Liebert DSE Packaged

Job Name
Model DP060DP
Quantity
Date
Invoice #
Purchaser
P.O. #
Tag #
Submitted By

PG1 Rev 6/20/18


LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
SINGLE POWER INPUT
STANDARD ELECTRICAL CONNECTIONS
1) HIGH VOLTAGE ENTRANCE – This area will be used for the high voltage fittings. Enclosure is not provided with holes or knockouts,
which must be done by the installer in the field. The fittings used must have the proper environmental rating per code.
2) LOW VOLTAGE ENTRANCE – This area will be used for the low voltage and communication fittings. Enclosure is not provided with
holes or knockouts, which must be done by the installer in the field. The fittings used must have the proper environmental rating per
code.
3) HIGH VOLTAGE WIRE DUCT – Wire duct to be used by the installer for high voltage wire routing.
4) MAIN UNIT POWER CONNECTIONS – Terminals are located on top of the locking disconnect switch. See side of disconnect switch
for wire range and tightening torque. Three phase service not provided by Liebert. Wire range and tightening torque will vary based on
disconnect size. Refer to label on side of disconnect.
5) EARTH GROUND CONNECTION FOR MAIN UNIT POWER – Terminal for field supplied Source 1 earth grounding wire. Earth
grounding required for Liebert units. 14-2AWG wire range, 275 in-lb wire tightening torque.
6) REMOTE SHUTDOWN - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
7) CUSTOMER ALARM INPUTS – Terminals for field supplied, normally open contacts, having a minimum 75va, 24vac rating, between
terminals 24 & 50, 51, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options.
8) COMMON ALARM – On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC
max load. Use Class 1 field supplied wiring.
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.

STANDARD COMMUNICATION CONNECTIONS


9) RS485 BMS CONNECTION – Terminal TB3-1 is TX/RX+. Terminal TB3-2 is TX/RX-. Terminal TB3-3 is earth ground. Use shielded
cable with 120ohm characteristic impedance. (Supplied by other).
10) CANBUS REMOTE SENSOR CONNECTION – Remove the inserted plug from this connector and attach the remote sensor cable to
power and communicate with Liebert remote Temperature/humidity sensors. Use shielded cable with 120ohm characteristic
impedance. (Supplied by other).
11) ETHERNET BMS CONNECTION – RJ-45 connection for connecting to BMS Ethernet network. Use Class 5 shielded cable (Supplied
by other).
12) ETHERNET UNIT TO UNIT CONNECTION – RJ-45 connection for connecting to other units. Use Class 5 shielded cable (Supplied by
other).
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.
Form No.: DPN001040_REV4

DPN004732 REV : 0
Page :1 /3 REV DATE : 4/18
LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
SINGLE POWER INPUT
OPTIONAL ELECTRICAL CONNECTIONS
13) SMOKE SENSOR ALARM – Factory wired dry contacts from smoke sensor are 91-common, 92-Normally Open, and 93-Normally
Closed. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended to function as, or
replace, any room smoke detection system that may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1
field supplied wiring.
14) CONDENSATE ALARM – Terminals are present with condensate pump option. On pump high water indication, normally open dry
contact is closed across terminals 88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
15) REMOTE HUMIDIFIER – On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field
supplied remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
16) FIELD SUPPLIED 120V UTILITY POWER – Terminals for the connection of a field supplied 120V 20A utility power to feed the light
and service electrical outlet. 22-8AWG wire range, 14.2lb-in tightening torque.
17) EARTH GROUNDING CONNECTION FOR FIELD SUPPLIED 120V UTILITY POWER - Terminal for field supplied 120V earth
grounding wire. Earth grounding required for Liebert units. 14-2AWG wire range, 275 in-lb wire tightening torque.

OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS


18) EXTRA REMOTE UNIT SHUTDOWN – Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C & 38C).
Replace jumpers with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1
wiring.
19) EXTRA COMMON ALARM – On any alarm, two additional normally open contacts are closed across terminals 94 & 95 and 96 & 97
for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
20) MAIN FAN AUXILIARY SWITCH – On closure of the main fan contactor, normally open dry contact is closed across terminals 84 &
85 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
21) LIQUITECT SHUTDOWN AND DRY CONTACT – On LiquiTect activation, normally open dry contact is closed across terminals 58 &
59 for remote indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.

Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protection device size.
Form No.: DPN001040_REV4

DPN004732 REV : 0
Page :2 /3 REV DATE : 4/18
LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
SINGLE POWER INPUT

5 17
4 3

16

10
6 18 7 15 9

12

11

21 8 19 20 14 13
200A DISCONNECT VIEW

3" 8" 3/4"


76 203 19
2" FRONT
51

4 1/4" 4 1/4"
109 109
6 1/2"
165

3"
76

3/4" 2 2 1 3/4"
BACK 20
Form No.: DPN001040_REV4

19
7 3/4"
197
BOTTOM VIEW
DPN004732 REV : 0
Page :3 /3 REV DATE : 4/18
LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
DUAL POWER INPUT
STANDARD ELECTRICAL CONNECTIONS
1) HIGH VOLTAGE ENTRANCE – This area will be used for the high voltage fittings. Enclosure is not provided with holes or knockouts,
which must be done by the installer in the field. The fittings used must have the proper environmental rating per code.
2) LOW VOLTAGE ENTRANCE – This area will be used for the low voltage and communication fittings. Enclosure is not provided with
holes or knockouts, which must be done by the installer in the field. The fittings used must have the proper environmental rating per
code.
3) HIGH VOLTAGE WIRE DUCT – Wire duct to be used by the installer for high voltage wire routing.
4) SOURCE 1 MAIN UNIT POWER CONNECTIONS – Terminals are located on top of the locking disconnect switch. See side of
disconnect switch for wire range and tightening torque. Three phase service not provided by Liebert. Wire range and tightening torque
will vary based on disconnect size. Refer to label on side of disconnect.
5) EARTH GROUND CONNECTION FOR SOURCE 1 MAIN UNIT POWER – Terminal for field supplied Source 1 earth grounding wire.
Earth grounding required for Liebert units. 14-2AWG wire range, 275 in-lb wire tightening torque.
6) SOURCE 2 MAIN UNIT POWER CONNECTIONS - Terminals are located on top of the locking disconnect switch. See side of
disconnect switch for wire range and tightening torque. Three phase service not provided by Liebert. Wire range and tightening torque
will vary based on disconnect size. Refer to label on side of disconnect.
7) EARTH GROUND CONNECTION FOR SOURCE 2 MAIN UNIT POWER - Terminal for field supplied Source 2 earth grounding wire.
Earth grounding required for Liebert units. 14-2AWG wire range, 275 in-lb wire tightening torque.
8) REMOTE SHUTDOWN - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
9) CUSTOMER ALARM INPUTS – Terminals for field supplied, normally open contacts, having a minimum 75va, 24vac rating, between
terminals 24 & 50, 51, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options.
10) COMMON ALARM – On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC
max load. Use Class 1 field supplied wiring.
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.

STANDARD COMMUNICATION CONNECTIONS


11) RS485 BMS CONNECTION – Terminal TB3-1 is TX/RX+. Terminal TB3-2 is TX/RX-. Terminal TB3-3 is earth ground. Use shielded
cable with 120ohm characteristic impedance. (Supplied by other).
12) CANBUS REMOTE SENSOR CONNECTION – Remove the inserted plug from this connector and attach the remote sensor cable to
power and communicate with Liebert remote Temperature/humidity sensors. Use shielded cable with 120ohm characteristic
impedance. (Supplied by other).
13) ETHERNET BMS CONNECTION – RJ-45 connection for connecting to BMS Ethernet network. Use Class 5 shielded cable (Supplied
by other).
14) ETHERNET UNIT TO UNIT CONNECTION – RJ-45 connection for connecting to other units. Use Class 5 shielded cable (Supplied by
other).
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.
Form No.: DPN001040_REV4

DPN004587 REV : 0
Page :1 /3 REV DATE : 3/18
LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
DUAL POWER INPUT
OPTIONAL ELECTRICAL CONNECTIONS
15) SMOKE SENSOR ALARM – Factory wired dry contacts from smoke sensor are 91-common, 92-Normally Open, and 93-Normally
Closed. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended to function as, or
replace, any room smoke detection system that may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1
field supplied wiring.
16) CONDENSATE ALARM – Terminals are present with condensate pump option. On pump high water indication, normally open dry
contact is closed across terminals 88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
17) REMOTE HUMIDIFIER – On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field
supplied remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
18) FIELD SUPPLIED 120V UTILITY POWER – Terminals for the connection of a field supplied 120V 20A utility power to feed the light
and service electrical outlet. 22-8AWG wire range, 14.2lb-in tightening torque.
19) EARTH GROUNDING CONNECTION FOR FIELD SUPPLIED 120V UTILITY POWER - Terminal for field supplied 120V earth
grounding wire. Earth grounding required for Liebert units. 14-2/0AWG wire range, 14-8AWG – 75lb-in, 6-4AWG – 110lb-in, 2-
1AWG – 150lb-in, 1/0 – 2/0AWG – 180lb-in.

OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS


20) EXTRA REMOTE UNIT SHUTDOWN – Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C & 38C).
Replace jumpers with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1
wiring.
21) EXTRA COMMON ALARM – On any alarm, two additional normally open contacts are closed across terminals 94 & 95 and 96 & 97
for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
22) MAIN FAN AUXILIARY SWITCH – On closure of the main fan contactor, normally open dry contact is closed across terminals 84 &
85 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
23) LIQUITECT SHUTDOWN AND DRY CONTACT – On LiquiTect activation, normally open dry contact is closed across terminals 58 &
59 for remote indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
NOTE: All low voltage terminal connections are spring-cage with a wire range of 28-12AWG.

Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protection device size.
Form No.: DPN001040_REV4

DPN004587 REV : 0
Page :2 /3 REV DATE : 3/18
LIEBERT DSE
ELECTRICAL FIELD CONNECTIONS
DP060 UNIT DEFINITIONS AND LOCATIONS
DUAL POWER INPUT
6 4 5 7 6
4 5 7

18

60A DISCONNECT VIEW


19 FOR REFERENCE

8 20 9 17 11 12

14

13

200A DISCONNECT VIEW


23 10 21 22 16 15
7 3/4" 3" 6" 3/4"
197 76 152 19
2"
51
FRONT
3/4"
19

4 1/4" 4 1/4"
109 109
6 1/2"
165

3"
75
Form No.: DPN001040_REV4

2 3/4"
3" 2 1 BACK 19
75 BOTTOM VIEW
DPN004587 REV : 0
Page :3 /3 REV DATE : 3/18
LIEBERT DSE
COMPONENT LOCATION DIAGRAM
EVPORATOR COMPARTMENT DP060 TOP INLET/FRONT SUPPLY

4 10
8

7 11

Front of unit 1 Compressor


5
2 Evaporator Coil
6
3 EC Fan
1
4 Interior 120V Light
5 Light Switch
6 GFI Outlet
7 Filters (qty. 3)
8 Duct Collar
9 Liebert EconoPhase
10 Condenser Fans
11 Condenser Coil
Form No.: DPN001040_REV4

DPN004597 REV : 0
Page :1 /1 REV DATE : 3/18
LIEBERT DSE
CABINET & ANCHOR DIMENSIONAL DATA
DP060 TOP INLET/FRONT SUPPLY
Shaded area indicates
required minimum clearance
for Electrical Box and
42" Component access.
1067mm

1"
25mm
Typ. (2) Places

Removable
Lifting Lugs
(Typ. 4 Plcs.)
Forklift access
Shaded area indicates Typ. both sides
recommended minimum
clearance between units
when lifting lugs are removed.

Shaded area indicates


recommended minimum
vertical clearance above fans. 72"
1829mm

Top View
83 3/4" 1 5/8"
2127mm 41mm
Typ.

104 1/2"
2653mm
Height from top of fans
to bottom of unit
105 1/4"
2673mm
Overall
Height

6 1/2"
83 1/2"
2121mm
5 7/8" Right Side View 3 3/4"
96mm 164mm
Form No.: DPN001040_REV4

91" 150mm 72"


2310mm Typ. (4) Plcs. 1829mm Typ. (4) Plcs.
134 1/2"
Front View 3418mm
DPN004600 REV : 1
Page :1 /2 REV DATE : 5/18
LIEBERT DSE
CABINET & ANCHOR DIMENSIONAL DATA
DP060 TOP INLET/FRONT SUPPLY
134"
3404mm
O 5/8"
16mm
3" 32" Anchor Holes
76mm 813mm 1"
Typ. Typ. Typ. (18) Plcs. 25mm
5 3/4" Typ.
146mm

24"
610mm
Typ.

Front
Rear of 83 1/2"
of Unit 2121mm
Unit

1"
25mm
Bottom View

Notes:
1. Underside of base of unit. Components removed for clarity.
2. Mounting requirement details such as brand type, embedment depth, edge spacing, anchor spacing, concrete strength, wall bracing, and special inspection
must be outlined and approved by the project Structural Engineer of Record.
3. Concrete Slab Preparation:
A) Sweep the slab broom clean
B) Lay out the final location of the unit in the slab using either chalk line or tape
C) Use a laser level or optical level to locate the high point of the slab and mark it.
Form No.: DPN001040_REV4

DPN004600 REV : 1
Page :2 /2 REV DATE : 5/18
LIEBERT DSE
EVAPORATOR COMPARTMENT SERVICE AREA
Notes: DP060 TOP INLET/FRONT SUPPLY
1. Evaporator Coil is removed into service area and through either door.
Requires 36" (914mm) X 60" (1524mm) clearance outside of door area.
2. NOTICE: Risk of equipment damage. Evaporator accent panel cannot be opened
while exterior man door is closed.

Access Door
swings inward
as shown
(Typ. both sides)

36"
1 914mm

Shaded are indicates


minimum clearance
required in front of Top View of Evaporator Section
Liebert DSE unit.
36" 120V
Plenum 914mm Interior
Light
Filter
Access

120V Interior
Light Switch

GFCI Outlet

Side View of Evaporator Compartment Front View of Evaporator Unit


Form No.: DPN001040_REV4

Access Door removed for clarity Wall & Access Doors removed for clarity

DPN004602 REV : 1
Page :1 /1 REV DATE : 5/18
LIEBERT DSE
AIRFLOW SCHEMATIC
DP060 TOP INLET/FRONT SUPPLY

Return Air In

Front of unit

Supply Air Out

Some panels removed for clarity


Form No.: DPN001040_REV4

DPN004598 REV : 0
Page :1 /1 REV DATE : 3/18
LIEBERT DSE
EVAPORATOR DUCTING DIMENSIONAL DATA
DP060 TOP INLET/FRONT SUPPLY

34 1/8"
866mm

2 5/8"
66mm
76 1/8" 4 1/4"
1933mm 107mm
Top View

2 3/8"
1 60mm 3 3/8"
At Center 2 7/8" 84mm
of Duct Flange 72mm At Rear
At Center of Duct Flange
of Duct Flange

105 1/8"
2670mm

A
18 1/2"
469mm
11 1/8"
283mm

6 7/8" 34 1/8"
174mm 867mm
55 5/8" Right Side View
1412mm
Front View
3/4"
19mm Typ.
Available space to
attach duct flange
with Gravity Damper
Notes:
1 1/2" Typ.
37mm
1. Duct Flange supplied by others. Available space to
2. Seal all ducts. attach duct flange
Form No.: DPN001040_REV4

without Gravity Damper

DETAIL A
DPN004599 REV : 0
Page :1 /1 REV DATE : 3/18
LIEBERT DSE
PIPING SCHEMATIC
DP060

Optional "EconoPhase" Unit


Differential Check Valve
Differential
Check Check Valve
Liquid from Condenser Valve
Pressure Transducer

LIEBERT MC CONDENSER LIEBERT DSE Solenoid


RECEIVER Valve

Ball Ball
Valve Valve

EVAPORATOR COMPARTMENT LIQUID


EVAPORATOR
COIL
Service
Valve

SUCTION

Check
Valve

Service
Valve

Check HOT GAS DISCHARGE


Valve

Electronic Sight LIQUID RETURN


Glass Filter Drier
Expansion Valve

FACTORY REFRIGERANT PIPING SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE.


SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE.
Form No.: DPN001040_REV4

DPN004566 REV : 0
Page :1 /1 REV DATE : 3/18
LIEBERT DSE
DRIP PAN CLEANOUT ACCESS & LOCATION
DP60 PERIMETER UNIT

Drip Pan Clean Out Location

O3/4" pipe with


CPVC 3/4” FPT fitting
Clean Out Port for
Service Pan

Rear
of
Unit

33 3/4" DETAIL A
857mm
Drip Pan Clean Out Location

50 3/4"
1289mm

Bottom View
Form No.: DPN001040_REV4

showing Drip Pan Cleanout locating dimensions


DPN004601 REV : 0
Page :1 /1 REV DATE : 3/18
LIEBERT DSE
RIGGING INSTRUCTIONS
DP060 PERIMETER UNIT
Note:
1. Inspect unit for damages.
2. Clear area of all unnecessary personnel.
3. Clear area of any debris, unrelated tools, or foreign objects.
4. Use indicated lifting lugs to lift the unit. Use spreader bars (provided by others) and/or shimmed blocks to prevent external damage.
5. Unit must be lifted level. Tilting can cause damage to the equipment inside. Use shims or blocks for leveling when placing the unit on the ground before lifting.
6. Approximate Shipping Weight: 5,500 lbs. (2495 kg).

9'-2"
(2.8m)

Indicated lugs to be used


for rigging purposes.
(Typ.) both sides.

7'-1"
(2.1m) 11'-3"
7'-11"
(2.4m) (3.4m)
Form No.: DPN001040_REV4

DPN004576 REV : 1
Page :1 /1 REV DATE : 5/18
LIEBERT DSE
INSTALLATION INSTRUCTIONS
Note: DP060 PERIMETER UNIT
1. Unit must be lifted level. Tilting can cause damage to the equipment inside.
Crane Method:
- Use indicated lifting lugs to lift the unit.
- Use spreader bars and/or shimmed blocks (provided by others) to prevent external damage.
Forklift Method:
- Use fork pockets (unit can be lifted from either side),
- Forklift must be rated for 5,500 lbs. (2495 kg) and have a fork length no less than 8' (2.4m).
- Protective material must be placed between fork mast and unit to prevent external damage.

Crane Lift Option

Indicated lugs to be used


for Crane Lift option.
(Typ.) both sides.

4'-11" Typ.
1.5m
Centerline
Fork Pockets

Indicated lugs to be used


Form No.: DPN001040_REV4

for Crane Lift option.


(Typ.) both sides.

DPN004792 REV : 0
Page :1 /1 REV DATE : 5/18
LIEBERT DSE
INSTALLATION & SERVICE CLEARANCE DATA
DP060

1" 2"
25mm 51mm
Typ. Between Units

41 1/8"
1044mm
60" 1
1524mm

1
36"
914mm
Typ.

2 2

42" 1
1067mm
Typ.

Top View
Rear of Units

Notes:

1. Required clearance between the end unit and the nearest obstruction.

2. Evaporator Coil may be removed into service area and through either door.
3. See DPN004600 fo additional dimensional information.
4. Multiple units can be placed side by side. Two units shown for reference.
Form No.: DPN001040_REV4

DPN004756 REV : 0
Page :1 /1 REV DATE : 5/18