembly. 7. 3/4”/ 19 mm wood dowel (Approx. 6”/
1. Soft plastic or wooden mallet. 152mm long).
154
SECTION 8 HORIZONTAL CLOSE COUPLED PUMP
155
HORIZONTAL CLOSE COUPLED PUMP SECTION 8
1. The seal seat (#125) must be installed in the Make sure the snap ring is locked in the
motor bracket before the bracket is installed groove.
on the motor.
4. Install the impeller (#11).
To install the seat: a. Place the key (#23) in the shaft sleeve.
a. Place the motor bracket face up on a flat sur- b. The impeller should slide on firmly, but eas-
face. ily, until it stops. Force should not be required
to install the impeller in the correct position.
b. Carefully press the seat, smooth side up,
into the seat cavity of the motor bracket. To c. The impeller hub should be facing toward the
make the installation of the seat easier, apply motor.
a very thin coating of compatible seal lubri-
d. Fasten the impeller using the washer (#41)
cant to the elastomer portion of the seat prior
and screw(#19). Tighten the screw securely
to installation. Care must be taken not to
(do not exceed 7 ft-lbs / 4.7m-kg of torque),
damage the seat face. Thumb pressure is
while holding the impeller stationary. The
usually sufficient to install the seat. Make
impeller should not have any play or wob-
sure the seat is installed firmly and squarely
ble.
and that it is then carefully cleaned.
5. Install the casing (#108).
2. Install the motor bracket (#84).
a. Hand tighten four (4) studs (#5) into the cas-
a. This is best done with the motor standing on
ing until they are seated.
end.
b. Lubricate and install the casing “O”-ring (#7)
b. From the motor side: If removed during dis-
onto the first step in the motor bracket.
assembly, thread the four (4) adjusting
screws (#33) into the mounting flanges of the c. Place the casing over the motor bracket
motor bracket until they are flush with the being careful not to pinch the “O”-ring. The
front faces of the flanges. casing discharge should be oriented to meet
system requirements.
c. Slide the four (4) small “O”-rings (#8) fully
onto the socket head screws (#33A). d. Loosely thread four (4) jam nuts (#20) onto
the casing studs.
d. Place the motor bracket (#84) on the motor.
Slide the bracket back until the feet are rest- 6. Adjusting Impeller/Casing Clearance
ing against the motor face. The orientation of
a. Seat the casing down against the impeller
the motor bracket is not critical unless a flush
with light hand pressure.
line is used. In that case, align the flush line
to meet system requirements. b. Turn the adjusting screws until they just
touch the back face of the casing. The cas-
e. Insert the four (4) socket head screws
ing should not move during this adjustment.
(#33A) into the motor bracket holes and
This will determine the zero clearance posi-
thread into the motor face. Tighten securely
tion. Set the minimum free running clearance
using a 5 mm allen wrench. Do not exceed 7
as follows:
ft-lbs (4.7 m/kg) of torque or damage to the
motor “C”-face may occur. 1. Viewing from the back of the motor
bracket, (rear of motor) turn each
3. Install rotating element (#12). adjusting screw clockwise exactly 30° (1/
a. Tip the pump assembly over into a horizontal 12 of a full revolution).
position on the work area. 2. Securely tighten the four (4) jam nuts
against the adjusting nuts using a 9/16”/
b. Lightly lubricate the motor shaft. Push the 14mm wrench and a 5/8”/16mm wrench,
rotating element, spring, and then spring being careful to prevent the adjusting
holder over the shaft. Prepare the snap ring nuts from turning.
in the snap ring pliers and then compress c. Turn the impeller clockwise and listen for any
and hold the seal spring slightly below the scraping noises or interference. This may be
snap ring groove. Install the snap ring (#4). done by turning the impeller screw with a 10
156
SECTION 8 HORIZONTAL CLOSE COUPLED PUMP
157
HORIZONTAL CLOSE COUPLED PUMP SECTION 8
158
NOTES
Always air. Always there.
WWW.SULLAIR.COM
SULLAIR
3700 East Michigan Boulevard • Michigan City, Indiana, 46360 U.S.A.
Telephone: 1-219-879-5451