Contract: SN:
Frequency: 60.0
Output Filename: D:\AMAAD BUSINESS PARK HOTEL\ETAP Model\Amaad Business Park Parcel-2\Substation
Grid_Untitled.GR1S
Project: ETAP Page: 2
Contract: SN:
System Data
Total Sf Cp Tf Tc Ts
Ambient Fault Division Projection for for Sizing for
Freq. Weight Temp. Current Factor Factor Total Fault Ground Available
Hz kg °C kA X/R % % Duration Conductors Body Current
60.0 70 40.00 44.000 10.00 100.0 100.0 0.50 0.50 0.25
Soil Data
Clean limestone 2500.0 0.500 Moist soil 200.0 3.00 Dry soil 200.0
Material Constants
Resistivity of Thermal
r Factor Fusing Ground Conductor Capacity
Conductivity @ 20 °C K0 @ Temperature @ 20°C Per Unit Volume
Conductor/Rod Type % 1/°C 0 °C °C micro ohm.cm J/(cm³.°C)
Conductor Copper, annealed soft-drawn 100.0 0.00393 234.0 1083.0 1.72 3.42
Rod Copper-clad steel rod 20.0 0.00378 245.0 1084.0 8.62 3.85
Rod Data
Grid Configuration
Contract: SN:
Cost
Conductor Rod
Total Total Length Cost Total Total Length Cost Total Cost
No. m $ No. m $ $
9 216 2160.00 10 60 1000.00 3160.00
Project: ETAP Page: 4
Contract: SN:
Rg GPR
Touch Potential Step Potential
Ground Ground
Resistance Potential Rise Tolerable Calculated Tolerable Calculated
Maximum Grid Current: 45.152 kA Surface Layer Derating Factor (Cs): 0.924
Warnings:
The maximum Touch Voltage exceeds the tolerable limits.
The maximum Step Voltage exceeds the tolerable limits.
- Correction factor for grid geometry regarding touch voltage (Kim): 1.347
- Correction factor for grid geometry regarding step voltage (Kis): 1.347
- Corrective weighting factor that adjusts for the effects of inner conductors on the corner mesh (Kii): 1.000