A B C A B C

1 S1
1
LEGEND:
BEDROOM BEDROOM
LIGHTING & POWER WIRING SYSTEM

DINING / DINING / M KILOWATT HOUR METER


KITCHEN KITCHEN
SERVICE ENTRANCE

2 S1
2 LIGHTING OUTLET

S1 SINGLE GANG SWITCH


T&B T&B 2
S1 CKT S2 DOUBLE GANG SWITCH

3 S1 3 CONVINIENCE OUTLET

PANEL BOARD
LIVING 3 LIVING
CKT
ROOM ROOM
1
CKT
BEDROOM BEDROOM

LP
LP
S2
4 4
LIGHTING LAYOUT PLAN POWER LAYOUT PLAN
SCALE 1:60 SCALE 1:60

SERVICE ENTRANCE SCHEDUE OF LOADS :


LP
CIRCUIT: LP
M KILOWATT HOUR
LIGHT CONVINIENCE OTHER LOAD
CIRCUIT NO. VOLTS AMPERE PROTECTION SIZE OF WIRE ELECTRICAL NOTES AND SPECIFICATIONS :
OUTLET OUTLET LOADS (VA)
1. ALL ELECTRICAL WORKS HEREIN SHALL CONFORM WITH THE RULES AND REGULATIONS OF THE LATEST EDITION
1 6 120 230 V 0.52 15 A 2 - 3.5mm2 & 1 - 3.5mm 2 THHN OF THE PHILIPPINE ELECTRICAL CODE PEC. ALL NATIONAL AND MUNICIPAL LAWS PERTINENT TO PRACTICE OF
ELECTRICAL ENGINEERS AND REQUIREMENTS OF LOCAL POWER COMPANY.
30 AMPERE 2. ALL INSTALLATION SHALL BE RIGID STEEL CONDUIT RSC PIPE AND POLYVINYL CHLORIDE PIPE PVC THE MINIMUM
M.C.B. 2 4 720 230 V 3.13 20 A 2 - 3.5mm2 & 1 - 3.5mm 2 THHN SIZE OF CONDUIT SHALL NOT SMALLER THAN 15 mm O 1-1/2" O NOMINAL DIAMETER AND SHALL BE LARGER
WHERE SO REQUIRED BY LAW.
3 4 720 230 V 3.13 20 A 2 - 3.5mm2 & 1 - 3.5mm 2 THHN 3. ELECTRICAL CONDUCTORS TO BE USED SHALL BE OF PHELPS DODGE BRAND OR APPROVED EQUIVALENT THE
1 15 A 20 A 2 MINIMUM CONDUCTOR SIZE SHALL NOT BE SMALLER THAN 3.5 mm (#12) TW. AND SHALL BE LARGER WHERE SO
4 SPARE 500 230 V 2.17 20 A 2 - 3.5mm2 & 1 - 3.5mm 2 THHN REQUIRED.
4. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL NEW AND IN GOOD CONDITION AND APPROVED TYPE FOR
3 20 A 20 A 4 LOCATION AND PURPOSES.
5. OUTDOOR INSTALLATION SHALL BE WEATHER PROOF.
6. ALL FEEDER RUN AND CIRCUIT HOMERUN TO THE PANEL BOARD SHALL NOT BE COMBINED IN THE RACEWAY
UNLESS SO INDICATED.
TOTAL 2060 8.95 7. SERVICE POWER SUPPLY TO THE BUILDING SHALL BE 220 / 110 V, SINGLE 1" O PHASE, THREE WIRES, SIXTY HERTZ
THERE SHALL BE ONLY SERVICE DROP TO THE BUILDING.
8. SERVICE SHALL BE REMODELLED FOR UNDERGROUND SERVICE CONNECTION.
PANEL BOARD COMPUTATION OF LOAD : PROTECTION : FEEDER : CONDUIT : 9. ALL SERVICE EQUIPMENT AND SPECIAL PURPOSE OUTLET SHALL BE READILY ACCESSIBLE.
IN BUILDING.
10. INSTALLATIONS SHALL CONFORM TO CODE RULES IN GROUPING OF SERVICE EQUIPMENTS AND CONDUCTORS
I TOTAL = 8.95 + 25% (8.95) USE : 230 V, 30 AMP. MAIN USE : 2 - 8.0mm2 & 1- 5.5mm2 11. ALL ELECTRICAL WORKS HERE INCLUDED SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED
= 11.19 x 80% D.F. CIRCUIT BREAKER ELECTRICAL ENGINEER.
RISER DIAGRAM = 8.95 AMP.
SCALE NTS

ENGINEER: PROJECT TITLE: OWNER: SHEET CONTENT: DESIGN SHEET NO.


DRAWN BY:
CHECKED BY:
LIGHTING & POWER LAYOUT PLAN, RISER
REG. NO.: TIN NO.: DIAGRAM AND SCHEDULE OF LOADS
DATE:

REVISION:
E-1
PTR NO: ISSUED ON/AT: LOCATION: SCALE: