Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
MELSEC FX Series
Programmable Logic Controllers
User's Manual
(Hardware)
FX3U
Base Units
and Extension Blocks
Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Depending on the circumstances, procedures indicated by may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.
1. DESIGN PRECAUTIONS
Reference
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation
even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an
interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock
circuit (to prevent damage to the equipment at the upper and lower positioning limits).
123
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-
147
diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC
164
CPU occurs in an input/output control block, output control may be disabled.
205
External circuits and mechanisms should be designed to ensure safe machinery operation in
223
such a case.
263
3) Note that the output current of the 24V DC service power supply varies depending on the
286
model and the absence/presence of extension blocks. If an overload occurs, the voltage
325
automatically drops, inputs in the PLC are disabled, and all outputs are turned off.
407
External circuits and mechanisms should be designed to ensure safe machinery operation in
such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be
held either on or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should
be designed to ensure safe machinery operation in such a case.
Reference
123
147
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a
164
guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power
205
line.
223
Noise may cause malfunctions.
263
• Install module so that excessive force will not be applied to peripheral device connectors.
286
Failure to do so may result in wire damage/breakage or PLC failure.
325
407
(1)
Safety Precautions
(Read these precautions before use.)
2. INSTALLATION PRECAUTIONS
Reference
• Make sure to cut off all phases of the power supply externally before attempting installation or
123
wiring work.
407
Failure to do so may cause electric shock.
Reference
• Use the product within the generic environment specifications described in Section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas
(salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or exposed to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage
may occur.
• Do not touch the conductive parts of the product directly to avoid failure or malfunctions.
• Install the product securely using a DIN rail or mounting screws.
FX2N-10GM, FX2N-20GM, and terminal block DIN rail only
Main unit, FX2N Series I/O extension unit/block, and FX0N/FX2N/
DIN rail or direct mounting
FX3U Series special extension block/special adapter
Memory
Good cassette
PLC body
Memory Raised cassette
Bad cassette
posture
Memory
Bad cassette Tilted cassette posture
(2)
Safety Precautions
(Read these precautions before use.)
3. WIRING PRECAUTIONS
Reference
124
• Connect the AC power supply to the dedicated terminals specified in this manual. 147
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the 150
PLC will burn out. 153
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid 164
damage to the product or electric shock. 205
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or 223
initiating operation after installation or wiring work. 263
Failure to do so may cause electric shock. 286
408
Reference
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main
unit or extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the
main unit and extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the
PLC will burn out.
• Do not wire vacant terminals externally.
Doing so may damage the product. 125
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation 148
slits. 150
Failure to do so may cause fire, equipment failures or malfunctions. 165
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in 206
accordance with the following precautions. 218
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the 219
product. 222
- The disposal size of the cable end should follow the dimensions described in this manual. 224
- Tightening torque should be between 0.5 and 0.8 N•m. 264
• Observe the following items when wiring to the European terminal board. 286
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product. 408
- The disposal size of the cable end should follow the dimensions described in this manual. 417
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly
stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below
in order to prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
(3)
Safety Precautions
(Read these precautions before use.)
Reference
Reference
• Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory
cassette is attached or detached while the PLC's power is on, the data in the memory may be
destroyed, or the memory cassette may be damaged.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric distributor. 240
• Turn off the power to the PLC before connecting or disconnecting any extension cable. 349
Failure to do so may cause equipment failures or malfunctions. 437
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- Display module, peripheral devices, expansion boards, and special adapters
- Connector conversion adapter, extension blocks, and FX Series terminal blocks
- Battery and memory cassette
5. DISPOSAL PRECAUTIONS
Reference
• Please contact a certified electronic waste disposal company for the environmentally safe
240
recycling and disposal of your device.
6. TRANSPORTATION PRECAUTIONS
Reference
• Before transporting the PLC, turn on the power to the PLC to check that the BATT LED is off.
If the PLC is transported with the BATT LED on or the battery exhausted, the battery-backed data
may be unstable during transportation.
240
• The PLC is a precision instrument. During transportation, avoid impacts larger than those specified
437
in the PLC main unit Hardware Edition manual (Section 4.1).
Failure to do so may cause failures in the PLC.
After transportation, verify the operations of the PLC.
(4)
FX3U Series Programmable Controllers
User's Manual - Hardware Edition
Foreword
This manual contains text, diagrams and explanations which will guide the reader in the correct installation,
safe use and operation of the FX3U Series Programmable Controllers and should be read and understood
before attempting to install or use the unit.
And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always
forward it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
1
FX3U Series Programmable Controllers
User's Manual - Hardware Edition
Outline Precautions
• This manual provides information for the use of the FX3U Series Programmable Controllers. The manual
has been written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
Note: the term 'completed equipment' refers to a third party constructed device which contains or uses
the product associated with this manual
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult the nearest Mitsubishi Electric distributor.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
distributor.
Registration
• Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
2
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
Table of Contents
SAFETY PRECAUTIONS .................................................................................................. (1)
Standards 15
1. Introduction 20
3.1 List of Products (to be Connected) and Interpretation of Model Names ....................................... 35
3.1.1 [A] Main units................................................................................................................................. 36
3.1.2 [B] Input/output powered extension units ...................................................................................... 37
3.1.3 [C] Input/output extension blocks .................................................................................................. 38
3.1.4 [D] [E] Special function units/blocks .............................................................................................. 39
3.1.5 [F] Display modules and holder ..................................................................................................... 41
3.1.6 [G] Expansion boards .................................................................................................................... 41
3.1.7 [H] Special adapters ...................................................................................................................... 41
3.1.8 [I] Extension power supply unit...................................................................................................... 42
3.1.9 [J] Extension cables and connector conversion adapter[K] Battery [L] Memory cassettes ........... 43
3.1.10 [M] FX Series terminal blocks (cables and connectors) .............................................................. 43
3.1.11 [N] Remote I/O............................................................................................................................. 44
3.1.12 [O] Power supply unit .................................................................................................................. 44
3.2 Connector Types and Cables for Program Communication.......................................................... 45
3.2.1 Programming tool .......................................................................................................................... 46
3.2.2 Communication cables .................................................................................................................. 46
3.2.3 Converters and interface ............................................................................................................... 47
3
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
4
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
5
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
8.7 Connecting Methods for Main Unit and Extension Devices ........................................................ 141
8.7.1 Connection of extension devices................................................................................................. 141
8.7.2 Connecting method A - connection of expansion board.............................................................. 142
8.7.3 Connecting method B - connection of special adapter ................................................................ 143
8.7.4 Connecting method C - connection of powered extension unit/block to main unit ...................... 143
8.7.5 Connecting method D - connection of powered extension units/blocks ...................................... 144
8.7.6 Connecting method E - connection of extension cable and FX2N-CNV-BC................................ 145
8.7.7 Connecting method F - connection of input/output powered extension unit................................ 145
8.7.8 Connecting method G - connection of extension block to input/output powered extension unit . 146
10. Input Wiring Procedures (Input Interruption and Pulse Catch) 164
6
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
7
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
8
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
9
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
10
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
11
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
12
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
13
FX3U Series Programmable Controllers
User's Manual - Hardware Edition Table of Contents
Warranty................................................................................................................................. 466
Revised History ..................................................................................................................... 467
14
Standards
15
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in accordance with the contents of
this note will comply with the following standards.
Compliance to EMC directive and LVD directive of the entire mechanical module should be checked by the
user / manufacturer. For more details please contact to the local Mitsubishi Electric sales site.
Standard Remark
EN61131-2:2003 Programmable controllers Compliance with all relevant aspects of the standard.
- Equipment requirements and tests • Radiated Emissions
• Mains Terminal Voltage Emissions
• RF immunity
• Fast Transients
• ESD
• Surge
• Voltage drops and iterruptions
• Conducted
• Power magnetic fields
16
Models : MELSEC FX2N series manufactured
from July 1st, 1997 FX2N- ER-ES/UL FX2N- ET-ESS/UL
Where indicates:32,48
FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL
from April 1st, 1998 FX2N-48ER-DS FX2N-48ET-DSS
from August 1st, 1998 FX2N-48ER-UA1/UL
from August 1st, 2005 FX2N-8ER-ES/UL FX2N-8EX-ES/UL FX2N-8EYR-ES/UL
FX2N-8EYT-ESS/UL
17
Requirement for Compliance with LVD directive
The following products have shown compliance through direct testing (of the identified standards below) and
design analysis (through the creation of a technical construction file) to the European Directive for Low
Voltage (73/23/EEC) when used as directed by the appropriate documentation.
Standard Remark
EN61131-2:2003 Programmable controllers The equipment has been assessed as a component for
- Equipment requirements and tests fitting in a suitable enclosure which meets the requirements
of EN61131-2:2003
18
Caution for compliance with EC Directive
1. Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and used within conductive
control boxes. Please use the FX3U Series programmable logic controllers while installed in conductive
shielded control boxes. Please secure the control box lid to the control box (for conduction). Installation within
a control box greatly affects the safety of the system and aids in shielding noise from the programmable logic
controller.
2. Caution for Analog Products in use
The analog special adapters have been found to be compliant to the European standards in the aforesaid
manual and directive. However, for the very best performance from what are in fact delicate measuring and
controlled output devices, Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered carefully. For users of proprietary
cables (integral with sensors or actuators), these users should follow those manufacturers' installation
requirements.
Mitsubishi Electric recommends that shielded cables be used. If NO other EMC protection is provided, users
may experience temporary induced errors not exceeding +10%/-10% in very heavy industrial areas.
However, Mitsubishi Electric suggests that if adequate EMC precautions are followed with general good EMC
practice for the users complete control system, users can expect errors as specified in this manual.
- Sensitive analog cables should not be laid in the same trunking or cable conduit as high voltage cabling.
Where possible, users should run analog cables separately.
- Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops
are accidentally created.
- When reading analog values, EMC induced errors can be smoothed out by averaging the readings. This
can be achieved either through functions on the analog special adapters/blocks or through a user's
program in the FX3U Series PLC main unit.
19
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
1. Introduction
This manual explains the procedures for selecting the system components, main unit specifications and
procedures for installing the main unit, specifications for the input/output powered extension units/blocks, and
procedures for adding input/output devices, and procedures for operating the display module etc.
FX3U PLCs can make various kinds of control in combination with the main unit functions and many extension
devices (expansion board, special adapters and special function units/blocks).
The detailed explanation of the sequence instructions, communication control, analog control and positioning
control are given in separate manuals.
→ For information on manual organization, refer to Subsection 1.1.2.
20
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
1
2. Extension devices (Chapter 15 to 18)
Introduction
Division Outline Reference
Input/output powered extension This chapter contains explanations for the input/output Chapter 15
units specifications, external dimensions and terminal layout for each
product.
Input/output extension blocks
This chapter contains explanations of specifications for the
Chapter 16
2
Extension power supply unit Chapter 17
Part Names
Features and
extension power supply unit and external dimensions.
Extension products for special This chapter contains explanations for the external dimensions and
functions, such as analog control, terminal layout (For details, refer to the manual for each extension Chapter 18
positioning and communication device).
Introduction
Product
Division Outline Reference
This chapter contains explanation of the specifications, external
Display module dimensions, mounting procedures and operating procedures for Chapter 19
display modules.
Specifications
This chapter contains explanations of the specifications for the
Memory cassette Chapter 21
memory cassette and the installation procedures.
This chapter contains explanations of the procedures for replacing
Battery Chapter 22
the battery and detecting battery voltage drop.
4. Others (Appendices A to C) 5
Devices
Peripheral
Version and
Division Outline Reference
This chapter contains an explanation list of the special auxiliary
List of special devices relays (M8000 to M8511) and special data registers (D8000 to Appendix A
D8511) (For details, refer to the programming manual.)
List of instructions
This chapter contains an explanation list of the basic instructions
and applied instructions Appendix B
6
Configuration
System
(For details, refer to the programming manual.)
This chapter contains an explanation list of the character codes that
List of character codes Appendix C
can be displayed on the display module (FX3U-7DM)
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
21
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
0 1
X12
2
X13
3 4
X14
X15
5
X16
6
X17
X20
X21
X22
X23
7 20 21 22 23 2 4 25 26 2 7
X24
X25
X26
X27
・
RUN
BATT
JY997D16501 (Model: FX3U-HW-E)
•PID
ERROR
ERROR
FX3U-48MR/ES OUT
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
0 111 122 133 14
10 4 155 166 177 20 21 22 23 2 4 25 26 2 7
FX 3U-48M
10 11 12 13 14 15 16 17
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 POWER
IN
0 1 2 3 4 5 6 7
POWER
separate
•Communication
POWER
manual
24+
•High-speed output
24-I1+ V 1+
RD
COM1
SD
C OM 2I2+
V3+
User's manual
The procedures for wiring and installing,
specifications and functions are explained.
To use some products, separate manuals may be
necessary.
22
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
1
1.1.3 List of manuals
Introduction
FX3U Series PLC main units supplied only with the hardware manual.
For the details of the hardware of FX3U Series, refer to this manual.
For instructions for programming and hardware information on special function devices, refer to the relevant
manuals. 2
: Indispensable manuals
Part Names
Features and
: Manuals necessary for some purposes
: Manuals with separate volumes for details
Manual Model
Manual title Contents
number name code
Manuals for PLC main unit 3
FX3U PLC main unit
Introduction
Product
Extractions of descriptions of input/output
specifications, wiring and installation of
Supplied
FX3U Series FX3U Series PLC main unit from FX3U
with JY997D18801 −
HARDWARE MANUAL Series User's Manual - Hardware Edition
product
For the detailed explanation, refer to this
manual.
4
Specifications
FX3U Series User's Details of hardware of FX3U Series PLC
Separate Manual - Hardware main unit, including input/output
JY997D16501 09R516
volume Edition specifications, wiring, installation and
(this manual) maintenance
Programming
FX3U/FX3UC Series Details of sequence programming for FX3U
5
Devices
Peripheral
Version and
Separate Programming Manual - Series, including explanation for basic
JY997D16601 09R517
volume Basic & Applied instructions, applied instructions and various
Instruction Edition devices
FX Series terminal block
FX INPUT AND
Supplied
OUTPUT TERMINAL Procedures for handling FX Series terminal 6
with JY992D50401 −
BLOCKS USER’S block
Configuration
System
product
GUIDE
Manuals for communication control
Common
Details of simple link between PCs, parallel
Separate
FX Series
User's Manual - Data JY997D16901
link, computer link and no-protocol
09R715
7
volume communication (RS instructions, FX2N-
User's Manual
product When using, refer also to FX Series User's
Manual - Data Communication Edition.
Procedures for handling the RS-232C
Supplied
FX3U-232-BD communication expansion board
with JY997D12901 −
Installation Manual When using, refer also to FX Series User's
product
Manual - Data Communication Edition. 9
Wiring
Power Supply
Preparation and
product
Manual - Data Communication Edition.
23
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
: Indispensable manuals
: Manuals necessary for some purposes
: Manuals with separate volumes for details
Manual Model
Manual title Contents
number name code
Procedures for handling the RS-422
Supplied
FX3U-422-BD communication expansion board
with JY997D13101 −
Installation Manual When using, refer also to FX Series User's
product
Manual - Data Communication Edition.
Procedures for handling the RS-485
Supplied
FX3U-485-BD communication expansion board
with JY997D13001 −
Installation Manual When using, refer also to FX Series User's
product
Manual - Data Communication Edition.
Procedures for handling the RS-485
Supplied
FX3U-485ADP communication special adapter
with JY997D13801 −
Installation Manual When using, refer also to FX Series User's
product
Manual - Data Communication Edition.
Procedures for handling the RS-232C/RS-
Supplied
FX-485PC-IF 485 conversion interface
with JY992D81801 −
Hardware Manual When using, refer also to FX Series User's
product
Manual - Data Communication Edition.
CC-Link, CC-Link/LT, MELSEC I/O LINK, and AS-i system
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Procedures for handling the CC-Link master
Supplied
FX2N-16CCL-M special function block
with JY992D93201 −
Hardware Manual When using, refer also to FX2N-16CCL-M
product
User's Manual.
Sepa-
FX2N-16CCL-M Details of CC-Link master special function
rate vol- JY992D93101 09R710
User's Manual block
ume
Supplied
FX2N-32CCL Procedures for handling the CC-Link remote
with JY992D71801 09R711
User's Manual device station special function block
product
Supplied Remote I/O station and
As for the CC-Link remote I/O station and remote device
with remote device station −
station, refer to the relevant manuals and related documents.
product for CC-Link
Procedures for handling the CC-Link/LT
Supplied FX2N-64CL-M
master special function block
with User's Manual - JY997D05401 −
When using, refer also to FX2N-64CL-M
product Hardware Volume
User's Manual - Details.
FX2N-64CL-M
Separate Details of the CC-Link/LT master special
User's Manual - JY997D08501 −
volume function block
Detailed Volume
Supplied Remote device As for the remote device station, remote I/O station, power
with Remote I/O supply adapter and dedicated power supply for CC-Link/LT, −
product Power supply adapter refer to the relevant manuals and related documents.
Supplied
FX2N-32ASI-M Procedures for handling the AS-i system
with JY992D76901 −
User's Manual master special function block
product
Supplied
FX2N-16LNK-M Procedures for handling the MELSEC I/O
with JY992D72101 09R703
User's Manual LINK master special function block
product
Manuals for analog/temperature control
Common
FX3U/FX3UC Series Details of analog special function block
Separate
User's Manual - Analog JY997D16701 (FX3U-4AD, FX3U-4DA, FX3UC-4AD) and 09R619
volume
Control Edition analog special adapter (FX3U-***-**-ADP)
24
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
1
: Indispensable manuals
Introduction
: Manuals necessary for some purposes
: Manuals with separate volumes for details
Manual Model
Manual title Contents
number name code
Analog input, temperature input and temperature control 2
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Part Names
Features and
Supplied
FX2N-2AD Procedures for handling the 2-ch analog
with JY992D74701 −
User's Guide input special function block
product
Procedures for handling the 4-ch analog
Supplied
FX3U-4AD
input special function block 3
with JY997D20701 When using, refer also to FX3U/FX3UC −
Installation Manual
Introduction
Product
product Series User's Manual - Analog Control
Edition.
Procedures for handling the 4-ch analog
Supplied input special adapter
FX3U-4AD-ADP
with JY997D13901 When using, refer also to FX3U/FX3UC −
product
User's Manual
Series User's Manual - Analog Control 4
Edition.
Specifications
Supplied
FX2N-4AD Procedures for handling the 4-ch analog
with JY992D65201 −
User's Guide input special function block
product
Supplied Procedures for handling the 8-ch analog
with
FX2N-8AD
User's Manual
JY992D86001 input special function block (to be used also 09R608 5
product for thermocouple input)
Devices
Peripheral
Version and
Procedures for handling the 4-ch Pt-100
Supplied temperature sensor input special adapter
FX3U-4AD-PT-ADP
with JY997D14701 When using, refer also to FX3U/FX3UC −
User's Manual
product Series User's Manual - Analog Control
Supplied
Edition.
Procedures for handling the 4-ch Pt-100
6
FX2N-4AD-PT
Configuration
System
with JY992D65601 temperature sensor input special function −
User's Guide
product block
Procedures for handling the 4-ch
Supplied thermocouple input special adapter
FX3U-4AD-TC-ADP
with JY997D14801 When using, refer also to FX3U/FX3UC −
product
User's Manual
Series User's Manual - Analog Control 7
Edition.
Manual.
Separate FX2N-2LC Procedures for handling the 2-ch
JY992D85801 09R607
volume User's Manual temperature control special function block
Analog output
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
9
FX2N-2DA Procedures for handling the 2-ch analog
Wiring
Power Supply
Preparation and
with JY992D74901 −
User's Guide output special function block
product
Procedures for handling the 4-ch analog
Supplied output special function block
FX3U-4DA
with JY997D20801 When using, refer also to FX3U/FX3UC −
product
Installation Manual
Series User's Manual - Analog Control 10
Edition.
Input Wiring
25
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
: Indispensable manuals
: Manuals necessary for some purposes
: Manuals with separate volumes for details
Manual Model
Manual title Contents
number name code
Procedures for handling the 3-ch analog
Supplied output special adapter
FX3U-4DA-ADP
with JY997D14001 When using, refer also to FX3U/FX3UC −
User's Manual
product Series User's Manual - Analog Control
Edition.
Supplied
FX2N-4DA Procedures for handling the 4-ch analog
with JY992D65901 −
User's Guide output special function block
product
Analog input/output (mixed)
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied Procedures for handling the 2-ch analog
FX0N-3A
with JY992D49001 input and 1-ch analog output special −
User's Guide
product function block
Supplied Procedures for handling the 4-ch analog
FX2N-5A
with JY997D11401 input and 1-ch analog output special 09R616
User's Manual
product function block
Manuals for high-speed counter
High-speed counter
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
FX3U-4HSX-ADP Procedures for handling the high-speed
with JY997D16301 −
Installation Manual input special adapter
product
Supplied
FX2N-1HC Procedures for handling the 1-ch high-speed
with JY992D65401 −
User's Guide counter special function block
product
Manuals for positioning control
Common
FX3U/FX3UC Series
Separate User's Manual - Details of positioning functions of FX3U/
JY997D16801 09R620
volume Positioning Control FX3UC Series
Edition
Pulse output and positioning
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Procedures for handling the high-speed
Supplied output special adapter
FX3U-2HSY-ADP
with JY997D16401 When using, refer also to FX3U/FX3UC −
Installation Manual
product Series User's Manual - Positioning Control
Edition.
Supplied
FX2N/FX-1PG Procedures for handling the 1-axis pulse
with JY992D65301 09R610
User's Manual output special function block
product
Procedures for handling the 1-axis pulse
Supplied
FX2N-10PG output special function block
with JY992D91901 −
Installation Manual When using, refer to FX2N-10PG User's
product
Manual.
Separate FX2N-10PG Details of 1-axis pulse output special
JY992D93401 09R611
volume User's Manual function block
Procedures for handling the 1-axis
Supplied
FX2N-10GM positioning special function unit
with JY992D77701 −
User's Guide When using, refer to FX2N-10GM/FX2N-
product
20GM Handy Manual.
26
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.1 Introduction of Manuals
1
: Indispensable manuals
Introduction
: Manuals necessary for some purposes
: Manuals with separate volumes for details
Manual Model
Manual title Contents
number name code
Supplied
Procedures for handling the 2-axis 2
FX2N-20GM positioning special function unit
Part Names
Features and
with JY992D77601 −
User's Guide When using, refer to FX2N-10GM/FX2N-
product
20GM Handy Manual.
FX2N-10GM/FX2N-20GM
Separate Procedures for handling the 1-axis/2-axis
Hardware/Programing JY992D77801 09R612
volume positioning special function unit
Manual 3
Programmable cam switch
Introduction
Product
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
FX2N-1RM-E-SET Procedures for handling the programmable
with JY992D71101 09R614
User's Manual cam switch special function unit
product
Manuals for FX3U-20SSC-H Positioning Block
4
Procedures for handling the 2-axis
Supplied
Specifications
FX3U-20SSC-H positioning special function block
with JY997D21101 -
Installation Manual When using, refer to FX3U-20SSC-H User's
product
Manual.
Separate FX3U-20SSC-H Describes FX3U-20SSC-H Positioning block
JY997D21301 09R622
volume User's Manual details.
Supplied
5
FX Configurator-FP Describes operation details of FX
Devices
Peripheral
Version and
with JY997D21801 09R916
Operation Manual Configurator-FP Configuration Software.
product
Other manuals
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Connector conversion
6
Procedures for handling the conversion
Supplied
Configuration
System
FX3U-CNV-BD function expansion board for connectors for
with JY997D13601 −
Installation Manual connecting communication and analog
product
special adapters
Battery (maintenance option)
Supplied
with
FX3U-32BL Battery
JY997D14101 Battery life and handling procedures −
7
Hardware Manual
Supplied
FX3U-7DM-HLD Procedures for mounting and handling the
with JY997D15401 −
User's Manual display module holder
product
Memorry cassette
Supplied Memorry cassette
with FX3U-FLROM-16/64/64L JY997D12801
Specifications and operating procedures of
−
9
the memory cassette
Wiring
Power Supply
Preparation and
27
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.2 Generic Names and Abbreviations Used in Manuals
28
FX3U Series Programmable Controllers 1 Introduction
User's Manual - Hardware Edition 1.2 Generic Names and Abbreviations Used in Manuals
1
Abbreviation/
Introduction
Description
generic name
Generic name for the following models
FX2N-232IF, FX2N-16CCL-M, FX2N-32CCL, FX2N-64CL-M, FX2N-16LNK-M, FX2N-
FX2N Series special 32ASI-M, FX2N-2AD, FX2N-4AD, FX2N-8AD, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC,
function blocks FX2N-2DA, FX2N-4DA, FX2N-5A, FX2N-1HC, FX2N-1PG(-E), FX2N-10PG
The devices that can be added depend on the main unit to be used. For applicable 2
devices, refer to the User's Manual - Hardware Edition for the main unit to be used.
Part Names
Features and
FX0N Series special Generic name for the following models
function blocks FX0N-3A
Generic name for the following models
Memory cassettes
FX3U-FLROM-16, FX3U-FLROM-64 and FX3U-FLROM-64L
Battery Abbreviation of model FX3U-32BL battery 3
Generic name for the following models
Introduction
Product
FX-16E-TB, FX-32E-TB, FX-16EX-A1-TB, FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-
FX Series terminal blocks TB, FX-16EYT-H-TB
The devices that can be added depend on the main unit to be used. For applicable
devices, refer to the User's Manual - Hardware Edition for the main unit to be used.
Extension cables
Generic name for the following models
FX0N-30EC, FX0N-65EC
4
Specifications
Generic name for the following models
Input/output cables FX-16E-500CAB-S, FX-16E- CAB, FX-16E- CAB-R, FX-A32E- CAB
150, 300 or 500 is entered in .
Generic name for the following models
Connectors for input/output
FX2C-I/O-CON, FX2C-I/O-CON-S, FX2C-I/O-CON-SA
CC-Link master Abbreviation of FX2N-16CCL-M 5
Remote I/O stations Remote stations that handle information in bit units only
Devices
Peripheral
Version and
Remote device stations Remote stations that handle information in bit units and word units
Remote stations Generic name for remote I/O stations and remote device stations
Power supply adapter Unit to be connected to supply power to the CC-Link/LT system
Dedicated power supply
AS-i master
Power supply to be connected to supply power to the CC-Link/LT system
Abbreviation of model FX2N-32ASI-M AS-i system master block
6
Configuration
System
Peripheral devices Generic name for programming software, handy programming panel (HPP) and indicator
Programming tool Generic name for programming software and handy programming panel (HPP)
Programming software Generic name for GX Developer and FX-PCS/WIN (-E)
Abbreviation of programming software packages SW D5C-GPPW-J and SW D5C-
GX Developer
GPPW-E 7
Abbreviation of model FX-PCS/WIN and FX-PCS/WIN-E programming software
Indicators
GOT1000 Series Generic name for GT15 and GT11
GOT-900 Series Generic name for GOT-A900 Series and GOT-F900 Series
GOT-A900 Series Generic name for GOT-A900 Series
GOT-F900 Series Generic name for GOT-F900 Series 9
Manuals
Wiring
Power Supply
Preparation and
FX3U Hardware Edition Abbreviation of FX3U Series User's Manual - Hardware Edition
Programming manual Abbreviation of FX3U/FX3UC Series Programming Manual - Basic & Applied Instructions
Data Communication
Abbreviation of FX Series User's Manual - Data Communication Edition
Edition
Analog Control Edition Abbreviation of FX3U/FX3UC Series User's Manual - Analog Control Edition 10
Input Wiring
Positioning Control Edition Abbreviation of FX3U/FX3UC Series User's Manual - Positioning Control Edition
29
FX3U Series Programmable Controllers 2 Features and Part Names
User's Manual - Hardware Edition 2.1 Major Features
30
FX3U Series Programmable Controllers 2 Features and Part Names
User’s Manual - Hardware Edition 2.1 Major Features
1
[Input interruption function (with delay function)] [Other functions]
Introduction
Interruption routines can be processed On the display module, you can set the time,
preferentially by external signals with the minimum adjust the contrast and display the PLC version
ON or OFF width of 5 µs (X000 to X005). and error codes.
(Timer interruption and high-speed counter
4. Communication and network functions
interruption functions are also provided.)
→ Refer to Chapter 10 "Input Wiring The expansion board, special adapter and
2
Part Names
Features and
Procedures (Input Interruption and Pulse special function block for each communication
Catch)" in this manual and Programming function can be connected.
Manual.
[Kinds of communication functions]
[Pulse output function] • Programming communication through RS-
1) When output terminals in the transistor 232C, RS-422 and USB 3
output type main unit are used, pulses (open → Refer to Data Communication Edition.
Introduction
Product
collector outputs) of up to 100 kHz can be • Simple link between PCs
output simultaneously to three axes (Y000, → Refer to Data Communication Edition.
Y001 and Y002).
• Parallel link
2) When two high-speed output special adapters → Refer to Data Communication Edition.
FX3U-2HSY-ADP are used, pulses (differential
• Computer link
4
line driver outputs) of up to 200 kHz can be
Specifications
output simultaneously to four axes. → Refer to Data Communication Edition.
→ Refer to Positioning Control Edition. • Inverter communication
→ Refer to Data Communication Edition.
[Various positioning instructions]
• No-protocol communication through RS-232C/
→ Refer to Positioning Control Edition.
Instruc-
RS-485 5
Description → Refer to Data Communication Edition.
Devices
Peripheral
Version and
tion
• CC-Link
Mechanical zero return instruction with
DSZR - Master: FX2N-16CCL-M
DOG search function
Instruction to read the current value - Remote device station: FX2N-32CCL
ABS from our servo amplifier with absolute → Refer to the manual for each product.
position (ABS) detecting function • CC-Link/LT 6
Configuration
System
Positioning (relative positioning) to - Master: FX2N-64CL-M
DRVI specify the movement from the current - Remote I/O station, Remote device station
position
→ Refer to the manual for each product.
Positioning (absolute positioning) to
DRVA specify the target position based on the • MELSEC I/O LINK
current value 0 - Master: FX2N-16LNK-M 7
Instruction to change the pulse train - Remote I/O station
5. Analog functions
3. Display functions (display module) The special adapter and special function block
FX3U-7DM Display Module (option) can be for each analog function are connected.
incorporated in the PLC. → For information not given in Analog
The display module can be mounted on the panel
by using the display module holder (option).
Control Edition, Refer to the manual for each
product.
9
Wiring
Power Supply
Preparation and
31
FX3U Series Programmable Controllers 2 Features and Part Names
User's Manual - Hardware Edition 2.2 Names and Functions of Parts
IN
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
10 11 12 13 14 15 16 17
POWER
[11] Extension device connecting
RUN
BATT
connector cover
[4] Expansion board FX3U-48MR/ES
ERROR
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27 [12] Operation status display LEDs
OUT
[1] Top cover Mount the memory cassette under this cover.
When FX3U-7DM (display module) is used, replace this cover with the
cover supplied with FX3U-7DM.
[2] Battery cover The battery (standard accessory) is set under this cover. When replacing
it with a new one, open this cover.
[3] Special adapter connecting When connecting the special adapter, secure it with these hooks.
hooks (2 places)
[4] Expansion board dummy cover Remove this dummy cover, and mount an expansion board.
[5] RUN/STOP switch To stop writing (batch) of the sequence program or operation, set the
switch to STOP (slide it downward).
To start operation (run the machine), set it to RUN (slide it upward).
[6] Peripheral device connecting Connect a programming tool to program a sequence.
connector → For details on applicable peripheral devices,
refer to Chapter 5.
[7] DIN rail mounting hooks The main unit can be installed on DIN46277 rail (35 mm (1.38") wide).
[8] Model name (abbreviation) The model name of the main unit is indicated.
Check the nameplate on the right side for the model name.
[9] Input display LEDs (red) When an input terminal (X000 or more) is turned on, the corresponding
LED lights.
[10] Terminal block covers The covers can be opened about 90° for wiring.
Keep the covers closed while the PLC is running (the unit power is on).
[11] Extension device connecting Connect the extension cables of input/output powered extension unit/
connector cover block or special function unit/block to the extension device connecting
connectors under this cover.
FX3U Series extension devices, FX2N Series extension devices and FX0N
Series extension devices can be connected.
→ For details on the extension devices, refer to
Chapter 15, Chapter 16 and Section 18.1.
32
FX3U Series Programmable Controllers 2 Features and Part Names
User’s Manual - Hardware Edition 2.2 Names and Functions of Parts
1
[12] Operation status display LEDs The operation status of the PLC can be checked with the LEDs.
Introduction
The LEDs turn off, light and flash according to the following table.
→ For details on the operation status, refer to Section 14.5.
LED name Display color Description
POWER Green On while power is on the PLC.
RUN Green On while the PLC is running. 2
Part Names
Features and
BATT.V Red Lights when the battery voltage drops.
Red Flashing when a program error occurs.
ERROR
Red Lights when a CPU error occurs.
[13] Output display LEDs (red) When an output terminal (Y000 or more) is turned on, the corresponding
LED lights.
3
Introduction
Product
When the terminal block covers are open
Specifications
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
L N 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
IN
10 11 12 13 14 15 16 17
POWER
RUN
BATT
ERROR
FX3U-48MR/ES
OUT
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
FX3U-48M
10 11 12 13 14 15 16 17
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
Devices
Peripheral
Version and
[17] Terminal block mounting screws
[15] Protective terminal covers
[19] Output (Y) terminals
[14] Power supply terminal Connect the power supply to the main unit.
[15] Protective terminal A protective terminal cover (refer to the following drawing) is fitted to the lower
covers stage of each terminal block. (FX3U-{{M /ES(S), and DS(S) are equipped.) 6
The cover prevents fingers from touching terminals, thereby improving safety.
Configuration
System
[16] Input (X) terminals Wire switches and sensors to the terminals.
[17] Terminal block If the main unit must be replaced, loosen the screws (slightly loosen the left and
mounting screws right screws), and the upper part of the terminal block can be removed. (On FX3U-
16M , the terminal block cannot be removed.)
7
IN
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
10 11 12 13 14 15 16 17
POWER
RUN
BATT
9
Wiring
Power Supply
Preparation and
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
OUT
10
0 11
1 12
2 13
3 14
4 15
5 16
6 17
7 20 21 22 23 24 25 26 27
FX3U-48M
10 11 12 13 14 15 16 17
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
[20] Display module (FX3U-7DM) The display module (option) can be installed. 10
[21] Top cover (accessory to FX3U- A square hole is made so that the display module can be seen. Replace
Input Wiring
33
FX3U Series Programmable Controllers 2 Features and Part Names
User's Manual - Hardware Edition 2.2 Names and Functions of Parts
2.2.2 Sides
[4] Nameplate
[5] DIN rail mounting groove
[1] Cover of special adapter Remove this cover, and connect the 1st special adapter to the connector
connector (when the expansion board is installed).
When the expansion board is not installed, the connector is not provided.
[2] Cover of high-speed input/ Remove this cover, and connect the first high-speed input special adapter
output special adapter (FX3U-4HSX-ADP) or high-speed output special adapter (FX3U-2HSY-
connector ADP) to the connector. When the communication/analog special adapter
is connected, this connector is not used.
[3] Expansion board securing These holes are designed to secure the expansion board with screws
screw holes (2 places) (supplied with the expansion board). The expansion board dummy cover
is fitted before shipment. Remove the dummy cover, and fit the board.
[4] Nameplate The product model name, control number and power supply
specifications are shown.
MITSUBISHI PROGRAMMABLE
CONTROLLER
MODEL FX3U-48MR/ES
100-240VAC 50/60Hz 40W
OUT:30VDC/240VAC 2A(COSφ=1)
SERIAL 570001
5 7 0 0 0 1
Control number
Month (Example: July):(1 to 9 = January to September,
X = October, Y = November, Z = December)
Year (Example: 2005): Last digit of year
[5] DIN rail mounting groove The unit can be installed on DIN46277 rail (35 mm (1.38") wide).
34
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
Introduction
3. Introduction of Products (Compliant with Overseas Standards)
2
3.1 List of Products (to be Connected) and Interpretation of Model Names
Part Names
Features and
The following system configuration is classified into product groups A to O in the product introduction sections
given below.
F Display modules
•FX3U-7DM
G Expansion boards
•FX3U-USB-BD •FX3U-CNV-BD
K Battery
•FX3U-32BL
L Memory cassettes
•FX3U-FLROM-16
3
•FX3U-7DM-HLD •FX3U-232-BD •FX3U-FLROM-64
Introduction
Product
RD
•FX3U-FLROM-64L
SD
•FX3U-422-BD
FX3U-32BL
LOT.44
············
•FX3U-485-BD
4
FX 3U -232ADP
FX 3U -232ADP OUT 0 IN 0
1 1
P O WE R 2 2
P OW E R
3 3
RD
RD 4 4
SD 5 5
SD
6 6
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 ・ 7
L N ・ 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 7
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
IN POWER POWER
10 11 12 13 14 15 16 17
Specifications
POWER
POWER
RUN
RUN
BATT
ERROR
ERROR
FX3U-48MR/ES OUT
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
0 11
10 1 122 133 144 155 166 177 20 21 22 23 24 25 26 27
FX 3U-48M FX2N -16EYR
10 11 12 13 14 15 16 17 FX2N -16EX
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
OUT 0 IN 0
1 1
2 2
R
3 3
4 4
5 5
6 6
7 7
•FX3U-4AD-ADP
Analog
•FX3U-16MR/ES
Input/output
•FX3U-16MT/ES(S) •FX2N-8EX-ES/UL
Input
•FX2N-8EYR-ES/UL
Output
5
•FX3U-4DA-ADP •FX3U-32MR/ES •FX3U-32MT/ES(S) •FX2N-8EX •FX2N-8EYT-ESS/UL
Devices
Peripheral
Version and
•FX2N-8EX-UA1/UL •FX2N-8EYR
•FX3U-4AD-PT-ADP •FX3U-48MR/ES •FX3U-48MT/ES(S) •FX2N-16EX-ES/UL •FX2N-8EYT
•FX3U-4AD-TC-ADP •FX3U-64MR/ES •FX3U-64MT/ES(S) •FX2N-16EX •FX2N-8EYT-H
Communication •FX3U-80MR/ES •FX3U-80MT/ES(S) •FX2N-16EX-C •FX2N-16EYR-ES/UL
•FX3U-128MR/ES •FX3U-128MT/ES(S) •FX2N-16EXL-C •FX2N-16EYT-ESS/UL
•FX3U-232ADP •FX2N-16EYR
•FX3U-485ADP •FX3U-16MR/DS •FX3U-16MT/DS(S) Input/Output •FX2N-16EYT
•FX3U-32MR/DS •FX3U-32MT/DS(S) •FX2N-16EYT-C
High-speed
input/output
•FX3U-48MR/DS
•FX3U-64MR/DS
•FX3U-48MT/DS(S)
•FX3U-64MT/DS(S)
•FX2N-8ER-ES/UL
•FX2N-8ER •FX2N-16EYS 6
FX Series terminal blocks can be
•FX3U-80MR/DS •FX3U-80MT/DS(S)
Configuration
System
•FX3U-4HSX-ADP connected to connector type units.
•FX3U-2HSY-ADP
J Extension cables J Connector conversion adapter
·FX0N-30EC ·FX2N-CNV-BC
·FX0N-65EC
L N
CO M
24+
X0
X1
X2
X3
X4
X5
X6
X7
X0
X1
X2
X3
X4
X5
IN
X6
X7
0
X0
1
X1
X2
2
X3
3
X4
X5
X6
4
X7
5 6 7 0 1 2 3 4 5 6 7
7
0 1 2 3 4 5 6 7
B Input/output powered
A/D D/A SD
RD
extension units
Input/output
D Special function blocks 8
Analog Positioning Communication
Installation
•FX2N-32ER-ES/UL
•FX2N-48ER-ES/UL •FX3U-4AD •FX3U-20SSC-H •FX2N-232IF
•FX2N-48ER-UA1/UL •FX3U-4DA •FX2N-1HC Network
•FX2N-32ER •FX2N-2AD •FX2N-1PG(-E)
•FX2N-48ER •FX2N-2DA •FX2N-10PG •FX2N-32CCL
•FX2N-48ER-DS •FX2N-4AD •FX2N-16CCL-M
•FX2N-48ER-D •FX2N-4AD-TC E Special function units •FX2N-64CL-M
•FX2N-32ES
•FX2N-48ES
•FX2N-4AD-PT
•FX2N-4DA Positioning
•FX2N-16LNK-M
•FX2N-32ASI-M
9
•FX2N-5A
Wiring
Power Supply
Preparation and
SD RD L ERR .
B RATE
01
4
2
3
S TATION NO .
0 1X109 0 1X1
PW L RUN
AJ65BTB1-16D
SD RD L E RR.
B RATE
01
4
2
3
STATION NO .
0 1X109 0 1X1
FX-16E-TB
10
•FX3U-1PSU-5V
0 1 2 3 4 5 6 7 8 9 A B C D E F 28 2 0 1 2 3 4 5 6 7 8 9 A B C D E F 28 2
37 3 37 3
654 654 654 654
35
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
Series name
Power supply, Input/output type: Connection on terminal block
• R/ES : AC power supply/24V DC (sink/source) input/relay output
• T/ES : AC power supply/24V DC (sink/source) input/transistor (sink) output
Total number of input Main unit
• T/ESS: AC power supply/24V DC (sink/source) input/transistor (source) output
and output points • R/DS : DC power supply/24V DC (sink/source) input/relay output
• T/DS : DC power supply/24V DC (sink/source) input/transistor (sink) output
• T/DSS: DC power supply/24V DC (sink/source) input/transistor (source) output
: Compliance with standard or self-declaration : Not targeted − : Not applicable
Number of input/output points CE
Output type UL
Total Number of Number of Model name (connection form: Marine
number of input output EMC LVD cUL
terminal block)
points points points
AC power supply common to 24V DC sink and source input
16 8 8 FX3U-16MR/ES Relay *
16 8 8 FX3U-16MT/ES Transistor (sink) *
16 8 8 FX3U-16MT/ESS Transistor (source) *
32 16 16 FX3U-32MR/ES Relay *
32 16 16 FX3U-32MT/ES Transistor (sink) *
32 16 16 FX3U-32MT/ESS Transistor (source) *
48 24 24 FX3U-48MR/ES Relay *
48 24 24 FX3U-48MT/ES Transistor (sink) *
48 24 24 FX3U-48MT/ESS Transistor (source) *
64 32 32 FX3U-64MR/ES Relay *
64 32 32 FX3U-64MT/ES Transistor (sink) *
64 32 32 FX3U-64MT/ESS Transistor (source) *
80 40 40 FX3U-80MR/ES Relay *
80 40 40 FX3U-80MT/ES Transistor (sink) *
80 40 40 FX3U-80MT/ESS Transistor (source) *
128 64 64 FX3U-128MR/ES Relay *
128 64 64 FX3U-128MT/ES Transistor (sink) *
128 64 64 FX3U-128MT/ESS Transistor (source) *
DC power supply common to 24V DC sink and source input
16 8 8 FX3U-16MR/DS Relay *
16 8 8 FX3U-16MT/DS Transistor (sink) *
16 8 8 FX3U-16MT/DSS Transistor (source) *
32 16 16 FX3U-32MR/DS Relay *
32 16 16 FX3U-32MT/DS Transistor (sink) *
32 16 16 FX3U-32MT/DSS Transistor (source) *
48 24 24 FX3U-48MR/DS Relay *
48 24 24 FX3U-48MT/DS Transistor (sink) *
48 24 24 FX3U-48MT/DSS Transistor (source) *
64 32 32 FX3U-64MR/DS Relay *
64 32 32 FX3U-64MT/DS Transistor (sink) *
64 32 32 FX3U-64MT/DSS Transistor (source) *
80 40 40 FX3U-80MR/DS Relay *
80 40 40 FX3U-80MT/DS Transistor (sink) *
80 40 40 FX3U-80MT/DSS Transistor (source) *
* Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment.
→ For more information on CE, UL and cUL, refer to Page 15 or later.
36
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
1
3.1.2 [B] Input/output powered extension units
Introduction
The input/output powered extension unit incorporates a power supply circuit and input and output terminals.
B It is designed to add input and output terminals.
It can supply power to extension devices connected on the downstream side.
Part Names
Features and
Series name Classification 1: None*1: Not compliant with standard
UL:Compliant with standard
Power supply, Input/output type: Connection on terminal block
•R : AC Power supply/24V DC (sink) input/relay output
•S
•T
: AC Power supply/24V DC (sink) input/triac (SSR) output
: AC Power supply/24V DC (sink) input/transistor (sink) output
3
Introduction
Product
•R-ES : AC Power supply/24V DC (sink/source) input/relay output
Total number of •T-ESS: AC Power supply/24V DC (sink/source) input/transistor (source) output
input and output •R-UA1: AC Power supply/100V AC input/relay output
points •R-DS : DC Power supply/24V DC (sink/source) input/relay output
Input/output extension •T-DSS: DC Power supply/24V DC (sink/source) input/transistor (source) output
•R-D : DC Power supply/24V DC (sink) input/relay output
•T-D : DC Power supply/24V DC (sink) input/transistor (sink) output 4
Specifications
: Compliance with standard or self-declaration : Not targeted − : Not applicable
Number of input/output points CE
Output type
Total Number of Number of UL
Model name (connection form: Marine
number of input output EMC LVD cUL
terminal block)
points points points
5
AC power supply common to 24V DC sink and source input
Devices
Peripheral
Version and
32 16 16 FX2N-32ER-ES/UL Relay *2
32 16 16 FX2N-32ET-ESS/UL Transistor (source) *2
48 24 24 FX2N-48ER-ES/UL Relay *2
48 24 24 FX2N-48ET-ESS/UL Transistor (source) *2
AC power supply common to 100V AC sink and source input 6
Configuration
System
48 24 24 FX2N-48ER-UA1/UL Relay −
AC power supply only for 24V DC sink input
32 16 16 FX2N-32ER Relay − − − −
32 16 16 FX2N-32ES Triac − − − −
32 16 16 FX2N-32ET Transistor (sink) − − − − 7
48 24 24 FX2N-48ER Relay − − − −
10
Input Wiring
37
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
38
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
1
3.1.4 [D] [E] Special function units/blocks
Introduction
For details of each product, refer to the product manual.
1. Analog control
: Compliance with standard or self-declaration
Analog
: Not targeted − : Not applicable
CE
2
D Model name Description
UL
Marine
Part Names
Features and
Input Output EMC LVD cUL
Analog input
FX3U-4AD 4ch − Voltage/current input −
FX2N-2AD 2ch − Voltage/current input *
FX2N-4AD 4ch − Voltage/current input * 3
Voltage/current/temperature
Introduction
Product
FX2N-8AD 8ch − *
(thermocouple) input
Temperature (resistance
FX2N-4AD-PT 4ch − *
thermometer sensor) input
Temperature (thermocouple)
FX2N-4AD-TC 4ch −
input
*
4
Analog output
Specifications
FX3U-4DA − 4ch Voltage/current output −
FX2N-2DA − 2ch Voltage/current output *
FX2N-4DA − 4ch Voltage/current output *
Analog input/output mixed
FX0N-3A 2ch 1ch Voltage/current input/output − *
5
Devices
Peripheral
Version and
FX2N-5A 4ch 1ch Voltage/current input/output *
Temperature control
Temperature control (resistance
FX2N-2LC 2 loops − thermometer sensor/ −
thermocouple)
6
* Please consult with Mitsubishi Electric for information on marine standard practices and the
Configuration
System
corresponding types of equipment.
→ For more information on CE, UL and cUL, refer to Page 15 or later.
2. High-speed counter
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE 7
D Model name Description
UL
Marine
9
Wiring
Power Supply
Preparation and
10
Input Wiring
39
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
40
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
1
3.1.5 [F] Display modules and holder
Introduction
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE
F Model name Description
UL
cUL
Marine
EMC LVD
FX3U-7DM
Display module that can be incorporated in FX3U Series *1 − *2
2
main unit
Part Names
Features and
Holder and extension cable to fit FX3U-7DM display module
FX3U-7DM-HLD − − − −
on panel
Display module to be connected to peripheral device
FX-10DM(-SET0) − − − −
connector with cable (manual in Japanese supplied)
FX-10DM-E
Display module to be connected to peripheral device
connector with cable (manual in English supplied)
− − 3
Introduction
Product
*1. Products manufactured in and after May, 2005 will comply with the overseas standard.
*2. Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment.
Specifications
3.1.6 [G] Expansion boards
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE
G Model name Description
UL
cUL
Marine
5
EMC LVD
FX3U-CNV-BD Conversion of connector for fitting special adapter *1 − *2
Devices
Peripheral
Version and
FX3U-232-BD For RS-232C communication *1 − *2
For RS-422 communication
FX3U-422-BD (having the same function as that of peripheral device *1 − *2
connector incorporated in main unit)
FX3U-485-BD For RS-485 communication *1 − *2
6
Configuration
System
For USB communication
FX3U-USB-BD *1 − *2
(for personal computer for programming)
*1. Products manufactured in and after May, 2005 will comply with the overseas standard.
*2. Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment. 7
→ For more information on CE, UL and cUL, refer to Page 15 or later.
1. Analog functions
: Compliance with standard or self-declaration : Not targeted − : Not applicable
8
Installation
CE
H Model name Description
UL
Marine
EMC LVD cUL
FX3U-4AD-ADP 4-ch voltage input/current input *1 *1 *2
FX3U-4DA-ADP 4-ch voltage output/current output *1 *1 *2
FX3U-4AD-PT-ADP 4-ch platinum resistance thermometer sensor input *1 *1 *2
9
Wiring
Power Supply
Preparation and
*1. Products manufactured in and after May, 2005 will comply with the overseas standard.
*2. Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment.
→ For more information on CE, UL and cUL, refer to Page 15 or later.
10
Input Wiring
41
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
2. Communication functions
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE
H Model name Description
UL
Marine
EMC LVD cUL
FX3U-232ADP RS-232C communication *1 *1 *2
FX3U-485ADP RS-485 communication *1 *1 *2
*1. Products manufactured in and after May, 2005 will comply with the overseas standard.
*2. Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment.
→ For more information on CE, UL and cUL, refer to Page 15 or later.
42
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
1
3.1.9 [J] Extension cables and connector conversion adapter
Introduction
[K] Battery [L] Memory cassettes
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE
J Classification Model name Description
UL
Marine
2
EMC LVD cUL
K
Part Names
Features and
0.65m These cables are used to mount input/output
FX0N-65EC*1 − − − −
(2’1") extension blocks for FX2N and special
L Extension 0.3m function units/blocks (except FX2N-10GM and
FX0N-30EC*1 − − − −
(0’11") FX2N-20GM) away from the main unit.
cables J
This cable is used when FX2N-10GM or
FX2N-GM-65EC
0.65m
(2’1")
FX2N-20GM is mounted at the top of the − − − − 3
extension units/blocks.
Introduction
Product
Connector Connector conversion adapter to connect input/
conversion FX2N-CNV-BC output extension blocks for FX2N and special function − − − −
adapter J blocks with model FXON-30/65EC extension cable
This battery backs up the following data.
• Program memory in built-in RAM
4
Specifications
Battery K FX3U-32BL • Keep devices (battery backup devices) − − − −
• Results of sampling trace
• Time on clock
FX3U-FLROM-
16k-step flash memory − *3
16
Memory FX3U-FLROM- 5
64k-step flash memory *2 − *3
64
Devices
Peripheral
Version and
cassettes L
FX3U-FLROM-
64k-step flash memory (with transfer switch) − *3
64L
*1. When the extension cable (FX0N-30EC or FX0N-65EC) is used, use up to one cable for one system.
When an extension block is added, use FX2N-CNV-BC in addition to the cable.
These extension cables are unusable for FX2N-10GM and FX2N-20GM.
6
Configuration
System
*2. Products manufactured in and after May, 2005 will comply with the overseas standard.
*3. Please consult with Mitsubishi Electric for information on marine standard practices and the
corresponding types of equipment.
→ For more information on CE, UL and cUL, refer to Page 15 or later.
7
3.1.10 [M] FX Series terminal blocks (cables and connectors)
FX-32E-TB
32 output points or input/output connector
− −
9
16 input/output
Wiring
Power Supply
Preparation and
points
FX-16EX-A1-TB 16 − 100V AC input − − −
FX-16EYR-TB − 16 Relay output − − −
FX-16EYS-TB − 16 Triac output − − − −
FX-16EYT-TB − 16 Transistor output (sink) − − 10
Input Wiring
43
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.1 List of Products (to be Connected) and Interpretation of Model Names
2. Input/output cables
Model name Function
FX-16E-500CAB-S 5m(16’4") Bulk wire
FX-16E-150CAB 1.5m(4’11")
FX-16E-300CAB 3m(9’10") Flat cable (with tube). Both ends are provided with 20-pin connectors.
FX-16E-500CAB 5m(16’4")
FX-16E-150CAB-R 1.5m(4’11")
FX-16E-300CAB-R 3m(9’10") Round multicore cable. Both ends are provided with 20-pin connectors.
FX-16E-500CAB-R 5m(16’4")
FX-A32E-150CAB 1.5m(4’11") Flat cable (with tube). The end on the PLC side is provided with two 20-pin
FX-A32E-300CAB 3m(9’10") connectors, and the end on the terminal block side is provided with a
FX-A32E-500CAB 5m(16’4") exclusive connector. 1 common terminal for 32 input/output points
3. Input/output connector
Model name Function
FX2C-I/O-CON 10-piece set Input/output connector for flat cable
FX2C-I/O-CON-S 5-piece set Input/output connector for bulk wire for 0.3 mm2 [AGW22]
FX2C-I/O-CON-SA 5-piece set Input/output connector for bulk wire for 0.5 mm2 [AGW20]
44
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.2 Connector Types and Cables for Program Communication
1
3.2 Connector Types and Cables for Program Communication
Introduction
RS-232C/RS-422 cable
Connection cabling
Connection cabling for extention devices
Peripheral device connector
FX-232AWC-H 3
2
A 2
Part Names
Features and
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 ・
1 2 RS-422
L N ・ 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
RS-232C
0 1 2 3 4 5 6 7 2 0 21 2 2 23 2 4 25 2 6 27
IN
10 11 12 1 3 14 1 5 16 1 7
POWER
POWER
RUN
RUN
4
BATT
ERROR
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 2 0 21 2 2 23 24 25 26 27
OUT
0 11
10 1 12
2 133 14
4 155 16
6 17
7 2 0 21 2 2 23 2 4 25 2 6 27
FX3U -48M
10 11 12 1 3 14 1 5 16 1 7
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
5
3 1
USB 8 FX-USB-AW
3
FX-USB-AW
MITSUBISHI
(RS-422)
RD
SD
PW
FX
B
Special adapter
Introduction
Product
FX3U-232ADP
A
6 FX 3U -232ADP
4
POW ER
RS-232C
RD
SD
4
Expansion board
Specifications
FX3U-232-BD
A
RS-232C 4 6 RD
4 SD
FX-232AWC-H
5
1
FX3U-422-BD 5
RS-232C 2 RS-422
Devices
Peripheral
Version and
7
USB 3 8 FX-USB-AW
FX-USB-AW
MITSUBISHI
(RS-422)
RD
SD
PW
FX
6
B
FX3U-USB-BD
Configuration
System
USB 3
8 RD
B
SD
2 "FX-422CAB0" + 1 "F2-232CAB-2" + 9
Half pitch
4 "FX-232AW/FX-232AWC/FX-232AWC-H"
Wiring
Power Supply
Preparation and
14Pin
4 FX-232CAB-2
2 "FX-422CAB0" + 1 "F2-232CAB" +
D-SUB "FX-232AW/FX-232AWC/FX-232AWC-H"
25Pin
4 F2-232CAB-1
10
Input Wiring
*1. When FX-232AW or FX-232AWC is used, the communication baud rate is 19,200 bps or less.
→ For details, refer to Subsection 3.2.3.
45
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.2 Connector Types and Cables for Program Communication
→ For more information, refer to Chapter 5 "Version Information and Peripheral Equipment
Connectability".
46
FX3U Series Programmable Controllers 3 Introduction of Products (Compliant with Overseas Standards)
User’s Manual - Hardware Edition 3.2 Connector Types and Cables for Program Communication
1
3.2.3 Converters and interface
Introduction
: Compliance with standard or self-declaration : Not targeted − : Not applicable
CE UL
Model name Description Marine
EMC LVD cUL
RS-232C/RS-422 Converters 2
Part Names
Features and
RS-232C/RS-422 converter (high-speed type)
FX-232AWC-H*1 *2 − −
Communication speed: Applicable to 9,600 to 115,000 bps .
FX-232AW RS-232C/RS-422 converters − − − −
FX-232AWC Communication speed: Applicable to 9,600/19,200 bps − − − −
USB Interface
3
FX-USB-AW*1 USB-RS-422 converter (with 3m(9’10") USB cable) *3 − −
Introduction
Product
*1. When the programming software is not applicable to FX3U or FX3UC, the converter is applicable only
to 9,600 or 19,200 bps.
*2. Products manufactured in and after July, 2004 conform to the overseas standard.
*3. Products manufactured in and after August, 2004 conform to the overseas standard. 4
Specifications
5
Devices
Peripheral
Version and
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
47
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.1 Generic Specifications
Item Specification
Ambient
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
temperature
Ambient
5 to 95%RH (no condensation) when operating
humidity
Compliant with EN 68-2-6
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Vibration Sweep Count for X,
When installed on 10 to 57 − 0.035 Y, Z: 10 times
resistance
DIN rail 57 to 150 4.9 − (80 min in each
direction)
When installed 10 to 57 − 0.075
directly 57 to 150 9.8 −
Shock Compliant with EN 68-2-27
resistance (147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z)
Noise By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of
resistance 30 to 100 Hz
Dielectric 1.5kV AC for one minute
Compliant with JEM-1021
withstand
500V AC for one minute Between each terminals*2 and ground terminal
voltage*2
Insulation Compliant with JEM-1021
5MΩ or more by 500V DC megger
resistance*2 Between each terminals*2 and ground terminal
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed>*1
Working
Free from corrosive or flammable gas and excessive conductive dust
atmosphere
Working
Compliant with IEC61131-2 (<2000m)*3
altitude
*2. For more information on the dielectric withstand voltage test and the insulation resistance test of the
terminals of each product, refer to the following.
→ Refer to Subsection 4.1.1.
*3. Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the
PLC.
48
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.1 Generic Specifications
1
4.1.1 Dielectric withstand voltage test and insulation resistance test
Introduction
Perform dielectric withstand voltage test and insulation resistance test at the following voltage between each
terminals and the main unit ground terminal.
Dielectric Insulation
Between terminals
strength resistance
Remarks 2
Part Names
Features and
Terminals of main unit and input/output powered extension unit/block
• Between power supply terminal (AC 1.5kV AC
−
power supply) and ground terminal for 1 min
• Between power supply terminal (DC 500V AC for
−
power supply) and ground terminal 1 min
• Between 24V DC service power supply
3
500V AC for
Introduction
Product
connected to input terminal (24V DC) −
1 min 5M Ω or
and ground terminal
more on
• Between input terminal (100V AC) and 1.5kV AC Only input/output powered extension unit/
500V DC
ground terminal for 1 min block
Megger
• Between output terminal (relay) and 1.5kV AC
ground terminal for 1 min
− 4
Specifications
• Between output terminal (transistor) 500V AC for
−
and ground terminal 1 min
• Between output terminal (triac) and 1.5kV AC Only input/output powered extension unit/
ground terminal for 1 min block
Terminals of expansion board, special adapter and special function unit/block
Since the communication line and the main
5
• Between terminal of expansion board
Devices
Peripheral
Version and
unit CPU are not insulated, it is not allowed to
(except FX3U-USB-BD and FX3U- Not allowed Not allowed
perform the dielectric withstand voltage test
CNV-BD) and ground terminal
and insulation resistance test between them.
Do not perform the dielectric withstand
• Between terminal of expansion board voltage test and insulation resistance test
(FX3U-USB-BD) and ground terminal
Not allowed Not allowed
between the communication line and the main 6
unit CPU.
Configuration
System
5M Ω or
• Between terminal of special adapter 500V AC for more on
−
and ground terminal 1 min 500V DC
Megger
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
49
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.2 Power Supply Specifications
Specifications
Item FX3U-16M / FX3U-32M / FX3U-48M / FX3U-64M / FX3U-80M / FX3U-128M /
E E E E E E
Supply voltage 100 to 240V AC
Allowable supply
85 to 264V AC
voltage range
Rated frequency 50 / 60 Hz
Allowable
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
instantaneous
When the supply voltage is 200V AC, the time can be change to 10 to 100 ms by editing the user
power failure
program.
time
Power fuse 250V, 3.15A 250V, 5A
Rush current 30 A max. 5 ms or less/100V AC, 65 A max. 5 ms or less/200V AC
Power
30 W 35 W 40 W 45 W 50 W 65 W
consumption*1
24V DC service
400 mA or less 600 mA or less
power supply*2
5V DC built-in
500 mA or less
power supply*3
*1. These power consumption values are maximum values which apply to the main unit's 24V DC service
power supply when there are input/output extension blocks and special function units/blocks.
→ For input/output powered extension units/blocks power consumption information,
refer to Section 15.2.
*2. When input/output extension blocks are connected, 24V DC service power is consumed by the blocks,
and the power to be consumed by the main unit is reduced.
→ For details on 24V DC service power supply, refer to Section 6.5.
*3. The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
50
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.2 Power Supply Specifications
1
4.2.2 DC Power Supply Type
Introduction
Specifications
Item
FX3U-16M /D FX3U-32M /D FX3U-48M /D FX3U-64M /D FX3U-80M /D
Supply voltage 24V DC
Allowable supply
2
16.8 to 28.8V DC*3
Part Names
Features and
voltage range
Allowable
instantaneous power Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
failure time
Power fuse 250V, 3.15A 250V, 5A
Rush current 35 A max. 0.5 ms or less/24V DC
3
Introduction
Product
Power consumption*1 25 W 30 W 35 W 40 W 45 W
24V DC service power
−
supply
5V DC built-in power
500 mA or less
supply*2 4
Specifications
*1. This power consumption is the value maximized by input/output extension blocks and special function
units/blocks connected to the main unit.
→ For input/output powered extension units/blocks power consumption information,
refer to Section 15.2.
*2. The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
5
Devices
Peripheral
Version and
special adapters and expansion boards.
*3. When supply voltage is 16.8 to 19.2V DC, the connectable extension equipment decreases.
For details, refer to Subsection 6.5.3 or 6.5.4.
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
51
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.3 Input Specifications
*1 *1
X X
Input circuit configuration
*1 Input impedance • DC power supply type
Sink input wiring Source input wiring
Fuse Fuse
24V 24V
(24V) DC (24V) DC
*3 *3
(0V) (0V)
S/S S/S
*1 *1
X X
52
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.4 Output Specifications
1
4.4 Output Specifications
Introduction
The main unit output specifications are explained below.
Part Names
Features and
from Y010 to the largest number that the main unit has.
(The output numbers of FX3U-16MR/ES are Y000 to Y007.)
Introduction
Product
Number of output
8 points 16 points 24 points 32 points 40 points 64 points
points
Fixed terminal
Connecting type block Removable terminal block (M3 screw)
(M3 screw)
Output type Relay 4
Specifications
External power 30V DC or less or 240V AC or less
supply (250V AC or less when the unit does not comply with CE, UL or cUL standards)
2 A / point
The total load current of resistance loads per common terminal should be the following value.
→ For details on the common terminal for each model,
Resistance
load
refer to the terminal block layout. 5
Max. • 1 output point/common terminal: 2 A or less
Devices
Peripheral
Version and
load • 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
80 VA
Inductive
→ For the product life, refer to Subsection 4.4.2.
load
→ For cautions on external wiring, refer to Subsection 12.2.4. 6
Min. load 5V DC, 2 mA (reference value)
Configuration
System
Open circuit leakage
−
current
OFF ON Approx. 10 ms
Response
time
ON OFF Approx. 10 ms 7
Load
Y
8
DC power
Installation
supply
COM
Fuse
Output circuit Load
configuration Y
External
power supply
Fuse
COM 9
Wiring
Power Supply
Preparation and
10
Input Wiring
53
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.4 Output Specifications
1. Inductive load
Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause
arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller,
the arc energy gets larger.
The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000
operations at 20VA.
The following table shows the approximate life of a relay based on the results of an operation life test.
The product life of relay contacts becomes considerably shorter than the above conditions when the rush
overcurrent is shut down.
→ For precautions on using inductive loads, refer to Subsection 12.2.4 2.
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make
sure that the rush current does not exceed the current corresponding to the maximum specified resistance
load.
2. Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
3. Capacitive load
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load. Capacitive
loads such as capacitors may be present in electronic circuit loads including inverters.
→ For the maximum specified resistance load, refer to Subsection 4.4.1.
54
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.4 Output Specifications
1
4.4.3 Transistor output (sink type)
Introduction
The output numbers in the table indicate the main unit terminal numbers. "Y010 or more" means the numbers
from Y010 to the largest number that the main unit has.
(The output numbers of FX3U-16MT/ S are Y000 to Y007.)
Item
Transistor output (sink) specifications 2
FX3U-16MT/ S FX3U-32MT/ S FX3U-48MT/ S FX3U-64MT/ S FX3U-80MT/ S FX3U-128MT/ES
Part Names
Features and
Number of output
8 points 16 points 24 points 32 points 40 points 64 points
points
Fixed terminal
Connecting type block Removable terminal block (M3 screw)
(M3 screw) 3
Output type/form Transistor/sink output
Introduction
Product
External power
5 to 30V DC
supply
0.5A / point
The total load current of resistance loads per common terminal should be the following value.
Resistance
→ For details on the common terminal for each model, 4
refer to the terminal block layout.
Specifications
load
Max. load • 1 output point/common terminal: 0.5 A or less
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 1.6 A or less
Inductive
12W/24V DC
load 5
Open circuit leakage
Devices
Peripheral
Version and
0.1 mA or less/30V DC
current
ON voltage 1.5 V or less
Min. load −
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Response
OFF→ON
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC) 6
time Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Configuration
System
ON→OFF
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Circuit insulation Photocoupler insulation
Display of output
LED on panel lights when photocoupler is driven.
operation
7
9
Wiring
Power Supply
Preparation and
10
Input Wiring
55
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.4 Output Specifications
Load
Y
Output circuit Fuse
configuration +V
DC power
supply
56
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.5 Performance Specifications
1
4.5 Performance Specifications
Introduction
The performance specifications are common to FX3U Series PLCs.
Item Performance
Part Names
Features and
Batch processing system (when END instruction is executed)
Input/output control system
Input/output refresh instruction and pulse catch function are provided.
Programming language Relay symbol system + step-ladder system (SFC notation possible)
64000-step (2k-, 4k-, 8k-, 16k- or 32k-step memory can be selected by
parameter settings.) 3
Comments and file registers can be created in the program memory by
Introduction
Product
Max. memory capacity parameter settings.
• Comments: Up to 6350 points (50 points/500 steps)
• File registers: Up to 7000 points (500 points/500 steps)
64000-step RAM (backed up by built-in lithium battery)
Built-in memory
Program capacity/type
• Battery life: Approx. 5 years (guarantee for 1 year) 4
• With password protection function (with entry code function)
memory
Specifications
Flash memory (The max. memory capacity varies depending on the
model of the memory cassette.)
Memory cassette • FX3U-FLROM-64L:64000 steps (with loader function)
(Option) • FX3U-FLROM-64: 64000 steps (without loader function)
• FX3U-FLROM-16: 16000 steps (without loader function)
Max. allowable write: 10,000 times
5
Devices
Peripheral
Version and
Writing function
Provided (Program can be modified while the PLC is running.)
during running
Built-in
Real-time
Clock function 1980 to 2079 (with correction for leap year)
clock
2- or 4-digit year, accuracy within ±45 seconds/month at 25°C
Ver.2.30 or later
6
• Sequence instructions: 29
Configuration
System
• Step-ladder instructions: 2
Kinds of Basic instructions
Former than Ver. 2.30
instructions • Sequence instructions: 27
• Step-ladder instructions: 2
Applied instructions 209 kinds, 486 instructions 7
Processing Basic instructions 0.065 µs/instruction
10
Input Wiring
57
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.5 Performance Specifications
Item Performance
For general
M0 to M499 500 points
[changeable] The retentive status can be changed by
For keeping parameter settings.
M500 to M1023 524 points
[changeable]
Auxiliary relay
For keeping M1024 to
6656 points −
[fixed] M7679
M8000 to
For special 512 points −
M8511
Initial state
(for general) S0 to S9 10 points
[changeable]
The retentive status can be changed by
For general
S10 to S499 490 points parameter settings.
[changeable]
For keeping
State S500 to S899 400 points
[changeable]
For annunciator
(For keeping) S900 to S999 100 points −
[changeable]
For keeping
S1000 to S4095 3096 points −
[fixed]
100 ms T0 to T191 192 points 0.1 to 3,276.7 sec
100 ms
[for subroutine/
T192 to T199 8 points 0.1 to 3,276.7 sec
interruption
subroutine]
Timer (on- 10 ms T200 to T245 46 points 0.01 to 327.67 sec
delay timer)
1 ms accumulating
T246 to T249 4 points 0.001 to 32.767 sec
type
100 ms accumulating
T250 to T255 6 points 0.1 to 3,276.7 sec
type
1 ms T256 to T511 256 points 0.001 to 32.767 sec
Increment for general
C0 to C99 100 points Counting from 0 to 32,767
(16 bits) [changeable]
The retentive status can be changed by
Increment for keeping
C100 to C199 100 points parameter settings.
(16 bits) [changeable]
Counter Both directions for
general (32 bits) C200 to C219 20 points Counting from -2,147,483,648 to
[changeable] +2,147,483,647
The retentive status can be changed by
Increment for keeping
C220 to C234 15 points parameter settings.
(32 bits) [changeable]
1-phase 1-count input
in both directions (32 C235 to C245 Counting from -2,147,483,648 to
bits) [changeable] Up to 8 +2.147,483,647 [For keeping]
points can The retentive status can be changed by
1-phase 2-count input
High-speed be used in parameter settings.
in both directions (32 C246 to C250
counter range from → For the high-speed
bits) [changeable]
C235 to counter operating
2-phase 2-count input C255. frequency, refer to the table
in both directions (32 C251 to C255 shown in the next page.
bits) [changeable]
58
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.5 Performance Specifications
1
Item Performance
Introduction
For general (16 bits)
D0 to D199 200 points
[changeable] The retentive status can be changed by
For keeping (16 bits) parameter settings.
D200 to D511 312 points
[changeable]
Data register
For keeping (16 bits) D512 to D7999 7488 points
D1000 and later in 7488 points of fixed 2
(32 bits when data register for keeping can be set as
Part Names
Features and
[fixed] <D1000 to <7000
paired) file register points in 500-point units by
<File register> D7999> points>
changing the parameter settings.
For special (16 bits) D8000 to D8511 512 points −
V0 to V7
For index (16 bits)
Z0 to Z7
16 points −
3
32768
Introduction
Product
Extension register (16 bits) R0 to R32767 Retained by battery during power failure
points
ER0 to 32768 Usable only when memory cassette is
Extension file register (16 bits)
ER32767 points mounted
For branching of For CJ instructions and CALL
JAMP and CALL
P0 to P4095 4096 points
instructions 4
Input interruption and
Specifications
Pointer input delay I0 to I5 6 points
interruption −
Devices
Peripheral
Version and
16 bits -32,768 to +32,767
Decimal number (K)
32 bits -2,147,483,648 to +2,147,483,647
Hexadecimal number 16 bits 0 to FFFF
(H) 32 bits 0 to FFFFFFFF
Constant
Real number (E) 32 bits -1.0 x 2128 to -1.0 x 2-126,0,1.0 x 2-126 to 1.0 x 2128 6
Decimal-point and exponential notations are possible.
Configuration
System
Designation by characters enclosed with " "
Character string (" ") Character string Up to 32 one-byte characters can be used for a
constant in an instruction.
9
Wiring
Power Supply
Preparation and
10
Input Wiring
59
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.6 External Dimensions (Weight and Installation)
0 1 2 3
80 (3.15")
90 (3.55")
IN
4 5 6 7
POWER
RUN
BATT
ERROR
0 1 2 3
OUT
4 5 6 7
FX3U-16M
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
60
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.6 External Dimensions (Weight and Installation)
1
4.6.2 FX3U-48M , FX3U-64M , FX3U-80M , FX3U-128M
Introduction
4-φ 4.5 mounting holes Unit: mm (inches)
Part Names
Features and
80 (3.15")
90 (3.55")
3
Introduction
Product
22 (0.87") W1 (mounting hole pitch) 9 (0.36")
86 (3.39")
W
Specifications
FX3U-48M 182 (7.17") 155 (6.11") 0.85 (1.87 lbs)
FX3U-48MR/DS
FX3U-48MT/DS
FX3U-48MT/DSS
FX3U-64MR/ES
FX3U-64MT/ES
5
Devices
Peripheral
Version and
FX3U-64MT/ESS
FX3U-64M 220 (8.67") 193 (7.6") 1.00 (2.2 lbs)
FX3U-64MR/DS
FX3U-64MT/DS
FX3U-64MT/DSS
FX3U-80MR/ES 6
Configuration
System
FX3U-80MT/ES
FX3U-80MT/ESS
FX3U-80M 285 (11.23") 258 (10.16") 1.20 (2.64 lbs)
FX3U-80MR/DS
FX3U-80MT/DS
FX3U-80MT/DSS 7
FX3U-128MR/ES
9
Wiring
Power Supply
Preparation and
10
Input Wiring
61
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.7 Terminal Layout
4.7.1 Interpretation
Output terminals
FX3U-32MR/ES (Output side terminals of FX3U-16MR/ )
connected to COM4
Common terminal
(4 points/common Output terminal Partition Same signal name Partition
terminal)
62
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.7 Terminal Layout
1
4.7.2 FX3U-16M
Introduction
• AC power supply type
S/S 0V X0 X2 X4 X6
L N 24V X1 X3 X5 X7
2
Part Names
Features and
FX3U-16MR/ES
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
FX3U-16MT/ES FX3U-16MT/ESS 3
Introduction
Product
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
COM0 COM1 COM2 COM3 COM4 COM5 COM6 COM7 +V0 +V1 +V2 +V3 +V4 +V5 +V6 +V7
Specifications
FX3U-16MR/DS
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
5
FX3U-16MT/DS FX3U-16MT/DSS
Devices
Peripheral
Version and
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
COM0 COM1 COM2 COM3 COM4 COM5 COM6 COM7 +V0 +V1 +V2 +V3 +V4 +V5 +V6 +V7
4.7.3 FX3U-32M 6
Configuration
System
• AC power supply type
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16
L N 24V X1 X3 X5 X7 X11 X13 X15 X17
FX3U-32MR/ES, FX3U-32MT/ES
7
FX3U-32MR/DS, FX3U-32MT/DS
FX3U-32MT/DSS 10
Input Wiring
63
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.7 Terminal Layout
4.7.4 FX3U-48M
FX3U-48MR/ES, FX3U-48MT/ES
FX3U-48MT/ESS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 Y21 Y23 Y25 Y27
FX3U-48MR/DS, FX3U-48MT/DS
FX3U-48MT/DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 Y21 Y23 Y25 Y27
4.7.5 FX3U-64M
FX3U-64MR/ES, FX3U-64MT/ES
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
FX3U-64MT/ESS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
FX3U-64MR/DS, FX3U-64MT/DS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6
COM1 Y1 Y3 COM2 Y5 Y7 COM3Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
FX3U-64MT/DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
64
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.7 Terminal Layout
1
4.7.6 FX3U-80M
Introduction
• AC power supply type
Terminal block 1
Terminal block 2
2
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16
Part Names
Features and
L N 24V 24V X1 X3 X5 X7 X11 X13 X15
X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47
FX3U-80MR/ES, FX3U-80MT/ES
Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46 3
Y27 COM6 Y31 Y33 Y35 Y37 COM7 Y41 Y43 Y45 Y47
Introduction
Product
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25
Terminal block 2
Terminal block 1
4
FX3U-80MT/ESS
Specifications
Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
Y27 +V5 Y31 Y33 Y35 Y37 +V6 Y41 Y43 Y45 Y47
Devices
Peripheral
Version and
Terminal block 2
Terminal block 1
Configuration
System
S/S (0V) (0V) X0 X2 X4 X6 X10 X12 X14 X16
(24V) (24V) X1 X3 X5 X7 X11 X13 X15
X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47
FX3U-80MR/DS,FX3U-80MT/DS
Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
7
Terminal block2
Terminal block 1 8
Installation
FX3U-80MT/DSS
Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
Y27 +V5 Y31 Y33 Y35 Y37 +V6 Y41 Y43 Y45 Y47
Terminal block 2
Terminal block 1
10
Input Wiring
65
FX3U Series Programmable Controllers 4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition 4.7 Terminal Layout
4.7.7 FX3U-128M
FX3U-128MR/ES,FX3U-128MT/ES Y44 Y46 COM8 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 COM10 Y71 Y73 Y75 Y77
Y43 Y45 Y47 Y50 Y52 Y54 Y56 COM9 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76
Y0 Y2 COM2 Y5 Y7 Y10 Y12 COM4 Y15 Y17 Y20 Y22 Y24 Y26 COM6 Y31 Y33 Y35 Y37 Y40 Y42
COM1 Y1 Y3 Y4 Y6 COM3 Y11 Y13 Y14 Y16 COM5 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 COM7 Y41
Terminal block 2
Terminal block 1
FX3U-128MT/ESS
Y44 Y46 +V7 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 +V9 Y71 Y73 Y75 Y77
Y43 Y45 Y47 Y50 Y52 Y54 Y56 +V8 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76
Y0 Y2 +V1 Y5 Y7 Y10 Y12 +V3 Y15 Y17 Y20 Y22 Y24 Y26 +V5 Y31 Y33 Y35 Y37 Y40 Y42
+V0 Y1 Y3 Y4 Y6 +V2 Y11 Y13 Y14 Y16 +V4 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 +V6 Y41
Terminal block 2
Terminal block 1
66
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.1 Version Upgrade History
Introduction
5. Version Information and Peripheral Equipment
Connectability
2
Part Names
Features and
5.1 Version Upgrade History
Introduction
Product
In FX3U PLCs, users can obtain the PLC version information by monitoring special data register D8001
(decimal number), or the PLC version can be checked in "PLC Status" in the display module.
→ For the operating procedure of the display module,
refer to Chapter 19.
D8001 2 4 2 2 0 4
PLC type and
Specifications
version Version information (Example: Ver. 2.20)
PLC type (Example: 24 = FX2N/FX2NC/FX3U/FX3UC PLC)
Devices
Peripheral
Version and
"SERIAL" indicated on the label adhered to the right side of the product.
MITSUBISHI PROGRAMMABLE
CONTROLLER
L N
S/S
・
0V
24V
X0
X1
X2
X3
X4
X5
X6
X7
X10
IN
X11
0 1
X12
2
X13
3
X14
4
10 11 12 13 14 15 16 17
X15
5 6
X16
X17
X20
X21
X22
X23
7 20 21 22 23 24 25 26 27
POWER
POWER
X24
X25
X26
X27
・
Configuration
System
100-240VAC 50/60Hz 40W
RUN
RUN
BATT
ERROR
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
OUT:30VDC/240VAC 2A(COSφ=1)
OUT
0 11
10 1 12
2 13
3 14
4 155 16
6 17
7 20 21 22 23 24 25 26 27
FX3U-48M
10 11 12 13 14 15 16 17
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
SERIAL 570001
R
Control number
Month (Example: July):(1 to 9 = January to September,
X = October, Y = November, Z = December)
Year (Example: 2005): Last digit of year 8
Installation
Manufacturer’s
Version Contents of version upgrade
serial number
9
55****** First product
Ver.2.20
Wiring
Power Supply
Preparation and
67
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.2 Programming Tool Applicability
2. Contents of restrictions
• Programming is enabled only in the function ranges such as instructions, device ranges and program sizes
available in a PLC selected as the alternative model.
• When "FX3UC" is selected, programs and functions of applied instructions added from the corresponding
version are different.
• Change the parameters such as the memory capacity and file register capacity using a programming tool
allowing selection of "FX3U(C)" or "FX3UC".
1. Applicable interface
• Standard built-in port or function extension board FX3U-422-BD for RS-422
When the RS-232C/RS-422 converter FX-232AWC-H or USB/RS-422 converter FX-USB-AW is connected
• Function extension board FX3U-232-BD for RS-232C
• Special adapter FX3U-232ADP for RS-232C
• Function extension board FX3U-USB-BD for USB
68
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.2 Programming Tool Applicability
1
5.2.4 Cautions on write during RUN
Introduction
In FX3U PLCs, write during RUN (program changes in the RUN mode) is enabled using the following
programming tools.
→ For the operating procedure of and cautions on write during RUN,
refer to the manual of the used programming tool. 2
Part Names
Features and
Programming tools supporting write during RUN
Programming tool Version Remarks
Supports write during RUN in the instruction and device ranges in FX2N PLCs
Ver.2.00A or later
Ver.1.00 or later.
Ver.7.00A or later
Supports write during RUN in the instruction and device ranges in FX2N PLCs
Ver.3.00 or later.
3
Introduction
Product
Supports write during RUN in the instruction and device ranges in FX3UC PLCs
Ver.8.13P or later
Ver.1.00 or later.
GX Developer
Supports write during RUN in the instruction and device ranges in FX3UC PLCs
Ver.8.18U or later
Ver.1.30 or later.
Supports write during RUN in the instruction and device ranges in FX3U and
Ver.8.23Z or later
FX3UC PLCs Ver.2.20 or later. 4
Supports write during RUN in the instruction and device ranges in FX3U and
Specifications
Ver.8.29F or later
FX3UC PLCs Ver.2.30 or later.
Supports write during RUN in the instruction and device ranges in FX2 PLCs
Ver.1.00 or later
Ver.3.30 or later.
Supports write during RUN in the instruction and device ranges in FX2N PLCs
FX-PCS/WIN(-E) Ver.2.00 or later
Ver.1.00 or later.
Supports write during RUN in the instruction and device ranges in FX2N PLCs
5
Ver.4.20 or later
Devices
Peripheral
Version and
Ver.3.00 or later.
Configuration
System
Number of program • GX Developer 256 steps or less after edition (addition/deletion) (including NOP immediately
steps which can be Ver.8.23Z or later after circuit blocks except final circuit)
written for circuit • GX Developer
change in RUN 127 steps or less after edition (addition/deletion) (including NOP immediately
Ver.8.22Y or former
mode after circuit blocks except final circuit)
• FX-PCS/WIN(-E)
Circuit blocks in which labels P and I are added, deleted or changed in edited 7
circuits
Avoid write during RUN to a circuit block including the following instructions
during execution. If write during RUN is executed to such a circuit block, the
PLC decelerates and stops pulse output.
• DSZR (FNC150), DVIT (FNC151), ZRN (FNC156), PLSV (FNC157)
instruction [with acceleration/deceleration operation], DRVI (FNC158) and/
or DRVA (FNC159) instruction
Avoid write during RUN to a circuit block including the following instruction
9
Wiring
Power Supply
Preparation and
during execution. If write during RUN is executed to such a circuit block, the
Circuit blocks which require attention on
PLC immediately stops pulse output.
operation after write during RUN
• PLSV (FNC157) instruction [without acceleration/deceleration operation]
Avoid write during RUN to a circuit block including the following instructions
during execution of communication. If write during RUN is executed to such a
circuit block, the PLC may stop communication after that.
If the PLC stops communication, set the PLC to the STOP mode once, and
10
Input Wiring
69
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.2 Programming Tool Applicability
Item Caution
• Instructions for falling edge pulse
When write during RUN is completed for a circuit including an instruction for
falling edge pulse (LDF, ANDF, or ORF instruction), the instruction for
falling edge pulse is not executed without regard to the ON/OFF status of
the target device.
When write during RUN is completed for a circuit including an instruction for
falling edge pulse (PLF instruction), the instruction for falling edge pulse is
not executed without regard to the ON/OFF status of the device that is set
as the operation condition.
It is necessary to set to ON the target device or operation condition device
once and then set it to OFF for executing the instruction for falling edge
pulse.
• Instructions for rising edge pulse
When write during RUN is completed for a circuit including an instruction for
rising edge pulse, the instruction for rising edge pulse is executed if a target
device of the instruction for rising edge pulse or the operation condition
device is ON.
Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse
operation type applied instructions (such as MOVP)
Contact ON/OFF status Instruction for Instruction for
(while write during RUN is rising edge falling edge
executed) pulse pulse
Circuit blocks which require attention on
OFF Not executed Not executed
operation after write during RUN
ON *1 Not executed
Executed
When writing during RUN with GX Developer Ver. 8.13P or later, the program
is as follows.
Others When the number of program steps is reduced by deletion of contacts, coils
and applied instructions, the program capacity becomes smaller by as many as
the reduced number of steps.
70
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.3 Cautions on using transparent function by way of USB in GOT1000 Series
1
5.3 Cautions on using transparent function by way of USB in GOT1000
Introduction
Series
When monitoring circuits, device registration, etc. or reading/writing programs in an FX3U PLC from GX
Developer Ver.8.22Y or later using the transparent function by way of USB in the GOT1000 Series, make
sure to execute the following setting. 2
If the following setting is not provided, a communication error occurs.
Part Names
Features and
GX Developer Ver.8.21X or former GX Developer Ver8.22Y or later*1
When using transparent function by way of
Not supported (not available) Setting shown below is required.
USB in GOT1000 Series
When using transparent function by way of
RS-232 in GOT1000 Series Set "COM port" and "Transmission Select "RS-232C" in setting shown 3
speed" on "PC side I/F Serial setting" below, and set "COM port" and
Introduction
Product
When directly connecting GX Developer to dialog box. "Transmission speed".
PLC
Specifications
1 Select [Online] → [Transfer setup...] to open the "Transfer setup" dialog box.
2 Double-click [Serial] in [PC side I/F] to open the "PC side I/F Serial setting"
dialog box. 5
3
Devices
Peripheral
Version and
Select "USB (GOT Transparent mode)".
Double-click it.
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
71
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.4 Cautions on using transparent port (2-port) function of GOT-F900 Series
1 Select [Online] → [Transfer setup...] to open the "Transfer Setup" dialog box.
2 Double-click [PLC module] in [PLC side I/F] to open the [PLC side I/F Detailed
setting of PLC module] dialog box.
3 Put a check mark to the check box [via GOT-F900 transparent mode] as
shown below.
Double-click it.
72
FX3U Series Programmable Controllers 5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition 5.5 Other Peripheral Equipment Applicability
1
5.5 Other Peripheral Equipment Applicability
Introduction
5.5.1 Applicable products and versions
Part Names
Features and
GOT1000 Series From first product
Caution
The GOT1000 Series is applicable to the device ranges in FX3U PLCs. Check the applicability of other items
in the GOT manual.
3
5.5.2 In the case of peripheral equipment not applicable
Introduction
Product
Model name Compatible versions
F940WGOT (with built-in 2-port interface) Ver.1.00 or later (from first product)
F940GOT(-E) (with built-in 2-port interface) Ver.1.00 or later (from first product)*1
F930GOT(-E)(-K) (with built-in 2-port interface) Ver.1.00 or later (from first product)
4
Specifications
F920GOT(-K) (with built-in 2-port interface) Ver.1.00 or later (from first product)
ET-940 (with built-in 2-port interface) Ver.1.00 or later (from first product)*1
FX-10DM(-SET0)(-E) From first product
FX-10DU(-E) Ver.3.00 or later
5
Contents of restrictions
Devices
Peripheral
Version and
Programming is enabled only in the function ranges such as instructions, device ranges and program sizes
available in FX2N and FX2NC PLCs.
*1. The F940GOT and ET-940 whose version is former than 1.10 do not support the transparent (2-port)
function of the GX Developer.
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
73
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.1 Configuration of a Whole System
SD
L N 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 24+ 24- V2+ I 2+ COM2 V4+ I4+ COM4
24-
0 1 2 3 4 5 6 7 20 21 22 2 3 24 25 26 27 POWER PO WER
IN
MITSUBIS HI
I 1+ V1+
10 11 12 13 14 15 16 17
POWER
POWER
FX 2N-8AD
COM1
RUN
V2+
BATT
POWER
COM2I2+
ERROR
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 2 0 21 22 23 24 25 26 2 7 24V
FX2N -16EYR FX2N -16EX
V3+
OUT
10
0 111 122 13
3 144 15
5 166 17
7 20 21 22 2 3 24 25 26 27
FX3U-48M
CO M3I 3+
10 11 12 13 14 15 16 17
V6+ I6+ COM6 V8+ I8+ COM8
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5 V 5+ I5+ COM5 V7+ I7+ COM7
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27 OUT 0 IN 0
V4+
1 1
COM4I4+
2 2
3 3
4 4
R 5 5
6 6
7 7
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
POWER POWER POWE R POWER
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N -48ER OUT
0 1 2 3 4 5 6 7
FX2N -16EX-C
FX2N-4AD FX2N-4DA FX2N-16CCL-M CC - L i nk
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 CO M3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7 IN 0 SW E
B 1 M/S R
2 PRM R
3 TIME O
4 LINE R
5 24V 24V
6 SD
7 A/D D/A RD
Y070 to Y117
The range of devices powered from the FX2N input/
output powered extension unit or the extension
power supply unit
FX-16E-TB 01
2
01
2
PW L RUN SD RD L ERR. 3 PW L RUN SD RD L ERR. 3
4 4
STATION NO . STATION NO .
0 1X109 0 1X1 0 1X109 0 1X1
0 1 2 3 4 5 6 7 8 9 A B C D E F 28 2 0 1 2 3 4 5 6 7 8 9 A B C D E F 28 2
37 3 37 3
654 6 54 654 654
Caution
When using an extension unit, select a power supply type that is the same as the main unit.
74
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.1 Configuration of a Whole System
1
6.1.1 List of system components
Introduction
Other items to be considered
Max.
Types (extracted) number of Max. number Number of 5V DC 24V DC
Classification input/output Reference
*1 connect- of input/
able units output points (occupied)
power
supply
power
supply 2
points
Part Names
Features and
FX3U-16MR/ES
A 1 unit 256 points or *6 − −
Subsection
...
Main unit 6.8.1
FX3U-80MR/ES less
D FX2N-32ER Not
256 points or *6 − − 3
Input/output powered FX2N-48ER specified
less
Introduction
Product
extension unit Subsection
FX2N-8EX 6.8.4
D FX2N-8EYR Not
256 points or *6 −
Input/output FX2N-16EX specified
extension block less
FX2N-16EYR
FX3U-232-BD 4
B FX3U-422-BD 1 unit − − −
Subsection
Specifications
Expansion board 6.8.2
FX3U-CNV-BD
FX3U-4AD-ADP Up to 4
Analog − − *4
FX3U-4AD-TC-ADP units
Commu- FX3U-232ADP Up to 2
− − −
nication FX3U-485ADP units*2 5
C High- Subsection
Devices
Peripheral
Version and
Special Up to 2 6.8.3
speed FX3U-4HSX-ADP − −
adapter units
input
High-
Up to 2
speed FX3U-2HSY-ADP − −
units
output
6
FX0N-3A
Configuration
System
FX2N-2AD 256 points or *7
FX2N-2DA less
Analog
FX2N-4AD
FX2N-8AD 256 points or *7 *4
FX2N-2LC less
7
Commu- *7 *4
FX2N-232IF 256 points or
less
Network
*3
FX2N-16CCL-M −
*7 *4
384 points or
FX2N-32ASI-M less
H Up to 2
9
FX3U-1PSU-5V − − − − Chapter 17
Wiring
Power Supply
Preparation and
→ For details, refer to Chapter 3 "Introduction of Products (Compliant with Overseas Standards)".
75
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.1 Configuration of a Whole System
*2. For some products, there are restrictions on combination and number of connected units.
→ For details on the special adapters, refer to Subsection 6.4.1.
→ For details on the special function units/blocks, refer to Subsection 6.4.2.
*3. When CC-Link master or AS-i master is used, the maximum number of input/output points is 384.
→ For an outline of CC-Link master, refer to Subsection 6.3.2 "Maximum number of input/output
points when CC-Link master is used".
→ For an outline of AS-i master, refer to Subsection 6.3.3 "Maximum number of input/output points
when AS-i master is used".
*4. When the special function units/blocks are externally wired to 24V DC power supply, the current
consumed by them is added to the current consumption.
*5. One extension cable can be used on a system. The cable to be used depends on the products to be
added. The extension cable must be selected carefully.
→ For an outline of the extension cable, refer to Subsection 6.4.3 "Extension cable".
*6. The number of input/output points varies depending on the type.
*7. The special function units/blocks (except FX2N-16LNK-M) occupy eight input/output points each.
→ For details on the special function units/blocks, refer to Subsection 6.4.2.
76
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.1 Configuration of a Whole System
1
6.1.2 System configuration with special adapters
Introduction
1. When high-speed input/output special adapters are used
When only high-speed input/output special adapters are connected, the adapters can be used without an
expansion board.
2
Part Names
Features and
Good Special adapter Special adapter Special adapter
(high-speed input) (high-speed input) (high-speed output)
Expansion board Main unit
Introduction
Product
When the board is not connected
Specifications
Special adapter Special adapter Expansion board Main unit
Good (communication) (analog)
Devices
Peripheral
Version and
The adapters do not function. When the board is not connected
2) When an expansion board (other than the FX3U-CNV-BD) is used, one communication special adapter
may be used.
6
Special adapter Special adapter Expansion board Main unit
Good
Configuration
System
(communication) (communication) (FX3U-CNV-BD)
main unit.
The high-speed input/output special adapters cannot be connected on the downstream side of any
communication/analog special adapter.
Special adapter Special adapter Special adapter Special adapter Main unit
Good (communication) (analog) (high-speed output) (high-speed input) 9
Wiring
Power Supply
Preparation and
Interchangeable
Special adapter Special adapter Special adapter Special adapter Main unit
Bad (analog) (high-speed input) (high-speed output) (communication)
10
Input Wiring
77
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.2 Rules of System Configuration
CC-Link/LT
Remote I/O station Remote I/O station Remote I/O station Remote I/O station
Remote I/O station Remote I/O station Remote I/O station Remote I/O station
*1. Regarding the type of network, the number of remote I/O is up to 224 points in CC-Link and is up to 248 points in
AS-i.
Input/output
Input/output powered Special function Special function
extension block unit block
extension unit
*1. When an expansion board other than FX3U-CNV-BD is used, up to 9 adapters can be connected.
78
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.2 Rules of System Configuration
1
3
Introduction
Calculation of current consumption
The power is supplied to each connected device from the built-in power supply of the main unit, the input/
output powered extension unit or the extension power supply unit.
There are three types of built-in power supplies; 24V DC service power, 5V DC power and internal 24V DC
power. The power to be consumed varies depending on the type of product to be added. 2
Part Names
Features and
Extension block Input/output Extension block Extension Extension block
Special Expansion Main unit (some blocks can powered (some blocks can power supply (some blocks can
adapter board be connected) extension be connected) unit be connected)
unit
Power supply Power supply Power supply from Power supply from
from main unit from main unit input/output powered
extension unit
extension power supply
unit*
3
Introduction
Product
Refer to Section 6.5. Refer to Section 6.6. Refer to Section 6.7.
* When connecting an input extension block on the downstream side of an extension power supply unit,
supply the power to the input extension block from the nearest main unit on the upstream side, or from an
input/output powered extension unit on the upstream side of the extension power supply unit. 4
In the example above, the input/output powered extension unit supplies the power to extension blocks.
Specifications
→ For details, refer to Section 6.5 "Expansion of Main Unit (Calculation of Current Consumption)".
→ For details, refer to Section 6.6 "Expansion of FX2N Series I/O Powered Extension Unit (Calculation
of Current Consumption)".
→ For details, refer to Section 6.7 "Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)".
5
Devices
Peripheral
Version and
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
79
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
1 Total the number of input/output points on the main unit and the number of
those on the input/output powered extension units/blocks.
To obtain the total number of input/output points, count the input points (X000 and more) and output
points (Y000 and more) of the main unit and input/output powered extension units/blocks.
The number of input/output points of each type of device is shown on the list below.
→ The list of numbers of input/output points is shown in Section 6.8.
2 Count the input/output points of the remote I/O stations connected on FX2N-
64CL-M or FX2N-16LNK-M network.
Add the number of remote I/O points to the number of input/output points from the main unit and
input/output powered extension units/blocks calculated in the above step.
→ For the method of calculating the number of remote I/O points, refer to the manual of each master.
80
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
1
4
Introduction
Calculate the total number of input/output points.
Total the number of points counted in Steps 1, 2 and 3, and check that it does not exceed 256
points (maximum number of input/output points).
Maximum number of
Number of input/output points
Number of input/output occupied 2
input/output points points
Part Names
Features and
256 points (A) + (B) + (C) (E) units × 8 points
Introduction
Product
system Total number of input/output points of input/output powered occupies eight input or output
extension units and input/output extension blocks points.
(A): Number of input/output points of main unit (D): Number of remote I/O points of FX2N-64CL-M or FX2N-
(B): Number of input/output points of input/output 16LNK-M
powered extension units (E): Number of special function units/blocks
(C): Number of input/output points of input/output 4
extension blocks
Specifications
5 When CC-Link or AS-i master is used, count the remote I/O points.
When CC-Link or AS-i master is used, the total number of input/output points of the remote I/O sta-
tions connected on the network and the number of input/output points calculated in the previous 5
step are 384 or less.
Devices
Peripheral
Version and
For details, refer to the following subsection.
Configuration
System
2. FX2N-32ASI-M (AS-i master)
Calculate the number of remote I/O points connected on the network in the following step.
→ When AS-i master is used, refer to Subsection 6.3.3.
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
81
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
×8 × 32
384 points (A)(B)(C)(D) (E) units (F) stations
points points
Maximum number
of points
≥ Total number of + Number of points occupied by + Total number of points obtained by
formula "number of remote I/O
input/output points special function units/blocks stations × 32 points" (The number is
controllable on
multiplied by 32 points regardless of
system
the number of remote I/O points.)
(A): Number of input/output points of main unit (D): Number of remote I/O points of FX2N-64CL-M or FX2N-
(B): Number of input/output points of input/output 16LNK-M
powered extension units (E): Number of input/output points occupied by special
(C): Number of input/output points of input/output function units/blocks
extension blocks (F): Number of remote I/O stations (units) connected to CC-
Link master
*1. When seven 32-point type remote I/O stations are used, the number of CC-Link remote I/O points
reaches the maximum number.
The number of CC-Link points is calculated by the formula "32 points × number of stations" even when
remote I/O stations having less than 32 points are used.
For details, refer to FX2N-16CCL-M User’s Manual.
CC-Link network
Remote I/O Remote I/O Remote I/O Remote I/O Remote I/O
(8 points) (16 points) (32 points) (32 points) (32 points)
Number of
Number of input/output points (128 points)
remaining points
Number of input/output points (excluding remote I/O points on CC-Link) + Number of
input/output occupied points
Up to 256 points
Number of
remaining 32 points × 5 units = 160 points
points
Number of CC-Link input/output points
Up to 224 points
384 points or less in total
82
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
1
6.3.3 Maximum number of input/output points when AS-i master is used
Introduction
1. Calculation of maximum number of input/output points
When AS-i system master block is used, the following maximum number of input/output points can be
connected.
Maximum number of Number of input/ Number of input/output occupied
2
Number of active slaves
Part Names
Features and
input/output points output points points
Maximum number
of points
≥ Total number of + Number of points occupied by + Total number of points obtained by
formula "number of active slaves × 8
points"
3
input/output points special function units/blocks
(The number is calculated by
Introduction
Product
controllable on
system multiplying by 8 points regardless of
the number of input/output points of
the active slaves.)
(A): Number of input/output points of main unit (D): Number of remote I/O points of FX2N-64CL-M or FX2N-
4
Specifications
(B): Number of input/output points of input/output 16LNK-M
powered extension units (E): Number of input/output points occupied by special
(C): Number of input/output points of input/output function units/blocks
extension blocks (F): Number of active slaves connected to AS-i system
master block
Devices
Peripheral
Version and
number of I/O points used on one slave.
For details, refer to AS-i System User’s Manual.
Configuration
System
X000 to X027 X030 to X057 X060 to X077 X100 to X117 − −
Input/output Input Input
Special FX2N-32ASI-M
Main unit powered extension extension
function unit
extension unit block block
Y000 to Y027 Y030 to Y057 − − − − 7
24/24 24/24 16/0 16/0
AS-i system
Repeater
83
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.4 Number of Connected Special Extension Devices (Including Extension Cable)
When connecting the following products, take into consideration the combination, number of units/blocks and
connecting order.
Type Limitations
• It cannot be used together with FX2N-32ASI-M.
FX2N-16CCL-M • When some units are used, a remote I/O station cannot be connected to the second and
following master stations.
• It cannot be used together with FX2N-16CCL-M.
FX2N-32ASI-M
• Only one unit can be used for the whole system.
• Up to 3 units can be sequentially connected to the end of a system.
FX2N-1RM(-E)-SET However, when three units are connected, they are counted as one unit, and the number of
input/output occupied points is 8.
When any of these products is connected to a FX2N Series input/output powered extension unit,
the current consumption is restricted.
The total current consumption of FX0N-3A, FX2N-2AD and FX2N-2DA must be the following
value or less.
FX0N-3A
- FX2N-32E :190mA or less
FX2N-2AD
- FX2N-48E :300mA or less
FX2N-2DA
The 5 special function units listed on the left have restrictions in current consumption (internal
FX3U-4HSX-ADP
24V DC) at startup when connected to FX3U Series main units (DC power type).
FX3U-2HSY-ADP
At the startup of an FX0N-3A, FX2N-2AD, FX2N-2DA, FX3U-4HSX-ADP or FX3U-2HSY-ADP,
make sure to set the total current consumption (internal 24V DC) less than the following values:
- FX3U-16, 32M /DS(S) : 640mA
- FX3U-48, 64, 80M /DS(S): 800mA
84
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
1
6.5 Expansion of Main Unit (Calculation of Current Consumption)
Introduction
The amount of connectable extension equipment to the main unit varies, depending on the power supply type
(AC/DC). For each power supply type, follow the instructions below.
Part Names
Features and
→ Refer to Subsection 6.5.1 "Quick reference matrix - when only input/output devices are added (AC
Power Type)".
Caution
Except FX2N-8ER and FX2N-8ER-ES/UL.
• When special extension devices, FX2N-8ER or FX2N-8ER-ES/UL are added, calculate the current
3
Introduction
Product
consumption to ensure that the total current to be consumed by the added extension devices can be
supplied by the built-in power supply.
→ Refer to Subsection 6.5.2 "When special extension devices are also added [calculation of current
consumption] (AC Power Type)".
Specifications
→ Refer to Subsection 6.5.3 "Quick reference matrix [when only input/output devices are added] (DC
Power Type)".
Caution
Except FX2N-8ER and FX2N-8ER-ES/UL. 5
• When special extension devices, FX2N-8ER or FX2N-8ER-ES/UL are added, calculate the current
Devices
Peripheral
Version and
consumption to ensure that the 5V DC and the internal 24V DC power can supply the total current by the
added extension devices.
When the added extension devices include FX0N-3A, FX2N-2AD, FX2N-2DA, FX3U-4HSX-ADP or FX3U-
2HSY-ADP, calculate the current consumption (internal 24V DC) at startup.
→ Refer to Subsection 6.5.4 "When special extension devices are also added [calculation of current
consumption] (DC Power Type)".
6
Configuration
System
6.5.1 Quick reference matrix - when only input/output devices are added (AC Power Type)
In the following quick reference matrix, the value at the intersection of the number of input points to be added
(horizontal axis) with the number of output points to be added (vertical axis) indicates the remaining power
supply capacity. 7
10
Input Wiring
85
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
added points
Number of
AC power supply 32 100 50 0 Not allowed to add
DC input type
24 175 125 75 25
FX3U-16M 16 250 200 150 100 50 0
FX3U-32M 8 325 275 225 175 125 75 25
0 400 350 300 250 200 150 100 50 0
0 8 16 24 32 40 48 56 64 Input
Number of added points
(Example) When a 16-input and 16-output point extension block is connected to FX3U-16/32M , the
current of the 24V DC service power supply becomes 150 mA or less.
48 150 100 50 0
Number of
(Example) When a 32-input and 16-output point extension block is connected to FX3U-48~128M , the
current of the 24V DC service power supply becomes 250 mA or less.
2 Confirm the current capacity of 24V DC service power supply from the value
shown in the quick reference matrix.
This remaining power supply capacity (current) can be used as a power supply to external loads
(sensors or the like) by the user.
When special adapters and special function units/blocks are connected, it is necessary to consider
whether they can be covered by this remaining power supply capacity.
86
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
1
6.5.2 When special extension devices are also added [calculation of current
Introduction
consumption] (AC Power Type)
Part Names
Features and
Select one main unit appropriate to the required number of input/output points from the following table.
Number of Capacity of built-in power supply
Input input/
Output 24V DC service
Classification Type specifi- output 5V DC power
specifications power supply
cations points
[points]
supply [mA]
[mA] 3
A
Introduction
Product
1-1 1-2 1-3
FX3U-16MR/ES Relay 16
FX3U-16MT/ES Transistor (sink) 16
FX3U-16MT/ESS Transistor (source) 16
FX3U-32MR/ES Relay 32
400 4
Specifications
FX3U-32MT/ES Transistor (sink) 32
FX3U-32MT/ESS Transistor (source) 32
FX3U-48MR/ES Relay 48
FX3U-48MT/ES Transistor (sink) 48
A FX3U-48MT/ESS
24V DC
Transistor (source) 48
500
5
FX3U-64MR/ES Relay 64
Devices
Peripheral
Version and
main unit
FX3U-64MT/ES Transistor (sink) 64
FX3U-64MT/ESS Transistor (source) 64
600
FX3U-80MR/ES Relay 80
FX3U-80MT/ES Transistor (sink) 80
FX3U-80MT/ESS Transistor (source) 80
6
Configuration
System
FX3U-128MR/ES Relay 128
FX3U-128MT/ES Transistor (sink) 128
FX3U-128MT/ESS Transistor (source) 128
When the number of input/output points is insufficient, add input/output extension blocks.
7
2 Enter the specifications for the selected main unit.
supply [mA]
[mA]
10
Input Wiring
87
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
Calculation of current
Number of Number of input/ consumption of built-in power
Classification connected Type output (occupied) supply
units points [points] 5V DC power 24V DC power
supply [mA] supply [mA]
B 1 FX3U- − −
Expansion board
FX3U- −
FX3U- −
FX3U- −
FX3U- −
C 10
FX3U- −
FX3U- −
Special adapter
FX3U- −
FX3U- −
FX3U- −
FX3U- −
FX2N- −
FX2N- −
FX2N- −
Enter the
products FX2N- −
connected −
to the D2 FX2N-
− FX2N- −
main unit Input/output
extension block* FX2N- −
FX2N- −
FX2N- −
FX2N- −
FX2N- −
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
E FX0N/FX2N/FX3U-
8
Special function FX0N/FX2N/FX3U-
unit/block FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
G 1 FX3U-7DM − −
Display module
2
2-1 2-2 2-3
Calculate the totals
* When connecting the FX3U-1PSU-5V extension power supply unit to a system where the nearest
upstream unit to the FX3U-1PSU-5V is a main unit, also enter the current consumption and number of
occupied I/O points for the input extension blocks (including FX2N-8ER-ES/UL and FX2N-8ER) that are
connected to the FX3U-1PSU- 5V.
88
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
1
4
Introduction
Determine whether the devices can be connected to the main unit.
Calculate the current to confirm whether the selected extension devices can be connected.
1. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply). 2
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24V DC
Part Names
Features and
service power supply, and the capacity can be used for external loads.
Capacity of 24V DC
power supply Current consumption Calculation result
Introduction
Product
mA mA mA
Specifications
Main unit Total of current consumed
by extension devices
1-2 2-2
mA
- mA
= mA
≥ 0mA
5
If the calculation results for the current consumption for the 24V DC power supply and 5V DC power supply
Devices
Peripheral
Version and
are negative values, the current consumption exceeds the capacity of the built-in power supply.
Reconfigure the system configuration, adding input/output powered extension units or extension power
supply units.
If the calculation results for the current consumption for the 24V DC power supply and 5V DC power supply
are negative values, add an input/output powered extension unit.
6
→ Refer to Section 6.6 "Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current
Configuration
System
Consumption)"
If the calculation results for the current consumption by 5V DC is a negative value, add an extension power
supply unit (FX3U-1PSU-5V).
→ Refer to Section 6.8 "Number of Input/Output (Occupied) Points and Current Consumption" 7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
89
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
6.5.3 Quick reference matrix [when only input/output devices are added] (DC Power Type)
The following matrix shows the expandable units up to the { mark, where the desired inputs (horizontal axis)
and outputs (vertical axis) intersect. System are expandable up to z mark when the supply voltage is 16.8V to
19.2V.
Caution
When FX2N-8ER and FX2N-8ER-ES/UL are added, refer to Subsection 6.5.4.
DC input type
Number of
48
FX3U-48M /D 40 Not allowed to add
FX3U-64M /D 32
FX3U-80M /D
24
16
8
0 -
0 8 16 24 32 40 48 56 64 72 80 88 96 Input
Number of added points
(Example) When adding 32 inputs to FX3U-48~80M /D , a maximum of 40 outputs are expandable.
Note : When adding 32 inputs under the supply voltage 16.8V to 19.2V, a maximum of 24
outputs are expandable.
90
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
1
6.5.4 When special extension devices are also added [calculation of current
Introduction
consumption] (DC Power Type)
Part Names
Features and
Select one main unit appropriate to the required number of input/output points from the following table.
Capacity of
built-in
Number of power Power
Input Current
Classifi- Output input/output supply supply for
A cation
Type specifi-
cations
specifications points
supply at
startup [mA] 5V DC
internal 24V 3
[points] DC [mA]
Introduction
Product
power
supply[mA]
1 -1 1 -2 1 -3 1 -4
FX3U-16MR/DS Relay 16
FX3U-16MT/DS Transistor (sink) 16 4
FX3U-16MT/DSS Transistor (source) 16
Specifications
640 400*1
FX3U-32MR/DS Relay 32
FX3U-32MT/DS Transistor (sink) 32
FX3U-32MT/DSS Transistor (source) 32
A
FX3U-48MR/DS
FX3U-48MT/DS 24V DC
Relay
Transistor (sink)
48
48 500
5
Devices
Peripheral
Version and
main unit FX3U-48MT/DSS Transistor (source) 48
FX3U-64MR/DS Relay 64
FX3U-64MT/DS Transistor (sink) 64 800 600*2
FX3U-64MT/DSS Transistor (source) 64
FX3U-80MR/DS Relay 80 6
FX3U-80MT/DS Transistor (sink) 80
Configuration
System
FX3U-80MT/DSS Transistor (source) 80
*1. When the supply voltage of the main unit is 16.8V to 19.2V DC, the power supply for the internal 24V
DC is 250mA.
*2. When the supply voltage of the main unit is 16.8V to 19.2V DC, the power supply for the internal 24V
DC is 450mA. 7
2
Nos., Unit Nos.
Input/Output
Enter the specifications for the selected main unit.
Enter the number of input/output points and power supply type of the main unit according to the
above table.
Number of Current
Capacity of
Power
8
Number of built-in power
Installation
1 -1 1 -2 1 -3 1 -4
1 With built-in
9
power A 1 FX3U-
Wiring
Power Supply
Preparation and
10
Input Wiring
91
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
Calculation of current
Number of consumption of built-in
Current power supply
Number of input/output
consumption
Classification connected Type (occupied) 5V DC
at startup Internal
units points power
[mA] 24V DC
[points] supply
[mA]
[mA]
B
1 FX3U- − − −
Expansion
board
FX3U- −
FX3U- −
FX3U- −
FX3U- −
C FX3U- −
10
Special FX3U- −
adapter FX3U- −
FX3U- −
FX3U- −
FX3U- −
FX2N- − −
FX2N- − −
Enter the FX2N- − −
products FX2N- − −
connected
to the D2 FX2N- − −
main unit. Input/output − FX2N- − −
extension FX2N- − −
block
FX2N- − −
FX2N- − −
FX2N- − −
FX2N- − −
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
E
FX0N/FX2N/FX3U-
Special 8
FX0N/FX2N/FX3U-
function unit/
block FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
2 G 1 FX3U-7DM − − −
Display module
2 -1 2 -2 2 -3 2 -4
Calculate the totals.
92
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.5 Expansion of Main Unit (Calculation of Current Consumption)
1
4
Introduction
Determine whether the devices can be connected to the main unit.
Calculate the current to confirm whether the selected extension devices can be connected.
Part Names
Features and
startup [mA] at startup [mA]
Total of current
Main unit consumed by
extension devices
1 -2 2 -2
mA - mA = mA ≥ 0mA
3
Introduction
Product
2. Calculate the current consumption of the internal 24V DC.
The positive value from the calculation means it is expandable.
Specifications
Main unit consumed by
extension devices
1 -4 2 -4
mA - mA = mA ≥ 0mA
5
3. Calculate the current consumption of the built-in 5V DC power supply.
Devices
Peripheral
Version and
Capacity of 5V DC Current
power supply consumption Calculation result
Total of current
Main unit consumed by
extension devices 6
1 -3 2 -3
≥
Configuration
System
mA - mA = mA 0mA
If the calculation results for the current consumption for the startup, the internal 24V DC power supply and 5V
DC power supply are negative values, the current consumption exceeds the capacity of the built-in power
supply. 7
Reexamine the system configuration adding input/output powered extension units.
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
93
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
Input/output
Before Main unit extension Special Input extension Output extension Special
selection block function block block (16 points) block (16 points) function block
6.6.1 Quick reference matrix (when only input/output devices are added)
In the following quick reference matrix, the value at the intersection of the number of input points to be added
(horizontal axis) with the number of output points to be added (vertical axis) indicates the remaining power
supply capacity.
(Example)
Number of
FX2N-32E 16 100 50 0
8 175 125 75 25
0 250 200 150 100 50
0 8 16 24 32 Input
Number of added points
(Example) When a 16-input and 0-output point extension block is connected to FX2N-32E , the current
of the 24V DC service power supply becomes 150 mA or less.
94
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
1
2) FX2N-48ER, FX2N-48ET, FX2N-48ES
Introduction
FX2N-48ER-ES/UL, FX2N-48ET-ESS/UL
added points
40 85 35
Number of
FX2N-48E
Part Names
Features and
32 160 110 60 10
24 235 185 135 85 35
16 310 260 210 160 110 60 10
8 385 335 285 235 185 135 85 35
0 460 410 360 310 260 210 160 110 60 3
Introduction
Product
0 8 16 24 32 40 48 56 64 Input
Number of added points
(Example) When a 32-input and 16-output point extension block is connected to FX2N-48E , the
current of 24V DC service power supply becomes 110 mA or less.
Specifications
(24V DC service power supply is not provided.)
(Example)
Number of
FX2N-48E /D 40
Devices
Peripheral
Version and
32
24
16
8
0 − 6
Configuration
System
0 8 16 24 32 40 48 56 64 Input
Number of added points
8
Number of
FX2N-48ER-UA1/UL 40
32
Installation
24
16
8
0 −
0 8 16 24 32 40 48 56 64
9
Input
Wiring
Power Supply
Preparation and
10
Input Wiring
95
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
2 Check the current capacity of the 24V DC service power supply based on the
value shown in the quick reference matrix.
1. In the case of AC power supply/DC input type
The remaining power supply capacity (current) can be used as a power supply to loads (sensors or the like).
When special adapters and special function units/blocks are connected by external wiring, it is necessary to
consider whether they can be covered by the remaining power supply capacity.
96
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
1
6.6.2 When special extension devices are also added (calculation of current consumption)
Introduction
1 Select an input/output powered extension unit.
→ For the data on the number of input/output occupied points and current consumption of each type,
refer to Section 6.8. 2
Capacity of built-in power
Part Names
Features and
Power Number of Number of supply
input/output
supply Classification connected Type 24V DC service
points 5V DC power
classification units [points] power supply
supply [mA]
[mA]
Introduction
Product
D1
With built-in
Input/output − FX2N-
power supply
3 powered
extension unit
Example of entry→ FX2N-48ER-ES/UL 48 690 460
4
2 Enter the specifications for the products to be added.
Specifications
Enter the data for the input/output extension blocks and special function units/blocks to be con-
nected to the input/output powered extension unit, and calculate the current.
→ For data on the number of input/output occupied points and current consumption of each type,
refer to Section 6.8.
Calculation of current
5
Power Number of consumption of built-in power
Devices
Peripheral
Version and
Number of
supply Classification connected Type input/output supply
classification units points [points] 5V DC power 24V DC power
supply [mA] supply [mA]
FX2N- −
FX2N- − 6
FX2N- −
Configuration
System
FX2N- −
FX2N- −
D2 FX2N- −
−
Input/output FX2N- −
Enter the extension block*1 FX2N- − 7
products FX2N- −
FX0N/FX2N/FX3U-
E FX0N/FX2N/FX3U-
8*2
Special function FX0N/FX2N/FX3U-
unit/block FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
FX0N/FX2N/FX3U-
9
4
Wiring
Power Supply
Preparation and
to the FX3U-1PSU-5V.
*2. A maximum of 8 special function units/blocks are connectable, including the main unit and extension power supply
unit.
97
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
90mA × units
+ 50mA × units
+ 85mA × units
=
mA
≤ 190mA
90mA × units
+ 50mA × units
+ 85mA × units
=
mA
≤ 300mA
1. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply).
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24V DC
service power supply, and the capacity can be used for external loads.
Capacity of 24V DC
power supply Current consumption Calculation result
3-2 4-2
mA
- mA
= mA
≥ 0mA
If the calculation results for the current consumption of the 24V DC power supply and 5V DC power supply
are negative values, the current consumption exceeds the capacity of the built-in power supply.
Reconfigure the system, adding input/output powered extension units or extension power supply units.
98
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
1
6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
Introduction
If the selected devices in section 6.5 are not connectable due to the built-in 5V DC power shortage, add an
extension power supply unit.
1 Enter the current supply specification of the extension power supply unit. 2
Part Names
Features and
The output current of the extension power supply unit is proportional to the ambient temperature as
shown by the derating curve below. Enter the output current value, based on this derating curve.
Also verify that the number of occupied input/output points from input/output extension block(s)
connected to the extension power supply unit is less than 32.
Derating curve
3
Output current [A]
Introduction
Product
5V DC
1.0
0.8
24V DC
0.3
0.2 4
Specifications
0 40 55
Ambient temperature [°C]
Devices
Peripheral
Version and
supply [mA]
5 24V DC [mA]
H1
With built-in
Extension − FX3U-1PSU-5V 32
6
power supply
Configuration
System
power supply
unit
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
99
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
100
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
1
3
Introduction
Determine whether the devices can be added to the extension power supply
unit.
Calculate the current to confirm whether the selected extension devices can be connected.
Part Names
Features and
Capacity of 5V DC
power supply Current consumption Calculation result
Introduction
Product
2. Calculate the available current supply from the internal 24V DC power supply.
Power supply
capacity for Current consumption Calculation result
internal 24V DC
Extension power
supply unit
Total of current consumed
by extension devices
4
Specifications
5-2
mA
- 6-2
mA = mA ≥ 0mA
3. Calculate the available input/output occupied points (excluding the occupied input/output
by special function units/blocks). 5
Devices
Peripheral
Version and
Connectable I/O Number of I/O
occupied points occupied points Calculation result
Extension power Total of I/O occupied points
supply unit by extension devices
5-3 6-3
points - points = points ≥ 0points 6
Configuration
System
If the calculation result for the 5V DC power supply is a negative value, the current consumption exceeds the
power supply capacity.
Reconfigure the system with an extension power supply unit.
If the calculation results for the internal 24V DC power supply and input/output occupied points are negative
values, the actual input/output occupied points exceed the connectable input/output occupied points.
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
101
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
102
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
1
6.8.1 [A] Main units
Introduction
Input/output Output current (mA)
A Number of input/
No. Type Input/output 5V DC power 24V DC service power
output points
[points]
[points] supply supply
2
AC power supply/24V DC input/relay output type
Part Names
Features and
FX3U-16MR/ES 16 8/8
400
FX3U-32MR/ES 32 16/16
A1 FX3U-48MR/ES 48 24/24
500
FX3U-64MR/ES 64 32/32
FX3U-80MR/ES 80 40/40
600 3
Introduction
Product
FX3U-128MR/ES 128 64/64
AC power supply/24V DC input/transistor output type
FX3U-16MT/ES 16 8/8
FX3U-16MT/ESS 16 8/8
400
FX3U-32MT/ES
FX3U-32MT/ESS
32
32
16/16
16/16
4
Specifications
FX3U-48MT/ES 48 24/24
FX3U-48MT/ESS 48 24/24
A1 FX3U-64MT/ES 64 32/32
500
FX3U-64MT/ESS 64 32/32
600
FX3U-80MT/ES 80 40/40 5
FX3U-80MT/ESS 80 40/40
Devices
Peripheral
Version and
FX3U-128MT/ES 128 64/64
FX3U-128MT/ESS 128 64/64
Configuration
System
output points
[points] supply internal 24V
[points] [mA]*3
DC
DC power supply/24V DC input/relay output type
FX3U-16MR/DS 16 8/8
400*1 640
FX3U-32MR/DS 32 16/16 7
A2 FX3U-48MR/DS 48 24/24 500
FX3U-32MT/DSS 32 16/16
FX3U-48MT/DS 48 24/24
500
A2 FX3U-48MT/DSS 48 24/24
FX3U-64MT/DS 64 32/32
FX3U-64MT/DSS 64 32/32
600*2 800 9
FX3U-80MT/DS 80 40/40
Wiring
Power Supply
Preparation and
FX3U-80MT/DSS 80 40/40
*1. When the supply voltage of the main unit is 16.8V to 19.2V DC, the power supply for the internal 24V
DC is 250mA.
*2. When the supply voltage of the main unit is 16.8V to 19.2V DC, the power supply for the internal 24V
DC is 450mA. 10
Input Wiring
*3. When adding the high-speed input/output special adapters (FX3U-4HSX-ADP/FX3U-2HSY-ADP) and
the analog special function blocks (only FX0N-3A/FX2N-2AD/FX2N-2DA), calculate the current supply
at startup.
103
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
*1. When FX3U-422-BD is connected, add the current consumed by GOT/programming tool F .
GOT/programming tool
−: No need to calculate
Number of input/ Current consumed (mA)
F No. Type output occupied
points 5V DC Internal 24V DC
FX-20P(-E) − 150*1 −
FX-10P(-E) − 120 −
FX-232AW − 220 −
FX-232AWC − 220 −
F1 FX-232AWC-H − 120 −
FX-USB-AW − 15 −
FX-10DM(-SET0)(-E) − 220 −
F920GOT-BBD5-K(-E) − 220 −
*1. When applying the DC power type main unit, calculate the current consumption at startup.
104
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
1
6.8.4 [D] Input/output powered extension units/blocks
Introduction
1. Input/output powered extension units
Input/output Output current (mA)
D
No. Type Number of input/
Input/output 5V DC power 24V DC service
2
output points
Part Names
Features and
[points] supply power supply
[points]
FX2N-32ER-ES/UL 32 16/16
FX2N-32ET-ESS/UL 32 16/16
FX2N-32ER 32 16/16 250
FX2N-32ES 32 16/16 3
Introduction
Product
FX2N-32ET 32 16/16
FX2N-48ER-ES/UL 48 24/24
FX2N-48ET-ESS/UL 48 24/24
D1 FX2N-48ER 48 24/24
690
460
FX2N-48ES 48 24/24 4
FX2N-48ET 48 24/24
Specifications
FX2N-48ER-DS 48 24/24
FX2N-48ET-DSS 48 24/24
−
FX2N-48ER-D 48 24/24
FX2N-48ET-D 48 24/24
5
Devices
Peripheral
Version and
2. Input/output extension blocks
−: No need to calculate
D No. Type
Number of input/ Current consumed (mA)
output points 5V DC Internal 24V DC External 24V DC
Types for addition of input/output 6
FX2N-8ER-ES/UL 16 * − 62.5 0
Configuration
System
FX2N-8ER 16* − 62.5 0
Types for addition of input
FX2N-8EX-ES/UL 8 − 50 0
FX2N-8EX 8 − 50 0 7
FX2N-8EX-UA1/UL 8 − 50 0
FX2N-8EYR-ES/UL 8 − 75 0
FX2N-8EYT-ESS/UL 8 − 75 0
FX2N-8EYR 8 − 75 0
FX2N-8EYT 8 − 75 0
FX2N-8EYT-H 8 − 75 0 9
Wiring
Power Supply
Preparation and
FX2N-16EYR-ES/UL 16 − 150 0
FX2N-16EYT-ESS/UL 16 − 150 0
FX2N-16EYR 16 − 150 0
FX2N-16EYS 16 − 150 0
FX2N-16EYT 16 − 150 0 10
FX2N-16EYT-C 16 − 150 0
Input Wiring
105
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
E2 FX2N-1HC 8 90 0 0 −
FX2N-1PG(-E) 8 55 0 40 −
FX2N-10PG 8 120 0 70 *1 −
FX2N-232IF 8 40 0 80 −
FX2N-16CCL-M 8 *2 0 0 150 −
FX2N-32CCL 8 130 0 50 −
Supplied from power supply for
FX2N-64CL-M 8*3 190 −
CC-Link/LT
FX2N-16LNK-M 0*4 200 0 90 −
FX2N-32ASI-M 8 *5 150 0 70 −
*1. When the voltage of the external DC power supply is 24V DC and 5V DC, the current is 70 mA and
100 mA, respectively.
*2. This block cannot be used together with FX2N-32ASI-M.
The following number of points is added according to the products connected to the network.
Number of remote I/O stations × 32 points
*3. The following number of points is added according to the products connected to the network.
Total number of input/output points of remote I/O stations
*4. The number of points varies according to the products connected to the network.
For details, refer to FX2N-16LNK-M Manual.
*5. This block cannot be used together with FX2N-16CCL-M. Only one unit can be added to the whole
system.
The following number of points is added according to the products connected to the network.
Number of active slaves × 8 points
*6. When analog special function blocks (FX0N-3A, FX2N-2AD and FX2N-2DA) are connected to an input/
output powered extension unit (FX2N-32E or FX2N-48E ), the following limitation must be taken into
consideration. (When the blocks are connected to the main unit, this limitation is not applied.)
The total current consumption of the analog special function blocks (FX0N-3A, FX2N-2AD and FX2N-
2DA) should be less than the following current values.
- Total current consumption of blocks connected to FX2N-32E : 190 mA or less
- Total current consumption of blocks connected to FX2N-48E : 300 mA or less
*7. When applying the DC power type main unit, calculate the current consumption at startup.
106
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.8 Number of Input/Output (Occupied) Points and Current Consumption
1
2. Special function units
Introduction
E No. Type
Number of input/
occupied output
Current consumed (mA)
FX2N-10GM 8 − − 5
2
E3 FX2N-20GM 8 − − 10
Part Names
Features and
FX2N-1RM(-E)-SET 8 − − 5
Introduction
Product
G No. Type
Number of input/
occupied output
Current consumed (mA)
G1 FX3U-7DM − 20 0 0
4
Specifications
6.8.7 [H] Extension power supply unit
−: No need to calculate
Devices
Peripheral
Version and
points 5V DC Internal 24V DC
*1. The ambient temperature restricts the output current. For details, refer to the derating curve in Section
6.7. 6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
107
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.9 Example of System Configuration and System Modification
The procedures for evaluating the suitability of the system configuration are explained using an
example system configuration consisting of an expansion board, special adapters, input/output
powered extension units/blocks and special function blocks.
FX2N-16EYT-ESS/UL
FX2N-16EX-ES/UL
FX3U-48MR/ES
FX3U-2HSY-ADP
FX3U-2HSY-ADP
FX3U-4HSX-ADP
FX3U-
FX3U-4AD-ADP
FX3U-4AD-ADP
FX3U-485ADP
232-BD
FX2N-1HC
Extension cable
FX2N-16EYR-ES/UL
FX2N-16EX-ES/UL
FX2N-CNV-BC
FX2N-64CL-M
CC-Link To CC-Link
FX2N-32CCL
FX2N-16CCL-M
FX2N-10PG
master station
FX2N-2LC
CC-Link/LT CC-Link
4 input
points
108
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.9 Example of System Configuration and System Modification
1
6.9.2 Expansion of main unit
Introduction
The suitability of the above system configuration is evaluated as shown below.
Part Names
Features and
Number of Number of supply
Classification connected Type input/output 24V DC service
units points [points] 5V DC power
power supply
supply [mA]
[mA]
Introduction
Product
With built-in
power A 1 FX3U-48MR/ES 48 500 600
supply Main unit
2 Enter the specifications for the products to be connected to the main unit.
4
Calculation of current
Specifications
Number of consumption of built-in
Number of
input/output power supply
Classification connected Type
(occupied)
units
points [points] 5V DC power 24V DC power
supply [mA] supply [mA]
B 5
−
Devices
Peripheral
Version and
1 FX3U-232-BD 20 0
Expansion
board
FX3U-4HSX-ADP − 30 30
FX3U-2HSY-ADP − 30 60
C 6
FX3U-2HSY-ADP − 30 60 6
FX3U-485ADP − 20 0
Configuration
System
Special adapter
FX3U-4AD-ADP − 15 0
Enter the FX3U-4AD-ADP − 15 0
products
connected to FX2N-16EX-ES/UL 16 − 100
the main unit. D2 FX2N-16EYT-ESS/UL 16 − 150 7
4
Input/output FX2N-16EX-ES/UL 16 − 100
unit/block
FX2N-16CCL-M 8 0 0
FX2N-32CCL 8 130 0
*1. The number for FX2N-64CL-M is calculated by adding the number of input/output points at the
connected remote I/O station to 8 points.
10
Input Wiring
109
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.9 Example of System Configuration and System Modification
1. Calculate the number of input/output points of the main unit and extension devices.
OK
1-1 2-1 A
48 points + 128 points = 176 points ≤ 256 points
1 station × 32 points =
B
32 points ≤ 224 points OK
FX2N-16CCL-M: up to 7 stations
3. Calculate the total number of input/output occupied points (number of input/output points).
110
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.9 Example of System Configuration and System Modification
1
4
Introduction
Determine whether the devices can be added to the main unit.
Calculate the current consumption to confirm whether the extension devices selected in the above
step can be connected.
Part Names
Features and
Capacity of 5V DC
power supply Current consumption Calculation result
1-2
500mA -
2-2
760mA = -260mA NG 3
Introduction
Product
5. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply).
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of the 24V
DC service power supply, that can be used for external loads.
Capacity of 24V DC
4
power supply Current consumption Calculation result
Specifications
Main unit Total of current consumed
by extension devices
1-3
600mA -
2-3
650mA = -50mA NG 5
Devices
Peripheral
Version and
Since the calculated values of the current consumption of the 5V DC and 24V DC power supplies
are negative, it is necessary to reexamine the configuration.
The next subsection explains the procedures for evaluating a reexamined and modified configura-
tion.
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
111
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.9 Example of System Configuration and System Modification
When the main unit is short of 5V DC or 24V DC current, use an input/output powered extension
unit.
Reexamine the system configuration using an input/output powered extension unit.
Example of reexamined system configuration
FX2N-16EYT-ESS/UL
FX2N-16EX-ES/UL
FX3U-48MR/ES
FX3U-2HSY-ADP
FX3U-2HSY-ADP
FX3U-4HSX-ADP
FX3U-
FX3U-4AD-ADP
FX3U-4AD-ADP
FX3U-485ADP
FX2N-1HC
232-BD
FX2N-32CCL
FX2N-16CCL-M
FX2N-10PG
FX2N-
CC-Link
FX2N-2LC
To CC-Link
BC
32ER
master station
-ES/UL
CC-Link/LT CC-Link
4 input
points
112
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.9 Example of System Configuration and System Modification
1
1
Introduction
Enter the specifications for the main unit.
Capacity of built-in power
Number of Number of supply
Classification connected
units
Type input/output
points [points]
5V DC 24V DC service
power supply power supply
2
Part Names
Features and
[mA] [mA]
Introduction
Product
Enter the specifications for the products to be added to the main unit.
Calculation of current
Number of consumption of built-in
Number of power supply
input/output
Classification connected
units
Type
(occupied) Internal 24V 4
points [points] 5V DC power DC power
Specifications
supply [mA]
supply [mA]
B
1 FX3U-232-BD − 20 0
Expansion
board
FX3U-4HSX-ADP − 30 30
5
Devices
Peripheral
Version and
FX3U-2HSY-ADP − 30 60
C 6
FX3U-2HSY-ADP − 30 60
FX3U-485ADP − 20 0
Enter the Special adapter
FX3U-4AD-ADP − 15 0
products
connected to FX3U-4AD-ADP − 15 0 6
the main unit.
Configuration
System
−
D2 FX2N-16EX-ES/UL 16 100
2
Input/output
extension block FX2N-16EYT-ESS/UL 16 − 150
E FX2N-1HC 8 90 0
7
2
Special function
D1
With built-in
power supply
Input/output
powered
1 FX2N-32ER-ES/UL 32 690 250
10
Input Wiring
extension unit
113
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.9 Example of System Configuration and System Modification
4 Enter the specifications for the products to be added to the input/output pow-
ered extension unit.
Calculation of current
Number of consumption of built-in power
Number of supply
input/output
Classification connected Type
occupied Internal 24V
units 5V DC power
points [points] DC power
supply [mA]
supply [mA]
Enter the FX2N-2LC 8 70 0
products
connected to E FX2N-64CL-M 8+16*1 190 0
the Input/ 4
Special function FX2N-16CCL-M 8 0 0
output
unit/block
powered
extension unit FX2N-32CCL 8 130 0
*1. The number for FX2N-64CL-M is calculated by adding the number of input/output points at the
connected remote I/O station to 8 points.
1. Calculate the number of input/output points of the main unit and extension devices.
= A
176 points ≤ 256 points OK
2. Calculate the number of remote I/O points on the network.
Since this system uses CC-Link, calculate the number of the remote I/O stations.
1 station × 32 points =
B
32 points ≤ 224 points OK
FX2N-16CCL-M: up to 7 stations
114
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardwaer Edition 6.9 Example of System Configuration and System Modification
1
3. Calculate the total number of input/output occupied points (number of input/output points).
Introduction
Total number of input/output points Calculation Max. number of
result input/output points
Number of input/output
Input/output on network
occupied points
2
A
176 points +
B
32 points = 208 points ≤ 384 points OK
Part Names
Features and
Total obtained in Step 1 Total obtained in Step 2
Introduction
Product
Calculate the current by the following formula to confirm whether the extension devices selected in
Step 2 can be connected.
Specifications
power supply Current consumption Calculation result
1-2
500mA -
2-2
370mA = 130mA ≥ 0mA OK 5
Devices
Peripheral
Version and
2. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply).
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of the 24V
DC service power supply, that can be used for external loads.
6
Configuration
System
Capacity of 24V DC
power supply Current consumption Calculation result
1-3
600mA -
2-3
400mA = 200mA ≥ 0mA OK 7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
115
FX3U Series Programmable Controllers 6 Examination of System Configuration
User’s Manual - Hardware Edition 6.9 Example of System Configuration and System Modification
Capacity of 5V DC
power supply Current consumption Calculation result
Input/output powered Total of current consumed by
extension unit extension devices
3-2
690mA -
4-2
390mA = 300mA ≥ 0mA OK
2. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply).
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24V DC
service power supply, and the capacity can be used for external loads
Capacity of 24V DC
power supply Current consumption Calculation result
Input/output powered Total of current consumed by
extension unit extension devices
3-3
250mA -
4-3
0mA = 250mA ≥ 0mA OK
8 Verify the evaluation results.
Since the capacities of the 5V DC and 24V DC power supplies and the number of input/output
points are within the specified ranges, the reexamined system configuration is feasible.
116
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.1 Assignment of Input/Output Numbers (X/Y)
Introduction
7. Assignment of Input/Output Numbers (X/Y) and Unit
Numbers
2
Part Names
Features and
7.1 Assignment of Input/Output Numbers (X/Y)
If input/output powered extension units/blocks have been connected when the power is turned on, the main
unit automatically assigns the input/output numbers (X/Y) (octal) to the units/blocks.
Therefore, it is unnecessary to specify the input/output numbers with parameters.
3
Introduction
Product
Accordingly, it is not necessary to specify input/output numbers using parameters.
It is necessary to assign input and output numbers in the following special extension unit/block:
• FX2N-64CL-M
• FX2N-16LNK-M
Specifications
When the power is turned on, input/output numbers (X/Y) are assigned in accordance with the following rules.
For special function blocks, such as FX2N-64CL-M and FX2N-16LNK-M, that assign input/output numbers to
connected remote I/O stations, refer to the manual for each block.
Devices
Peripheral
Version and
- X000 to X007, X010 to X017, X020 to X027......, X070 to X077, X100 to 107...
- Y000 to Y007, Y010 to Y017, Y020 to Y027......, Y070 to Y077, Y100 to Y107...
Configuration
System
The last digit of the assigned numbers must begin with 0.
For example, when the last number on the preceding device is X043, the input numbers are assigned to the
next device starting from X050.
(When the FX2N-8ER is used, some input/output numbers are not used.)
9
Wiring
Power Supply
Preparation and
10
Input Wiring
117
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.1 Assignment of Input/Output Numbers (X/Y)
1. Example of configuration
Special Input extension Input/output Special
Expansion
adapter Main unit block extension block function
board
FX3U-4AD- FX3U-64MR/ES FX2N-8EX FX2N-8ER block
FX3U-232-BD
ADP -ES/UL -ES/UL FX2N-4AD
Input/output
Input/output Special Special function Output extension
powered extension
extension block function block block block
unit
FX2N-8ER-ES/UL FX2N-10PG FX2N-64CL-M FX2N-16EYT-ESS/UL
FX2N-32ET-ESS/UL
118
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.1 Assignment of Input/Output Numbers (X/Y)
1
7.1.3 Application of I/O number label
Introduction
The input/output powered extension units/blocks come with an I/O number label.
Apply the I/O number label to spaces on the enclosure (see the following figure) so that the input/output
numbers can be identified.
2
Part Names
Features and
For X050
I/O NUMBER
LABEL
JY818D25401B
70
10
X0
L N
20
3
2 3 4 5 6 7
30
2 3 4 5 6 7
50
40 40
Introduction
Product
2 3 4 5 6 7
50 2 3 4 5 6 7
Y0
60
70
100
110 For Y040 4
Specifications
120
Devices
Peripheral
Version and
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
119
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.2 Unit Numbers of Special Function Units/Blocks
2. FX2N-1RM(-E)-SET
Up to three FX2N-1RM(-E)-SET can be sequentially connected to the end of one system.
All these connected units have the same number as the unit number of the first unit (FX2N-1RM(-E)-SET).
→ For FX2N-1RM-E-SET, refer to FX2N-1RM-E-SET USER’S MANUAL.
120
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.2 Unit Numbers of Special Function Units/Blocks
1
7.2.2 Example of assigning
Introduction
Unit numbers are assigned to the special function units/blocks in the following configuration.
→ For assignment of input/output numbers, refer to Section 7.1.
Special adapter
Expansion
board
Main unit
Input/output Input/output Special
extension block extension block function 2
FX3U-4AD-ADP FX3U-64MR/ES FX2N-16EX FX2N-16EYT block
Part Names
Features and
FX3U-232-BD
-ES/UL -ESS/UL FX2N-4AD
Input/output
Special Special Special Special
powered extension
unit
function block function block function unit
FX2N-10PG FX2N-64CL-M FX2N-1RM
function unit
FX2N-1RM
3
FX2N-32ET-ESS/UL
Introduction
Product
Station No.1 Station No.2 Station No.3
4 input 4 input/ 4 input/
points output points output points 4
Specifications
CL1X4-D1B2 CL1XY4-DT1B2 CL1XY4-DT1B2
Unit numbers are assigned to the special function units/blocks in the above configuration as shown below.
Unit No.
No.0
5
Devices
Peripheral
Version and
Input/output Input/output Special
Expansion
Special adapter Main unit extension block extension block function
board
FX3U-4AD-ADP FX3U-64MR/ES FX2N-16EX FX2N-16EYT block
FX3U-232-BD
-ES/UL -ESS/UL FX2N-4AD
Unit No.
No.1
Unit No.
No.2
Unit No.
No.3
Unit No.
No.3 6
Configuration
System
Input/output
Special Special Special Special
powered extension
function block function block function unit function unit
unit
FX2N-10PG FX2N-64CL-M FX2N-1RM FX2N-1RM
FX2N-32ET-ESS/UL
7
Station No.1 Station No.2 Station No.3
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
121
FX3U Series Programmable Controllers 7 Assignment of Input/Output Numbers (X/Y) and Unit Numbers
User’s Manual - Hardwaer Edition 7.2 Unit Numbers of Special Function Units/Blocks
Y818D33101
No.0
No.1
No.2 RUN
ERR.
MST
TEST1
TEST2
No.3 L RUN
L ERR.
No.5
122
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition
Introduction
8. Installation In Enclosure
2
DESIGN PRECAUTIONS
Part Names
Features and
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
3
Introduction
Product
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 4
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Specifications
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case. 5
Devices
Peripheral
Version and
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line. 6
Noise may cause malfunctions.
Configuration
System
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
INSTALLATION PRECAUTIONS 7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
123
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition
INSTALLATION PRECAUTIONS
• Use the product within the generic environment specifications described in Section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S,
SO2 or NO2), flammable gas, vibration or impacts, or exposed to high temperature, condensation, or rain and
wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
• Do not touch the conductive parts of the product directly to avoid failure or malfunctions.
• Install the product securely using a DIN rail or mounting screws.
FX2N-10GM, FX2N-20GM, and terminal block DIN rail only
Main unit, FX2N Series I/O extension unit/block, and FX0N/FX2N/
DIN rail or direct mounting
FX3U Series special extension block/special adapter
WIRING PRECAUTIONS
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
124
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition
Introduction
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension
units.
Doing so may cause damage to the product. 2
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
Part Names
Features and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally. 3
Doing so may damage the product.
Introduction
Product
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
4
Specifications
- Tightening torque should be between 0.5 and 0.8 N•m.
• Observe the following items when wiring to the European terminal board.
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
5
Devices
Peripheral
Version and
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m. 6
Configuration
System
This chapter explains the procedures for installing the PLC in enclosure.
The procedures for wiring the input and output terminals are described in the following chapters.
• Installation location and layout in enclosure
• Procedures for connecting extension devices
• Procedures for power supply wiring 7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
125
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.1 Generic Specifications
Item Specification
Ambient
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
temperature
Ambient
5 to 95%RH (no condensation) when operating
humidity
Complies with EN 68-2-6
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Vibration Sweep Count for X,
When installed on 10 to 57 − 0.035 Y, Z: 10 times
resistance
DIN rail 57 to 150 4.9 − (80 min in each
direction)
When installed 10 to 57 − 0.075
directly 57 to 150 9.8 −
Shock Complies with EN 68-2-27
resistance (147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z)
Noise By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of
resistance 30 to 100 Hz
Dielectric 1.5kV AC for one minute
Complying with JEM-1021
withstand
500V AC for one minute Between each terminals and ground terminal
voltage*2
Insulation Complying with JEM-1021
5MΩ or more by 500V DC megger
resistance*2 Between each terminals and ground terminal
Class D grounding (grounding resistance: 100 Ω or less) <Common grounding with a heavy
Grounding
electrical system is not allowed.>*1
Working
Free from corrosive or flammable gas and excessive conductive dusts
atmosphere
Working
Complies with IEC61131-2 (<2000m)*3
altitude
*2. For more information on the dielectric withstand voltage test and the insulation resistance test of the
terminals of each product, refer to the following subsection.
→ Refer to Subsection 4.1.1.
*3. Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the
PLC.
126
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.2 Installation location
1
8.2 Installation location
Introduction
Use the PLC under the environmental conditions complying with the generic specifications (Section 8.1).
Notes
• Keep a space of 50 mm (1.97") away between the unit main body and other devices and structure.
Install the unit as far away as possible from high-voltage lines, high-voltage devices and power equipment.
2
Part Names
Features and
• To prevent temperature rise, do not install the PLC on a floor or a ceiling or in the vertical direction.
Install it horizontally on a wall as shown below.
• Arrange the extension cable in such a way that the left connectors of the input/output powered extension units/
blocks or special function units/blocks are connected on the side closer to the main unit.
Introduction
Product
4
Specifications
5
Devices
Peripheral
Version and
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
127
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.2 Installation location
FX2N-16EYT
FX2N-16EX
A FX3U Series A
-ESS/UL
-ES/UL
main unit
A
A ≥ 50mm (1.97")
A
equipment
Another
A
FX2N-16EYR
FX3U-4AD-ADP
FX2N-16EYT
FX2N-16EX
A
FX2N-4AD
FX3U Series
-ESS/UL
-ES/UL
-ES/UL
main unit
A
Extension cable
·FX0N-65EC
FX2N-CNV-
·FX0N-30EC
FX2N-10PG
FX2N-16EX
Input/output
FX2N-8AD
BC
powered
-ES/UL
A extension unit A
Another
A equipment
Another equipment
A ≥ 50mm (1.97")
128
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.3 Layout in Enclosure
1
8.3 Layout in Enclosure
Introduction
The PLC components can be laid out in one stage or in two stages, upper and lower. The connecting
procedures in each case are explained below.
Part Names
Features and
Input/output powered extension units/blocks
Special adapter Special function units/blocks
Extension
Extension
Extension
Extension
A Input/output A
block
block
block
block
FX3U Series
10 9 8 7 6 5 4 3 2 1 main unit powered
Introduction
Product
extension units
A ≥ 50mm (1.97") 4
Specifications
8.3.2 2-stage layout
In the case of a 2-stage layout, connect the first stage and the second stage with the extension cable.
When an extension block is connected at the top of the second stage, FX2N-CNV-BC (connector conversion
adapter) is necessary.
5
Devices
Peripheral
Version and
1. When an input/output powered extension unit is connected at the top of the 2nd stage
Input/output powered extension
Special adapter units/blocks
Special function units/blocks
6
Extension
Extension
Extension
A
block
block
block
FX3U Series
Configuration
System
10 9 8 7 6 5 4 3 2 1
main unit
Up to 10 units (approx. 18mm For the dimensions of each product, refer to the
(0.71") x number of units) external dimensions diagram.
A 7
Extension
Extension
Extension
Input/output A
block
block
block
block
powered
extension
units*1
Extension cable
•FX0N-65EC (650mm (25.59"))
8
For the dimensions of each product, refer to the
Installation
*1 The shaded part in the above figure includes FX2N-1RM(-E)-SET A ≥ 50mm (1.97")
and FX3U-1PSU-5V, however only FX2N-1RM(-E)-SET is
connectable to FX2N-1RM(-E)-SET.
9
Wiring
Power Supply
Preparation and
10
Input Wiring
129
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.3 Layout in Enclosure
2. When an input/output extension block or a special function block is connected at the top of
the 2nd stage
Input/output powered extension
Special adapter units/blocks
Special function units/blocks
Extension
Extension
Extension
A
block
block
block
FX3U Series
10 9 8 7 6 5 4 3 2 1 main unit
FX2N-CNV-BC
Extension
Extension
Extension
Extension
Input/output A
block*1
block
block
block
powered
extension units
Extension cable
•FX0N-65EC (650mm (25.59")) For the dimensions of each product, refer to the
•FX0N-30EC (300mm (11.81")) external dimensions diagram.
Extension
Extension
A
block
block
block
10 9 8 7 6 5 4 3 2 1 FX3U Series
main unit
Up to 10 units (approx. 18mm For the dimensions of each product, refer to the
(0.71") x number of units) external dimensions diagram.
A
Extension
Extension
Extension
A
block
block
block
FX2N-10GM
FX2N-20GM
Extension cable
•FX2N-GM-65EC (650mm) For the dimensions of each product, refer
to the external dimensions diagram.
A ≥ 50mm (1.97")
130
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.4 Examination for Installing Method in Enclosure
1
8.4 Examination for Installing Method in Enclosure
Introduction
Examine the installation location of PLC in consideration of the environmental conditions (generic
specifications).
Part Names
Features and
The PLC can be installed by the following two methods.
Introduction
Product
• The PLC is installed higher by the height of the DIN rail.
→ For details on the procedures on mounting and removing the DIN rail, refer to Section 8.5.
Specifications
8.4.2 Cautions in examining installing method
→ Refer to Section 8.3.
Devices
Peripheral
Version and
CNV-BC cannot be installed directly.
Configuration
System
8.4.3 Examples of installation
As shown in the following example, when the main unit is installed on the DIN rail, the extension devices
connected with the extension cable can be installed directly in the enclosure.
1 to 2mm
(0.04" to 0.08") Extension cable
*1 •FX0N-65EC
FX2N-CNV-BC •FX0N-30EC
FX2N-
16EX- FX2N- DIN rail 9
ES/UL 10PG
Wiring
Power Supply
Preparation and
(+ indicates an M4 screw.)
*1. FX2N-CNV-BC can be installed directly in the enclosure but cannot be installed on the DIN rail.
10
Input Wiring
131
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.4 Examination for Installing Method in Enclosure
1 to 2mm
(0.04" to 0.08")
FX2N-CNV-BC Extension cable
•FX0N-65EC
FX2N- •FX0N-30EC
16EX- FX2N-
ES/UL 10PG
(+ indicates an M4 screw.)
DIN rail
1 to 2mm
(0.04" to 0.08")
*1
Extension cable
FX2N-CNV-BC •FX0N-65EC
FX2N- •FX0N-30EC
16EX- FX2N-
ES/UL 10PG
(+ indicates an M4 screw.)
*1. FX2N-CNV-BC can be installed directly in the enclosure but cannot be installed on the DIN rail.
132
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.5 Procedures for Installing on and Detaching from DIN Rail
1
8.5 Procedures for Installing on and Detaching from DIN Rail
Introduction
The main unit can be installed on a DIN46277 rail (35 mm (1.38") wide).
Part Names
Features and
1. Connecting extension devices
Some extension devices must be mounted on the main unit before the unit is installed in the enclosure.
• Mount the expansion board and special adapters on the main unit before installing it in the enclosure.
• Mount the input/output powered extension units/blocks and the special function units/blocks in the
enclosure after installing the main unit in the enclosure. 3
Introduction
Product
• The memory cassette and the display module can be fitted to the main unit after it is installed.
• The battery can be replaced with a new one in the state where the main unit is in the enclosure.
→ For the replacement procedures, refer to Subsection 14.4.4.
Specifications
Be sure to remove the dust proof sheet when the installation and wiring work is completed.
Devices
Peripheral
Version and
6
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
133
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.5 Procedures for Installing on and Detaching from DIN Rail
1 A 1
1 1
D D
3 3
134
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.5 Procedures for Installing on and Detaching from DIN Rail
1
8.5.3 Installation of input/output powered extension unit/block and special function unit/
Introduction
block
1 Push out the DIN rail mounting hook (A in the right fig- Rear panel Rear panel
2
ure) of the input/output extension block.
Part Names
Features and
• For input/output powered extension units, 8-point type input/output extension 1
blocks and special extension units/blocks, this operation is unnecessary.
A
3
Introduction
Product
2 Fit the upper edge of the DIN rail mounting groove (B in
the right figure) onto the DIN rail.
Specifications
• Keep a gap of 1 to 2 mm (0.04" to 0.08") between the products.
3
Devices
Peripheral
Version and
8.5.4 Removal of main unit
Configuration
System
in the right figure). L N
S/S 0V
24V
X0
X1
X2
X3
X4
X5
X6
X7
X10
IN
X11
X12
X13
X14
X15
X16
X17
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
X20
X21
X22
X23
X24
X25
X26
X27
2
10 11 12 13 14 15 16 17
POWER
RUN
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
OUT
10 11 12 13 14 15 16 17
FX3U-48M
7
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
9
Wiring
Power Supply
Preparation and
10
Input Wiring
135
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.5 Procedures for Installing on and Detaching from DIN Rail
right figure).
7 E 7
136
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.6 Procedures for Installing Directly (with M4 Screws)
1
8.6 Procedures for Installing Directly (with M4 Screws)
Introduction
The product can be installed directly in the enclosure (with screws).
Point
2
Position the holes so that there is a gap of 1 to 2 mm (0.04" to 0.08") between the products.
Part Names
Features and
8.6.1 Hole pitches for direct mounting
The product mounting hole pitches are shown below.
For the pitch that varies depending on the product, refer to the table. 3
1. Main unit (A or B)
Introduction
Product
22 Unit: mm (inches)
5
(0.87") W (0.2") Mounting hole
Model name
pitch (W)
FX3U-16MR/ES
4
80 (3.15")
90 (3.55")
Specifications
FX3U-16MT/ES
A FX3U-16MT/ESS
103 (4.06")
FX3U-16MR/DS
FX3U-16MT/DS
22 5 A
FX3U-16MT/DSS 5
(0.87") (0.2") FX3U-32MR/ES
Devices
Peripheral
Version and
W
FX3U-32MT/ES
FX3U-32MT/ESS
123 (4.85")
80 (3.15")
90 (3.55")
FX3U-32MR/DS
B FX3U-32MT/DS 6
FX3U-32MT/DSS
Configuration
System
FX3U-48MR/ES
FX3U-48MT/ES
FX3U-48MT/ESS
155 (6.11")
FX3U-48MR/DS
FX3U-48MT/DS
7
FX3U-64MT/DSS
FX3U-80MR/ES
FX3U-80MT/ES
FX3U-80MT/ESS
258 (10.16") 9
FX3U-80MR/DS
Wiring
Power Supply
Preparation and
FX3U-80MT/DS
FX3U-80MT/DSS
FX3U-128MR/ES
FX3U-128MT/ES 323 (12.72")
FX3U-128MT/ESS
10
Input Wiring
137
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.6 Procedures for Installing Directly (with M4 Screws)
105 (4.14")
FX3U-4DA-ADP
98 (3.86")
FX3U-4AD-PT-ADP
C FX3U-4AD-TC-ADP Refer to the
C
FX3U-232ADP figure shown left.
FX3U-485ADP
FX3U-4HSX-ADP
FX3U-2HSY-ADP
FX2N-32ER-ES/UL
D FX2N-32ET-ESS/UL
D FX2N-32ER 140 (5.52")
FX2N-32ET
FX2N-32ES
5 5 FX2N-48ER-ES/UL
(0.2") W (0.2") FX2N-48ET-ESS/UL
FX2N-48ER
FX2N-48ET
172 (6.78")
FX2N-48ER-DS
80 (3.15")
90 (3.55")
E
FX2N-48ET-DSS
E FX2N-48ER-D
FX2N-48ET-D
FX2N-48ER-UA1/UL 210 (8.27")
Unit: mm (inches)
4
(0.16") W Mounting hole
Model name
pitch (W)
FX2N-8ER-ES/UL
80 (3.15")
90 (3.55")
FX2N-8ER
F FX2N-8EX-ES/UL
FX2N-8EX
FX2N-8EX-UA1/UL
F 39 (1.54")
FX2N-8EYR-ES/UL
FX2N-8EYT-ESS/UL
FX2N-8EYR
20 20
(0.87") (0.87") FX2N-8EYT
FX2N-8EYT-H
FX2N-16EX-ES/UL
80 (3.15")
90 (3.55")
FX2N-16EX
G FX2N-16EX-C
FX2N-16EXL-C
FX2N-16EYR-ES/UL Refer to the
G
FX2N-16EYR figure shown left.
FX2N-16EYT-ESS/UL
FX2N-16EYT
FX2N-16EYT-C
FX2N-16EYS
138
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.6 Procedures for Installing Directly (with M4 Screws)
1
5. Special function unit/block (H, I or J)
Introduction
Unit: mm (inches)
Mounting hole
4 4 75 4 Model name
(0.16") (0.16") (2.96") (0.16") pitch(W)
W
FX0N-3A 2
FX2N-2AD
Part Names
Features and
80 (3.15")
FX2N-2DA
80 (3.15")
90 (3.55")
90 (3.55")
FX2N-1PG
H I
FX2N-1PG-E 39 (1.54")
FX2N-10PG
FX2N-64CL-M
FX2N-32CCL
3
4 FX2N-16LNK-M
Introduction
Product
4
(0.16") W (0.16")
FX3U-4AD
FX3U-4DA
H FX3U-20SSC-H
FX3U-1PSU-5V
4
105 (4.14")
98 (3.86")
FX2N-4AD
J FX2N-4DA
Specifications
FX2N-4AD-PT
FX2N-4AD-TC 51 (2.01")
FX2N-5A
FX2N-2LC
FX2N-1HC
FX2N-1RM-SET 5
FX2N-1RM-E-SET
Devices
Peripheral
Version and
FX2N-232IF
FX2N-32ASI-M
Refer to the
I FX2N-16CCL-M
figure shown left.
J
FX2N-8AD 67 (2’64")
6
FX2N-20PSU 52 (2’05")
Configuration
System
These units can-
FX2N-10GM
− not be installed
FX2N-20GM
directly.
8
80 (3.15")
98 (3.86")
C B G H J D
Installation
2* 2* 2*
FX3U-48MR/ES (0.08") (0.08") (0.08") 2 * (0.08") FX2N-32ER-ES/UL
FX2N-16EX-ES/UL FX2N-2AD FX2N-8AD
9
FX3U-232ADP
Wiring
Power Supply
Preparation and
10
Input Wiring
139
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.6 Procedures for Installing Directly (with M4 Screws)
2
B
Fit the main unit (A in the right figure)
based on the holes, and secure it with M4
screws (B in the right figure).
The positions and number of screws depend on the
product. Refer to the external dimensions diagram.
→ For the external dimensions, refer to Section 4.6.
8.6.4 Installation of input/output powered extension unit/block and special function unit/
block
1 Make mounting holes in the mounting sur- Rear panel Rear panel
140
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
1
8.7 Connecting Methods for Main Unit and Extension Devices
Introduction
This section explains the connecting methods for extension devices.
Part Names
Features and
board, special adapters, input/output extension blocks and special function units/blocks.
The connecting methods are explained with the following configuration examples.
Example of configuration
Introduction
Product
FX3U Series
main unit
4
Specifications
Connecting Connecting Connecting Connecting method D
method B method A method C
FX2N Series FX2N Series input/output FX2N Series special function units
extension block powered extension unit
Extension cable 5
•FX0N-65EC
Devices
Peripheral
Version and
•FX0N-30EC
FX2N- FX2N Series
CNV- Input/output powered
BC extension unit
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
141
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
→ Refer to Subsection 8.5.4 for the "removal from DIN rail" procedure.
→ Refer to Section 8.6 for the "direct mounting" removal procedure.
142
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
1
8.7.3 Connecting method B - connection of special adapter
Introduction
When an expansion board is used, connect the board as stated in the previous subsection before connecting
the special adapter.
When a high-speed input/output special adapter is used, fit the adapter before connecting other special
adapters. 2
1
Part Names
Features and
Remove the special adapter connector cover (A 26
27
R
22
E
W
21
N
P
U
20
TT
A
27
R
17
6
26
O
R
16
R
25
E
15
4
24
14
3
23
13
2
22
12
1
11 21
0
10 20
IN
7
17
6
16
5
15
4
14
3
13
2
12
1
11
T
0
U
10
O
• When fitting a high-speed input/output special adapter, also FX33U-4
FX M
U-488M
3U
cover (C in the right figure).
Introduction
Product
N
U
R
P
TO
S
• When adding a special adapter to the special adapter that has B 1
been connected to the expansion board, read "expansion board" 2
as "special adapter." A
C
2 Slide the special adapter connecting hooks (B in B
4
Specifications
the right figure) of the main unit.
• When adding a special adapter to the special adapter that has been connected to the main unit, read "main
unit" as "special adapter." (This applies to the following steps.)
5
3 Connect the special adapter (C in
Devices
Peripheral
Version and
the right figure) to the main unit as
shown in the right figure.
B
4 Slide the special adapter connecting
C
4
6
hooks (B in the right figure) of the
Configuration
System
main unit to secure the special 3 4
adapter (C in the right figure).
3
3
B
7
8.7.4 Connecting method C - connection of powered extension unit/block to main unit
main unit. 3
2
1
B
Connect the extension cable (B in the right fig-
ure) from the extension block to be connected
(right side) to the extension device connector 9
of the main unit.
Wiring
Power Supply
Preparation and
143
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
1 3
the existing unit/block (left side) (A in the right
figure). C
A
• When connecting FX2N-10GM or FX2N-20GM, remove the PLC
extension block connector cover.
• When connecting FX2N-1RM(-E)-SET or FX3U-1PSU-5V,
remove the top cover of FX2N-1RM(-E)-SET or FX3U-1PSU-5V.
2 Connect the extension cable (C in the above figure) of the block to be con-
nected (right side) to the existing unit/block (A in the above figure).
• When FX2N Series input/output powered extension units, FX2N-10GM, FX2N-20GM, FX2N-1RM(-E)-SET or
FX3U-1PSU-5V units are connected, connect the unit to be added (right side) and the existing unit (left
side) with the supplied extension cable.
3 Fit the top cover (B in the above figure) (except when connecting FX2N-10GM
or FX2N-20GM).
144
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
1
8.7.6 Connecting method E - connection of extension cable and FX2N-CNV-BC
Introduction
This subsection explains the procedures for connecting an extension cable and FX2N-CNV-BC to the
extension cable of the powered extension unit/block.
Part Names
Features and
To separate the case, use a precision flathead screw-
B
driver. A
Slightly insert the tip of the screwdriver into the part A
shown in the right figure, and the hook (B in the right fig- A 3
ure) will come off (4 places). A
Introduction
Product
1
A
2
1
Connect the extension cable on the upstream
side (C in the right figure). 4 4
4
Specifications
E
Connect the extension cable on the down-
stream side (D in the right figure).
C
4 Fit the upper cover (E in the right figure) and FX0N-30EC
2
5
the lower cover (F in the right figure), and FX0N-65EC 3
Devices
Peripheral
Version and
press down the upper cover until it is D
hooked.
F
Configuration
System
8.7.7 Connecting method F - connection of input/output powered extension unit
This subsection explains the procedures for connecting an input/output powered extension unit.
sion connector. 4
145
FX3U Series Programmable Controllers 8 Installation In Enclosure
User’s Manual - Hardware Edition 8.7 Connecting Methods for Main Unit and Extension Devices
IN
2N 0 1
-32 1
2
2
3
ET 3 4
5
4 6
5 7
0 6
O
U
1
T
0 7
1 2
2 3
2
3 4
4 5
5 6
6 7
2
7
146
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition
Introduction
9. Preparation for Wiring and Power Supply Wiring
Procedures
2
Part Names
Features and
DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
3
Introduction
Product
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled. 4
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
Specifications
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off. 5
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
Devices
Peripheral
Version and
to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS
6
Configuration
System
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
7
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
8
Installation
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
9
Wiring
Power Supply
Preparation and
10
Input Wiring
147
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
• Observe the following items when wiring to the European terminal board.
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
This chapter explains the procedures for wiring, cabling and wiring the power supply.
The input/output wiring procedures are stated in the following chapter.
• Wiring procedures
• Procedures for connecting cables to various shapes of power supply and input/output terminals
• Procedures for the wiring power supply
148
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.1 Preparation for Wiring
1
9.1 Preparation for Wiring
Introduction
9.1.1 Wiring procedures
Before starting wiring work, make sure that the main power is off. 2
Part Names
Features and
1 Prepare the parts for wiring.
Prepare the solderless terminals and cables necessary for wiring.
→ For details, refer to Section 9.2.
3
2
Introduction
Product
Wire the power supply terminals.
In the case of AC power supply type
Specifications
Connect the power supply to the terminals [ ] and [ ].
Provide the power supply circuit with the protection circuit shown in this subsection.
→ For details, refer to Section 9.5.
Devices
Peripheral
Version and
(Class D).
Connect a class D ground wire to the terminal.
→ For details, refer to Section 9.4 and 9.5.
Configuration
System
For a type (24V DC input type) common to sink/source input, select sink or source input by the
following connection.
149
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.2 Cable Connecting Procedures
WIRING PRECAUTIONS
• Cut off all phases of the power source externally before installation or wiring work in order to avoid electric shock
or damage of product.
• Make sure to attach the terminal cover offered as an accessory to the product before turning on the power or
starting the operation after installation or wiring work.
Failure to do so may cause electric shock.
WIRING PRECAUTIONS
• Perform wiring properly to the FX0N/FX2N/FX3U Series extension equipment of the terminal block type in
accordance with the following precautions.
Failure to do so may cause electric shock, short-circuit, wire breakage, or damages to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 to 0.8 N•m.
• Properly perform wiring to the FX Series terminal blocks following the precautions below in order to prevent
electrical shock, short-circuit, breakage of wire, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 to 0.8 N•m.
For the main unit, FX2N Series input/output powered extension units/blocks and FX0N/FX2N/FX3U Series
special function units/blocks, an M3 or M3.5 screw terminal block is used.
1. Applicable products
Product type Model name
Main unit All models of FX3U Series main units
Input/output powered extension unit All models of FX2N Series input/output powered extension units
All models of FX2N Series input/output extension blocks
Input/output extension block
(except FX2N-16EX-C, FX2N-16EXL-C and FX2N-16EYT-C)
Extension power supply unit FX3U-1PSU-5V
Special function unit/block Refer to the manual for each special function unit/block.
FX Series terminal block All models
Power supply unit FX2N-20PSU
150
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.2 Cable Connecting Procedures
1
3. Wire end treatment
Introduction
The solderless terminal size depends on the terminal screw size and wiring method.
- Use solderless terminals of the following size.
- Tighten the terminals to a torque of 0.5 N•m to 0.8 N•m.
Part Names
Features and
• When one wire is connected to one terminal
Terminal Crimp
φ 3.2(0.13") screw terminal
6.2mm(0.24")
or less 3
Introduction
Product
φ 3.2(0.13")
6.2mm(0.24") Terminal
or less
Specifications
6.2mm(0.24") Terminal Crimp
or less screw terminal
6.3mm(0.25")
or more
φ 3.2(0.13") 5
6.2mm(0.24") Terminal
Devices
Peripheral
Version and
or less 6.3mm(0.25")
or more
Configuration
System
• When one wire is connected to one terminal
Terminal Crimp
φ 3.7(0.15") screw terminal
6.8mm(0.27")
or less 7
6.8mm(0.27")
φ 3.7(0.15") 9
Terminal
Wiring
Power Supply
Preparation and
or less 6.0mm(0.24")
or more
10
Input Wiring
151
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.2 Cable Connecting Procedures
1. Applicable products
Classification Model names
Input/output extension blocks FX2N-16EX-C, FX2N-16EXL-C, FX2N-16EYT-C
Special function units/blocks FX3U-20SSC-H, FX2N-10PG, FX2N-10GM, FX2N-20GM
152
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.2 Cable Connecting Procedures
1
4) Certified connectors (commercially available connectors)
Introduction
Connectors made by DDK Ltd. shown in Item (3) described in the previous page and connectors made by
Matsushita Electric Works, Ltd. shown in the following table
Compliant electric wires
Model name of connector Pressure bonding tool
(UL-1061 is recommended)
Housing AXW1204A 2
AWG22 (0.3mm2)
Part Names
Features and
Contact AXW7221 AXY52000
AWG24 (0.2mm2)
Semi-cover AXW62001A
9.2.3 Terminal block (for europe) [expansion board and special adapters]
3
Introduction
Product
WIRING PRECAUTIONS
• Cut off all phases of the power source externally before installation or wiring work in order to avoid electric shock
or damage of product.
• Observe the following items to wire the lines to the European terminal board. Ignorance of the following items may 4
cause electric shock, short circuit, disconnection, or damage of the product.
Specifications
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there is no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect electric wires of unspecified size or beyond the specified number of electric wires.
- Fix the electric wires so that the terminal block and connected parts of electric wires are not directly stressed. 5
Devices
Peripheral
Version and
The expansion board and special adapters of a terminal block type have terminal blocks for Europe.
1. Applicable products
Classification Model names
Expansion Board FX3U-485-BD 6
FX3U-485ADP, FX3U-4AD-ADP, FX3U-4DA-ADP, FX3U-4AD-PT-ADP, FX3U-4AD-TC-ADP,
Configuration
System
Special Adapters
FX3U-4HSX-ADP, FX3U-2HSY-ADP
2. Electric wires
153
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.3 Power Supply Specifications
• Treatment using bar terminal with insulating sleeve • Bar terminal with insulating sleeve
It may be difficult to insert the electric wire into the insulating sleeve
Insulating sleeve
depending on the thickness of the electric wire sheath. Select the Contact portion
electric wire referring to the outline drawing.
Manufacturer Model names Caulking tool 8mm
Phoenix Contact AI 0.5-8WH CRIMPFOX UD6 2.6mm (0.32")
(0.11") 14mm(0.56")
4. Tool
• For tightening the terminal, use a commercially available small
screwdriver having a straight form that is not widened toward the end as
shown right. With
straight tip
Manufacturer Model names
Phoenix Contact SZS 0.4 x 2.5 0.4mm 2.5mm
(0.02") (0.1")
Specifications
Item
FX3U-16M /E FX3U-32M /E FX3U-48M /E FX3U-64M /E FX3U-80M /E FX3U-128M
Supply voltage 100 to 240V AC
Allowable supply
85 to 264V AC
voltage range
Rated frequency 50/60Hz
Allowable Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
instantaneous When the supply voltage is 200V AC, the time can be changed to 10 to 100 ms by editing the user
power failure time program.
Power fuse 250V, 3.15A 250V, 5A
30 A max. 5 ms or less/100V AC
Rush current
65 A max. 5 ms or less/200V AC
Power
30W 35W 40W 45W 50W 65W
consumption*1
24V DC service
400 mA or less 600 mA or less
power supply*2
5V DC built-in
500 mA or less
power supply*3
*1. These power consumption values are maximum values which apply to the main unit's 24V DC service
power supply when there are input/output extension blocks and special function units/blocks.
→ For input/output powered extension units/blocks power consumption information,
refer to Section 15.2.
*2. When input/output extension blocks are connected, 24V DC service power is consumed by the blocks,
and the power to be consumed by the main unit is reduced.
→ For details on the 24V DC service power supply, refer to Section 6.5.
*3. The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
154
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.3 Power Supply Specifications
1
9.3.2 DC Power Supply Type
Introduction
Specifications
Item
FX3U-16M /D FX3U-32M /D FX3U-48M /D FX3U-64M /D FX3U-80M /D
Supply voltage
Allowable supply voltage
24V DC
2
*3
16.8 to 28.8V DC
Part Names
Features and
range
Allowable instantaneous
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
power failure time
Power fuse 250V, 3.15A 250V, 5A
Power consumption*1 25W 30W 35W 40W 45W 3
Rush current 35 A max. 0.5 ms or less/24V DC
Introduction
Product
24V DC service power
−
supply
5V DC built-in power
500 mA or less
supply*2
4
*1. This power consumption is the value maximized by input/output extension blocks and special function
Specifications
units/blocks connected to the main unit.
→ For input/output powered extension units/blocks power consumption information,
refer to Section 15.2.
*2. The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
5
Devices
Peripheral
Version and
*3. When supply voltage is 16.8 to 19.2V DC, the connectable extension equipment decreases.
For details, refer to Subsection 6.5.3 or 6.5.4.
Configuration
System
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
155
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.4 Grounding
9.4 Grounding
Ground the PLC as stated below.
• Perform class D grounding. (Grounding resistance: 100Ω or less)
• Ground the PLC independently if possible.
If it cannot be grounded independently, ground it jointly as shown below.
Extension devices of PLC (except expansion board and special communication/high-speed input/output
adapter)
PLC
Special Expansion Input/output Special Another
Main unit
adapter board extension unit extension equipment
Independent grounding
Class D grounding
(grounding resistance : 100Ω or less)
156
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.5 Examples of External Wiring [AC Power Supply Type]
1
9.5 Examples of External Wiring [AC Power Supply Type]
Introduction
9.5.1 Example of input/output wiring with 24V DC service power supply
24V DC service power supply of the main unit can be used as a power supply for loads. 2
However, the power consumed by extension devices should be subtracted from the 24V DC service power,
Part Names
Features and
and the remainder can be used as power for loads.
AC power supply of
100 to 240V
Breaker 3
Power ON
Introduction
Product
PL
MC
MC
Emergency
In the case of sink input wiring stop
4
Specifications
Main unit *1
L
Class D
grounding
N
MC MC
S/S
0V
5
0V
Power supply for loads
Devices
Peripheral
Version and
24V 24V
connected to sequencer
output terminals
X0
As for the details of
X1 emergency stop, see
"DESIGN PRECAUTIONS" 6
at "Safety Precautions"
Configuration
System
field.
X7
Input
In the case of source input wiring
impedance
S/S
0V 0V 7
COM1
24V
Y3
5V 0V 24V Load
8
*2
Installation
X0
5V 0V 24V X1 9
Wiring
Power Supply
Preparation and
*1 Connect the AC power supply to the L and N *2 Connect the 24V terminal (in the case of sink input)
terminals (in any case of 100V AC system and or the 0V terminal (in the case of source input) to
200V AC system). the S/S terminal on the input extension block.
As for the details, see "WIRING PRECAUTIONS"
at "Safety Precautions" field. 10
Input Wiring
157
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.5 Examples of External Wiring [AC Power Supply Type]
DC AC
Class D
Input / output powered extension unit *1 grounding Power supply for loads to
L be connected to PLC
output terminals
N
Sink and S/S 24V DC As for the details of
5V 0V 24V service
source 0V emergency stop
power operation, see "DESIGN
input 24V supply
type *5 output PRECAUTIONS" at
*2,3 "Safety Precautions" field.
Input extension S/S
block
Sink input type
5V 0V 24V
*6 Class D 24V DC
Special function 24+ grounding COM
service power
block 24+
supply output
*5
5V 0V 24V 24-
*3 In the case of the sink input type, the S/S terminal is used
as the 24+ terminal.
Output extension *4 Some special function units/blocks do not have the power
block supply terminal.
5V 0V 24V When using an external power supply, turn it ON at the
same time with the main unit or earlier than the main unit.
When turning OFF the power, confirm the safety of the
system, and then turn OFF the power of the PLC (including
*1 Connect the AC power supply to the L and N terminals (in
special extension equipment) at the same time.
any case of 100V AC system and 200V AC system).
*5 Do not connect the 24V terminals (24V DC service power
Make sure that the power is turned ON at the same time in
supply) of the main unit and the input/output extension unit
the main unit and extension units or earlier in extension
with each other. Connect the 0V terminal.
units than the main unit.
*6 Some special extension units/blocks do not have power
For the details, refer to "W IRING PRECAUTIONS" in
terminals.
"Safety Precautions".
When using an external power supply, turn it ON at the
As for the details, see "W IRING PRECAUTIONS" at
same time with the extension unit or earlier than the
"Safety Precautions" field.
extension unit.
*2 Connect the 24V terminal of the main unit or the input/
When turning OFF the power, confirm the safety of the
output extension unit to the S/S terminal of the input
system, and then turn OFF the power of the PLC (including
extension block.
special extension equipment) at the same time.
158
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.5 Examples of External Wiring [AC Power Supply Type]
1
9.5.3 Example of source input [+common] wiring
Introduction
An example of source input [+common] wiring is shown below.
Part Names
Features and
24- Breaker
Class D Power supply ON
Main unit *1 grounding
L
PL
N
MC 3
Introduction
Product
Sink and 5V 0V 24V S/S MC
Emergency
source 0V
*4 stop
input 24V
type 24V DC
*2 service
Input extension S/S
block
power
supply
MC MC 4
5V 0V 24V
Specifications
output
*3 Class D DC
grounding power
Special function 24+
block supply
5V 0V 24V 24- 5
Devices
Peripheral
Version and
Class D DC AC
Input/output powered extension unit *1 grounding
L Power supply for loads to
be connected to PLC
N output terminals
Sink and 5V 0V 24V S/S
24V DC As for the details of 6
source 0V emergency stop
service
Configuration
System
input 24V operation, see "DESIGN
type *4 power
supply PRECAUTIONS" at
*2 output "Safety Precautions" field.
Input extension S/S
block
5V 0V 24V 7
block same time with the main unit or earlier than the main unit.
5V 0V 24V When turning OFF the power, confirm the safety of the
system, and then turn OFF the power of the PLC
(including special extension equipment) at the same time.
*1 Connect the AC power supply to the L and N terminals *4 Do not connect the 24V terminals (24V DC service power
(in any case of 100V AC system and 200V AC system).
Make sure that the power is turned ON at the same time
supply) of the main unit and the input/output extension
unit with each other. Connect the 0V terminal.
9
in the main unit and extension units or earlier in *5 Some special extension units/blocks do not have power
Wiring
Power Supply
Preparation and
159
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.5 Examples of External Wiring [AC Power Supply Type]
9.5.4 An external wiring example for the extension power supply unit (sink input [-common])
This example shows a sink input wiring (-common),including the extension power supply unit.When adding an
input extension block,check the signal name on the terminal block since the sink/source type and sink type
differ from each ther.
Sink and source input type AC power supply of
Class D 100 to 240V
Special adapter 24+ grounding
5V 0V 24V
24- Breaker
Class D
Main unit *1 grounding Power supply ON
L
PL
MC
N
Sink and 5V 0V 24V S/S MC
source 0V Emergency
input 24V stop
type 24V DC
*2,3 service
Input extension S/S power MC MC
block supply
5V 0V 24V output
DC
*4 Class D power
Special function 24+ grounding supply
block
5V 0V 24V 24-
DC AC
Class D
Extension power supply unit *1 grounding Power supply for loads to
L be connected to PLC
output terminals
N As for the details of emergency stop
5V 0V 24V operation, see "DESIGN
PRECAUTIONS" at "Safety Precautions"
field.
Class D Wiring precaution:
*5 grounding Grounding and power cables should be positioned
Special function 24+ to exit the unit from above as shown in the figure.
block
Grounding and
5V 0V 24V 24- power cables
*2,3
Sink and Input extension S/S
source block
input
type 5V 0V 24V
Output extension
block
5V 0V 24V
When turning OFF the power, confirm the
safety of the system, and then turn OFF the
*1 Connect the AC power supply to the L and N terminals (in any case of 100V p o we r o f t h e P L C ( i n c l u d i n g s p e c i a l
AC system and 200V AC system).
Make sure that the power is turned ON at the same time in the main unit extension equipment) at the same time.
and extension power supply units or earlier in extension power supply units *5 Some special function units/blocks do not
than the main unit. have the power supply terminals.
As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions" When using an external power supply, turn it
field. ON at the same time with the extension
*2 Connect the 24V terminal of the main unit to the S/S terminal of the input p owe r s u p p l y u n i t o r e a rl i e r t h a n t h e
extension block. extension power supply unit.
*3 In the case of the sink input type, the S/S terminal is used as the 24+
terminal. When turning OFF the power, confirm the
*4 Some special function units/blocks do not have the power supply terminal. safety of the system, and then turn OFF the
When using an external power supply, turn it ON at the same time with the p o we r o f t h e P L C ( i n c l u d i n g s p e c i a l
main unit or earlier than the main unit. extension equipment) at the same time.
160
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.5 Examples of External Wiring [AC Power Supply Type]
1
9.5.5 An external wiring example for the extension power supply unit (source input [+common])
Introduction
This example shows a source input wiring (+common), including the extension power supply unit.
Part Names
Features and
24- Breaker
Class D
Main unit *1 grounding Power supply ON
L
N
PL
MC 3
Introduction
Product
Sink and 5V 0V 24V S/S MC
source 0V Emergency
input 24V stop
type 24V DC
*2 service
Input extension S/S power MC MC 4
block supply
Specifications
5V 0V 24V output
Class D DC
*3 grounding power
Special function 24+ supply
block
5V 0V 24V 24- 5
Devices
Peripheral
Version and
Class D DC AC
Extension power supply unit *1 grounding
Power supply for loads to
L
be connected to PLC
output terminals
N
5V 0V 24V
As for the details of emergency stop 6
operation, see "DESIGN PRECAUTIONS"
Configuration
System
at "Safety Precautions" field.
Wiring precaution:
*2 Grounding and power cables should be positioned
Sink and Input extension S/S to exit the unit from above as shown in the figure.
source
input 5V 0V 24V
block
Grounding and 7
type power cables
Output extension
block
5V 0V 24V
W hen turning OFF the power, confirm the
safety of the system, and then turn OFF the
*1 Connect the AC power supply to the L and N terminals (in any case
of 100V AC system and 200V AC system).
power of the PLC (including special extension 9
equipment) at the same time.
Wiring
Power Supply
Preparation and
Make sure that the power is turned ON at the same time in the *4 Some special function units/blocks do not have
main unit and extension power supply units or earlier in extension the power supply terminals.
power supply units than the main unit. When using an external power supply, turn it
As for the details, see "WIRING PRECAUTIONS" at "Safety
ON at the same time with the extension power
Precautions" field.
*2 Connect the 0V terminal of the main unit to the S/S terminal of the supply unit or earlier than the extension power
*3
input extension block.
Some special function units/blocks do not have the power supply
supply unit.
W hen turning OFF the power, confirm the 10
terminal. safety of the system, and then turn OFF the
Input Wiring
When using an external power supply, turn it ON at the same time power of the PLC (including special extension
with the main unit or earlier than the main unit. equipment) at the same time.
161
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.6 Examples of External Wiring [DC Power Supply Type]
PL
MC
Sink and 5V 0V 24V S/S MC Emergency
source (0V)
*2 stop
input (24V)
type
*3, 4
Input extension S/S MC MC
block
5V 0V 24V
*1, 5 Class D
Special function 24+ grounding
block
5V 0V 24V 24-
Output extension
block
5V 0V 24V
*1 Connect DC power to [+] and [-] terminals. The same power source for the *3 24V DC [+] supplies power to the [S/S]
main unit, extention unit and special function unit/block is preferable. When terminal at the input extension block.
using the different power source from the main unit, turn ON the perepheral *4 In the case of the sink input type, the [S/S]
devices' power simaltaneously, or earlier than the main unit's. When turning terminal is used as the [24+] terminal.
OFF the power, confirm the safety of the system and then turn OFF the *5 Some special function units/blocks do not
power of the PLC (including special extension equipment) at the same time. have power supply terminal.
*2 Do not connect with [0V] and [24V] terminals. *6 Do not connect with [24+] and [ · ] terminals.
162
FX3U Series Programmable Controllers 9 Preparation for Wiring and Power Supply Wiring Procedures
User’s Manual - Hardware Edition 9.6 Examples of External Wiring [DC Power Supply Type]
1
9.6.2 Example of source input [+common] wiring
Introduction
An example of source input [+common] wiring is shown below.
Part Names
Features and
Circuit protector
24-
Class D
Main unit *1 grounding Power supply ON
PL
MC
3
Introduction
Product
Sink and 5V 0V 24V S/S MC
source (0V) Emergency
input (24V)
*2 stop
type
*3
Input extension S/S MC MC 4
block
Specifications
5V 0V 24V
*1, 4 Class D
grounding
Special function 24+
block
5V 0V 24V 24-
5
Devices
Peripheral
Version and
Class D
*1 grounding Power supply for loads to
Input/output powered extension unit
be connected to PLC
output terminals
Configuration
System
source 0V operation, see "DESIGN
input 24V *2 PRECAUTIONS" at
type "Safety Precautions" field.
*3
Input extension S/S
5V 0V 24V
block
7
Output extension
block
5V 0V 24V
unit/block is preferable. When using the different power source *3 24V DC [-] supplies power to the [S/S]
from the main unit, turn ON the perepheral devices' power terminal at the input extension block.
simaltaneously, or earlier than the main unit's. When turning *4 Some special function units/blocks do not
OFF the power, confirm the safety of the system, and then turn have power supply terminal.
OFF the power of the PLC (including special extension
equipment) at the same time. 10
Input Wiring
163
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition
DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
WIRING PRECAUTIONS
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
164
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition
Introduction
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product. 2
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
Part Names
Features and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
•
out.
Do not wire vacant terminals externally.
3
Introduction
Product
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. 4
- The disposal size of the cable end should follow the dimensions described in this manual.
Specifications
- Tightening torque should be between 0.5 and 0.8 N•m.
• Observe the following items when wiring to the European terminal board.
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires. 5
- Do not solder-plate the electric wire ends.
Devices
Peripheral
Version and
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m. 6
Configuration
System
This chapter explains the followings.
• Sink/source input (24V DC input)
• Input specifications (main unit), instructions for wiring and examples of external wiring
• Input interruption function 7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
165
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.1 Before Starting Input Wiring
166
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
1
10.2 24V DC Input Type (Common to Sink/Source Input)
Introduction
The input specifications for the main unit, cautions in wiring the unit and examples of wiring are given below.
Part Names
Features and
from X010 to the largest number that the main unit has.
(The input numbers of FX3U-16M are X000 to X007.)
→ For details on sink/source input, refer to Subsection 10.1.1.
Specifications
Item *2
FX3U-16M FX3U-32M FX3U-48M FX3U-64M FX3U-80M
Number of input points 8 points 16 points 24 points 32 points 40 points
FX3U-128M
64 points
3
Introduction
Product
Fixed terminal
Input connecting type block Removable terminal block (M3 screw)
(M3 screw)
Input form sink/source
Input signal voltage AC power type: 24V DC ±10% DC power type: 16.8 to 28.8V DC
Input
X000 to X005 3.9 kΩ 4
X006, X007 3.3 kΩ
impedance
Specifications
X010 or more − 4.3 kΩ
X000 to X005 6 mA/24V DC
Input signal X006, X007 7 mA/24V DC
current
X010 or more − 5 mA/24V DC
ON input
X000 to X005 3.5 mA or more 5
sensitivity X006, X007 4.5 mA or more
Devices
Peripheral
Version and
current
X010 or more − 3.5 mA or more
OFF input sensitivity
current 1.5 mA or less
Configuration
System
Input circuit insulation Photocoupler insulation
Input operation display LED on panel lights when photocoupler is driven.
• AC power supply type
Sink input wiring Source input wiring
Fuse Fuse 7
L L
X X
Input circuit configuration
*1 Input impedance
• DC power supply type
Sink input wiring Source input wiring
Fuse Fuse
9
Wiring
Power Supply
Preparation and
24V 24V
(24V) DC (24V) DC
*3 *3
(0V) (0V)
S/S S/S
*1
X
*1
X
10
Input Wiring
167
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
1. Input terminals
Fuse
L
Sink input
N
When a no-voltage contact or NPN open collector transistor 100 to 240V AC
output is connected between an input (X) terminal and the 0V S/S
terminal and the circuit is closed, the input (X) turns on. 0V
Then, the input display LED lights. 24V
* X000
X001
X007
* Input impedance
Source input
When a no-voltage contact or PNP open collector transistor Fuse
L
output is connected between an input (X) terminal and the 24V N
terminal and the circuit is closed, the input (X) turns on. 100 to 240V AC
Then, the input display LED lights. S/S
0V
Display module (option) 24V
When the display module is mounted, the ON/OFF status can
be checked on the LCD display. * X000
X001
RUN terminal setting
X000 to X017 (up to the largest input number in the main
unit*1) of the main unit can be used as RUN input terminals by X007
setting parameters. * Input impedance
*1. The FX3U-16M main unit input range is X000 to X007.
→ For the functions of the RUN terminals, refer to Subsection 14.2.1.
2. Input circuit
Function of input circuit
The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is
provided with a C-R filter.
The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from
the input line.
There is a delay of approx. 10ms in response to input-switching from ON to OFF and from OFF to ON.
*1. When the circuit is used at an input filter value of 5µs, be careful when wiring.
(The details are stated later.)
*2. The FX3U-16M main unit input range is X000 to X007.
The filter time for input numbers X010 to X017 is kept 10 ms because the input filters of the input/
output powered extension units/blocks are used for them.
168
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
1
Cautions in wiring when changing filter time
Introduction
When setting the input filter to 5µs or capturing pulses of a response frequency of 50 to 100kHz with a high-
speed counter, wire the terminals as stated below.
1) The wiring length should be 5m or less.
2) Connect a bleeder resistance of 1.5kΩ (1 W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the mating device and the input current of the main body 2
is 20 mA or more.
Part Names
Features and
3. Input sensitivity
The PLC input current and input sensitivity are shown in the following table.
When there is a series diode or resistance at the input contact or there is a parallel resistance or leakage
current at the input contact, wire the terminals in accordance with the following table.
→ For the instructions for connecting input devices, refer to Subsection 10.2.3. 3
X010 to max input number
Introduction
Product
Item X000 to X005 X006 to X007
of the main unit
Input voltage AC power type: 24V DC ±10% DC power type: 16.8 to 28.8V DC
Input current 6 mA 7 mA 5 mA
Input sensitivity ON 3.5 mA or more 4.5 mA or more 3.5 mA or more
current OFF 1.5 mA or less 1.5 mA or less 1.5 mA or less 4
Specifications
4. Examples of input wiring
For the wiring of input interruption, pulse catch and rotary encoder, refer to the following sections.
→ Example of wiring of input interruption: Refer to Section 10.4.
→ Example of wiring of pulse catch: Refer to Section 10.5.
→ Example of wiring of rotary encoder: Refer to Section 11.10. 5
Devices
Peripheral
Version and
10.2.3 Instructions for connecting input devices
Configuration
System
Input number Input current
X000 to X005 6 mA/24V DC
X006, X007 7 mA/24V DC
X010 or more 5 mA/24V DC
7
<Example> Products of OMRON
24V 0V
9
Wiring
Power Supply
Preparation and
S/S S/S
LED LED
PLC PLC
(sink input) X (source input) X
0V 24V 10
*1
Input Wiring
169
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
15kΩ or 15kΩ or
more Rp Rp
more
0V 24V
*1
0V 24V
*1
170
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
1
10.2.4 Examples of external wiring (sink input) [AC Power Supply Type]
Introduction
Sink and source input type
Part Names
Features and
N
Class D
S/S grounding
0V
*3 3
Introduction
Product
24V
X0
X1
Input Input
Three-
wire
4
5V 0V 24V impedance terminal
Specifications
sensor
X0 5
Sink and source *2
Devices
Peripheral
Version and
input type X1 Two-wire
5V 0V 24V
Input proximity
terminal sensor
Input / output powered extension unit
L
6
Configuration
System
N
Class D
*3 grounding
S/S
0V
24V 7
X1
5V 0V 24V
Input
S/S
Chapter 9 "Preparation for Wiring
and Power Supply Wiring
X0 Procedures."
*2 For an input device having a
X1
parallel resistance or a two-wire
5V 0V 24V
Input proximity switch, a bleeder 9
terminal resistance may be required.
Wiring
Power Supply
Preparation and
171
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
N
Class D
grounding
S/S
*3
Sink and source 0V
input type 24V
X0
X1 Three-
Input Input wire
5V 0V 24V impedance terminal sensor
X0
*2
X1 Two-wire
5V 0V 24V
Input proximity
terminal sensor
Input / output powered extension unit
L
N
Class D
Sink input type grounding
COM
24+
X0
X1
5V 0V 24V
Input
terminal
Input extension block 0V 24V *1 Handle the power supply circuit
24+ correctly in accordance with
Chapter 9 "Preparation for Wiring
X0 and Power Supply Wiring
Procedures."
X1 *2 For an input device having a
5V 0V 24V Input parallel resistance or a two-wire
terminal proximity switch, a bleeder
Special function block resistance may be required.
24+ *3 In the case of sink input wiring,
24- short-circuit the S/S terminal and
the 24V terminal of the main unit.
5V 0V 24V
Class D
grounding
172
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
1
10.2.5 Example of external wiring (source input) [AC Power Supply Type]
Introduction
Sink and source input type
Main unit
2
Fuse *1
Part Names
Features and
L
N
Class D
grounding
S/S
*3
3
0V
Introduction
Product
24V
X0 Three-
wire
X1 sensor
Input Input
4
impedance
Specifications
5V 0V 24V terminal
0V 24V
Input extension block
S/S
X0 Two-wire 5
proximity
Devices
Peripheral
Version and
Sink and source X1 sensor
input type 5V 0V 24V *2
Input
terminal
Input / output powered extension unit
L 6
Configuration
System
N
Class D
*3
S/S grounding
0V
24V 7
X1
5V 0V 24V
Input *1 Handle the power supply circuit
173
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
10.2.6 Examples of external wiring (sink input) [DC power supply type]
*3
S/S
(0V)
(24V)
*4
X0
X1 Three-
Input Input wire
5V 0V 24V impedance terminal sensor
X0
Sink and source *2
input type X1 Two-wire
5V 0V 24V
Input proximity
terminal sensor
Input/output powered extension unit
Class D
*3 grounding
S/S
0V
*4
24V
X0
174
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
Introduction
Use of input/output extension units/blocks of sink input type
Part Names
Features and
*3
S/S
Introduction
Product
X0
X1 Three-
Input Input wire
5V 0V 24V impedance terminal sensor
4
Specifications
Input extension block
24+
X0
*2
5V 0V 24V
X1 Two-wire 5
Input proximity
Devices
Peripheral
Version and
terminal sensor
Input/output powered extension unit
Class D 6
grounding
Configuration
System
Sink input type
COM
24+ *5
X0 7
10
Input Wiring
175
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.2 24V DC Input Type (Common to Sink/Source Input)
10.2.7 Examle of external wiring (source input) [DC Power Supply Type]
*3
S/S
(0V)
(24V)
*4
X0 Three-
wire
X1 sensor
Input Input
5V 0V 24V impedance terminal
X0 Two-wire
proximity
Sink and source X1 sensor
input type 5V 0V 24V *2
Input
terminal
Input/output powered extension unit
Class D
S/S grounding
0V
*4
24V
X0
176
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.3 100V AC Input (Except Main Unit)
1
10.3 100V AC Input (Except Main Unit)
Introduction
10.3.1 Input specifications
Select the input for the input/output powered extension units/blocks. 2
Main units of a 100V AC input type are not available.
Part Names
Features and
→ For the specifications on input/output powered extension units, refer to Chapter 15.
→ For the specifications on input/output extension blocks, refer to Chapter 16.
Introduction
Product
When voltage of 100 to 120V AC is applied between the input Fuse
terminal and COM terminal, the input terminal is turned on. L
The input display LED lights. N
Do not connect the COM terminal of an AC input type input/ 100 to 240V AC
output powered extension unit/block with the COM terminal of
COM 100 to 120V AC 4
a DC system.
Specifications
* Fuse
2. Input circuit X000
X001
The primary input circuit and the secondary input circuit are
insulated with a photocoupler.
There is a delay of approx. 25 to 30ms in response to input 5
X007
switching from ON to OFF and from OFF to ON.
Devices
Peripheral
Version and
* Input impedance
3. Input sensitivity
The input current and input sensitivity of these PLCs are
shown in the following table. 6
Input Specifications
Configuration
System
Input voltage 100 to 120V AC +10%, -15% 50/60Hz
6.2 mA/110V 60Hz Percentage of simultaneous power-on:
Input current
4.7 mA/100V 50Hz 70% or less
ON 3.8 mA/80V AC
Input
sensitivity OFF 1.7 mA/30V AC
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
177
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.3 100V AC Input (Except Main Unit)
S/S Class D
grounding
0V
24V
24V DC X000
input type
(Sink wiring) X001
Three-
Input Input wire
5V 0V 24V impedance terminal sensor
0V 24V
Input extension block
S/S
X0
*2
X1 Two-wire
5V 0V 24V
Input proximity
terminal sensor
Input / output powered extension unit
FX2N-48ER-UA1/UL
L
N
Class D
grounding
COM
COM
100V AC X0
input type
X1
5V 0V 24V
Input
terminal
Input extension block
COM
MC*3
X0
X1
5V 0V 24V
*1 Handle the power supply circuit correctly in
accordance with Chapter 9 "Preparation for
Wiring and Power Supply Wiring Procedures."
*2 For an input device having a parallel resistance
or a two-wire proximity switch, a bleeder
resistance may be required.
*3 Do not take input signals from loads generating
surge.
178
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.4 Input Interruption (I00 to I50 ) - With Delay Function
1
10.4 Input Interruption (I00 to I50 ) - With Delay Function
Introduction
The PLC (main unit) is provided with an input interruption function (input delay interruption function) and has
six interruption input points.
The ON or OFF duration of interruption input signals should be 5µs or more.
→ For details on programming, refer to the programming manual. 2
Part Names
Features and
10.4.1 Allocation of pointers to input numbers (input signal ON/OFF duration)
Interrupt pointer
Interrupt disable ON or OFF duration of input
Input No. Interruption on Interruption on
leading edge trailing edge
control signal
3
X000 I001 I000 M8050
Introduction
Product
X001 I101 I100 M8051
X002 I201 I200 M8052
5µs or more
X003 I301 I300 M8053
X004 I401 I400 M8054 4
X005 I501 I500 M8055
Specifications
10.4.2 Input interruption delay function
This input interruption has a function to delay execution of interruption routine in 1ms units.
With this delay function, the position of the sensor used for input interruption can be adjusted in the sequence 5
program. It is necessary to adjust the actual position of the sensor.
Devices
Peripheral
Version and
→ For the programming, refer to the programming manual.
Configuration
System
ZRN, DSZR and DVIT instructions and general-purpose inputs.
Take care not to overlap the input numbers.
Example:
When the input interrupt pointer "I001" is used, X000 is occupied. Therefore, it is impossible to use C235,
C241, C244, C246, C247, C249, C252 and C254, input interruption (including delay interruption) pointer I000,
7
2. Cautions in wiring
• The wiring length should be 5m or less.
• Connect a bleeder resistance of 1.5kΩ (1 W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the other side device and the input current of the main
8
Installation
body is 20 mA or more.
- Source input: PNP open collector transistor
- Sink input: NPN open collector transistor
2-wire 2-wire
S/S Rb proximity S/S Rb proximity
PLC I sensor PLC I sensor
(sink input) X (source input) X
10
0V 24V
Input Wiring
179
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.4 Input Interruption (I00 to I50 ) - With Delay Function
Fuse Fuse
L L
Class D grounding * Class D grounding *
N N
S/S S/S
0V 0V
24V 24V
1.5 1.5
kΩ kΩ Three-
X000 X000 wire
Three-wire
Fuse Fuse
L L
Class D grounding * Class D grounding *
N N
24V DC 24V DC
S/S S/S
0V 0V
24V 24V 1.5
1.5 kΩ
kΩ Three-
X000 X000 wire
Three-wire
180
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.5 Pulse Catch (M8170 to M8177)
1
10.5 Pulse Catch (M8170 to M8177)
Introduction
The PLC (main unit) is provided with a pulse catch function and has 8 pulse catch input points.
→ For details on programming, refer to the programming manual.
10.5.1 Allocation of special memories to Iinput numbers (ON duration of input signals) 2
Part Names
Features and
Input No. Contact on sequence program ON duration of input signal
X000 M8170
X001 M8171
X002 M8172
5µs or more 3
X003 M8173
Introduction
Product
X004 M8174
X005 M8175
X006 M8176
50µs or more
X007 M8177
4
Specifications
10.5.2 Cautions for pulse catch
Devices
Peripheral
Version and
Example:
When the pulse catch input contact M8170 is used, X000 is occupied. Therefore, it is impossible to use C235,
C241, C244, C246, C247, C249, C252 and C254, input interruption (including delay interruption) pointers
I000 and I001 and SPD, ZRN, DSZR and DVIT instructions at the same time.
6
2. Cautions in wiring
Configuration
System
• The wiring length should be 5 m (16’4") or less.
• Connect a bleeder resistance of 1.5kΩ (1 W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the other side device and the input current of the main
body is 20 mA or more.
7
8
Installation
9
Wiring
Power Supply
Preparation and
10
Input Wiring
181
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch)
User’s Manual - Hardware Edition 10.5 Pulse Catch (M8170 to M8177)
Fuse Fuse
L L
Class D grounding * Class D grounding *
N N
S/S S/S
0V 0V
24V 24V
1.5 1.5
kΩ kΩ Three-
X000 X000 wire
Three-wire
Fuse Fuse
L L
Class D grounding * Class D grounding *
N N
24V DC 24V DC
S/S S/S
0V 0V
24V 24V 1.5
1.5 kΩ
kΩ Three-
X000 X000 wire
Three-wire
182
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.1 Outline
11
Counters
High-Speed
11. Use of High-speed Counters (C235 to C255)
12
11.1 Outline
Output Wiring
The high-speed counters can count the signals to the general-purpose input terminals to the main unit or to
the high-speed input special adapters (options).
These two types of counters differ in the maximum response frequency and type of input signals to be
counted. 13
→ For details, refer to Section 11.2.
Various Uses
Wiring for
• General-purpose input terminals of main unit
Signals from an open collector transistor output can be input to the counters. The counters can count
signals of up to 100kHz (1-phase).
• High-speed input special adapters
Signals from a differential line driver output can be input to the counters. The counters can count signals of 14
up to 200kHz (1-phase).
Troubleshooting
Maintenance,
Test Run,
Rotary encoder, etc.
Main unit (Output form: Open collector transistor)
General-purpose input terminal block X000 to X007
15
Extension Units
Powered
IInput/Output
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 ・
L N ・ 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
IN
10 11 12 13 14 15 16 17
POWER
POWER
RUN
RUN
BATT
ERROR
ERROR
FX3U-48MR/ES OUT
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
0 11
10 1 12
2 13
3 14
4 15
5 16
6 17
7 20 21 22 23 24 25 26 27
FX 3U-48M
10 11 12 13 14 15 16 17
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5
16
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
Rotary encoder
Blocks
Extension
Input/Output
(Output form: Differential line driver)
1st unit : X000,X001,X002,X006
2nd unit : X003,X004,X005,X007
High-speed input special adapters
FX3U-4HSX-ADP
17
Unit
Power Supply
Extension
Cautions for high-speed input special adapters
Do not use the same input number for both the high-speed input special adapter terminal and the main unit
terminal.
18
Options
Units and
Other Extension
• When wiring the input numbers assigned to a high-speed input special adapter, do not wire the same input
number in main unit.
• When not wiring the input numbers assigned to a high-speed input special adapter, the main unit’s input
terminals can be used as general inputs.
19
Display Module
20
Terminal Block
183
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.2 Input Specifications
1. Performance specifications
Item Specification
Number of input points 4 points (These points are not included in the total number of PLC input/output points.)
Input form Differential line receiver (equivalent to AM26C32)
1-phase 1-input
200kHz
Max. input frequency 1-phase 2-input High-speed counter operating with hardware counter*1
2-phase 2-input 100kHz
Min. pulse width 1 µs or more
The external wiring of the input block and the PLC are insulated with a photocoupler or a
Insulation
transformer.
Wiring length Up to 10m
*1. The maximum input frequency to the software counters*2 is the same as that of signals to be captured
to the input terminals of the main unit.
→ For details on the responce frequency, refer to Subsection 11.9.2.
*2. The software counters include hardware counters that operate as software counters.
→ For the conditions under which the hardware counters operate as software counters,
refer to Subsection 11.8.1.
184
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.3 Types of Counting and Operations
11
11.3 Types of Counting and Operations
Counters
High-Speed
The main unit has built-in 32-bit high speed bi-directional counters (1-phase 1-count input, 1-phase 2-count
input and 2-phase 2-count input). The high-speed counters are classified into hardware counters and
software counters according to the counting method.
For some high-speed counters, external reset input terminals or external start input terminals (start of 12
counting) can be selected.
Output Wiring
11.3.1 Classification according to counting method
Classification Details
Hardware counters
Counting by hardware 13
They are switched to software counters under some working conditions.
Various Uses
Wiring for
Counting through interrupt handling by CPU
Software counters Each counter must be used within limitations on maximum response frequency and overall
frequency.
Troubleshooting
Maintenance,
Test Run,
The types and input signals (waveforms) of high-speed counters (1-phase 1-count input, 1-phase 2-count
input and 2-phase 2-count input) are shown below.
Type of counter Input signal form Counting direction
Down-counting or up-counting is specified by
1-phase 1-count UP/ turning on or off M8235 to M8245. 15
input DOWN ON: Down-counting
Extension Units
Powered
IInput/Output
OFF: Up-counting
Up-counting or down-counting
+1 +1
The counting direction can be checked with
1-phase 2-count UP
M8246 to M8250.
input -1 -1
DOWN
ON: Down-counting
OFF: Up-counting
16
Blocks
Extension
Input/Output
Phase A
1 edge +1 +1 -1 -1
count Phase B
Automatic up-counting or down-counting
Up-counting Down-counting
according to change in input status of phase A/B
2-phase
2-count
The counting direction can be checked with 17
+1 +1 +1 +1 +1 -1 -1 -1 -1 -1 M8251 to M8255.
Unit
Power Supply
Extension
input Phase A ON: Down-counting
4 edge OFF: Up-counting
count Phase B
+1 +1 +1 +1 -1 -1 -1 -1
Up-counting Down-counting
18
Options
Units and
Other Extension
185
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.4 List of Device Numbers and Functions
*1. These counters are handled as software counters depending on working conditions. When they are
handled as software counters, they have limitations on maximum response frequency and overall
frequency.
→ For the conditions under which they are handled as software counter, refer to Section 11.8.
→ For the overall frequency, refer to Section 11.9.
*2. When the input terminals of the main unit receive pulses having a response frequency of 50k to
100kHz, wire the terminals as stated below.
- The wiring length should be 5m (16’4") or less.
- Connect a bleeder resistance of 1.5kΩ (1W or more) to the input terminal, so that the load current
of the open collector transistor output on the mating device side is 20mA or more.
→ For the wiring, refer to Section 11.10.
*3. C244, C245 and C248 are useally used as software counters. When they are used in combination
with special auxiliary relays (M8388 and M8390 to M8392), they can be used as hardware counters
C244(OP), C245(OP) and C248(OP).
→ For the procedures on switching the counter function, refer to Subsection 11.11.3.
*4. The 2-phase 2-input counters are 1 edge count counters. When they are used in combination with
special auxiliary relays (M8388, M8198 and M8199), they can be used as 4 edge count counters.
→ For the procedures on using them as 4 edge count counters, refer to Subsection 11.11.4.
186
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.4 List of Device Numbers and Functions
11
*5. The external reset input terminals are reset when they are turned on. When they are used in
Counters
High-Speed
combination with special auxiliary relays (M8388 and M8389), they can be reset when turned off.
→ For the procedures on changing the external reset input logic, refer to Subsection 11.11.3.
*6. C253 is usually used as a hardware counter. When it is used in combination with the special auxiliary
relay (M8388 and M8392), it can be used as a counter C253(OP) without reset input.
In this case, C253(OP) is handled as a software counter. 12
Output Wiring
13
Various Uses
Wiring for
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
187
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.5 Allocation of Device Numbers to Input Numbers
*1. When the input terminals of the main unit receive pulses having a response frequency of 50k to
100kHz, wire the terminals as stated below.
- The wiring length should be 5m (16’4") or less.
- Connect a bleeder resistance of 1.5kΩ (1 W or more) to the input terminal, so that the load current
of the open collector transistor output on the mating device side to 20mA or more.
→ For the wiring, refer to Section 11.10.
188
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.5 Allocation of Device Numbers to Input Numbers
11
*2. When the comparison set/reset instructions (DHSCS, DHSCR, DHSZ and DHSCT) for high-speed
Counters
High-Speed
counters are used, the hardware (H/W) counters are switched to software (S/W) counters.
When the input signal logic is inverted by the reset input signal logic switching function (M8388 and
M8389), C253 is switched from a hardware counter to a software counter.
→ For the conditions under which it is handled as a software counter, refer to Section 11.8.
*3. The input terminals to be used and the functions are switched by driving the special auxiliary relays in 12
the program.
Output Wiring
→ For the procedures on switching to hardware counters, refer to Subsection 11.11.3.
*4. The 2-phase 2-count input counters are 1 edge count counters. The use of special auxiliary relays
changes them to 4 edge count counters.
→ For the procedures on operating them as 4 edge count counters, refer to Subsection 11.11.4.
13
11.5.2 Inhibition of redundant use of input numbers
Various Uses
Wiring for
• The input terminals X000 to X007 can be used for high-speed counters, input interruption, pulse catch,
SPD, ZRN, DSZR and DVIT instructions and general-purpose inputs. Take care not to overlap the input
numbers.
For example, when C251 is used, X000 and X001 are occupied. Therefore, it is impossible to use C235,
C236, C241, C244, C246, C247, C249, C252 and C254, input interruption pointers I000 and I101, pulse
14
Troubleshooting
Maintenance,
Test Run,
catch contacts M8170 and M8171 and SPD, ZRN, DSZR and DVIT instructions at the same time.
• The same input numbers are allocated to the input terminals on FX3U-4HSX-ADP and the input terminals
of the main unit of FX3U PLC. Use one of the terminals with the same number. If both input terminals are
being used, intended operation cannot be realized because the input terminals on FX3U-4HSX-ADP and
the main unit operate in the OR relation.
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
189
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.6 Handling of High-speed Counters
Examples of program
1) For C235
X010 • C235 counts the number of times the input terminal X000
M8235 Down-count/ switches from OFF to ON while X012 is on.
up-count
X011 • While X011 is on, the counter resets when RST instruction
RST C235 Reset is executed.
X012 • The counters C235 to C245 switch to the down-count or
C235 K-5 up-count mode by turning on or off M8235 to M8245.
Count input
X000
Main unit
2) For C244
X010 • C244 starts counting immediately when the input terminal
M8244 Down-count/ X006 turns on while X012 is on. The count input terminal is
up-count
X000. The setting for this example is the data of the
X011
Reset indirectly designated data register (D1,D0).
RST C244
• C244 can be reset by X011 on the sequence. For C244,
X012 X001 is allocated as the external reset input. The counter
C244 D0(D1)
resets immediately when X001 turns on.
• The counters C235 to C245 switch to the down-count or
The setting is (D1,D0).
up-count mode by turning on or off M8235 to M8245.
3)
Example of operation
The above counter C235 operates as shown below.
X010 Up-count Down-count Up-count
X000
Count
input 5
4 4
3 3
C235 2 2
Current 1 1
value 0 0 0
-1
-2
-3 -3
When output has -4 -4
operated -5 -5
-6 -6
-7 -7
-8
C235 output contact
190
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.6 Handling of High-speed Counters
11
C235 is set to the up-count or down-count mode through interruption by the count input X000.
Counters
High-Speed
• When the current value increases from -6 to -5, the output contact is set, and when the value decreases
from -5 to -6, it is reset.
• The current value increases and decreases regardless of the operation of the output contact. However,
when the counter’s value increments from 2,147,483,647, it changes to -2,147,483,648. In the same
manner, when it decrements from -2,147,483,648, it changes to 2,147,483,647. (This type of counter is 12
called a ring counter.)
Output Wiring
• When RST instruction is executed after the reset input X011 turns on, the current counter’s value resets to
0, and the output contact is restored.
• The current values, output contact operations and reset status of the high-speed counters for retention
upon power failure are kept even if power is turned off.
13
Various Uses
Wiring for
11.6.2 1-phase 2-count input
These counters are 32-bit up-count/down-count binary counters.
The operations of the output contact according to the current value are the same as those of the above-
mentioned 1-phase 1-count input high-speed counters.
14
Examples of program
Troubleshooting
Maintenance,
Test Run,
1) For C246
X011 • While X012 is on, C246 increments the value when the input
RST C246 terminal X000 switches from OFF to ON and decrements the
value when the input terminal X001 switches from OFF to ON.
X012
D2(D3) • The down-count/up-count operations of C246 to C250 can be
15
C246
Extension Units
Powered
IInput/Output
monitored through the ON/OFF operations of M8246 to M8250.
ON: Down-counting
The setting is (D3,D2)
OFF: Up-counting
Up-counting Down-counting
input input
16
X000 X001
Blocks
Extension
Input/Output
Main unit
2) For C249
X011 • While X012 is on, C249 starts counting immediately when 17
RST C249 the input terminal X006 turns on.
Unit
Power Supply
Extension
The up-counting input terminal is X000, and the down-
X012
C249 K1234 counting input terminal is X001.
• C249 can be reset on the sequence by X011.
For C249, X002 is allocated as reset input. When X002
Down-counting
input
External start
input turns on, C249 is immediately reset. 18
Up-counting External
• The down-count/up-count operations of C246 to C250 can
Options
Units and
Other Extension
20
Terminal Block
191
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.6 Handling of High-speed Counters
Examples of program
1) For C251
X011 • While X012 is on, C251 counts the operation of the input terminals
RST C251 X000 (A-phase) and X001 (B-phase) through interruption.
X012 While X011 is turned on, the counter is reset when RST instruction
C251 K1234 is executed.
• When the current value exceeds the setting, Y002 turns on, and
C251
Y002 when the current value becomes lower than the setting, Y002 turns
off.
M8251
• Y003 turns on (down-count) or off (up-count) according to the
Y003
counting direction.
A-phase input B-phase input
X000 X001
Main unit
2) For C254
X011 • C254 starts counting immediately when the input terminal
RST C254 X006 is turned on while X012 is on.
The count input terminals are X000 (A-phase) and X001 (B-
X012
C254 D0(D1) phase).
• C254 is reset by X011 on the sequence, and it is reset
C254 immediately when X002 is turned on.
Y004 The setting is (D1,D0).
• When the current value exceeds the setting (D1,D0), Y004
M8254 operates, and when the current value becomes lower than
Y005 the setting, Y004 turns off.
B-phase input External start input • Y005 turns on (down-count) or off (up-count) according to
A-phase input External reset the counting direction.
input
• A 2-phase encoder generates A-phase output and B-phase output between which there is a 90° phase
difference. The high-speed counter automatically counts up or down according to the output as shown
below.
- Operation by 1 edge count
Phase A
+1 +1 -1 -1
Phase B
Up-counting Down-counting
- Operation by 4 edge count
+1 +1 +1 +1 +1 -1 -1 -1 -1 -1
Phase A
Phase B
+1 +1 +1 +1 -1 -1 -1 -1
Up-counting Down-counting
• The down-count/up-count operations of C251 to C255 can be monitored through the ON/OFF operations
of M8251 to M8255.
ON: Down-counting
OFF: Up-counting
192
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.7 Timing of Updating of Current Value and Comparison of Current Value
11
11.7 Timing of Updating of Current Value and Comparison of Current Value
Counters
High-Speed
11.7.1 Timing of updating of current value
When a pulse is input to a high-speed counter input terminal, the counter increments or decrements. The 12
current value of the device is updated at the timing shown in the following table.
Output Wiring
Therefore, when the hardware counter directly handles the current value of the high-speed counter for MOV
instruction or CMP instruction or an applied instruction (such as a contact comparison instruction), it uses the
current value updated at the timing shown in the following table. As a result, the counter operation is affected
by the scan time.
Classification Timing of updating of current value 13
OUT instruction of counter
Various Uses
Wiring for
Hardware counter
HCMOV instruction
Software counter When count is input
Troubleshooting
Maintenance,
Test Run,
1. Use of comparison instruction (CMP), band comparison instruction (ZCP) or contact
comparison instruction
When the comparison results are necessary for counting operation, the value can be compared with time*1 in
the main program by using HCMOV instruction just before a comparison command (CMP command/ZCP 15
command) or a contact comparison instruction.
Extension Units
Powered
IInput/Output
*1. To compare the value with the high-speed counter's changing value and to change the output contact
(Y), use Comparison instruction for high-speed counters (HSCS/HSCR/HSZ/HSCT instruction).
Blocks
Extension
Input/Output
instructions have limitations on the number of times of use as shown in the following table.
When the output relay (Y) has been designated for comparison results, the ON/OFF status of the output is
affected directly until END instruction output is refreshed.
When the PLC is a relay output type, a mechanical delay in operation (approx. 10ms) is caused. Therefore,
use a transistor output type PLC.
Applied instruction Limitation on number of times of use of instruction
17
Unit
Power Supply
Extension
HSCS
HSCR Up to 32 times including the number of times of use of
HSCT instruction
HSZ*1
HSCT*1 Only once
18
*1. When HSZ or HSCT instruction is used, the maximum response frequencies and overall frequency of
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
193
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.8 Conditions for Hardware Counter to be Handled as Software Counter
C235
K
DHSCS K100 C235 Y000
C253
K
194
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.9 Calculation of Response Frequency and Overall Frequency
11
11.9 Calculation of Response Frequency and Overall Frequency
Counters
High-Speed
11.9.1 Response frequencies of hardware counters
The maximum response frequencies of the hardware counters are shown in the following table. 12
Depending on the working conditions, the maximum response frequencies of hardware counters are the
Output Wiring
same as those of the software counters, and limitations on overall frequency are set up.
→ For the conditions under which the hardware counters are handled as software counters,
refer to the previous page.
Max. response frequency
Counter type Counter Nos.
Main unit FX3U-4HSX-ADP 13
C235,C236,C237,C238,C239,C240 100kHz
Various Uses
Wiring for
1-phase 1-count input
C244(OP),C245(OP) 10kHz 200kHz
1-phase 2-count input C246,C248(OP) 100kHz
2-phase 2-count 1 edge count 50kHz 100kHz
C251,C253
input 4 edge count 50kHz 100kHz
14
Troubleshooting
Maintenance,
Test Run,
11.9.2 Response frequencies and overall frequency of software counters
The maximum response frequencies and overall frequency of software counters are shown below.
When HSZ or HSCT instruction is used in the program, limitations are put on the maximum response
frequencies and overall frequency of all software counters regardless of the instruction operand.
When examining the system or creating the program, use the counters within the maximum response 15
frequency and overall frequency ranges suitable to the conditions in consideration of the limitations.
Extension Units
Powered
IInput/Output
1. When FX3U Series special function units/blocks and analog special adapters are not used
Examples of calculation are given in the heavy-line frame.
Software Magni- Response frequency and overall frequency depending
counters fication
with for
on conditions of instruction to be used 16
Neither HSZ nor Only HSCT Both HSZ and HSCT
Blocks
Extension
Input/Output
HSCS, calcu- Only HSZ instruction
Counter HSCT instruction instruction instructions
Counter type HSCR, lation
Nos. Max. Max. Max. Max.
HSZ or of Overall Overall Overall Overall
HSCT overall response frequency response frequency response frequency response frequency
instruc- frequ- frequency frequency frequency frequency
(kHz) (kHz) (kHz) (kHz)
tion*1 ency (kHz) (kHz) (kHz) (kHz)
C241,
C235, 17
C236,
Unit
Power Supply
Extension
C242,
C237,
C243, ×1 40 30
1-phase C238,
C244,
1-count input C245 C239,
C240 40 - 30 -
C244(OP), (number of (number of
−
C245(OP)
×1 10 10 instruc-
tion) 80 - 1.5 ×
instruc-
tion) 60 - 1.5 × 18
C247, (number of (number of
Options
Units and
Other Extension
80 60 *2 *2
1-phase C248, C246, instruc- instruc-
2-count input C249, C248(OP)
×1 40 30
tion) tion)
C250
1 edge
2- count C252,
×1 40 30
phase
2-
C253
(OP),
C251, (40 - (30 - 19
C253
count 4 edge C254, ×4
number of number of
Display Module
10 7.5
input count C255 instruc- instruc-
tion) / 4 tion) / 4
*1. When an index register is added to a counter number specified by HSCS, HSCR, HSZ or HSCT
instruction, all hardware counters are switched to software counters.
*2. The high-speed counters C244(OP) and C245(OP) cannot count signals of 10kHz or more. 20
Terminal Block
195
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.9 Calculation of Response Frequency and Overall Frequency
2. When FX3U Series special function units/blocks and analog special adapters are used
Software Magni- Response frequency and overall frequency depending on
counters fication conditions of instruction to be used
with for Neither HSZ nor Only HSCT Both HSZ and HSCT
HSCS, calcu- Only HSZ instruction
Counter HSCT instruction instruction instructions
Counter type HSCR, lation
Nos. Max. Max. Max. Max.
HSZ or of Overall Overall Overall Overall
HSCT overall response frequency response frequency response frequency response frequency
instructio frequ- frequency (kHz)
frequency
(kHz)
frequency
(kHz)
frequency
(kHz)
n *1 ency (kHz) (kHz) (kHz) (kHz)
C235,
C241,
C236,
C242,
C237,
C243,
C238,
×1 30 25
1-phase C244,
1-count input C245 C239,
C240 30 - 25 -
C244(OP), (number of (number of
−
C245(OP)
×1 10 10 instruc- instruc-
tions) 50 - 1.5 × tions) 50 - 1.5 ×
C247, *2 (number of *2 (number of
60 50
1-phase C248, C246, instruc- instruc-
2-count input C249, C248(OP)
×1 30 25
tions) tions)
C250
1 edge
2- count C252,
×1 30 25
phase C253
C251, (30 - (25 -
2- (OP),
C253
count 4 edge C254, ×4 7.5 6.2
number of number of
input count C255 instruc- instruc-
tions) / 4 tions) / 4
*1. When an index register is added to a counter number specified by HSCS, HSCR, HSZ or HSCT
instruction, all hardware counters are switched to software counters.
*2. The high-speed counters C244(OP) and C245(OP) cannot count signals of 10 kHz or more.
196
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.9 Calculation of Response Frequency and Overall Frequency
11
1) Calculation of overall frequency
Counters
High-Speed
The overall frequency is calculated by the high-speed comparison instruction used in the program based
on the above table.
Output Wiring
When only HSZ instruction is used six times in a program, the frequency is calculated by the formulas
shown in the "Only HSZ instruction" column in the above table.
Magnification
for
High-speed counter No. to be Input Calculation of max. Instruction
used frequency response frequency
calculation of
overall
to be used 13
frequency
Various Uses
Wiring for
Operation as
C237 20kHz 30 - 6(times) = 24kHz ×1
software counter HSZ instruc-
C241 10kHz 30 - 6(times) = 24kHz ×1 tion is used
Software counter six times.
C253(OP)
[4 edge count]
2kHz {30 - 6(times)} / 4 = 6kHz ×4 14
Troubleshooting
Maintenance,
Test Run,
1) The overall frequency is calculated as shown below because HSZ instruction is used six times.
Overall frequency = 50 - 1.5 × 6 = 41kHz
2) The sum of the response frequencies of the high-speed counters used is
calculated as shown below.
"20kHz × 1[C237]" + "10kHz × 1[C241]" + "2kHz × 4[C253(OP)]" = 38kHz ≤ 41kHz 15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
197
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.10 Examples of External Wiring (Rotary Encoder)
198
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.10 Examples of External Wiring (Rotary Encoder)
11
2. When high-speed input special adapter (FX3U-4HSX-ADP) is used
Counters
High-Speed
1) Differential line driver output rotary encoder
Output Wiring
-
X000 Twisted-pair
Equivalent to shielded wire Non-inverted
AM26C32 X0/3+
output
Phase A+
X000
330Ω
X0/3-
Inverted
Phase A-
13
output
Various Uses
Wiring for
Phase B+
SG Phase B-
SG
Class D Phase Z+
High-speed input
special adapter
grounding*
Phase Z- 14
Troubleshooting
Maintenance,
Test Run,
* The grounding resistance should be 100Ω or less.
Extension Units
Powered
IInput/Output
The following examples of wiring apply to the cases where C251 is used. When another high-speed counter
number is used, wire the counter referring to the following diagrams.
Blocks
Extension
Input/Output
• For connecting cables, use shielded twisted-pair cables. Ground the shield of each shielded cable only on
the PLC side.
• Connect a bleeder resistance of 1.5kΩ (1W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the mating device side and the input current of the main
unit is 20mA or more.
17
Unit
Power Supply
Extension
1) NPN open collector transistor output rotary encoder
L
Fuse 24V DC
24V 18
0V
Options
Units and
Other Extension
N
Class D
S/S grounding*
0V
24V
1.5kΩ
Phase A 19
Display Module
X000 Phase B
X001 Phase Z
PLC
20mA or
* The grounding resistance should be 100Ω or less. more 20
Terminal Block
199
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.10 Examples of External Wiring (Rotary Encoder)
X001 Phase Z
PLC
20mA or
* The grounding resistance should be 100Ω or less. more
SG
Phase Z+
SG
Class D Phase Z-
High-speed input grounding*
special adapter
200
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.11 Related Devices and Function Switching Procedures
11
11.11 Related Devices and Function Switching Procedures
Counters
High-Speed
11.11.1 Related devices
Output Wiring
Counter Counter Specifying Up- Down-
type No. device counting counting
C235 M8235
C236 M8236
C237 M8237 13
C238 M8238
Various Uses
Wiring for
1-phase C239 M8239
1-count C240 M8240 OFF ON
input C241 M8241
C242 M8242
C243 M8243
14
Troubleshooting
Maintenance,
Test Run,
C244 M8244
C245 M8245
Extension Units
Powered
IInput/Output
type No. device type No. device
C246 M8246 C251 M8251
1-phase C247 M8247 2-phase C252 M8252
Up- Down- Up- Down-
2-count C248 M8248 2-count C253 M8253
counting counting counting counting
input C249 M8249 input C254 M8254 16
C250 M8250 C255 M8255
Blocks
Extension
Input/Output
3. For switching high-speed counter function
Device No. Name Description Reference
Contact for
M8388
changing high-
Contact for changing the high-speed counter function −
17
speed counter
Unit
Power Supply
Extension
function
Subsection
M8389 Switching of logic of external reset input
11.11.2
Subsection
M8390 Function switching device for C244
11.11.3 18
Subsection
M8391 Function switching device for C245
Options
Units and
Other Extension
count 11.11.4
20
Terminal Block
201
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.11 Related Devices and Function Switching Procedures
202
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.11 Related Devices and Function Switching Procedures
11
11.11.2 [Function switching] switching of logic of external reset input signal
Counters
High-Speed
The external reset input for the counters C241 to C245, C247 to C250 and C252 to C255 resets the counters
when it is turned ON. If the logic is inverted by the following program, the counters can be reset by turning
OFF the input.
Counter No.
Inversion of logic of external reset input
Details of change
12
signal
Output Wiring
M8388
M8389 The logic of external reset input is inverted to
C241 to C245
reset the counters when the input is turned OFF.
C247 to C250
(The logic for all applicable counter numbers is
C252 to C255
C253
K
inverted.)
13
Various Uses
Wiring for
Cautions in inverting the logic of the external reset input signal
Although C253 is a hardware counter, it is switched to a software counter by inverting the logic of the external
reset input signal.
Troubleshooting
Maintenance,
Test Run,
When the software counters C244, C245, C248 and C253 are combined with the following special auxiliary
relays, the allocation of the input terminals and functions are changed.
Program the special auxiliary relays just before the counters.
Counter No. When used as hardware counter Details of change
Extension Units
Powered
IInput/Output
M8390 X006.
C244(OP) • Reset input is not given.
• Start input is not given.
C244
K • The counter functions as a hardware counter.
Blocks
Extension
Input/Output
C245(OP) • Reset input is not given.
• Start input is not given.
C245
K • The counter functions as a hardware counter.
M8388
M8392
17
• Reset input is not given.
Unit
Power Supply
Extension
C248(OP)
• The counter functions as a hardware counter.
C248
K
M8388
M8392
• Reset input is not given.
18
C253(OP)
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
203
FX3U Series Programmable Controllers 11 Use of High-speed Counters (C235 to C255)
User’s Manual - Hardware Edition 11.11 Related Devices and Function Switching Procedures
11.11.4 [Function switching] procedures for using 2-phase 2-count input counters C251 to
C255 in 4 edge count mode
The 2-phase 2-count input counters C251 to C255 are in the 1 edge count mode. The counters can be
operated in the 4 edge count mode by programming as shown below.
Counter No. To use 4 edge count 2-phase 2-input counter Details of change
M8000
M8198
C251
C251 1 edge count (before change)
K
Phase A
M8000 +1 +1
M8198 Phase B
C252 Up-counting
C252
K
Phase A
M8000 -1 -1
M8199
Phase B
C253 Down-counting
C253
K
M8000 -1 -1 -1 -1 -1
M8198 Phase A
C254
C254 Phase B
K -1 -1 -1 -1
Down-counting
M8000
M8199
C255
C255
K
204
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition
11
Counters
High-Speed
12. Output Wiring Procedures
12
DESIGN PRECAUTIONS
Output Wiring
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for 13
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
Various Uses
Wiring for
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 14
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Troubleshooting
Maintenance,
Test Run,
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
to ensure safe machinery operation in such a case. 15
Extension Units
Powered
IInput/Output
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the 16
control line at least 100mm (3.94") or more away from the main circuit or power line.
Blocks
Extension
Input/Output
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
17
WIRING PRECAUTIONS
Unit
Power Supply
Extension
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
18
Options
Units and
Other Extension
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
19
Display Module
20
Terminal Block
205
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
• Observe the following items when wiring to the European terminal board.
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
This chapter explains the procedures for wiring the output terminals.
• Wiring procedures
• Procedures for cabling according to shape of output terminal
• Output wiring procedures
206
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.1 Sink and Source Output (Transistor)
11
12.1 Sink and Source Output (Transistor)
Counters
High-Speed
FX3U Series main units and FX2N Series input/output extension units/blocks of transistor sink output type and
of transistor source output type are available.
1. Differences in circuit 12
• Sink output [-common]
Output Wiring
Output to make load current flow into the output (Y) terminal is
called sink output. Load
Y
13
COM
Various Uses
Wiring for
Fuse DC
power
supply
Troubleshooting
Maintenance,
Test Run,
+V
Fuse DC
power
supply 15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
207
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.2 External Wiring for Relay Output
Load
Y
DC power
supply
COM
Fuse
Output circuit Load
configuration Y
External
power supply
COM
Fuse
A common number applies to the of [COM ].
208
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.2 External Wiring for Relay Output
11
12.2.2 Product life of relay contacts
Counters
High-Speed
→ For product life of relay contacts, refer to Subsection 4.4.2.
Output Wiring
1. Output terminal
Load
One common terminal is used for 1, 4 or 8 relay output points. Y 0
The common terminal blocks can drive loads of different circuit Y 1
voltage systems (for example, 200V AC, 100V AC and 24V Fuse 24V DC
DC). COM1
Load 13
Y 4
Various Uses
Wiring for
Y 5
Fuse 100V AC
COM2
PLC
2. External power supply
Use an external power supply of 30V DC or less or 240V AC or less (250V AC or less when the unit does not
14
Troubleshooting
Maintenance,
Test Run,
comply with CE, UL or cUL standards) for loads.
3. Circuit insulation
The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and
contact. The common terminal blocks are separated from one another.
4. Display of operation
15
Extension Units
Powered
IInput/Output
When power is applied to the output relay coil, the LED is lit, and the output contact is turned on.
5. Response time
The response time of the output relay from when the power is applied to the coil until the output contact is
turned on and from when the coil is shut off until the output contact is turned off is approx. 10ms.
16
6. Output current
Blocks
Extension
Input/Output
At a circuit voltage of 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL
standards), a resistance load of 2A per point or an inductive load of 80VA or less (100V AC or 200V AC) can
be driven.
→ For the life of the contact for switching an inductive load, refer to Subsection 12.2.2.
When an inductive load is switched, connect a diode (for commutation) or a surge absorber in parallel with
this load.
17
Unit
Power Supply
Extension
DC circuit Diode (for commutation)
AC circuit Surge absorber
19
Display Module
20
Terminal Block
209
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.2 External Wiring for Relay Output
COM1
PLC
2) AC circuit
Connect the surge absorber (combined CR components
such as a surge killer and spark killer, etc.) parallel to the Inductive load
load. PLC output
Select the rated voltage of a surge absorber that is suitable contact Surge
for the load being used. Refer to the table below for other absorber
specifications.
Item Guide
Electrostatic capacity Approx. 0.1µF
Resistance value Approx. 100 to 200Ω
Reference
Manufacturer Model name Manufacturer Model name
Okaya Electric Industries Co., Ltd. CR-10201 Rubycon Corporation 250MCRA104100M B0325
3. Interlock
For loads such as forward/reverse contactors, etc., where a Inter- Limit of normal
hazardous condition could result if switched ON simultaneously, lock rotation
an external interlock should be provided for interlocking the PLC output
PLC’s internal programs as shown to the right. contact
PLC output Limit of reverse
contact rotation
4. In-phase
PLC output contacts (*) should be used in an "in-phase"
manner. *
Bad
*
*
Good
*
210
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.2 External Wiring for Relay Output
11
12.2.5 Example of external wiring
Counters
High-Speed
AC power supply Fuse* Main unit
100 to 240V COM1 relay output
Y0
Y1 12
Breaker
Y2
Output Wiring
Power ON Y3
Load (Vacant terminal)
PL Fuse*
MC
COM2
Y4
MC Emergen
cy stop
Y5 13
Y6
Various Uses
Wiring for
MC MC Y7
Load (Vacant terminal)
Troubleshooting
Maintenance,
Test Run,
DC power
supply
Y7
Load (Vacant terminal)
Fuse*
COM2
Y0 15
Extension Units
Powered
IInput/Output
Y7
Load (Vacant terminal)
Fuse*
COM1
Input/output powered
extension unit 16
Y0 relay output
Blocks
Extension
Input/Output
Y1
Y2
Y3
Load (Vacant terminal)
Fuse*
COM5 17
Y0
Unit
Power Supply
Extension
Y7
Load (Vacant terminal)
18
Power supply for load
Options
Units and
Other Extension
Cautions in wiring
Do not wire the vacant terminals externally. Doing so may damage the product.
211
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
Load
Y
Output circuit
Fuse
configuration COM
DC power
supply
212
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
11
12.3.2 Output specifications (main unit) transistor output (source type)
Counters
High-Speed
Transistor output (source) specifications
Item FX3U-16MT/ FX3U-32MT/ FX3U-48MT/ FX3U-64MT/ FX3U-80MT/ FX3U-128MT/
SS SS SS SS SS ESS
Number of output
8 points 16 points 24 points 32 points 40 points 64 points
12
points
Output Wiring
Fixed terminal
Connecting type block Removable terminal block (M3 screw)
(M3 screw)
Output type/form Transistor/source output
External power
5 to 30V DC
13
supply
Various Uses
Wiring for
0.5A / point
The total load current of resistance loads per common terminal should be the following
value.
Resistance → For details on the common terminal for each model,
Max. load
load
• 1 output point/common terminal: 0.5 A or less
refer to the terminal block layout.
14
Troubleshooting
Maintenance,
Test Run,
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 1.6 A or less
Inductive
12W/24V DC
load
Open circuit leakage
current
0.1 mA or less/30V DC 15
Extension Units
Powered
IInput/Output
ON voltage 1.5 V or less
Min. load −
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
OFF→ON
Response Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
time
ON→OFF
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
16
Blocks
Extension
Input/Output
Circuit insulation Photocoupler insulation
Display of output
LED on panel lights when photocoupler is driven.
operation
17
Unit
Power Supply
Extension
Load
Y
Output circuit Fuse
configuration +V
DC power
supply 18
Options
Units and
Other Extension
20
Terminal Block
213
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
1. Output terminals
One, 4 or 8 transistor output points are covered by one common terminal.
Sink output
Sink output type
Load current flows into the output (Y) terminals.
Connect each COM (number) terminal to the minus side of Load
Y 0
the load power supply. Y 1
The COM terminals are not connected internally. Fuse DC power
supply
COM1
Load
Y 4
Y 5
Fuse DC power
supply
COM2
PLC
Source output
Source output type
Load current flows out of the output (Y) terminals.
Connect each +V (number) terminal to the plus side of the Load
Y 0
load power supply. Y 1
The +V terminals are not connected internally. Fuse DC power
supply
+V0
Load
Y 4
Y 5
Fuse DC power
supply
+V1
PLC
3. Insulation of circuit
The internal circuit of the PLC and the output transistor are insulated with a photocoupler.
The common blocks are separated from one another.
4. Display of operation
When any photocoupler operates, the corresponding LED lights and corresponding output transistor turns
ON.
214
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
11
5. Response time
Counters
High-Speed
The time from when the PLC drives (or shuts down) the photocoupler until the transistor is turned on (or off) is
shown in the following table.
Classification Response time Load current
5 to 24V When using an instruction related to pulse train
Y000 to Y002 5 µs or less DC 10mA output or positioning, make sure to set the load 12
Main unit or more current to 10 to 100 mA (5 to 24V DC).
Output Wiring
Y003 or more 0.2 ms or less 24V DC 200 mA or more *1
Input/output powered extension unit
0.2ms or less 24V DC 200 mA *1
Output extension block
Various Uses
Wiring for
performance is required under light loads, provide a dummy resistance as shown to the right to
increase the load current.
- Sink output type - Source output type
PLC PLC
Fuse Load
Dummy
resistance Fuse Load
Dummy
resistance
14
Troubleshooting
Maintenance,
Test Run,
Y Y
COM1 +V0
15
Extension Units
Powered
IInput/Output
6. Output current
The maximum resistance loads for the input/output powered extension units and output extension blocks are
shown in the following table.
The ON voltage of the output transistor is approx. 1.5V.
When driving a semiconductor element, carefully check the input voltage characteristics of the applied 16
element.
Blocks
Extension
Input/Output
Model Output current Limitation
FX3U-16MT-ES(S)
FX3U-32MT-ES(S)
Main unit
FX3U-48MT-ES(S) 17
FX3U-64MT-ES(S)
Unit
Power Supply
Extension
FX3U-80MT-ES(S)
The total load current of resistance loads per
FX3U-128MT-ES(S)
common terminal should be the following value.
FX2N-32ET-ESS/UL 1 point/common: 0.5A or less
FX2N-48ET-ESS/UL 4 points/common: 0.8A or less
Input/output powered FX2N-48ET-DSS
0.5A/point 8 points/common: 1.6A or less 18
Options
Units and
Other Extension
Extension block
FX2N-8EYT
FX2N-8EYT-H 1A/point
FX2N-16EYT-C 0.3A/point
20
Terminal Block
215
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
Load
Y
Fuse
COM1
PLC
Load
Y
Fuse
+V0
PLC
2. Interlock
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON
simultaneously, an external interlock should be provided for interlocking the PLC’s internal programs, as
shown to the right.
• External Wiring of Sink Output Type
Interlock
Limit of normal
rotation
Interlock
Limit of normal
rotation
216
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
11
3. Contact protection circuit for inductive loads
Counters
High-Speed
When an inductive load is connected, connect a diode (for commutation) in parallel with the load as
necessary.
The diode (for commutation) must comply with the following specifications.
Item Guide
Reverse voltage 5 to 10 times of the load voltage 12
Output Wiring
Forward current Load current or more
Various Uses
Wiring for
COM1
PLC
Troubleshooting
Maintenance,
Test Run,
load
Y
Fuse
+V0
PLC
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
217
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
Breaker Y3
Load
Power ON Fuse*
COM2
PL Y4
MC
MC Y7
Emergency Load
stop
MC MC
Output extension block
Fuse* transistor output (sink)
COM1
Y0
DC power
supply Y7
Load
Fuse*
COM2
Y0
Y7
Load
Y7
Load
Fuse*
COM2
Power supply for load
Y0
connected to PLC output
WIRING PRECAUTIONS
218
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.3 External Wiring of Transistor Output (Sink/Source) Type
11
2. Transistor output (source)
Counters
High-Speed
AC power supply Main unit
Fuse*
100 to 240V +V0 transistor output
Y0 (source)
Breaker Y3 12
Load
Output Wiring
Power ON Fuse*
+V1
PL Y4
MC
Y7
MC
Emergency Load 13
stop
Various Uses
Wiring for
MC MC
Output extension block
Fuse* transistor output (source)
+V0
DC power
Y0
14
supply Y7
Troubleshooting
Maintenance,
Test Run,
Load
Fuse*
+V1
Y0
Y7 15
Load
Extension Units
Powered
IInput/Output
Input/output powered extension unit
transistor output (source)
Fuse*
+V0
Y0
16
Blocks
Extension
Input/Output
Y7
Load
Fuse*
+V1
Power supply for load
Y0
connected to PLC output 17
Y7
Unit
Power Supply
Extension
For details on emergency
stop operation, refer to Load
"DESIGN PRECAUTIONS"
at "Safety Precautions" field.
Output extension block
* The output circuit of this PLC does not
have a built-in fuse.
Fuse*
+V0
transistor output (source)
18
Provide a fuse suitable to each load to
Options
Units and
Other Extension
Y0
prevent blowout of the wires on the circuit
board caused by output element fracture Y7
due to load short-circuiting. Load
19
WIRING PRECAUTIONS
Display Module
20
Terminal Block
219
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.4 External Wiring for Triac (SSR) Output Type
1. Output terminals
On the triac output type units/blocks, one common terminal is FX2N-16EYS
used for 4 or 8 points. Load
Y0
Therefore, the common terminal blocks can drive loads of Y1
different circuit voltage systems (for example, 100V AC and Fuse 100VAC
U
2. Circuit insulation
The PLC internal circuit and the output element (triac) are insulated with a photo-thyristor.
The common terminal blocks are separate from one another.
3. Display of operation
When the photo-thyristor is driven, the LED is lit, and the output triac is turned on.
4. Response time
The time from when the photo-thyristor is driven or shut down until the output triac is turned on and until it is
turned off is 1ms or less and 10ms or less, respectively.
5. Output current
The max current per output point is 0.3A. However, to restrict temperature rise, the max current per one
output from four points should be 0.8A (average per point is 0.2A).
When a load with high rush current is turned on and off frequently, the root-mean-square current should be
0.2A or less.
<Example>
0.4A
4A
42 × 0.02 + 0.42 × 0.7
= 0.2A
0.02 + 0.7 + 10
0.02 0.7 10
sec sec sec
Since the triac output type devices leak current when the circuits are open, small-size relays and micro
current loads having low rated operating current may keep operating even when the triac output is turned off.
Therefore, use a load of 0.4VA or more at 100V AC or 1.6VA or more at 200V AC. If the load is less than this
value, connect a surge absorber as stated below in parallel with the load.
→ For the connection of the surge absorber, refer to Subsection 12.4.2 "External wiring precautions".
220
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.4 External Wiring for Triac (SSR) Output Type
11
12.4.2 External wiring precautions
Counters
High-Speed
1. Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could Load
cause burnout at the output element or the PCB. To prevent Y
this, a protection fuse should be inserted at the output. Fuse 12
Output Wiring
COM1
PLC
Various Uses
Wiring for
off C-R absorber. When connecting a very low current load of
"0.4VA/100V AC or less, or 1.6VA/200V AC or less", please
connect a surge absorber parallel to the load. Surge
Select the rated voltage of a surge absorber that is suitable for absorber
the load being used. Refer to the table below for other
specifications. 14
Troubleshooting
Maintenance,
Test Run,
Item Standard
Static electricity capacity Approx. 0.1µF
Resistance value Approx. 100 to 200Ω
Reference
15
Manufacturer Model name Manufacturer Model name
Extension Units
Powered
IInput/Output
Okaya Electric Industries Co., Ltd. CR-10201 Rubycon Corporation 250MCRA104100M B0325
3. Interlock
For loads such as forward/reverse contactors, etc., where a Inter- Limit of normal
hazardous condition could result if switched ON
simultaneously, an external interlock should be provided for
lock rotation Normal
rotation
16
Blocks
Extension
Input/Output
interlocking the PLC’s internal programs as shown to the Reverse
right. Limit of reverse rotation
PLC output rotation
element
4. In-phase 17
PLC output contacts (*) should be used in an "in-phase" *
Unit
Power Supply
Extension
manner.
Bad *
* 18
Good
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
221
FX3U Series Programmable Controllers 12 Output Wiring Procedures
User’s Manual - Hardware Edition 12.4 External Wiring for Triac (SSR) Output Type
Power ON Y3
For the relay output wiring of
(Vacant terminal)
the main unit, refer to
PL Subsection 12.2.5 "Relay COM2
MC
Output." Y4
MC
Emergency
Y7
stop
(Vacant terminal)
MC MC
Y7
Load
U
Y3
Load
U
WIRING PRECAUTIONS
222
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition
11
Counters
High-Speed
13. Examples of Wiring for Various Uses
12
DESIGN PRECAUTIONS
Output Wiring
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for 13
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
Various Uses
Wiring for
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 14
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Troubleshooting
Maintenance,
Test Run,
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
to ensure safe machinery operation in such a case. 15
Extension Units
Powered
IInput/Output
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the 16
control line at least 100mm (3.94") or more away from the main circuit or power line.
Blocks
Extension
Input/Output
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
17
WIRING PRECAUTIONS
Unit
Power Supply
Extension
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
18
Options
Units and
Other Extension
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
19
Display Module
20
Terminal Block
223
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.1 Notes about Examples of Wiring
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
• Observe the following items when wiring to the European terminal board.
Failure to do so may cause electric shock, a short-circuit, disconnection, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
• The input/output numbers are the actual numbers on the program. (They may differ from the numbers
shown on the product terminals.)
• Some examples show wiring to be used for transistor output. They are examples of wiring for the transistor
output types of input/output powered extension units/blocks.
• Product input/output specifications
Check the product input/output specifications when using any example of wiring.
- Products only for sink input and products both for sink input and for source input are available.
- Products for sink output and products for source output are available.
• The examples of programming (applied instructions) are given based on the allocation of the input/output
numbers for wiring.
→ For the applied instructions, refer to the Programming Manual.
224
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.2 Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]
11
13.2 Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]
Counters
High-Speed
13.2.1 When DSW instructions are used
Examples of wiring for capturing values from a 4-digit digital switch to the data register D100 are given below. 12
Output Wiring
1. Main unit
Example of program
M8000
DSW X010 Y010 D100 K1 13
Various Uses
Wiring for
Example of wiring
Troubleshooting
Maintenance,
Test Run,
Digital 100 101 102 103
switch of
BCD
0.1A 50V 15
diode is
Extension Units
Powered
IInput/Output
necessary.
1 2 4 8
S/S 0V 24V X010 X011 X012 X013
Blocks
Extension
Input/Output
COM3 Y010 Y011 Y012 Y015
100 101 102 103
Unit
Power Supply
Extension
When inputs are used for both sink and source and outputs are the transistor source type in the used main unit
0.1A 50V
diode is
necessary.
1 2 4 8
S/S 0V 24V X010 X011 X012 X013 19
Display Module
20
Terminal Block
225
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.2 Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]
Examples of wiring
0.1A 50V
diode is
necessary.
*1
1 2 4 8 *2
S/S 0V 24V X010 X011 X012 X013 COM 24+ X
Input/output powered extension unit
Main unit Output extension block
Transistor output (sink)
COM1 Y050 Y051 Y052 Y053
100 101 102 103
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET).
Output extension blocks do not have the terminals.
0.1A 50V
diode is
necessary.
*1
1 2 4 8 *2
S/S 0V 24V X010 X011 X012 X013 S/S 0V 24V X
Input/output powered extension unit
Main unit Output extension block
Transistor output (source)
+V0 Y050 Y051 Y052 Y053
100 101 102 103
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET-ESS/UL).
Output extension blocks do not have the terminals.
226
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.2 Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]
11
3. Input/output powered extension unit
Counters
High-Speed
Example of program
M8000
DSW X060 Y050 D100 K1
12
Output Wiring
Examples of wiring
Various Uses
Wiring for
Digital 100 101 102 103
switch of
BCD
0.1A 50V 14
diode is
Troubleshooting
Maintenance,
Test Run,
necessary.
1 2 4 8
COM X060 X061 X062 X063 X064 X065 X066 X067
First input group Input/output powered
extension unit 15
Transistor output (sink) FX2N-32ET
Extension Units
Powered
IInput/Output
FX2N-48ET
COM1 Y050 Y051 Y052 Y053
100 101 102 103
16
Blocks
Extension
Input/Output
In the case of source wiring
When an input /output powered extension unit/block with transistor output (source) is used with input/output
powered extension unit
17
100 101 102 103
Unit
Power Supply
Extension
Digital
switch of
BCD
0.1A 50V
diode is
necessary. 18
Options
Units and
Other Extension
1 2 4 8
S/S 0V 24V X060 X061 X062 X063 X064 X065 X066 X067
First input group
Input/output powered
extension unit
Transistor output (source) FX2N-32ET-ESS/UL
FX2N-48ET-ESS/UL 19
+V0 Y050 Y051 Y052 Y053
Display Module
20
Terminal Block
227
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.2 Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]
Example of program
M8000
BIN K2X010 D102
Examples of wiring
1 2 4 8 1 2 4 8
S/S 0V 24V X010 X011 X012 X013 X014 X015 X016 X017
1 2 4 8 1 2 4 8
COM X010 X011 X012 X013 X014 X015 X016 X017
100 101
1 2 4 8 1 2 4 8
S/S 0V 24V X010 X011 X012 X013 X014 X015 X016 X017
228
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.3 Ten Key Input [TKY Instructions (FNC70)]
11
13.3 Ten Key Input [TKY Instructions (FNC70)]
Counters
High-Speed
This section gives examples of wiring for capturing values from ten-key pad to D100 using TKY instructions.
Example of program
M8000 12
TKY X000 D100 M10
Output Wiring
Examples of wiring
In the case of sink wiring
13
Various Uses
Wiring for
When a sink and source input type unit is used
0 1 2 3 4 5 6 7 8 9
14
S/S 0V 24V X000 X001 X002 X003 X004 X005 X006 X007 X010 X011
Troubleshooting
Maintenance,
Test Run,
Main unit and input/output powered extension units
Extension Units
Powered
IInput/Output
COM X000 X001 X002 X003 X004 X005 X006 X007 X010 X011
Blocks
Extension
Input/Output
In the case of source wiring
Unit
Power Supply
Extension
0 1 2 3 4 5 6 7 8 9
S/S 0V 24V X000 X001 X002 X003 X004 X005 X006 X007 X010 X011 18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
229
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.4 Hexadecimal Input [HKY Instructions (FNC71)]
1. Main Unit
Example of program
M8000
HKY X010 Y010 D100 M0
Example of wiring
8 9 A B
4 5 6 7
0 1 2 3
1 2 4 8
S/S 0V 24V X010 X011 X012 X013
8 9 A B
4 5 6 7
0 1 2 3
1 2 4 8
S/S 0V 24V X010 X011 X012 X013
230
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.4 Hexadecimal Input [HKY Instructions (FNC71)]
11
2. Main unit + input/output powered extension unit/block
Counters
High-Speed
Example of program
M8000
HKY X010 Y050 D100 M0
12
Examples of wiring
Output Wiring
In the case of sink wiring
When the main unit and a transistor output (sink) type input/output powered extension unit/block are used
External wiring
C D E F 13
Various Uses
Wiring for
8 9 A B
4 5 6 7
0 1 2 3 14
Troubleshooting
Maintenance,
Test Run,
*1
1 2 4 8 *2
S/S 0V 24V X010 X011 X012 X013 COM 24+ X
Input/output powered extension unit/block
Main unit Output extension block
Transistor output (sink)
COM1 Y050 Y051 Y052 Y053
15
Extension Units
Powered
IInput/Output
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET).
Output extension blocks do not have the terminals.
16
In the case of source wiring
Blocks
Extension
Input/Output
When the main unit and a transistor output (source) type input/output powered extension unit/block are used
External wiring
C D E F
17
8 9 A B
Unit
Power Supply
Extension
4 5 6 7
0 1 2 3
*1
18
*2
Options
Units and
Other Extension
1 2 4 8
S/S 0V 24V X010 X011 X012 X013 S/S 0V 24V X
Input/output powered extension unit/block
Main unit Output extension block
Transistor output (source)
+V0 Y050 Y051 Y052 Y053
19
Display Module
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET-ESS/UL).
Output extension blocks do not have the terminals.
20
Terminal Block
231
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.4 Hexadecimal Input [HKY Instructions (FNC71)]
Examples of wiring
External wiring
C D E F
8 9 A B
4 5 6 7
0 1 2 3
External wiring
C D E F
8 9 A B
4 5 6 7
0 1 2 3
232
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.5 Input Matrix [MTR Instructions (FNC 52)]
11
13.5 Input Matrix [MTR Instructions (FNC 52)]
Counters
High-Speed
This section gives examples of wiring for capturing the ON/OFF status of 24 switches to M30 to M37, M40 to
M47 and M50 to M57 using MTR instructions.
12
1. Main Unit
Output Wiring
Example of program
M8000
MTR X020 Y010 M30 K3
13
Example of wiring
Various Uses
Wiring for
In the case of sink wiring
When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit
14
M50
M51
M52
M53
M54
M55
M56
M57
0.1A 50V
diode is
necessary.
Troubleshooting
Maintenance,
Test Run,
X021 X022 X023 X024 X025 X026 X027
M40
M41
M42
M43
M44
M45
M46
M47
X021 X022 X023 X024 X025 X026 X027
15
M30
M31
M32
M33
M34
M35
M36
M37
Extension Units
Powered
IInput/Output
S/S 0V 24V X020 X021 X022 X023 X024 X025 X026 X027
Main unit
16
Blocks
Extension
Input/Output
COM3 Y010 Y011 Y012
Unit
Power Supply
Extension
When inputs are used for both sink and source and outputs are the transistor source type in the used main unit
M50
M51
M52
M53
M54
M55
M56
M57
0.1A 50V
diode is
necessary.
X021 X022 X023 X024 X025 X026 X027
18
M40
M41
M42
M43
M44
M45
M46
M47
Options
Units and
Other Extension
M31
M32
M33
M34
M35
M36
M37
19
Display Module
S/S 0V 24V X020 X021 X022 X023 X024 X025 X026 X027
Main unit
233
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.5 Input Matrix [MTR Instructions (FNC 52)]
Examples of wiring
In the case of sink wiring
When the main unit and a transistor output (sink) type input/output powered extension unit/block are used
M50
M51
M52
M53
M54
M55
M56
M57
0.1A 50V
diode is
necessary. X021 X022 X023 X024 X025 X026 X027
M40
M41
M42
M43
M44
M45
M46
M47
X021 X022 X023 X024 X025 X026 X027
M30
M31
M32
M33
M34
M35
M36
M37
*1
*2
S/S 0V 24V X020 X021 X022 X023 X024 X025 X026 X027 COM 24+ X
Input/output powered
extension unit/block
Main unit
Transistor output (sink)
COM1 Y050 Y051 Y052
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET).
Output extension blocks do not have the terminals.
M51
M52
M53
M54
M55
M56
M57
0.1A 50V
diode is
necessary. X021 X022 X023 X024 X025 X026 X027
M40
M41
M42
M43
M44
M45
M46
M47
M31
M32
M33
M34
M35
M36
M37
*1
*2
S/S 0V 24V X020 X021 X022 X023 X024 X025 X026 X027 S/S 0V 24V X
Input/output powered
extension unit/block
Main unit
Transistor output (source)
+V0 Y050 Y051 Y052
*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line.
*2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N-32ET-ESS/UL).
Output extension blocks do not have the terminals.
234
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.5 Input Matrix [MTR Instructions (FNC 52)]
11
3. Input/output powered extension unit
Counters
High-Speed
Example of program
M8000
MTR X060 Y050 M30 K3
12
Examples of wiring
Output Wiring
In the case of sink wiring
When a sink input type unit is used
M50
13
M51
M52
M53
M54
M55
M56
M57
Various Uses
Wiring for
0.1A 50V
diode is X061 X062 X063 X064 X065 X066 X067
necessary.
M40
M41
M42
M43
M44
M45
M46
M47
X061 X062 X063 X064 X065 X066 X067 14
M30
M31
M32
M33
M34
M35
M36
M37
Troubleshooting
Maintenance,
Test Run,
COM X060 X061 X062 X063 X064 X065 X066 X067
Input/output powered extension unit FX2N-32ET
FX2N-48ET 15
Extension Units
Powered
IInput/Output
Transistor output (sink)
COM1 Y050 Y051 Y052 Y053 Y054 Y055 Y056 Y057
Blocks
Extension
Input/Output
When a source input type unit is used
M50
M51
M52
M53
M54
M55
M56
M57
0.1A 50V
diode is
necessary.
X061 X062 X063 X064 X065 X066 X067 17
M40
M41
M42
M43
M44
M45
M46
M47
Unit
Power Supply
Extension
X061 X062 X063 X064 X065 X066 X067
M30
M31
M32
M33
M34
M35
M36
M37
18
Options
Units and
Other Extension
S/S 0V 24V X060 X061 X062 X063 X064 X065 X066 X067
Input/output powered extension unit FX2N-32ET-ESS/UL
FX2N-48ET-ESS/UL
Transistor output (source)
+V0 Y050 Y051 Y052 Y053 Y054 Y055 Y056 Y057 19
Display Module
20
Terminal Block
235
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.6 Seven Segment with Latch [SEGL Instructions (FNC74)/BCD Instructions (FNC18)]
1. Main Unit
Example of program
M8000
SEGL D100 Y010 K1
Example of wiring
+
Transistor output (sink)
COM3 Y010 Y011 Y012 Y013 Y014 Y015 Y016 Y017
1 2 4 8 100 101 102 103 Y Signal Internal
circuit
COM1 -
3 2 1 0
10 10 10 10
1 *
2
4
8
In the case of source wiring 7-segment display to be used for source wiring
(in the case of transistor output)
+V0 +
Transistor output (source)
+V2 Y010 Y011 Y012 Y013 Y014 Y015 Y016 Y017
1 2 4 8 100 101 102 103 Y Signal Internal
circuit
-
103 102 101 100
1 *
2
4
8
236
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.6 Seven Segment with Latch [SEGL Instructions (FNC74)/BCD Instructions (FNC18)]
11
2. Input/output powered extension unit/block
Counters
High-Speed
Example of program
M8000
SEGL D100 Y020 K1
12
Output Wiring
Examples of wiring
Various Uses
Wiring for
+
Transistor output (sink)
COM1 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027
1 2 4 8 100 101 102 103 Y Signal Internal
circuit
COM1 - 14
3 2 1 0
10 10 10 10
Troubleshooting
Maintenance,
Test Run,
1 *
2
4
8
15
* Use a 7-segment display with a latch and a built-in BCD decoder.
Extension Units
Powered
IInput/Output
In the case of source wiring 7-segment display to be used for source wiring
(in the case of transistor output)
Input/output powered extension unit
FX2N-32ET-ESS/UL PLC 7-segment display 16
FX2N-48ET-ESS/UL
Blocks
Extension
Input/Output
+V0 +
Transistor output (source)
+V0 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027
1 2 4 8 10 0
10 1
10 2
103 Y Signal Internal
circuit
- 17
103 102 101 100
Unit
Power Supply
Extension
1 *
2
4
8
18
* Use a 7-segment display with a latch and a built-in BCD decoder.
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
237
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.6 Seven Segment with Latch [SEGL Instructions (FNC74)/BCD Instructions (FNC18)]
1. Main Unit
Example of program
M8000
BCD D100 K2Y010
Example of wiring
+
Transistor output (sink)
COM3 Y010 Y011 Y012 Y013 Y014 Y015 Y016 Y017
1 2 4 8 1 2 4 8 Y Signal
COM1 -
1248 1248
+V0 +
Transistor output (source)
+V2 Y010 Y011 Y012 Y013 Y014 Y015 Y016 Y017
1 2 4 8 1 2 4 8 Y Signal
-
1248 1248
238
FX3U Series Programmable Controllers 13 Examples of Wiring for Various Uses
User’s Manual - Hardware Edition 13.6 Seven Segment with Latch [SEGL Instructions (FNC74)/BCD Instructions (FNC18)]
11
2. Main unit and input/output powered extension units
Counters
High-Speed
Example of program
M8000
BCD D100 K2Y020
12
Output Wiring
Examples of wiring
Various Uses
Wiring for
+
Transistor output (sink)
COM1 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027
Y Signal
1 2 4 8 1 2 4 8
1248 1248
COM1 -
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
In the case of source wiring
7-segment display to be used for source
wiring (in the case of transistor output)
Blocks
Extension
Input/Output
+V0 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027
1 2 4 8 1 2 4 8 Y Signal
-
1248 1248
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
239
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition
DISPOSAL PRECAUTIONS
• Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal
of your device.
TRANSPORTATION PRECAUTIONS
• Before transporting the PLC, turn on the power to the PLC to check that the BATT LED is off.
If the PLC is transported with the BATT LED on or the battery exhausted, the battery-backed data may be
unstable during transportation.
• The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in the PLC
main unit Hardware Edition manual (Section 4.1).
Failure to do so may cause failures in the PLC.
After transportation, verify the operations of the PLC.
240
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.1 Preparation for Test Operation
11
14.1 Preparation for Test Operation
Counters
High-Speed
14.1.1 Preliminary inspection [power OFF]
Incorrect connection of the power supply terminal, contact of the DC input wire and power supply wire, or 12
short-circuiting of output wires may result in serious damage.
Output Wiring
Before applying power, check that the power supply and ground terminals are connected correctly and input/
output devices are wired properly.
Notes
The dielectric withstand voltage and insulation resistance test of the PLC should be measured in accordance with the
following procedures. 13
1) Remove all input/output wires and power supply wires from the PLC.
Various Uses
Wiring for
2) Connect a crossing wire to each of the PLC terminals (power supply terminal, input terminals and output
terminals) except the ground terminal.
For the dielectric withstand voltage test of each terminal, refer to the generic specifications for the product.
→ Refer to Section 4.1.
3) Measure the dielectric withstand voltage and insulation resistance between each terminal and the ground
terminal. 14
Dielectric withstand voltage: 1.5kV AC or 500V for 1min (The terminals vary in dielectric withstand voltage.)
Troubleshooting
Maintenance,
Test Run,
Insulation resistance: 500V DC / 5MΩ or more
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
FX3U-48M Programming
connector
FX
3U
-48
17
M IN 0
1
10 2
11 3
12 4
13 5
14 6
15 7
16 20
17 21
22
23
24
Positioning mark
25
OU 0 26
Unit
Power Supply
Extension
T 1 PO 27
PWO
10 2 EWRER
11 3
12 4 RUR
13 5 NUN
14 6
15 7 BA B
16 20 TTAT
17 21 E E T
22 RR R
23 ORROR
24
25
26
27
Communication cable
Positioning
mark
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
241
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.1 Preparation for Test Operation
14.1.3 Writing of program and program check [power ON and PLC stopped]
242
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.2 Running and Stopping Procedures [Power ON]
11
14.2 Running and Stopping Procedures [Power ON]
Counters
High-Speed
14.2.1 Methods of running and stopping
FX3U PLCs can be started or stopped by any of the following three methods. 12
Two of the methods can be combined.
Output Wiring
1. Operation with built-in RUN/STOP switch
Operate the RUN/STOP switch on the front panel of the main unit to start and stop the
PLC (refer to the right figure).
Turn the switch to RUN, and the PLC will start. Turn it to STOP, and the PLC will stop.
13
Various Uses
Wiring for
2. Running and stopping with general-purpose input (RUN terminal)
Operation with one switch (RUN)
14
Troubleshooting
Maintenance,
Test Run,
One of the input terminals X000 to X017 of the main unit (X000 to X007 on a 16-point type unit) can be used
as a RUN input terminal by a parameter setting (refer to the figure below).
When the specified input terminal is turned on, the PLC starts. When it is turned off, the PLC is started or
stopped depending on the state of the built-in RUN/STOP switch.
→ For details, refer to "Kinds of Parameters and Settings" in Programming Manual.
15
General-purpose General-purpose
Extension Units
Powered
IInput/Output
input terminal input terminal
RUN specified as RUN RUN specified as RUN
input by parameter input by parameter
S/S 0V 24V X000 X001 X002 S/S 0V 24V X000 X001 X002
Main unit (sink input) Main unit (source input)
16
Blocks
Extension
Input/Output
Operation with two switches (RUN and STOP)
The PLC can be started and stopped with individual RUN and STOP pushbutton switches.
For this operation, a sequence program using M8035 to M8037 is necessary.
→ For details, refer to "Operations of Special Devices" in Programming Manual.
General-purpose General-purpose 17
input terminal input terminal
Unit
Power Supply
Extension
RUN STOP specified as RUN RUN STOP specified as RUN
input by parameter input by parameter
S/S 0V 24V X000 X001 X002 S/S 0V 24V X000 X001 X002
Main unit (sink input) Main unit (source input)
18
3. Starting and stopping by remote control from programming software
Options
Units and
Other Extension
The programming software has a function to forcibly start and stop the PLC by remote control (remote RUN/
STOP function).
However, when power is reapplied, the remote RUN/STOP function is disabled. The RUN/STOP status is
then determined by the RUN/STOP switch or RUN terminal.
The remote operation for starting and stopping from the programming software is used in combination with
the built-in RUN/STOP switch.
19
Display Module
20
Terminal Block
243
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.2 Running and Stopping Procedures [Power ON]
1. When the built-in RUN/STOP switch and the general-purpose RUN terminal are used
(without remote running/stopping operation from the programming software)
The RUN/STOP status of the PLC is determined by the conditions shown in the following table.
Condition of built-in Condition of general-purpose input terminal
Status of PLC
RUN/STOP switch specified as RUN terminal by parameter
OFF RUN
RUN
ON RUN
OFF STOP
STOP
ON RUN
Use either built-in RUN/STOP switch or the general input specified as RUN terminal.
(When specifying the general-purpose terminal as the RUN terminal, always set the built-in RUN/STOP
switch to STOP.)
2. When the remote running/stopping operation from the programming software is performed
For this operation, keep both the built-in RUN/STOP switch and the general-purpose input RUN terminal in
the STOP position.
If the stop command is given from the programming software after the PLC is started by either the built-in
RUN/STOP switch or the general-purpose input RUN terminal, the PLC will be restored to the running status
by giving the RUN command from the programming software. This can also be accomplished by setting the
built-in RUN/STOP switch or the general-purpose input RUN terminal to STOP and then to RUN.
244
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.3 Operation and Test [Power ON and PLC Running]
11
14.3 Operation and Test [Power ON and PLC Running]
Counters
High-Speed
14.3.1 Self-diagnostic function
When the PLC's power is turned on, its self-diagnostic function starts automatically. If there are no problems 12
with the hardware, parameters or program, the PLC will start and the RUN command (refer to Section 14.2) is
Output Wiring
given (RUN LED is lit).
If any problems are found, the "ERROR" LED flashes or lights.
Various Uses
Wiring for
effective or ineffective depending on the PLC status as shown below.
: Effective : Conditionally effective − : Ineffective
In running In stopped
Item
status status
Forcible ON/OFF*1
Devices used in program *1 *1 14
Devices not in use
Troubleshooting
Maintenance,
Test Run,
Change of current values of timers, counters, Devices used in program *2*3 *3
data registers, extension registers, extension
Devices not in use *3 *3
file registers and file registers*4
When the program memory is the built-in
RAM 15
Extension Units
Powered
IInput/Output
When the program memory is in the memory
Change of settings of timers and counters*5 − −
cassette and the PROTECT switch is on
When the program memory is in the memory
−
cassette and the PROTECT switch is off
Blocks
Extension
Input/Output
(S), timers (T) and counters (C). On the display module, the function cannot be operated for the input relays
(X).
- The forcible ON/OFF function can turn on or off the devices only for one scan.
While the PLC is running, the function is substantially effective in clearing the current values of the timers (T),
counters (C), data registers (D), index registers (Z and V) and extension registers (R) and in controlling the
SET/RST circuit and self-retaining circuit. (The operation to forcibly turn on timers is effective only when the
timers are driven by the program.)
17
Unit
Power Supply
Extension
- The results of forcible ON/OFF operation performed while the PLC in the stopped state or performed for
devices not used in the program are retained.
However, the results of the operation performed for the input relays (X) are not retained because the relays
refresh input even while the PLC is in the stopped state. (They are updated according to the input terminal
conditions.)
*2. Since the current values may be changed according to MOV instruction in the program and the operation results,
the most recently obtained values are retained.
18
Options
Units and
Other Extension
*3. Only display modules can change the current value by the extension file register test function.
*4. The current values of the file registers stored in the program memory cannot be monitored or tested on the display
module.
*5. Change of timer and counter settings
The settings of the timers (T) and counters (C) can be changed only when the timers are driven by the program.
19
Display Module
20
Terminal Block
245
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.3 Operation and Test [Power ON and PLC Running]
*1. Since the writing function is used during running, the programming tool must be applicable to the writing function
white running, such as GX Developer.
246
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.4 Maintenance and Periodic Inspection
11
14.4 Maintenance and Periodic Inspection
Counters
High-Speed
This PLC does not incorporate consumable parts that are factors in the reduction of service life.
However, the batteries and output relays (points of contact) have a limited life expectancy.
Output Wiring
The model name of the main unit can be checked on the nameplate on the right side. After extension devices
are connected, the nameplate cannot be seen. Check the model name in the following places.
When the terminal block cover (output side) When the top cover is removed
is opened
13
Various Uses
Wiring for
Model name
Model name
(abbreviation) 14
Troubleshooting
Maintenance,
Test Run,
Output form R: Relay output
T: Transistor output
15
Extension Units
Powered
IInput/Output
14.4.2 Periodic inspection - battery life, etc.
1. Battery
Part Life 16
Standard life: 5 years (at ambient temperature of 25°C (77°F))
Blocks
Extension
Input/Output
Model FX3U-32BL battery
[Guarantee for 1 year]
Unit
Power Supply
Extension
When inspecting the battery, check the following points.
• Check that the temperature in the panel is not abnormally increased by other heat generating bodies or
direct sunlight.
• Check that dust or conductive dust has not entered the panel. 18
• Check for loosening of wiring and other abnormalities.
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
247
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.4 Maintenance and Periodic Inspection
1. Inductive load
Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause
arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller,
the arc energy gets larger.
1) Main unit, input/output powered extension units and input/output extension blocks
The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000
operations at 20 VA.
The following table shows the approximate life of a relay based on the results of an operation life test.
The product life of relay contacts becomes considerably shorter than the above conditions when the rush
overcurrent is shut down.
Please refer to the following measures regarding the inductive load.
→ For precautions on the main unit, input/output powered extension unit and input/output
extension block, refer to Subsection 12.2.4 2.
→ For precautions on inductive loads for the terminal block, refer to
Subsection 20.7.4 2.
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation.
Make sure that the rush current does not exceed the current corresponding to the maximum specified
resistance load.
2. Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
248
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.4 Maintenance and Periodic Inspection
11
3. Capacitive load
Counters
High-Speed
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load. Capacitive
loads such as capacitors may be present in electronic circuit loads including inverters.
*About the maximum load specifications of the resistance load, refer to the specification for each model.
→ For specifications on the main unit, refer to Subsection 12.2.1.
→ For specifications on the input/output powered extension units, refer to Chapter 15.
12
Output Wiring
→ For specifications on the input/output extension blocks, refer to Chapter 16.
→ For specifications on the terminal block, refer to Subsection 20.7.1.
Various Uses
Wiring for
M8005 and M8006 (latch) are turned on.
The memory can be retained for about one month after the lamps turn on. However, the operators may not
immediately find the lamps to be on. Prepare a new battery promptly, and replace the battery with the new
one.
→ For details on the specifications and functions of the battery, refer to Chapter 22 "FX3U-32BL
(Battery)" 14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
249
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.5 Troubleshooting with LEDs
State of
State of PLC Remedies
LED
Power of the specified voltage is
On being correctly supplied to the power The power supply is normal.
supply terminal.
One of the following problems may
have occurred. • Check the supply voltage.
• Power of the specified voltage and • After disconnecting the cables other than the power cable, re-
Flashing current is not being supplied to the apply power to the PLC, and check for changes in the state. If
power supply terminal. no improvement is obtained, consult your local Mitsubishi
• External wiring is incorrect. Electric distributer.
• Internal error of PLC
One of the following problems may • If the power is not off, check the power supply and the power
have occurred. supply route.
• The power supply is off. If power is being supplied correctly, consult your local
• External wiring is incorrect. Mitsubishi Electric distributer.
Off
• Power of the specified voltage is • After disconnecting the cables other than the power cable, re-
not being supplied to the power apply power to the PLC, and check for changes in the state. If
supply terminal. no improvement is obtained, consult your local Mitsubishi
• The power cable is broken. Electric distributer.
State of
State of PLC Remedies
LED
On The battery voltage is low. Immediately replace the battery. (Refer to Section 22.5.)
The battery voltage is higher than the
Off Normal
value set with D8006.
250
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.5 Troubleshooting with LEDs
11
14.5.3 ERROR LED [on/flashing/off]
Counters
High-Speed
State of
State of PLC Remedies
LED
1) Stop the PLC, and re-apply power.
If ERROR LED goes off, a watchdog timer error may have 12
occurred. Take any of the following measures.
Output Wiring
- Review the program.
The maximum value (D8012) of the scan time should not
exceed the setting (D8000) of the watchdog timer.
- Check that the input used for input interruption or pulse
catch is not being abnormally turned on and off in one scan.
- Check that the frequency of the pulse (duty of 50%) input to 13
the high-speed counter does not exceed the specified
Various Uses
Wiring for
range.
- Add the WDT instructions.
Add some WDT instructions to the program, and reset the
A watchdog timer error may have watchdog timer several times in one scan.
On occurred, or the hardware of the PLC - Change the setting of the watchdog timer.
may be damaged. Change the watchdog timer setting (D8000) in the program 14
so that the setting is larger than the maximum value of the
Troubleshooting
Maintenance,
Test Run,
scan time (D8012).
2) Remove the PLC and supply power to it from another power
supply on a desk.
If the ERROR LED goes off, noise may have affected the
PLC. Take the following measures.
- Check the ground wiring, and reexamine the wiring route 15
and installation location.
Extension Units
Powered
IInput/Output
- Fit a noise filter onto the power supply line.
3) If the ERROR LED does not go off even after the measures
stated in (1) and (2) are taken, consult your local Mitsubishi
Electric distributer.
One of the following errors has
occurred in the PLC. Perform PLC diagnosis and program check with the 16
programming tool.
Blocks
Extension
Input/Output
Flashing • Parameter error
For the remedies, refer to Section 14.6 "Judgment by Error
• Syntax error
Codes and Representation of Error Codes".
• Ladder error
If the operations of the PLC are abnormal, perform PLC
No errors that stop the PLC have
Off diagnosis and program check with the programming tool.
occurred.
An I/O error, Comms.error or Runtime error may have occurred. 17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
251
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
1) Move the cursor to "ErrorCheck" pressing the + or - button on the menu screen (shown right).
For the menu configuration, refer to Section 19.6.
The buttons on the menu screen work as stated below. Mo n i t o r / T e s t
Operation E r r o r Ch e c k
Operation
button L A NGU A G E
ESC The screen returns to the top screen (time display). Co n t r a s t
The cursor moves upward. When the button is held
for 1 second or more, the cursor moves quickly. C l o c kMe n u
-
When the cursor is in the uppermost position, the En t r yCo d e
button is ineffective. C l e a r A l l De v
The cursor moves downward. When the button is
PLC S t a t u s
held for 1 second or more, the cursor moves
+ quickly. S c a n T i me
When the cursor is in the lowermost position, the Ca s s e t t e
button is ineffective.
OK The flashing item at the cursor is selected.
4) Pressing the ESC button cancels the operation and returns the screen to the Menu screen.
252
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
11
14.6.2 Operation and check by GX developer
Counters
High-Speed
1 Connect the personal computer and the PLC.
Output Wiring
Click [Diagnostics] → [PLC diagnostics] on the tool menu, and the diagnosis of PLC will start.
13
Various Uses
Wiring for
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
3 Check the results of diagnosis.
Display the following window to check the errors.
Blocks
Extension
Input/Output
Display of
conditions of
LEDs on FX
PLC The help function of 17
GX Developer opens,
Unit
Power Supply
Extension
and you can check
the details of the
The PLC error error code.
is displayed.
18
Options
Units and
Other Extension
19
Display Module
253
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
254
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
11
14.6.4 Error Code List and Action
Counters
High-Speed
When a program error occurs in the PLC, the error code is stored in special data registers D8060 - D8067 and
D8438. The following actions should be followed for diagnostic errors.
Error codes in shaded columns are added in FX3U PLCs.
Error PLC operation at
12
Contents of error Action
Output Wiring
code error occurrence
I/O configuration error [M8060(D8060)]
The head number of unconnected I/O device
Example: When X020 is unconnected
1 0 2 0 BCD conversion value 13
Unconnected I/O relay numbers are programmed.
Ex-
Various Uses
Wiring for
Continues Device number: 10 to 337 The PLC continues its operation. Modify the
ample:
operation 1: Input (X), 0: Output (Y) program, check wiring connection, or add the
1020
• 1st to 3rd digits: Device number appropriate unit/block.
• 4th digit: I/O type
(1 = input (X), 0 = output (Y))
Example: When 1020 is stored in D8060 14
Inputs X020 and later are unconnected.
Troubleshooting
Maintenance,
Test Run,
Serial communication error 2 [M8438 (D8438)]
0000 ⎯ No error
3801 Parity, overrun or framing error
3802 Communication character error • Inverter communication, computer link and
3803 Communication data sum check error programming:
Ensure the communication parameters are
15
3804 Communication data format error
Extension Units
Powered
IInput/Output
correctly set according to their applications.
3805 Command error • N:N network, parallel link, etc.:
3806 Continues Communication time-out detected Check programs according to the applications.
3807 operation Modem initialization error • Remote maintenance:
3808 N:N network parameter error Ensure modem power is ON and check the
settings of the AT commands.
3812 Parallel link character error
• Wiring: 16
3813 Parallel link sum error Check the communication cables for correct
Blocks
Extension
Input/Output
3814 Parallel link format error wiring.
3820 Inverter communication error
PLC hardware error [M8061(D8061)]
0000 ⎯ No error
6101 RAM error 17
6102 Operation circuit error
Unit
Power Supply
Extension
6103 I/O bus error (M8069 = ON) Check for the correct connection of extension
6104 Powered extension unit 24 V failure (M8069 = ON) cables.
Check user program.
6105 Watchdog timer error
The scan time exceeds the value stored in D8000.
Stops
operation
When turning the power ON to the main unit, a
24V power failure occurs in a powered extension
18
Options
Units and
Other Extension
6106 I/O table creation error (CPU error) unit. (The error occurs if the 24V power is not
supplied for 10 seconds or more after the main
power is turned ON.)
Check the number of the connected special function
6107 System configuration error units/blocks. For a few special function units/blocks,
the connectable number is limited. 19
Display Module
20
Terminal Block
255
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
256
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
11
Error codes in shaded columns are added in FX3U PLCs.
Counters
High-Speed
Error PLC operation at
Contents of error Action
code error occurrence
Circuit error [M8066(D8066)]
0000 ⎯ No error
6610 LD, LDI is continuously used 9 times or more. 12
More ANB/ORB instructions than LD/LDI
Output Wiring
6611
instructions
Less ANB/ORB instructions than LD/LDI
6612
instructions
6613 MPS is continuously used 12 times or more.
6614
6615
No MPS instruction
No MPP instruction
13
Various Uses
Wiring for
No coil between MPS, MRD and MPP, or incorrect
6616
combination
Instruction below is not connected to bus line:
6617 STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET,
IRET, FEND or END
STL, MC or MCR can be used only in main 14
6618 program, but it is used elsewhere (e.g. in interrupt
Troubleshooting
Maintenance,
Test Run,
routine or subroutine).
Invalid instruction is used in FOR-NEXT loop: This error occurs when a combination of
6619
STL, RET, MC, MCR, I (interrupt pointer) or IRET. instructions is incorrect in the entire circuit block or
6620 Stops FOR-NEXT instruction nesting level exceeded when the relationship between a pair of instructions
operation is incorrect.
6621
Numbers of FOR and NEXT instructions do not
match.
Modify the instructions in the program mode so that 15
their mutual relationship becomes correct.
Extension Units
Powered
IInput/Output
6622 No NEXT instruction
6623 No MC instruction
6624 No MCR instruction
STL instruction is continuously used 9 times or
6625
more.
Invalid instruction is programmed within STL-RET 16
6626 loop:
Blocks
Extension
Input/Output
MC, MCR, I (interrupt pointer), SRET or IRET.
6627 No STL instruction
Invalid instruction is used in main program:
6628
I (interrupt pointer), SRET or IRET
6629 No P or I (interrupt pointer) 17
No SRET or IRET instruction
6630
Unit
Power Supply
Extension
STL-RET or MC-MCR instructions in subroutine
6631 SRET programmed in invalid location
6632 FEND programmed in invalid location
Operation error [M8067(D8067)]
0000 No error
• No jump destination (pointer) for CJ or CALL
18
Options
Units and
Other Extension
instruction
• Label is undefined or out of P0 to P4095 due to
6701 indexing
• Label P63 is executed in CALL instruction; This error occurs in the execution of operation.
cannot be used in CALL instruction as P63 is for Review the program, or check the contents of the
6702
jumping to END instruction.
CALL instruction nesting level is 6 or more
operands used in the applied instructions.
Even if the syntax or circuit design is correct, an
19
Display Module
6703 Continues Interrupt nesting level is 3 or more operation error may still occur.
operation For example:
FOR-NEXT instruction nesting level is 6 or
6704 "T200Z" itself is not an error. But if Z had a value of
more.
400, the timer T600 would attempt to be accessed.
Operand of applied instruction is inapplicable This would cause an operation error since there is
6705
device.
6706
Device number range or data value for operand of
no T600 device available.
20
applied instruction exceeds limit.
Terminal Block
257
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
258
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
11
Error codes in shaded columns are added in FX3U PLCs.
Counters
High-Speed
Error PLC operation at
Contents of error Action
code error occurrence
Operation error [M8067(D8067)]
<Auto tuning is finished. → PID operation is
started.>
• When auto tuning was started, the difference
12
Output Wiring
between the measured value and the target
<Step response method> value was 150 or less. (SV−PV≤150)
6750
Improper auto tuning result • When auto tuning was started, the difference
between the measured value and the target
value was 1/3 or more.
• Check the measured value and target value, and
then execute auto tuning again. 13
<Auto tuning is forcibly finished. → PID operation is
Various Uses
Wiring for
not started.>
The operation direction estimated from the
measured value at the start of auto tuning was
<Step response method>
6751 different from the actual operation direction of the
Auto tuning operation direction mismatch
output during auto tuning.
Correct the relationship among the target value, 14
output value for auto tuning, and the measured
Troubleshooting
Maintenance,
Test Run,
value, and then execute auto tuning again.
<Auto tuning is finished. → PID operation is not
started.>
Because the set value was fluctuated during auto
tuning, auto tuning was not executed correctly.
6752
<Step response method>
Improper auto tuning operation
Set the sampling time to a value larger than the 15
output change cycle, or set a larger value for the
Extension Units
Powered
IInput/Output
input filter constant.
After changing the setting, execute auto tuning
again.
<Limit cycle method>
6753 Abnormal output set value for auto tuning <Auto tuning is forcibly finished. → PID operation is
Continues [ULV (upper limit) ≤ LLV (lower limit)] not started.> 16
operation <Limit cycle method> Check whether the target setting contents are
Blocks
Extension
Input/Output
6754 Abnormal PV threshold (hysteresis) set value for correct.
auto tuning (SHPV < 0)
<Limit cycle method> <Auto tuning is forcibly finished. → PID operation is
Abnormal auto tuning transfer status not started.>
6755
(Data of device controlling transfer status is
abnormally overwritten.)
Ensure that devices occupied by PID instruction are
not overwritten in the program. 17
Unit
Power Supply
Extension
<Auto tuning is forcibly finished. → PID operation is
not started.>
The auto tuning time is longer than necessary.
<Limit cycle method> Increase the difference (ULV - LLV) between the
6756 Abnormal result due to excessive auto tuning upper limit and lower limit of the output value for
measurement time (τon > τ, τon < 0, τ < 0) auto tuning, set a smaller value to the input filter
constant (α), or set a smaller value to the PV 18
threshold (SHPV) for auto tuning, and then check
Options
Units and
Other Extension
(TD = outside range from 0 to 32767) threshold (SHPV) for auto tuning, and then check
the result for improvement.
259
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.6 Judgment by Error Codes and Representation of Error Codes
260
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.7 Troubleshooting
11
14.7 Troubleshooting
Counters
High-Speed
→ For the procedures on running and stopping the PLC, refer to Section 14.2.
→ For the procedures on operating the display module, refer to Chapter 19.
→ For the procedures on operating peripheral devices, refer to the manuals for the peripheral devices.
→ For the phone numbers and addresses of Mitsubishi Electric System & Service Co., Ltd., 12
refer to the service network at the end of this manual.
Output Wiring
14.7.1 Output does not operate (main unit and input/output extension blocks)
Various Uses
Wiring for
module to check its operation.
Check for troubles with external wiring.
• When the output operates
The output may be turned off unintentionally in the program. Reexamine the program.
(Duplicate coil or RST instructions)
• When the output does not operate
14
Troubleshooting
Maintenance,
Test Run,
Check the configuration of the connected devices and the connection of the extension cables.
If the configuration of the external wiring and connected devices and the connection of the extension
cables are acceptable, the output circuit may be damaged.
Consult your local Mitsubishi Electric distributer.
Extension Units
Powered
IInput/Output
Check for trouble with external wiring.
→ For the procedures on running and stopping the PLC, refer to Section 14.2.
• When the output turns off
The output may be turned on unintentionally in the program.
Check that there are no duplicate coils in the program. 16
• When the output does not turn off
Blocks
Extension
Input/Output
The output circuit may be damaged. Consult your local Mitsubishi Electric distributer.
14.7.2 24V DC input does not operate (main unit and input/output extension blocks)
Unit
Power Supply
Extension
Disconnect the external wiring and connect the S/S terminal and the 0V terminal or the 24V terminal.
Short-circuit the 0V terminal or 24V terminal not connected to the S/S terminal and the input terminal, then
check the input display LED or a peripheral device to confirm that the input turns on.
Measures
Measure the voltage between the 0V terminal or 24V terminal not connected to the S/S
When input does not terminal and the input terminal with a tester to confirm that the voltage is 24V DC.
turn on • Check the configuration of the external wiring and connected devices and the connection of
the extension cables.
20
Terminal Block
261
FX3U Series Programmable Controllers 14 Test Operation, Adjustment, Maintenance and Troubleshooting
User’s Manual - Hardware Edition 14.7 Troubleshooting
262
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition
11
Counters
High-Speed
15. FX2N-32/48E*-* (Input/Output Powered Extension Units)
12
DESIGN PRECAUTIONS
Output Wiring
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
13
Various Uses
Wiring for
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 14
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Troubleshooting
Maintenance,
Test Run,
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
to ensure safe machinery operation in such a case. 15
Extension Units
Powered
IInput/Output
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
16
Blocks
Extension
Input/Output
Noise may cause malfunctions.
WIRING PRECAUTIONS
17
• Connect the AC power supply to the dedicated terminals specified in this manual.
Unit
Power Supply
Extension
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
263
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
264
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.1 Outline
11
15.1 Outline
Counters
High-Speed
An input/output powered extension unit is used to expand inputs/outputs.
Power can be supplied to subsequent extension blocks from an input/output powered extension unit with a
built-in 24V DC power supply.
An input/output powered extension unit is required when the capacity of the main unit's built-in power supply
is insufficient for the current consumption demands of the extension blocks. 12
Output Wiring
15.1.1 Product configuration
There are various types of input/output powered extension units. They differ in supply voltage, number of
input/output points, input form, output form and connection type.
Input/output powered extension units 13
Various Uses
Wiring for
Power supply Number of points Input form Output form Connection type
Troubleshooting
Maintenance,
Test Run,
(source)
100V AC
Transistor (sink)
Extension Units
Powered
IInput/Output
Each model of input/output powered extension unit has a sink and source type and a sink type. If you intend
to add input/output powered extension units, we recommend you to add the same types of units as the main
unit or the sink and source type.
→ For details on sink and source, refer to Subsection 10.1.1.
Sink :Sink [-common], Source :Source [+common]
Input Output 16
Connection
Model
Blocks
Extension
Input/Output
Number Common wiring Number Common wiring type
Type Type
of points system of points system
AC power supply common to 24V DC sink and source input
FX2N-32ER-ES/UL 16 Sink Source 16 −
Relay
FX2N-48ER-ES/UL
24V DC
24 Sink Source 24 −
Terminal
block
17
FX2N-32ET-ESS/UL 16 Sink Source 16 Source
Unit
Power Supply
Extension
Transistor
FX2N-48ET-ESS/UL 24 Sink Source 24 Source
AC power supply only for 24V DC sink input
FX2N-32ER 16 Sink 16 −
FX2N-48ER 24 Sink
Relay
24 − 18
Options
Units and
Other Extension
Terminal
FX2N-32ES 24V DC 16 Sink Triac(SSR) 16 −
block
FX2N-32ET 16 Sink 16 Sink
Transistor
FX2N-48ET 24 Sink 24 Sink
AC power supply only for 100V AC
Terminal
19
FX2N-48ER-UA1/UL 100V AC 24 − Relay 24 −
Display Module
block
DC power supply common to 24V DC sink and source input
FX2N-48ER-DS Sink Source Relay −
Terminal
24V DC 24 24
block
FX2N-48ET-DSS Sink Source Transistor Source
DC power supply only for 24V DC sink input
20
Terminal Block
265
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.2 Power Supply Specifications (Power Supply Input/24V DC Service Power Supply)
FX2N-48ER-DS FX2N-48ER-D
Item FX2N-48ER-UA1/UL
FX2N-48ET-DSS FX2N-48ET-D
Classification FX2N powered extension unit
Supply voltage 100 to 240V AC 24V DC
Allowable supply voltage range 85 to 264V AC +20%, -30%
Power fuse 250V 5 A 5φ × 20mm (0.79")
100V AC Up to 40 A, 5 ms or less −
Rush current
200V AC Up to 60 A, 5 ms or less −
Power consumption 35 W (45 VA)
24V DC service power supply None
Connection type Removable terminal block (M3 screw)
FX2N-48ER-ES/UL FX2N-48ER
FX2N-32ER
FX2N-32ER-ES/UL FX2N-48ET-ESS/UL FX2N-48ET FX2N-48ER-
Item FX2N-32ES
FX2N-32ET-ESS/UL FX2N-48ER-DS FX2N-48ER-D UA1/UL
FX2N-32ET
FX2N-48ET-DSS FX2N-48ET-D
Weight 0.65 kg (1.43 lbs) 0.85 kg (1.87 lbs) 1.00 kg (2.2 lbs)
• Terminal protective cover (2 pcs.)
(Fitted to FX2N-32ER-ES/UL, FX2N-32ET-ESS/UL, FX2N-48ER-ES/UL, FX2N-48ET-ESS/UL and
FX2N-48ER-UA1/UL, FX2N-48ER-DS, FX2N-48ET-DSS)
Accessories
• Extension cable (55 mm (2.16"))
Optional extension cables (FX0N-30EC and FX0N-65EC) are available.
• Input/output number label
• The terminal block uses M3 terminal screws.
Others
• Installation of the DIN46277 (35 mm (1.37") wide) rail or screws.
266
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.2 Power Supply Specifications (Power Supply Input/24V DC Service Power Supply)
11
15.2.2 Part names
Counters
High-Speed
1. Front
[4] Input display LEDs
[1] Top cover [5] Terminal block covers 12
Output Wiring
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
IN
0 1
0 1
2 3 4 5 6 7
2 3 4 5 6 7
0 1 2 3 4 5 6 7
[6] Extension device connecting
POWER
connector cover
Y0
COM1 Y1
Y2
Y3
Y4
FX2N-48ER
COM2 Y5
Y6
Y7
Y0
COM3 Y1
Y2
Y3
OUT
0 1
0 1
2 3 4 5 6 7
2 3 4 5 6 7
Y4
COM4 Y5
Y6
Y7
Y0
Y1
Y2
Y3
Y4
0 1
Y5
Y6
Y7
2 3 4 5 6 7
COM5
[7] POWER LED
13
Various Uses
Wiring for
[2] DIN rail mounting hooks [8] Output display LEDs
[3] Model name
14
[1] Top cover When adding this to the main unit, connect the supplied extension cable or
Troubleshooting
Maintenance,
Test Run,
the optional extension cable to the connector under this top cover.
[2] DIN rail mounting hooks The input/output powered extension unit can be installed on DIN rail
(2 places) (35 mm (1.38") wide).
[3] Model name (abbreviation) The model name of the input/output powered extension unit is indicated.
[4] Input display LEDs (red) When an input terminal (X0, X1, etc.) is turned on, the corresponding LED 15
lamps are also turned on.
Extension Units
Powered
IInput/Output
The input numbers change depending on input/output allocation.
The input/output powered extension unit (48 points type) assigns input
numbers in ascending order from A→B→C below.
A C
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
16
Blocks
Extension
Input/Output
B
0 1 2 3 4 5 6 7
[5] Terminal block covers The covers can be opened about 90° for wiring.
Keep the covers closed while the PLC is running (the unit power is on).
17
Unit
Power Supply
Extension
[6] Extension device connecting Connect the extension cable of input/output powered extension unit/block
connector cover or special function unit/block to the extension device connecting connector
under this cover.
FX3U Series extension devices, FX2N Series extension devices and FX0N
Series special function devices are compatible and can be connected.
→ For details on extension devices, refer to Chapter 15, 18
Chapter 16 and Section 18.1.
Options
Units and
Other Extension
[7] POWER LED (green) The LED lamp is on (green) while the power supply terminal is on.
[8] Output display LEDs (red) When an output terminal (Y0, Y1, etc.) is turned on, the corresponding
LED lamps are also turned on. The output numbers change depending on
input/output allocation.
The input/output powered extension unit (48 points type) assigns output
numbers in ascending order from A→B→C below.
19
Display Module
A C
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
B
0 1 2 3 4 5 6 7
20
Terminal Block
267
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.2 Power Supply Specifications (Power Supply Input/24V DC Service Power Supply)
L N
S/S 0V
24V
X0
X1
X2
X3
X4
X5
X6
X7
X0
X1
X2
X3
X4
X5
X6
X7
X0
X1
X2
X3
X4
X5
X6
X7 [12] Terminal names
IN
0 1
0 1
2 3 4 5 6 7
2 3 4 5 6 7
0 1 2 3 4 5 6 7
[13] Terminal block covers
POWER
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ER OUT
0 1 2 3 4 5 6 7
Y0
COM1 Y1
Y2
Y3
Y4
COM2 Y5
Y6
Y7
Y0
COM3 Y1
Y2
Y3
Y4
COM4 Y5
Y6
Y7
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
COM5
[12] Terminal names
[9] Power supply terminal Connect the power supply to the input/output powered extension unit at
this terminal.
[10] Input (X) terminals Wire switches and sensors to these terminals.
[11] Terminal block mounting screws If the input/output powered extension unit must be replaced, loosen these
screws to remove the upper part of the terminal block.
→ For anchoring the terminal block, refer to Subsection 9.1.2.
[12] Terminal names The signal names for the power supply, input terminals and output
terminals are shown.
[13] Terminal block covers Protects the upper and lower stages of the terminal block.
[14] Output (Y) terminals Wire the intended loads (contactors, solenoid valves, etc.) to these
terminals.
[15] Protective terminal covers A protective terminal cover (refer to the following drawing) is fitted to the
lower stage of each terminal block to prevent fingers from touching
terminals, thereby improving the safety.
2. Side
[1] Nameplate
[1] Nameplate The product model name, control number and power supply
specifications are shown.
[2] DIN rail mounting groove The unit can be installed on DIN46277 rail (35 mm (1.38") wide).
268
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
11
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
Counters
High-Speed
15.3.1 Product specifications
The generic specifications are the same as those for the main unit.
→ For the generic specifications, refer to Section 4.1. 12
For external wiring, refer to the following chapters.
Output Wiring
→ Refer to Chapter 9 for power supply wiring.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
1. Power supply specifications
→ For the power supply specifications, refer to Section 15.2. 13
Various Uses
Wiring for
2. Input specifications (for sink input [-common] and source input [+common])
Item FX2N-32ER-ES/UL FX2N-48ER-ES/UL, FX2N-48ER-DS
Number of input points 16 points 24 points
Connection type Removable terminal block (M3 screw)
Input form sink/source 14
Input signal voltage 24V DC ± 10%*1
Troubleshooting
Maintenance,
Test Run,
Input signal current 5 mA/24V DC
Input impedance 4.3 kΩ
Input ON current 3.5 mA or more/24V DC
Input sensitivity
Input OFF
current
current
1.5 mA or less
15
Input response time About 10 ms
Extension Units
Powered
IInput/Output
No-voltage contact input
Input signal form Sink: NPN open collector transistor
Source: PNP open collector transistor
Input circuit insulation Insulation with photocoupler
Indication of input operation
• AC power supply type
LED on panel is lit when there is input.
16
Blocks
Extension
Input/Output
Sink input wiring Source input wiring
Fuse Fuse
L L
N N
S/S
100 to 240V AC
S/S
100 to 240V AC
17
0V 0V
Unit
Power Supply
Extension
24V 24V
4.3kΩ 4.3kΩ
X X
Input circuit diagram 18
• DC power supply type
Options
Units and
Other Extension
S/S 24V
DC
S/S 24V
DC 19
0V 0V
Display Module
*2 *2
24V 24V
4.3kΩ 4.3kΩ
X X
20
*1. The DC power type applies to the power supply voltage in "Power Supply Specifications (Power Supply
Terminal Block
269
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
Load
Y
DC power
supply
COM
Fuse
Output circuit diagram
Y
External
power supply
COM
Fuse
A number (1 or more) is entered in of [COM ].
FX2N-32ER-ES/UL
2-φ4.5 mounting holes Unit : mm (inches)
(mounting hole pitch)
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7
FX2N-32ER OUT
0 1 2 3 4 5 6 7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
270
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
11
FX2N-48ER-ES/UL, FX2N-48ER-DS
Counters
High-Speed
4-φ4.5 mounting holes
Unit : mm (inches)
12
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
Output Wiring
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ER OUT
0 1 2 3 4 5 6 7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
Various Uses
Wiring for
The terminal block uses
M3 terminal screws.
Troubleshooting
Maintenance,
Test Run,
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7
FX2N-32ER-ES/UL
15
Extension Units
Powered
IInput/Output
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-48ER-ES/UL
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
16
Blocks
Extension
Input/Output
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ER-ES/UL
COM1
Y0 Y2
Y1 Y3 COM2
Y4 Y6
Y5 Y7 COM3
Y0 Y2
Y1 Y3 COM4
Y4 Y6 Y0 Y2 Y4 Y6 COM5
Y5 Y7 Y1 Y3 Y5 Y7
17
Unit
Power Supply
Extension
FX2N-48ER-DS
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
18
Options
Units and
Other Extension
FX2N-48ER-DS
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
19
Display Module
20
Terminal Block
271
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL, FX2N-48ET-DSS
2. Input specifications (for sink input [-common] and source input [+common])
Item FX2N-32ET-ESS/UL FX2N-48ET-ESS/UL, FX2N-48ET-DSS
Number of input points 16 points 24 points
Connection type Removable terminal block (M3 screw)
Input form sink/source
Input signal voltage 24V DC ± 10%*1
Input signal current 5 mA/24V DC
Input impedance 4.3 kΩ
Input ON current 3.5 mA or more/24V DC
Input sensitivity
current Input OFF
current 1.5 mA or less
4.3kΩ 4.3kΩ
X X
Input circuit diagram
• DC power supply type
Sink input wiring Source input wiring
Fuse Fuse
4.3kΩ 4.3kΩ
X X
*1. The DC power type applies to the power supply voltage in "Power Supply Specifications (Power Supply
Input/24V DC Service Power Supply)."
*2. Do not connect with 0V and 24V terminals.
272
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL, FX2N-48ET-DSS
11
3. Output specifications (transistor output type)
Counters
High-Speed
Item FX2N-32ET-ESS/UL FX2N-48ET-ESS/UL, FX2N-48ET-DSS
Number of output points 16 points 24 points
Connection type Removable terminal block (M3 screw)
Output unit/type Transistor/source output 12
External power supply 5 to 30V DC
Output Wiring
Output circuit insulation Insulation with photocoupler
Indication of output operation When photocoupler is driven, LED on panel is lit.
0.5A/point 0.5A/point
The total load current per common ter- The total load current per common ter-
Resistance
minal should be the following value. minal should be the following value. 13
• 4 output points/common terminal: 0.8 • 4 output points/common terminal: 0.8
Various Uses
Wiring for
Max. load load
A or less A or less
• 8 output points/common terminal: 1.6
A or less
Inductive load 12 W/24V DC
Open circuit leakage current 0.1 mA/30V DC 14
Min. load −
Troubleshooting
Maintenance,
Test Run,
OFF→ON 0.2 ms or less/200 mA (at 24V DC)
Response time
ON→OFF 0.2 ms or less/200 mA (at 24V DC)
15
Load
Extension Units
Powered
IInput/Output
Y
Fuse
Output circuit diagram +V
DC power
supply
16
Blocks
Extension
Input/Output
A common number applies to the of [+V ].
Unit
Power Supply
Extension
2-φ4.5 mounting holes
Unit : mm (inches)
(mounting hole pitch)
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7
18
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
Options
Units and
Other Extension
0 1 2 3 4 5 6 7
FX2N-32ET OUT
0 1 2 3 4 5 6 7
TRANSISTOR UNIT
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7
M3 terminal screws.
20
Terminal Block
273
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL, FX2N-48ET-DSS
FX2N-48ET-ESS/UL, FX2N-48ET-DSS
4-φ4.5 mounting holes
Unit : mm (inches)
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ET OUT
0 1 2 3 4 5 6 7
TRANSISTOR UNIT
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7
FX2N-32ET-ESS/UL
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7
FX2N-32ET-ESS/UL
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7
FX2N-48ET-ESS/UL
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ET-ESS/UL
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7
FX2N-48ET-DSS
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ET-DSS
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7
274
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.5 FX2N-32ER, FX2N-48ER, FX2N-48ER-D
11
15.5 FX2N-32ER, FX2N-48ER, FX2N-48ER-D
Counters
High-Speed
15.5.1 Product specifications
The generic specifications are the same as those for the main unit. 12
→ For the generic specifications, refer to Section 4.1.
Output Wiring
For external wiring, refer to the following chapters.
→ Refer to Chapter 9 for power supply wiring.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
2. Input specifications (sink input [-common])
Item FX2N-32ER FX2N-48ER, FX2N-48ER-D
Number of input points 16 points 24 points
Connection type Removable terminal block (M3 screw)
14
Troubleshooting
Maintenance,
Test Run,
Input form Sink
Input signal voltage 24V DC ± 10%*1
Input signal current 5 mA/24V DC
Input impedance 4.3 kΩ
Input ON 15
Input 3.5 mA or more/24V DC
current
Extension Units
Powered
IInput/Output
sensitivity
current Input OFF
1.5 mA or less
current
Input response time About 10 ms
Input signal form No-voltage contact input or NPN open collector transistor
Input circuit insulation Insulation with photocoupler
16
Blocks
Extension
Input/Output
Indication of input operation LED on panel is lit when there is input.
• AC power supply type • DC power supply type
Sink input wiring Sink input wiring
Fuse Fuse
L 17
N
Unit
Power Supply
Extension
100 to 240V AC 24V
Input circuit diagram 24+ 24+ *2
DC
COM COM
X X 18
4.3kΩ 4.3kΩ
Options
Units and
Other Extension
*1. The DC power type applies to the power supply voltage in "Power Supply Specifications (Power
Supply Input/24V DC Service Power Supply)."
*2. Do not connect with 24+ terminals.
19
Display Module
20
Terminal Block
275
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.5 FX2N-32ER, FX2N-48ER, FX2N-48ER-D
Load
Y
DC power
supply
COM
Fuse
Output circuit diagram
Y
External
power supply
COM
Fuse
A common number applies to the of [COM ].
FX2N-32ER
2-φ4.5 mounting holes Unit : mm (inches)
(mounting hole pitch)
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7
FX2N-32ER OUT
0 1 2 3 4 5 6 7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
276
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.5 FX2N-32ER, FX2N-48ER, FX2N-48ER-D
11
FX2N-48ER, FX2N-48ER-D
Counters
High-Speed
4-φ4.5 mounting holes
Unit : mm (inches)
12
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
Output Wiring
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ER OUT
0 1 2 3 4 5 6 7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
Various Uses
Wiring for
M3 terminal screws.
FX2N-32ER 14
Troubleshooting
Maintenance,
Test Run,
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
FX2N-32ER
15
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
Extension Units
Powered
IInput/Output
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-48ER
L N
COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
16
Blocks
Extension
Input/Output
FX2N-48ER
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7 17
Unit
Power Supply
Extension
FX2N-48ER-D
COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ER-D
18
Options
Units and
Other Extension
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
19
Display Module
20
Terminal Block
277
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.6 FX2N-32ET, FX2N-48ET, FX2N-48ET-D
X X
4.3kΩ 4.3kΩ
*1. The DC power type applies to the power supply voltage in "Power Supply Specifications (Power
Supply Input/24V DC Service Power Supply)."
*2. Do not connect with 24+ terminal.
278
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.6 FX2N-32ET, FX2N-48ET, FX2N-48ET-D
11
3. Output specifications (transistor output type)
Counters
High-Speed
Item FX2N-32ET FX2N-48ET, FX2N-48ET-D
Number of output points 16 points 24 points
Connection type Removable terminal block (M3 screw)
Output unit/type Transistor/sink output 12
External power supply 5 to 30V DC
Output Wiring
Output circuit insulation Insulation with photocoupler
Indication of output operation When photocoupler is driven, LED on panel is lit.
0.5A/point 0.5A/point
The total load current per common The total load current per common
Resistance
terminal should be the following value. terminal should be the following value. 13
• 8 output points/common terminal: 1.6 • 4 output points/common terminal: 0.8
Various Uses
Wiring for
Max. load load
A or less A or less
• 8 output points/common terminal: 1.6
A or less
Inductive load 12 W/24V DC
Open circuit leakage current 0.1 mA or less/30V DC 14
Min. load −
Troubleshooting
Maintenance,
Test Run,
OFF→ON 0.2 ms or less/200 mA (at 24V DC)
Response time
ON→OFF 0.2 ms or less/200 mA (at 24V DC)
15
Load
Extension Units
Powered
IInput/Output
Y
Output circuit diagram Fuse
COM
DC power
supply
16
Blocks
Extension
Input/Output
A common number applies to the of [COM ].
Unit
Power Supply
Extension
2-φ4.5 mounting holes
Unit : mm (inches)
(mounting hole pitch)
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
18
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
Options
Units and
Other Extension
0 1 2 3 4 5 6 7
FX2N-32ET OUT
0 1 2 3 4 5 6 7
TRANSISTOR UNIT
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
M3 terminal screws.
20
Terminal Block
279
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.6 FX2N-32ET, FX2N-48ET, FX2N-48ET-D
FX2N-48ET, FX2N-48ET-D
2-φ4.5 mounting holes
Unit : mm (inches)
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ET OUT
0 1 2 3 4 5 6 7
TRANSISTOR UNIT
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
FX2N-32ET
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
FX2N-32ET
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-48ET
COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ET
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
FX2N-48ET-D
COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ET-D
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
280
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.7 FX2N-32ES
11
15.7 FX2N-32ES
Counters
High-Speed
15.7.1 Product specifications
The generic specifications are the same as those for the main unit. 12
→ For the generic specifications, refer to Section 4.1.
Output Wiring
For external wiring, refer to the following chapters.
→ Refer to Chapter 9 for power supply wiring.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
2. Input specifications (sink input [-common])
Item FX2N-32ES
Number of input points 16 points
Connection type Removable terminal block (M3 screw)
14
Troubleshooting
Maintenance,
Test Run,
Input form Sink
Input signal voltage 24V DC ± 10%
Input signal current 5 mA/24V DC
Input impedance 4.3 kΩ
Input ON
3.5 mA or more/24V DC
15
Input sensitivity current
Extension Units
Powered
IInput/Output
current Input OFF
1.5 mA or less
current
Input response time About 10 ms
Input signal form No-voltage contact input or NPN open collector transistor
Input circuit insulation Insulation with photocoupler 16
Blocks
Extension
Input/Output
Indication of input operation LED on panel is lit when there is input.
Unit
Power Supply
Extension
Input circuit diagram
COM
X
4.3kΩ 18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
281
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.7 FX2N-32ES
Load
Y
External
power supply
Output circuit diagram U
COM
Fuse
FX2N-32ES
2-φ4.5 mounting holes
Unit : mm (inches)
(mounting hole pitch)
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
90 (3.55")
80 (3.15")
0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7
FX2N-32ES OUT
0 1 2 3 4 5 6 7
TRIAC UNIT
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-32ES
COM X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
282
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.8 FX2N-48ER-UA1/UL
11
15.8 FX2N-48ER-UA1/UL
Counters
High-Speed
15.8.1 Product specifications
The generic specifications are the same as those for the main unit. 12
→ For the generic specifications, refer to Section 4.1.
Output Wiring
For external wiring, refer to the following chapters.
→ Refer to Chapter 9 for power supply wiring.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
2. Input specifications (100V AC Input)
Item FX2N-48ER-UA1/UL
Number of input points
Connection type
24 points
Removable terminal block (M3 screw)
14
Troubleshooting
Maintenance,
Test Run,
Input form AC input
Input signal voltage 100 to 120V AC +10%,-15% 50/60 Hz
4.7 mA/100V AC 50 Hz (70% or less when turned on simultaneously)
Input signal current
6.2 mA/110V AC 60 Hz (70% or less when turned on simultaneously)
Input impedance
Approx. 21 kΩ/50 Hz 15
Approx. 18 kΩ/60 Hz
Extension Units
Powered
IInput/Output
Input ON
3.8 mA or more/80V AC
Input sensitivity current
current Input OFF
1.7 mA or less/30V AC
current
Input response time Approx. 25 to 30 ms 16
Input signal form Contact input
Blocks
Extension
Input/Output
Input circuit insulation Photocoupler insulation
Indication of input operation LED on panel is lit when there is input.
Fuse
L
N
17
Unit
Power Supply
Extension
100 to 240V AC
Input circuit diagram COM
*1
X
*1 Input impedance 18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
283
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.8 FX2N-48ER-UA1/UL
Load
Y
DC power
supply
COM
Fuse
Output circuit diagram
Y
External
power supply
COM
Fuse
A common number applies to the of [COM ].
FX2N-48ER-UA1/UL
4-φ4.5 mounting holes
Unit : mm (inches)
(mounting hole pitch)
COM COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
110VAC INPUT
80 (3.15")
90 (3.55")
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
IN
0 1 2 3 4 5 6 7
POWER
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
FX2N-48ER-UA1 OUT
0 1 2 3 4 5 6 7
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 C0M5 Y1 Y3 Y5 Y7
284
FX3U Series Programmable Controllers 15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
User’s Manual - Hardware Edition 15.8 FX2N-48ER-UA1/UL
11
15.8.3 Terminal layout
Counters
High-Speed
FX2N-48ER-UA1/UL
COM COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7 12
Output Wiring
FX2N-48ER-UA1/UL
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 Y5 Y7
COM2 COM3Y1 Y3 Y5 Y7
COM4 COM5 Y1 Y3 Y5 Y7
13
Various Uses
Wiring for
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
285
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition
DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
WIRING PRECAUTIONS
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX0N/FX2N/FX3U Series extension equipment to the main unit in accordance with
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
286
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.1 Outline
11
16.1 Outline
Counters
High-Speed
Connect input/output extension blocks to the PLC to add more input/output points. 8 or 16 points can be
added by an input/output extension block.
Since the power is supplied from the main unit, it is not necessary to prepare another power supply unit for
each input/output extension block. 12
Output Wiring
16.1.1 Product type
There are various types of input/output extension blocks. Select optimum blocks considering the input type,
output type, and connection unit of your system.
13
Input/output extension blocks
Various Uses
Wiring for
Power supply Number of points Input type Output type Connection unit
Troubleshooting
Maintenance,
Test Run,
(Sink) Transistor
(Source)
5V DC
Transistor
100V AC system (Sink)
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
287
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.1 Outline
*1. Four inputs and four outputs are occupied as unused numbers.
288
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.1 Outline
11
3. For output extension
Counters
High-Speed
Sink :Sink [-common], Source :Source [+common]
Input Output
Connection
Model Number Common Number Common
Type Type unit
of points system of points system 12
Relay output type
Output Wiring
Terminal
FX2N-8EYR-ES/UL − − − Relay 8 −
block
Terminal
FX2N-8EYR − − − Relay 8 −
block
FX2N-16EYR-ES/UL − − − Relay 16 −
Terminal 13
block
Various Uses
Wiring for
Terminal
FX2N-16EYR − − − Relay 16 −
block
Dedicated to sink output only
Terminal
− − −
FX2N-8EYT Transistor 8 Sink
block 14
Terminal
Troubleshooting
Maintenance,
Test Run,
FX2N-8EYT-H − − − Transistor 8 Sink
block
Terminal
FX2N-16EYT − − − Transistor 16 Sink
block
FX2N-16EYT-C − − − Transistor 16 Sink Connector
Terminal
15
FX2N-16EYS − − − Triac(SSR) 16 −
Extension Units
Powered
IInput/Output
block
Dedicated to source output only
Terminal
FX2N-8EYT-ESS/UL − − − Transistor 8 Source
block
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
289
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
S/S S/S
X X
4.3kΩ 4.3kΩ
290
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
11
4. Output specifications (Relay output type)
Counters
High-Speed
Item FX2N-8ER-ES/UL
Output points 4 points
Connection unit Vertical terminal block (M3 screws)
Output unit Relay 12
5 to 30V DC
Output Wiring
External power supply 240V AC or less
(250V AC or less when the unit does not comply with CE, UL, or cUL standards)
Output circuit insulation method Mechanical insulation
Indication of output operation Supplying power to the relay coil will light the LED indicator lamp on panel.
Resistance
2 A/point 13
The total resistance load current per common should be as follows:
Various Uses
Wiring for
load
• 4 output points/common: 8A or less
Maximum load
80 VA
Inductive load → For the product life, refer to Subsection 4.4.2.
→ For cautions on external wiring, refer to Subsection 12.2.4.
Open circuit leakage current − 14
Minimum load 5V DC, 2 mA (reference values)
Troubleshooting
Maintenance,
Test Run,
OFF→ON Approx. 10 ms
Response time
ON→OFF Approx. 10 ms
15
Load
Extension Units
Powered
IInput/Output
Y
DC power
Output circuit diagram supply unit
COM1
Fuse
16
Blocks
Extension
Input/Output
16.2.2 Parts identification and terminal arrangement
Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower
four points. 17
With cover Without cover FX2N-8ER-ES/UL
Unit
Power Supply
Extension
S/S
S/S X1 X3
X0 X2
FX2N-8ER-ES FX2N-
18
POWER
Input indicator Rear line
IN 0 1 2 3
OUT 0 1 2 3
lamps (LED lamps) extension
Output indicator connector
Options
Units and
Other Extension
19
Display Module
COM1 Y1
Y0 Y2
Y3
20
Terminal Block
291
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
90(3.55")
80(3.15")
POWER
IN 0 1 2 3
OUT 0 1 2 3
9(0.36")
43(1.7") 87(3.43")
292
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
11
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
Counters
High-Speed
16.3.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapters.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
Product type FX2N extension block
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Input specifications 15
Extension Units
Powered
IInput/Output
Item FX2N-8ER
Input points 4 points
Vertical terminal block (M3 screws) /
For a detailed description of wiring, refer
Connection unit Connector terminal block
to the input line connection diagram of
the main unit. 16
Input type Sink
Blocks
Extension
Input/Output
Input signal voltage 24V DC ± 10%
Input signal current 5 mA/24V DC
Input impedance 4.3kΩ
Input-ON
3.5 mA or more at 24V DC 17
Input sensitivity current
Unit
Power Supply
Extension
current Input-OFF
1.5 mA or less
current
Input response time Approx. 10 ms
No-voltage contact input
Input signal type
NPN open collector transistor 18
Input circuit insulation Photo-coupler insulation
Options
Units and
Other Extension
24V
Input circuit diagram
24+
20
X
Terminal Block
4.3kΩ
293
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
Load
Y
DC power
Output circuit diagram supply unit
COM1
Fuse
FX2N-8ER FX2N-
POWER
Input indicator Rear line
IN 0
OUT 0
1
1
2
2
3
3
lamps (LED lamps) extension
Output indicator connector
lamps (LED lamps)
COM1 Y1
Y0 Y2
Y3
294
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
11
16.3.3 External dimensions
Counters
High-Speed
2-φ4.5 mounting holes Unit:mm(inches)
12
Output Wiring
90(3.55")
80(3.15")
POWER
IN 0 1 2 3
OUT 0 1 2 3
13
9(0.36")
Various Uses
Wiring for
43(1.7") 87(3.43")
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
295
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)
S/S S/S
X X
4.3kΩ 4.3kΩ
296
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)
11
16.4.2 Parts identification and terminal arrangement
Counters
High-Speed
FX2N-8EX-ES/UL
FX2N-8EX-ES/UL
With cover Without cover
12
S/S
S/S X1 X3
Output Wiring
X0 X2
FX2N-8EX-ES FX2N-
POWER
Rear line
IN 0 1 2 3
extension
4 5 6 7 Input indicator 4 5 6 connector
lamps
(LED lamps)
13
X4
X5
X6
X7
Various Uses
Wiring for
14
X4 X6
X5 X7
Troubleshooting
Maintenance,
Test Run,
FX2N-16EX-ES/UL 15
When an input (X) number is assigned, 8 points on the upper side will be used for the lower input numbers,
Extension Units
Powered
IInput/Output
and 8 points on the lower side will be used for the higher input numbers.
With cover Without cover FX2N-16EX-ES/UL
Input indicator
S/S X1 X3
X0
lamps S/S X1 X3 X5 X6 X7 X0 X1 X3 X5 X7
16
X2 X4
(LED lamps) X0 X2 X4
X5
Rear line
X6
Blocks
Extension
Input/Output
X7
extension
X0
connector Lower
X1
X2
numbers
X3 X5
Input indicator
X4
lamps
X6
X7
(LED lamps)
17
Unit
Power Supply
Extension
X2 X4 X6
Higher
numbers
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
297
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)
FX2N-8EX-ES/UL
2-φ4.5 mounting holes Unit:mm (inches)
90(3.55")
FX2N-8EX-ES
POWER
IN 0 1 2 3
4 5 6 7
9(0.36")
43(1.7") 87(3.43")
FX2N-16EX-ES/UL
2-φ4.5 mounting holes Unit:mm (inches)
(mounting hole pitch)
80(3.15")
90(3.55")
9(0.36")
40(1.58") 87(3.43")
298
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C
11
16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C
Counters
High-Speed
16.5.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapter.
→ Refer to Chapter 10 for input wiring.
Various Uses
Wiring for
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Input specifications
Item FX2N-8EX FX2N-16EX FX2N-16EX-C 15
Extension Units
Powered
IInput/Output
Input points 8 points 16 points
Vertical terminal block (M3 screws) /
For a detailed description of wiring, refer
Connection unit Connector terminal block
to the input line connection diagram of
the main unit.
Input type Sink 16
Blocks
Extension
Input/Output
Input signal voltage 24V DC ± 10%
Input signal current 5 mA/24V DC
Input impedance 4.3kΩ
Input Input-ON current 3.5 mA or more at 24V DC
sensitivity
current Input-OFF current 1.5 mA or less 17
Unit
Power Supply
Extension
Input response time Approx. 10 ms
No-voltage contact input
Input signal type
NPN open collector transistor
Input circuit insulation Photo-coupler insulation
Indication of input operation LED on panel lights when input. 18
Options
Units and
Other Extension
24+
X
4.3kΩ
20
Terminal Block
299
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C
FX2N-8EX
FX2N-8EX
With cover Without cover
24+
24+ X1 X3
X0 X2
FX2N-8EX FX2N-
Rear line
POWER
Input extension
IN 0
4
1
5
2
6
3
7
indicator connector
lamps 4 5 6
(LED lamps)
X4
X5
X6
X7
X4 X6
X5 X7
FX2N-16EX
When an input (X) number is assigned, 8 points on the upper side will be used for the lower input numbers,
and 8 points on the lower side will be used for the higher input numbers.
24+ X1 X3 X5 X6 X7 X0 X1 X3 X5 X7
lamps
X2 X4
X0 X2 X4
(LED lamps)
X5
Rear line
X6
X7
extension
X0
connector Lower
X1
numbers
X2
X3 X5
Input indicator
X4
lamps
X6
X7
(LED lamps)
X2 X4 X6
Higher
numbers
300
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C
11
FX2N-16EX-C
Counters
High-Speed
When an input (X) number is assigned, 8 points on side A will be used for the lower input numbers, and 8
points on side B will be used for the higher input numbers.
Output Wiring
Rear line X2 3 13 X2
extension X3 4 14 X3
connector X4 5 15 X4
Input indicator
X5 6 16 X5
lamps
Terminal arrangement
X6 7
X7 8
17 X6
18 X7
13
(LED lamps)
Various Uses
Wiring for
9 19
24+ 10 20 24+
Troubleshooting
Maintenance,
Test Run,
2-φ4.5 mounting holes Unit:mm (inches)
(mounting hole pitch)
15
80(3.15")
90(3.55")
FX2N-8EX
Extension Units
Powered
IInput/Output
POWER
IN 0 1 2 3
4 5 6 7
9(0.36") 16
43(1.7") 87(3.43")
Blocks
Extension
Input/Output
FX2N-16EX
2-φ4.5 mounting holes Unit:mm (inches)
17
(mounting hole pitch)
Unit
Power Supply
Extension
80(3.15")
90(3.55")
18
Options
Units and
Other Extension
9(0.36")
40(1.58") 87(3.43")
19
Display Module
20
Terminal Block
301
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C
FX2N-16EX-C
90(3.55")
9(0.36")
40(1.58") 87(3.43")
(Socket)
Connection face of connector
The polarity is shown in the following table.
20
FX-16E-
CAB type cable
19 17 15 13 11
B 20 18 16 14 12 19 17 15 13 11
20 18 16 14 12
10 8 6 4 2
A 10 8 6 4 2 9 7 5 3 1
9 7 5 3 1
302
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.6 FX2N-16EXL-C (5V DC Input: 16 Points)
11
16.6 FX2N-16EXL-C (5V DC Input: 16 Points)
Counters
High-Speed
16.6.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
1. Power supply specifications
Item FX2N-16EXL-C
Product type FX2N connector type extension block for each application
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit) 13
Various Uses
Wiring for
2. Weight and Other specifications
Item FX2N-16EXL-C
MASS (Weight) 0.3 kg (0.66lbs)
Other
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
14
Troubleshooting
Maintenance,
Test Run,
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Input specifications
Item FX2N-16EXL-C
Input points 16 points 15
Connection unit Connector terminal block
Extension Units
Powered
IInput/Output
Input type TTL level
Input signal voltage 5V DC ± 5%
Input signal current 20 mA (at 5V DC), maximum
Input impedance 2.2kΩ
Input sensitivity ON(Low) 1 mA or more
16
Blocks
Extension
Input/Output
current OFF(High) 0.4 mA or less
Input sensitivity ON(Low) 1.5V DC or less
voltage OFF(High) 3.5V DC or more
OFF→ON
Input response (High→Low)
1 ms +1 ms, -0.5 ms
17
time ON→OFF
Unit
Power Supply
Extension
1 ms +1 ms, -0.5 ms
(Low→High)
Input signal type TTL input
Input circuit insulation Photo-coupler insulation
Indication of input operation LED on panel lights when input.
18
External unit
Options
Units and
Other Extension
5V DC
5+
Input circuit diagram
X
2.2kΩ TTL 19
Display Module
20
Terminal Block
303
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.6 FX2N-16EXL-C (5V DC Input: 16 Points)
90(3.55")
9(0.36")
40(1.58") 87(3.43")
L N S/S 0V 24V X0 5+ X0 X1 X3
main unit or
input/output powered extension unit
304
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.6 FX2N-16EXL-C (5V DC Input: 16 Points)
11
How to connect connector
Counters
High-Speed
(Socket)
Connection face of connector
The polarity is shown in the following table.
20
FX-16E-
CAB type cable 12
Output Wiring
Cross section of 20-core flat cable
(Be sure to check the wire number.)
20
13
19 17 15 13 11
B 20 18 16 14 12 19 17 15 13 11
20 18 16 14 12
Various Uses
Wiring for
10 8 6 4 2
A 10 8 6 4 2 9 7 5 3 1
9 7 5 3 1
14
Troubleshooting
Maintenance,
Test Run,
Side B is for the higher input numbers,
Side B 5+ X7 X6 X5 X4 X3 X2 X1 X0
and side A is for the lower input numbers.
Side A 5+ X7 X6 X5 X4 X3 X2 X1 X0
(Exe.) Side B X050 to X057
Side A X040 to X047
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
305
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.7 FX2N-8EX-UA1/UL (100V AC Input)
3. Input specifications
Item FX2N-8EX-UA1/UL
Input points 8 points
Vertical terminal block (M3 screws) / For a detailed description of wiring, refer to
Connection unit
the input line connection diagram of the main unit.
Input type AC input
Input signal voltage 100 to 120V AC
Input signal current 6.2mA/110V AC 60Hz 4.7mA/100V AC 50Hz
Approx. 21kΩ/50Hz
Input impedance
Approx. 18kΩ/60Hz
Input-ON
3.8mA/80V AC or more
Input sensitivity current
current Input-OFF
1.7mA/30V AC or more
current
Input response time Approx. 25 to 30 ms
Input signal type Voltage contact
Input circuit insulation Photocoupler insulation
Indication of input operation LED on panel lights when input.
100 to 120V AC
COM
Photocoupler
Input impedance Fuse
X*0
Input circuit diagram
Photocoupler
Input impedance
X*7
306
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.7 FX2N-8EX-UA1/UL (100V AC Input)
11
16.7.2 Parts identification and terminal arrangment
Counters
High-Speed
FX2N-8EX-UA1/UL
With cover Without cover
COM
COM X1
12
X0 X2
FX2N-8EX-UA1 FX2N-
Rear line
Output Wiring
POWER
Input extension
X3
IN 0
4
1
5
2
6
3
7
indicator connector
4 5 6
lamps
(LED lamps)
X4
X5
X6
13
X7
Various Uses
Wiring for
X4 X6
14
X5 X7
Troubleshooting
Maintenance,
Test Run,
16.7.3 External dimensions
15
2-φ4.5 mounting holes Unit:mm (inches)
Extension Units
Powered
IInput/Output
(mounting hole pitch)
80(3.15")
90(3.55")
FX2N-8EX-UA1
16
POWER
IN 0 1 2 3
4 5 6 7
Blocks
Extension
Input/Output
9(0.36")
43(1.7") 87(3.43")
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
307
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
Load
Y
Fuse
COM
DC power
supply unit
Output circuit diagram Y
Fuse
COM
AC power
supply unit
A common number applies to the of [COM ].
308
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
11
16.8.2 Parts identification and terminal arrangement
Counters
High-Speed
FX2N-8EYR-ES/UL
FX2N-8EYR-ES/UL
With cover Without cover
12
COM1 Y1
COM1 Y1 Y3
Y0 Y2
Output Wiring
Y0 Y2
FX2N-8EYR-ES FX2N-
Rear line
Output
Y3
POWER
extension
OUT 0
4
1
5
2
6
3
7
indicator OUT
connector
lamps 4 5 6
(LED lamps)
13
COM2 Y5
Y4 Y6
Various Uses
Wiring for
Y7
COM2 Y5
14
Y4 Y6
Troubleshooting
Maintenance,
Test Run,
Y7
FX2N-16EYR-ES/UL
When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers,
and 8 points on the lower side will be used for the higher output numbers.
15
Extension Units
Powered
IInput/Output
With cover Without cover
COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Output indicator
COM1 Y1 Y3
Y0 Y2 Y4
Y0
lamps
Y2 Y4
(LED lamps)
16
Y5
Rear line
Y6
Lower
Y7
extension
Blocks
Extension
Input/Output
numbers
Y0
connector
Y1
Y2
Y3 Y5
Output indicator
Y4
lamps
Y6 COM2
Y7
(LED lamps)
17
Unit
Power Supply
Extension
Y2 Y4 Y6 COM2
Higher
numbers
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
309
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
FX2N-8EYR-ES/UL
90(3.55")
POWER
0 1 2 3
4 5 6 7
9(0.36")
43(1.7") 87(3.43")
FX2N-16EYR-ES/UL
90(3.55")
9(0.36")
40(1.58") 87(3.43")
310
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
11
16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
Counters
High-Speed
16.9.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapter.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Extension Units
Powered
IInput/Output
Output points 8 points 16 points
Connection unit Vertical terminal block (M3 screws)
Output unit/type Transistor/source output
External power supply 5 to 30V DC
Output circuit insulation method Photo-coupler insulation 16
Indication of output operation Activation of the photo-coupler will light the LED indicator lamp on panel.
Blocks
Extension
Input/Output
0.5 A/point
Resistance The total load current per common should be as follows:
Maximum load load • 4 output points/common: 0.8A or less
• 8 output points/common: 1.6A or less
Inductive load 12 W/24V DC 17
Open circuit leakage current 0.1 mA/30 A DC
Unit
Power Supply
Extension
Minimum load −
OFF→ON 0.2 ms or less for 200 mA (at 24V DC)
Response time
ON→OFF 0.2 ms or less for 200 mA (at 24V DC)
18
Options
Units and
Other Extension
Load
Y
Fuse
Output circuit diagram +V
DC power
supply
19
Display Module
20
Terminal Block
311
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
FX2N-8EYT-ESS/UL
With cover Without cover FX2N-8EYT-ESS/UL
+V0
Y0
+V0 Y1 Y3
Y1
Y2
Y3
Y0 Y2
FX2N-8EYT-ESS FX2N-
POWER
Output Rear line
OUT 0 1 2 3
indicator OUT
extension
4 5 6 7
lamps
4 5 6
connector
(LED lamps)
+V1
Y4
Y5
Y6
Y7
+V1 Y5 Y7
Y4 Y6
FX2N-16EYT-ESS/UL
When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers,
and 8 points on the lower side will be used for the higher output numbers.
FX2N-16EYT-ESS/UL
With cover Without cover
Output indicator
+V0 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
+V0 Y1 Y3
Y0
lamps
Y0 Y2 Y4
Y2 Y4
(LED lamps)
Y5
Rear line
Y6
Y7
extension
Lower
Y0
connector
numbers
Y1
Y2
Y3 Y5
Output indicator
Y4
lamps
Y6 +V1
Y7
(LED lamps)
Y2 Y4 Y6 +V1
Higher
numbers
312
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
11
16.9.3 External dimensions
Counters
High-Speed
FX2N-8EYT-ESS/UL
Output Wiring
FX2N-8EYT-ESS 80(3.15")
90(3.55")
POWER
OUT 0 1 2 3
4 5 6 7
13
Various Uses
Wiring for
9(0.36")
43(1.7") 87(3.43")
FX2N-16EYT-ESS/UL
14
Troubleshooting
Maintenance,
Test Run,
2-φ4.5 mounting holes Unit:mm (inches)
(mounting hole pitch)
80(3.15")
90(3.55")
15
Extension Units
Powered
IInput/Output
9(0.36")
40(1.58") 87(3.43")
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
313
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
Load
Y
Fuse
COM
DC power
supply
Output circuit diagram Load
Y
Fuse
COM
AC power
supply
A common number applies to the of [COM ].
314
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
11
16.10.2 Parts identification and terminal arrangement
Counters
High-Speed
FX2N-8EYR
With cover Without cover FX2N-8EYR
12
COM1 Y1 Y3
COM1 Y1
Y0 Y2
Output Wiring
Y0 Y2
FX2N-8EYR FX2N-
Y3
OUT 0 1 2 3
OUT
4 5 6 7
lamps
4 5 6 connector
(LED lamps)
13
COM2 Y5
Y4 Y6
Y7
Various Uses
Wiring for
14
COM2 Y5
Y4 Y6
Troubleshooting
Maintenance,
Test Run,
Y7
FX2N-16EYR
When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, 15
and 8 points on the lower side will be used for the higher output numbers.
Extension Units
Powered
IInput/Output
With cover Without cover
COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Output indicator
COM1 Y1 Y3
Y0
Y0 Y2 Y4
lamps
Y2 Y4
(LED lamps)
16
Y5
Rear line
Y6
Blocks
Extension
Input/Output
Y7
extension Lower
Y0
connector numbers
Y1
Y2
Y3 Y5
Output indicator
Y4
lamps
Y6 COM2
Y7
(LED lamps)
17
Unit
Power Supply
Extension
Y2 Y4 Y6 COM2
Higher
numbers
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
315
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
FX2N-8EYR
90(3.55")
POWER
OUT 0 1 2 3
4 5 6 7
9(0.36")
43(1.7") 87(3.43")
FX2N-16EYR
90(3.55")
9(0.36")
40(1.58") 87(3.43")
316
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
11
16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
Counters
High-Speed
16.11.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapter.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Extension Units
Powered
IInput/Output
Output points 8 points 16 points
Connection unit Removable terminal block (M3 screws) Connector terminal block
Output unit/type Transistor/sink output
External power supply 5 to 30V DC
Output circuit insulation method Photo-coupler insulation 16
Indication of output operation Activation of the photo-coupler will light the LED indicator lamp on panel.
Blocks
Extension
Input/Output
0.5 A/point 0.3 A/point
The total load current per common The total load current per common
Resistance
should be as follows: should be as follows:
Maximum load load
• 4 output points/common: 0.8A or less • 16 output points/common: 1.6A or
• 8 output points/common: 1.6A or less less 17
Inductive load 12 W/24V DC 7.2 W/24V DC
Unit
Power Supply
Extension
Open circuit leakage current 0.1 mA/30 A DC
Minimum load −
OFF→ON 0.2 ms or less for 200 mA (at 24V DC)
Response time
ON→OFF 0.2 ms or less for 200 mA (at 24V DC)
18
Load Load
Options
Units and
Other Extension
Y Y
Fuse Fuse
COM1 COM
DC power DC power
Output circuit diagram supply unit supply unit
Y Y
Fuse Fuse
19
COM2 COM
Display Module
DC power DC power
supply unit supply unit
20
Terminal Block
317
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
FX2N-8EYT
With cover Without cover FX2N-8EYT
COM1 Y1 Y3
Y0 Y2
COM1 Y1
Y0 Y2
FX2N-8EYT FX2N-
Y3
4 5 6 7
lamps
4 5 6 connector
(LED lamps)
COM2 Y5
Y4 Y6
Y7
COM2 Y5
Y4 Y6
Y7
FX2N-16EYT
When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers,
and 8 points on the lower side will be used for the higher output numbers.
COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Output indicator
COM1 Y1 Y3
Y0 Y2 Y4
Y0
lamps
Y2 Y4
(LED lamps)
Y5
Rear line
Y6
Lower
Y7
extension
numbers
Y0
connector
Y1
Y2
Y3 Y5
Output indicator
Y4
lamps
Y6 COM2
Y7
(LED lamps)
Y2 Y4 Y6 COM2
Higher
numbers
318
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
11
FX2N-16EYT-C
Counters
High-Speed
When an output (Y) number is assigned, 8 points on side A will be used for the lower output numbers, and 8
points on side B will be used for the higher output numbers.
Output Wiring
(LED lamps)
Y1 2 12 Y1
Rear line Y2 3 13 Y2
extension Y3 4 14 Y3
connector Y4 5 15 Y4
Y5 6 16 Y5
Output indicator
lamps Y6 7 17 Y6 13
Terminal arrangement Y7 8 18 Y7
Various Uses
Wiring for
(LED lamps)
COM 9 19 COM
10 20
Troubleshooting
Maintenance,
Test Run,
FX2N-8EYT
2-φ4.5 mounting holes Unit:mm (inches)
15
(mounting hole pitch)
FX2N-8EYT
80(3.15")
90(3.55")
Extension Units
Powered
IInput/Output
POWER
OUT 0 1 2 3
4 5 6 7
9(0.36")
16
Blocks
Extension
Input/Output
43(1.7") 87(3.43")
FX2N-16EYT
2-φ4.5 mounting holes Unit:mm (inches) 17
Unit
Power Supply
Extension
(mounting hole pitch)
80(3.15")
90(3.55")
18
Options
Units and
Other Extension
9(0.36")
40(1.58") 87(3.43")
19
Display Module
20
Terminal Block
319
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
FX2N-16EYT-C
90(3.55")
9(0.36")
40(1.58") 87(3.43")
(Socket)
Connection face of connector
The polarity is shown in the following table.
20
FX-16E-
CAB type cable
19 17 15 13 11
B 20 18 16 14 12 19 17 15 13 11
20 18 16 14 12
10 8 6 4 2
A 10 8 6 4 2 9 7 5 3 1
9 7 5 3 1
320
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.12 FX2N-8EYT-H (Transistor Output)
11
16.12 FX2N-8EYT-H (Transistor Output)
Counters
High-Speed
16.12.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapter.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Extension Units
Powered
IInput/Output
Output points 8 points
Connection unit Removable terminal block (M3 screws)
Output unit/type Transistor/sink output
External power supply 5 to 30V DC
Output circuit insulation method Photo-coupler insulation 16
Indication of output operation Activation of the photo-coupler will light the LED indicator lamp on panel.
Blocks
Extension
Input/Output
1A/point
Resistance
The total load current per common should be as follows:
Maximum load load
• 4 output points/common: 2A or less
Inductive load 24W/24V DC
Open circuit leakage current 0.1 mA/30V DC 17
Unit
Power Supply
Extension
Minimum load −
OFF→ON 0.2 ms or less/1A
Response time
ON→OFF 0.4 ms or less/1A
Load
Y 18
Fuse
Options
Units and
Other Extension
COM1
Output circuit diagram DC power
supply unit
Y
Fuse
COM2
DC power 19
supply unit
Display Module
20
Terminal Block
321
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.12 FX2N-8EYT-H (Transistor Output)
COM1 Y1 Y3
Y0 Y2
COM1 Y1
Y0 Y2
FX2N-8EYT-H FX2N-
Y3
OUT 0 1 2 3
OUT
4 5 6 7
lamps 4 5 6 connector
(LED lamps)
COM2 Y5
Y4 Y6
Y7
COM2 Y5
Y4 Y6
Y7
16.12.3 External dimensions
FX2N-8EYT-H
80(3.15")
90(3.55")
POWER
OUT 0 1 2 3
4 5 6 7
9(0.36")
43(1.7") 87(3.43")
322
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.13 FX2N-16EYS (Triac Output: 16 Points)
11
16.13 FX2N-16EYS (Triac Output: 16 Points)
Counters
High-Speed
16.13.1 Product specifications
The generic specifications are identical to the main unit specifications. 12
→ Refer to Section 4.1 for generic specifications.
Output Wiring
For external wiring, refer to the following chapter.
→ Refer to Chapter 12 for output wiring.
Various Uses
Wiring for
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Troubleshooting
Maintenance,
Test Run,
• The extension cable is already connected to the extension block.
Other • Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Extension Units
Powered
IInput/Output
Output points 16 points
Connection unit Vertical terminal block (M3 screws)
Output unit Triac output (SSR)
External power supply 85 to 242V AC
Output circuit insulation method Photo-coupler insulation 16
Indication of output operation Activation of the photo-thyristor will light the LED indicator lamp on panel.
Blocks
Extension
Input/Output
0.3 A/point
Resistance
The total load current per common should be as follows:
Maximum load load
• 8 output points/common: 0.8A or less
Inductive load 15 VA/100V AC, 30 VA/200V AC
Open circuit leakage current 1 mA/100V AC, 2 mA/200V AC 17
Unit
Power Supply
Extension
Minimum load 0.4 VA/100V AC, 1.6 VA/200V AC
OFF→ON 1 ms or less
Response time
ON→OFF 10 ms or less
18
Options
Units and
Other Extension
Load
Y
COM
AC power
supply 19
Display Module
20
Terminal Block
323
FX3U Series Programmable Controllers 16 FX2N-8/16E*-*(Input/Output Extension Blocks)
User’s Manual - Hardware Edition 16.13 FX2N-16EYS (Triac Output: 16 Points)
COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Output indicator
COM1 Y1 Y3
Y0 Y2 Y4
Y0
lamps
Y2 Y4
(LED lamps)
Y5
Rear line
Y6
Lower
Y7
extension
numbers
Y0
connector
Y1
Y2
Y3 Y5
Output indicator
Y4
lamps
Y6 COM2
Y7
(LED lamps)
Y2 Y4 Y6 COM2
Higher
numbers
90(3.55")
9(0.36")
40(1.58") 87(3.43")
324
FX3U Series Programmable Controllers 17 FX3U-1PSU-5V (Extension Power Supply Unit)
User’s Manual - Hardware Edition 17.1 Introduction
11
Counters
High-Speed
17. FX3U-1PSU-5V (Extension Power Supply Unit)
12
DESIGN PRECAUTIONS
Output Wiring
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
13
Various Uses
Wiring for
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 14
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Troubleshooting
Maintenance,
Test Run,
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case. 15
Extension Units
Powered
IInput/Output
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line. 16
Noise may cause malfunctions.
Blocks
Extension
Input/Output
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
17.1 Introduction 17
Unit
Power Supply
Extension
When the internal power supplied from the FX3U Series PLC (AC power supply type) is insufficient for powering
output extension blocks or special function blocks, the FX3U-1PSU-5V (extension power supply unit) is available.
Up to two units of FX3U-1PSU-5V may be connected in one system.
Connect extension equipment to the FX3U-1PSU-5V according to the configuration specification limits described
in Subsection 17.2.2. 18
→ For the system configuration with FX3U-1PSU-5V, refer to Chapter 6.
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
325
FX3U Series Programmable Controllers 17 FX3U-1PSU-5V (Extension Power Supply Unit)
User’s Manual - Hardware Edition 17.2 Specifications
17.2 Specifications
Items Specifications
Supply voltage 100-240V AC
Allowable supply voltage range 85-264V AC
Rated frequency 50/60Hz
The allowable momentary power failure time depends on the
power supply used.
• 100V AC power supply system:
The operation is continued to the momentary power failure
Allowable instantaneous power failure time
for 10 or less ms.
• 200V AC power supply system:
The operation is continued to the momentary power failure
for 100 or less ms.
Rush current 30A max. 5ms or less/100V AC, 65A max. 5ms or less/200V AC
Power consumption 20W Max.
*1. The output current is restricted, depending on the ambient temprature. For details, refer to the derating
curve in Section 6.7.
90(3.55")
4(0.16") 9(0.36")
55(2.17") 87(3.43")
3. Grounding and power cables should be positioned to exit the unit from above.
→ For details, refer to Subsection 9.5.4 and 9.5.5.
326
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
Counters
High-Speed
18. Other Extension Devices and Optional Units
(External Dimensions and Terminal Arrangement)
12
Output Wiring
18.1 Special Function Units/Blocks
18.1.1 FX0N-3A
13
Various Uses
Wiring for
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.2kg (0.44lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Troubleshooting
Maintenance,
Test Run,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
15
4(0.16")
Extension Units
Powered
IInput/Output
87(3.43")
43(1.7")
Terminal Layout
VIN2 IIN2 COM2 VOUT
VIN1 IIN1 COM1 IOUT COM 16
Blocks
Extension
Input/Output
18.1.2 FX2N-2AD
17
Unit
Power Supply
Extension
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.2kg (0.44lbs)
•Installation: DIN rail of 35 mm (1.38") in
(mounting hole pitch)
width or screws
•Accessories: Label for indication of special 18
80(3.15")
90(3.55")
unit/block number,
Options
Units and
Other Extension
9(0.36")
the extension block
19
4(0.16")
Display Module
43(1.7") 87(3.43")
Terminal Layout
VIN2 IIN2 COM
VIN1 IIN1 COM 20
Terminal Block
327
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.3 FX2N-2DA
External Dimensions
•MASS(Weight): 0.2kg (0.44lbs)
2-φ4.5 mounting holes Unit:mm (inches)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
4(0.16") 9(0.36")
43(1.7") 87(3.43")
Terminal Layout
18.1.4 FX3U-4AD
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.2kg (0.44lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Dust Proof sheet,
FX3U-4AD
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout
24- V+ I+ V+ I+ V+ I+ V+ I+
24+ VI- FG VI- FG VI- FG VI-
CH1 CH2 CH3 CH4
328
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.5 FX3U-4DA
Counters
High-Speed
External Dimensions
Output Wiring
(mounting hole pitch)
•Accessories: Label for indication of special
unit/block number,
90(3.55")
80(3.15")
Dust Proof sheet,
Manual supplied with product
FX3U-4DA
•Terminal block: M3 screws 13
Various Uses
Wiring for
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
14
Troubleshooting
Maintenance,
Test Run,
Terminal Layout
24- V+ I+ V+ I+ V+ I+ V+ I+
24+ VI- VI- VI- VI-
CH1 CH2 CH3 CH4
15
Extension Units
Powered
IInput/Output
18.1.6 FX2N-4AD
External Dimensions
16
Blocks
Extension
Input/Output
•MASS(Weight): 0.3kg (0.66lbs)
2-φ4.5 mounting holes Unit:mm (inches)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
Unit
Power Supply
Extension
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36") 18
Options
Units and
Other Extension
55(2.17") 87(3.43")
Terminal Layout
24- V+ I+
24+ VI-
V+ I+ V+
FG VI- FG
I+ V+ I+
VI- FG VI-
19
Display Module
20
Terminal Block
329
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.7 FX2N-4DA
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout
24- V+ I+ V+ I+ V+ I+ V+ I+
24+ VI- VI- VI- VI-
CH1 CH2 CH3 CH4
18.1.8 FX2N-4AD-PT
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout
24- I- L- I- L- I- L- I- L-
24+ L+ FG L+ FG L+ FG L+
CH1 CH2 CH3 CH4
330
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.9 FX2N-4AD-TC
Counters
High-Speed
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in 12
width or screws
Output Wiring
•Accessories: Label for indication of special
80(3.15")
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
13
Various Uses
Wiring for
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout 14
Troubleshooting
Maintenance,
Test Run,
24- SLD L- SLD L- SLD L- SLD L-
24+ L+ L+ L+ L+
CH1 CH2 CH3 CH4
15
Extension Units
Powered
IInput/Output
18.1.10 FX2N-5A
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs) 16
Blocks
Extension
Input/Output
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
17
Unit
Power Supply
Extension
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
18
Terminal Layout
Options
Units and
Other Extension
20
Terminal Block
331
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.11 FX2N-2LC
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
80(3.15")
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout
TC- TC-
24- OUT1OUT2 CT FG PTB CT FG PTB
TC+ TC+
24+ COM CT PTA PTB CT PTA PTB
CH1 CH2
18.1.12 FX2N-8AD
External Dimensions
2-φ4.5 mounting holes •MASS(Weight): 0.4kg (0.88lbs)
Unit:mm (inches)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
67(2.64") 8(0.32")
(mounting hole pitch)
75(2.96") 75(2.96")
Terminal Layout
332
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.13 FX2N-1HC
Counters
High-Speed
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in 12
width or screws
Output Wiring
•Accessories: Label for indication of special
80(3.15")
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
13
Various Uses
Wiring for
the extension block
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout 14
Troubleshooting
Maintenance,
Test Run,
A24+ A5+ B24+ B5+ XD24 XP24 XP5 YH+ YS+
A12+ A- B12+ B- XD5 COMD COMP YH- YS-
15
Extension Units
Powered
IInput/Output
18.1.14 FX3U-20SSC-H
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches)
•MASS(Weight): 0.3kg (0.66lbs) 16
Blocks
Extension
Input/Output
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
unit/block number,
80(3.15")
Unit
Power Supply
Extension
Manual supplied with product
4(0.16") •Terminal block: Connector
9(0.36")
55(2.17") 87(3.43") •The extension cable is already connected to
the extension block
18
Terminal Layout
Options
Units and
Other Extension
X-INT0 Y-INT0
NC NC
X-INT1 Y-INT1
X-φA+
X-φA-
Y-φA+
Y-φA-
Notch
19
Display Module
X-φB+ Y-φB+
X-φB- Y-φB-
X-DOG Y-DOG
S/S S/S
X-START Y-START
20
Terminal Block
333
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.15 FX2N-1PG(-E)
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •installation: DIN rail of 35 mm (1.38") in
width or screws
•Accessories: Label for indication of special
4(0.16") 9(0.36")
43(1.7") 87(3.43")
Terminal Layout
18.1.16 FX2N-10PG
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight):0.2kg (0.44lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: Connector
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
43(1.7") 74(2.92")
87(3.43")
Terminal Layout
VIN+ VIN-
FP+ FP-
RP+ RP-
PG0+ PG0-
CLR+ CLR-
Notch
φA+ φA-
φB+ φB-
DOG START
S/S S/S
X0 X1
334
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.17 FX2N-10GM
Counters
High-Speed
External Dimensions
Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35mm (1.38") in 12
width only can be used for
Output Wiring
90(3.55") installation
•Accessories: FX2NC-100MPCB power
cable, FX2N-GM-5EC
extension cable, label for
indication of special unit/
block number, Manual
13
Various Uses
Wiring for
supplied with product
60(2.37") 13(0.52") 74(2.92")
•Terminal block: Connector
Terminal Layout
CON1 CON2 14
START X0 SVRDY SVEND
Troubleshooting
Maintenance,
Test Run,
STOP X1 COM2 COM2
ZRN X2 CLR PG0
FWD X3 COM3 COM4
RVS Y0
Notch
DOG
LSF
Y1
Y2
FP
VIN
RP
VIN
15
Extension Units
Powered
IInput/Output
LSR Y3 VIN VIN
COM1 COM1 COM5 COM5
Y4 Y5 ST1 ST2
18.1.18 FX2N-20GM 16
Blocks
Extension
Input/Output
External Dimensions
Unit:mm (inches) •MASS(Weight): 0.4kg (0.88lbs)
•Installation: DIN rail of 35mm (1.38") in
width only 17
•Accessories: FX2NC-100MPCB power
Unit
Power Supply
Extension
90(3.55")
cable, FX2NC-100BPCB
power cable, FX2N-GM-5EC
extension cable, label for
indication of special unit/
block number,
Manual supplied with product
18
Options
Units and
Other Extension
Terminal Layout
CON1 Y axis CON2 X axis CON3 (X axis) CON4 (Y axis)
Y00 X00 START START SVRDY SVEND SVRDY SVEND 19
Y01 X01 STOP STOP COM2 COM2 COM6 COM6
Display Module
335
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.19 FX2N-1RM(-E)-SET
External Dimensions
FX2N-1RM Unit:mm (inches) •MASS(Weight): 0.5kg (1.1lbs)
2-φ4.5 mounting holes •Installation: DIN rail of 35 mm (1.38") in
width or screws
(0.83")
21
•Accessories: FX2N-RS-5CAB signal cable
(5m(16’4")), F2-720RSV
111(4.38")
80(3.15")
90(3.55")
indication of special unit/
block number, Manual
supplied with product
•Terminal block: M3 screws
9 50 4 30
(0.36") (1.97") (0.16") (1.19")
97(3.82") 55(2.17")
Unit:mm (inches)
4-φ4.5 mounting holes
(0.38") 45(1.78")
φ40
φ33.32
φ10
0
φ5
(0.56") (1.78")
10
14 45
9.5
(0.4")
3 4
(0.12") (0.16")
9.5(0.38") 28 60
45(1.78") (1.11") (2.37")
Terminal Layout
336
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.20 FX2N-232IF
Counters
High-Speed
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.3kg (0.66lbs)
•Installation: DIN rail of 35 mm (1.38") in 12
width or screws
Output Wiring
•Accessories: Label for indication of special
80(3.15")
90(3.55")
unit/block number,
Manual supplied with product
•Connector: RS-232C
(D-SUB 9-pin, male) 13
Various Uses
Wiring for
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36")
55(2.17") 85(3.35")
Terminal Layout 14
1 CD(DCD)
Troubleshooting
Maintenance,
Test Run,
2 RD(RXD)
5
9 3 SD(TXD)
4
8 4 ER(DTR)
3
7 5 SG
2
1 6 6
7
DR(DSR)
RS(RTS)
15
Extension Units
Powered
IInput/Output
8 CS(CTS)
9 CI(RI)
18.1.21 FX2N-32ASI-M
16
External Dimensions
Blocks
Extension
Input/Output
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.2kg (0.44lbs)
•installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Unit
Power Supply
Extension
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
the extension block
4(0.16") 9(0.36") 18
55(2.17") 87(3.43")
Options
Units and
Other Extension
Terminal Layout
ASI+ ASI- 19
ASI+ ASI-
Display Module
20
Terminal Block
337
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
18.1.22 FX2N-64CL-M
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.15kg (0.33lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch) •Accessories: Label for indication of special
80(3.15")
18.1.23 FX2N-16CCL-M
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.4kg (0.88lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
90(3.55")
unit/block number,
Terminal resistor:
2 resistors for standard cable
2 resistors for high-
performance cable,
Manual supplied with product
75(2.96") 9(0.36") •Terminal block: M3 screw for power supply
(mounting hole pitch) 87(3.43") terminal
85(3.35") M3.5 screw for signal
terminal
•The extension cable is already connected to
the extension block
Terminal Layout
24-
24+ FG SLD DG DA DB
338
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.1 Special Function Units/Blocks
11
18.1.24 FX2N-32CCL
Counters
High-Speed
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 0.2kg (0.44lbs)
•Installation: DIN rail of 35 mm (1.38") in 12
width or screws
Output Wiring
80(3.15") •Accessories: Label for indication of special
90(3.55")
unit/block number,
Manual supplied with product
•Terminal block: M3 screws
•The extension cable is already connected to
13
Various Uses
Wiring for
the extension block
4(0.16") 9(0.36")
43(1.7") 87(3.43")
Terminal Layout 14
Troubleshooting
Maintenance,
Test Run,
24- DA DB DG
24+ FG DA DB SLD
15
Extension Units
Powered
IInput/Output
18.1.25 FX2N-16LNK-M
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •Installation: DIN rail of 35 mm (1.38") in
16
Blocks
Extension
Input/Output
width or screws
•Accessories: Label for indication of special
(mounting hole pitch)
unit/block number,
Manual supplied with product
80(3.15")
90(3.55")
Unit
Power Supply
Extension
the extension block
4(0.16") 9(0.36")
43(1.7") 87(3.43")
18
Options
Units and
Other Extension
Terminal Layout
24- DG RUNB
24+ DATA RUNA
19
Display Module
20
Terminal Block
339
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.2 Extension Power Supply Unit
18.2.1 FX3U-1PSU-5V
External Dimensions
•MASS(Weight): 0.3kg (0.66lbs)
2-φ4.5 mounting holes Unit:mm (inches)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mouning hole pitch)
90(3.55")
4(0.16") 9(0.36")
55(2.17") 87(3.43")
Terminal Layout
L N
18.3.1 FX3U-4AD-ADP
10 I1+
poles COM1 •Terminal block: European type
106(4.18")
90(3.55")
98(3.86")
V2+
I2+
COM2
V3+
I3+
COM3
7(0.28") 5
74 15.5 15.1(0.6") V4+
poles
(2.92") (0.62") 17.6(0.7") I4+
COM4
340
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.3 Special Adapters
11
18.3.2 FX3U-4DA-ADP
Counters
High-Speed
External Dimensions, Terminal Layout
•MASS(Weight): 0.1kg (0.22lbs)
24+
12
2-φ4.5 mounting holes Unit:mm (inches)
24- •Installation: DIN rail of 35 mm (1.38") in
width or screws
Output Wiring
V1+ •Accessories: Manual supplied with product
106(4.18")
poles
90(3.55")
98(3.86")
V2+
I2+
COM2
13
Various Uses
Wiring for
V3+
I3+
COM3
7(0.28") 5
74 15.5 15.1(0.6") V4+
(2.92") (0.62") 17.6(0.7") poles
I4+
COM4 14
Troubleshooting
Maintenance,
Test Run,
18.3.3 FX3U-4AD-PT-ADP
Extension Units
Powered
IInput/Output
24- •Installation: DIN rail of 35 mm (1.38") in
width or screws
L1+
•Accessories: Manual supplied with product
(mounting hole pitch)
10 L1-
poles I1- •Terminal block: European type
106(4.18")
16
90(3.55")
98(3.86")
L2+
L2-
Blocks
Extension
Input/Output
I2-
L3+
L3-
I3-
5
17
7(0.28")
74 15.5 15.1(0.6") L4+
poles
(2.92") (0.62") 17.6(0.7") L4-
Unit
Power Supply
Extension
I4-
18.3.4 FX3U-4AD-TC-ADP
J-type
90(3.55")
98(3.86")
Display Module
J-type
L1+
L1-
L2+
L2-
7(0.28") L3- 20
74 15.5 15.1(0.6") 5
L3-
Terminal Block
341
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.3 Special Adapters
18.3.5 FX3U-232ADP
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 80g (0.18lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
106(4.18")
•Connector: RS-232C
90(3.55")
98(3.86")
(D-SUB 9-pin, male)
7(0.28") 74 7.5
15.1(0.6")
(0.3")
(2.92") 17.6(0.7")
Terminal Layout
1 CD(DCD)
2 RD(RXD)
5
9 3 SD(TXD)
4
8 4 ER(DTR)
3
7 5 SG(GND)
2
6 6 DR(DSR)
1
7 Not used
8 Not used
9 Not used
18.3.6 FX3U-485ADP
External Dimensions
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 80g (0.18lbs)
•Installation: DIN rail of 35 mm (1.38") in
width or screws
(mounting hole pitch)
7(0.28")
74 15.5 15.1(0.6")
(2.92") (0.62") 17.6(0.7")
Terminal Layout
342
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.3 Special Adapters
11
18.3.7 FX3U-4HSX-ADP
Counters
High-Speed
External Dimensions, Terminal Layout
2-φ4.5 mounting holes Unit:mm (inches) •MASS(Weight): 80g (0.18lbs)
•Installation: DIN rail of 35 mm (1.38") in 12
X0/3+ width or screws
Output Wiring
(mounting hole pitch)
X0/3-
•Accessories: Manual supplied with product
X1/4+
106(4.18")
90(3.55")
98(3.86")
X1/4- •Terminal block: European type
10 X2/5+
poles X2/5-
X6/7+ 13
X6/7-
Various Uses
Wiring for
SG
SG
7(0.28") 15.1(0.6")
74 15.5 17.6(0.7")
(2.92") (0.62") 14
Troubleshooting
Maintenance,
Test Run,
18.3.8 FX3U-2HSY-ADP
Extension Units
Powered
IInput/Output
Y0/2+ width or screws
(mounting hole pitch)
Y0/2-
•Accessories: Manual supplied with product
Y4/6+
106(4.18")
Blocks
Extension
Input/Output
Y5/7+
Y5/7-
SGB
7(0.28") 15.1(0.6")
74
(2.92")
15.5
(0.62")
17.6(0.7")
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
343
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.4 Expansion Board
18.4.1 FX3U-USB-BD
External Dimensions
2-φ3.2 •MASS(Weight): 20g (0.05lbs)
mounting holes Unit:mm (inches)
•Accessories: Two M3 tapping screws (for
46.1(1.82") installation of board), USB
driver software (CD-ROM),
USB cable (3m(9’10")),
Manual supplied with product
•Connector: USB (MINI B connector,
female)
53.5(2.11") 19.6
(0.78")
18.4.2 FX3U-232-BD
External Dimensions
2-φ3.2 •MASS(Weight): 20g (0.05lbs)
mounting holes Unit:mm (inches)
•Accessories: Two M3 tapping screws (for
installation of board),
Manual supplied with product
46.1(1.82")
•Connector: RS-232C
(D-SUB 9-pin, male)
Terminal Layout
1 CD(DCD)
2 RD(RXD)
1
6 3 SD(TXD)
2
7 4 ER(DTR)
3
8 5 SG(GND)
4
9 6 DR(DSR)
5
7 Not used
8 Not used
9 Not used
18.4.3 FX3U-422-BD
External Dimensions
2-φ3.2 •MASS(Weight): 20g (0.05lbs)
mounting holes Unit:mm (inches)
•Accessories: Two M3 tapping screws (for
installation of board),
Manual supplied with product
46.1(1.82")
•Connector: RS-422
(MINI DIN 8-pin, female)
53.5(2.11") 19.6
(0.78")
344
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.4 Expansion Board
11
18.4.4 FX3U-485-BD
Counters
High-Speed
External Dimensions
2-φ3.2 •MASS(Weight): 20g (0.05lbs)
Unit:mm (inches)
12
mounting holes
•Accessories: Two M3 tapping screws (for
installation of board),
Output Wiring
46.1(1.82")
Label for indication of link
station number,
Manual supplied with product
•Terminal block: European type
19.6 •Terminal resistance:330Ω/110Ω, built-in 13
53.5(2.11") 15.5
Various Uses
Wiring for
(0.62") (0.78")
69.0(2.72")
Terminal Layout
Troubleshooting
Maintenance,
Test Run,
SDB OPEN
SG 110Ω
18.4.5 FX3U-CNV-BD 15
Extension Units
Powered
IInput/Output
External Dimensions
2-φ3.2 •MASS(Weight): 10g (0.03lbs)
mounting holes Unit:mm (inches)
•Accessories: Two M3 tapping screws (for
installation of board),
16
46.1(1.82")
Blocks
Extension
Input/Output
53.5(2.11") 19.6
(0.78") 17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
345
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.5 Power Supply
18.5.1 FX2N-20PSU
External Dimensions
2-φ4.5 •MASS(Weight): 0.3kg (0.66lbs)
(0.3")
7.5
mounting holes Unit:mm (inches) •Installation: DIN rail of 35 mm (1.38") in
4(0.16") width or screws
•Accessories: Manual supplied with product
(mounting hole pitch) •Terminal block: M3 screws
90(3.55")
98(3.86")
Terminal Layout
L N
24V+ 24V-
24V+ 24V-
18.6.1 FX2N-CNV-BC
External Dimensions
2-φ3.2 •MASS(Weight): 40g (0.09lbs)
mounting holes Unit:mm (inches)
•Installation: Screws only
30(1.19")
40(1.58")
60.5(2.39")
(0.65")
16.4
346
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.7 Interface Module
11
18.7 Interface Module
Counters
High-Speed
18.7.1 FX-232AWC-H
External Dimensions
12
Output Wiring
Unit:mm (inches) •MASS(Weight): 0.1kg (0.22lbs)
•Accessories: Manual supplied with product
•Connector: RS-232C
MITSUBISHI (D-SUB 25-pin, female)
POWER
RS-422 13
60(2.37") (D-SUB 25-pin, female)
Various Uses
Wiring for
CONPUTER
(RS232C)
(RS422)
FX
FX-232AWC-H
14
80(3.15") 25
Troubleshooting
Maintenance,
Test Run,
(0.99")
18.7.2 FX-USB-AW
15
External Dimensions
Extension Units
Powered
IInput/Output
•MASS(Weight): 20g (0.05lbs)
Unit:mm (inches)
•Accessories: USB driver software
(CD-ROM),
(0.6")
15
Blocks
Extension
Input/Output
•Connector: RS-422
(MINI DIN 8-pin, male)
MITSUBISHI
(0.83")
FX-USB-AW
21
FX
PW
RD
SD
female)
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
347
FX3U Series Programmable Controllers 18 Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)
User’s Manual - Hardware Edition 18.8 Display Module
18.8.1 FX3U-7DM
External Dimensions
Unit:mm (inches) •MASS(Weight): 20g (0.05lbs)
35 (1.38")
•Accessories: Display module mounting top
cover,
Manual supplied with product
11.5 Approx.
48 (1.89") (0.46") 8.5 (0.34")
18.8.2 FX3U-7DM-HLD
External Dimensions
70 (2.76") Unit:mm (inches) •MASS(Weight): 20g (0.05lbs)
53 (2.09")
•Accessories: PLC cover,
Mounting bracket × 2 pieces,
Tightening bolt
(M4 × 25) × 2 pieces,
Mounting Extension cable with ferrite
bracket core (1.4m(4’7")),
Display module fixing hooks Clamp A × 5 pieces,
59 (2.33") Clamp B × 1 piece,
5 (0.2") 49 (1.93") Guides 4 28 (1.11") Cable tie × 1 piece,
(0.16")
Manual supplied with product
36 (1.42")
46 (1.82")
40 (1.58")
5 (0.2")
348
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition
11
Counters
High-Speed
19. FX3U-7DM (Display Module)
12
Output Wiring
STARTUP AND MAINTENANCE
PRECAUTIONS
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
• Before cleaning or retightening terminals externally cut off all phases of the power supply. 13
Failure to do so may cause electric shock.
Various Uses
Wiring for
• Make sure to connect the battery for memory backup correctly.
Do not charge, disassemble, heat, short-circuit, or expose the battery to fire.
Doing so may rupture or ignite it.
• Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual
and the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents. 14
• Do not change the program in the PLC from two or more peripheral equipment devices at the same time.
Troubleshooting
Maintenance,
Test Run,
(i.e. from a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
Extension Units
Powered
IInput/Output
• Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is
attached or detached while the PLC's power is on, the data in the memory may be destroyed, or the memory
cassette may be damaged.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric distributor. 16
• Turn off the power to the PLC before connecting or disconnecting any extension cable.
Blocks
Extension
Input/Output
Failure to do so may cause equipment failures or malfunctions.
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- Display module, peripheral devices, expansion boards, and special adapters
- Connector conversion adapter, extension blocks, and FX Series terminal blocks
- Battery and memory cassette 17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
349
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.1 Description of Products (Introduction of Related Products)
Optional Optional
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
IN
10 11 12 13 14 15 16 17
POWER
POWER
RUN
BATT
ERROR
ERROR
FX3U-48MR/ES 0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
OUT
10
0 11
1 12
2 133 14
4 15
5 166 17
7 20 21 22 23 24 25 26 27
FX 3U-48M
10 11 12 13 14 15 16 17
Y0 Y2 ・ Y4 Y6 ・ Y10 Y12 ・ Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27
FX3U PLC
For a detailed description of the display module holder, refer to the "FX3U-7DM-HLD User’s Manual".
350
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.2 Specifications
11
19.2 Specifications
Counters
High-Speed
19.2.1 Display/switch specifications
Item Description 12
Output Wiring
Display device/ backlight STN monochrome liquid crystal display/Backlight: LED (green)
Number of letters 16 letters × 4 lines (2 byte letters: 8 letters × 4 lines)
Displaed
Characters English Alphabet, Numbers, Japanese Characters, Shift JIS Level-1, 2
letters
Language for menu display Japanese/English
Button 4 operation buttons (OK, ESC, +, and -) 13
Various Uses
Wiring for
Notes for displaying symbols(ASCII Code)
• (ASCII Code:5C) symbol is displayed as " " even if the language display setting at FX3U-7DM is set to
English(LANGUAGE:ENGLISH).
• The Character at ASCII Code:7E "~" is not displayed.
14
19.2.2 Parts layout
Troubleshooting
Maintenance,
Test Run,
Liquid crystal screen
ESC button
15
"-" button
Extension Units
Powered
IInput/Output
"+" button
OK button
Blocks
Extension
Input/Output
Name of button Function of operation button
ESC Use this button to cancel the operation and to return to the previous screen.
- Use this button to move the cursor or to set a numeric value.
+ Use this button to move the cursor or to set a numeric value. 17
OK Use this button to select an item or to determine the set numeric value.
Unit
Power Supply
Extension
19.2.3 External dimensions
Unit:mm (inches)
18
35(1.38")
Options
Units and
Other Extension
351
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.3 Installation and Removal
Enlarged view
The top cover of the display module is supplied with the FX3U-7DM
(display module).
352
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.4 Summary of Functions
11
19.4 Summary of Functions
Counters
High-Speed
The display module functions are summarized below.
Item Function Remarks Reference
Output Wiring
Menu screen functions
Input (X)*1, output (Y), auxiliary relay (M), state (S),
Devices timer (T), counter (C), data register (D) [16-bit/32-bit], Button Section 19.7
extended register (R), and extended file register (ER) operation
Monitor/Test
User
[16-bit/32-bit] monitor/test function.
13
Various Uses
Wiring for
(User- Up to 4 data registers (D) [16-bit/32-bit] can be Requires Section 19.8 and
registered registered. program Section 19.19
device)
Button
ErrorCheck Performs error checks and displays the results. Section 19.9
operation
LANGUAGE (selects the Selects either Japanese or English as the menu Button 14
Section 19.10
menu display language) display language. operation
Troubleshooting
Maintenance,
Test Run,
Button
Contrast Adjusts the contrast (-5 to 10); default setting: 0 Section 19.11
operation
ClockMenu Setting Sets the current time. Button Subsection 19.12.1
(Time setting) operation
Display Displays the current time.
Button
Subsection 19.12.2
15
EntryCode The currently specified entry code can be canceled. Section 19.13
Extension Units
Powered
IInput/Output
operation
Initializes the Input (X)*1, output (Y), auxiliary relay
(M), state (S), timer (T), counter (C), data register (D)
ClearAllDev [16-bit/32-bit], and extended register (R). The file Button
Section 19.14
(Device all clear) register (D) is excluded from this function. (Bit operation
devices are turned OFF, and word device current 16
values are set to "0".)
Blocks
Extension
Input/Output
Verifies the version information, entry code status, Button
PLC Status Section 19.15
program memory type status, and battery voltage, etc. operation
Button
ScanTime Displays the scan time (max./min./current value) Section 19.16
operation
Cassette Allows data transfers (and consistency checks) Button
Section 19.17
17
(Memory cassette transfer) between the internal RAM and the memory cassette. operation
Unit
Power Supply
Extension
Non-menu functions
Requires
Operation button ON/OFF
Allows monitoring of operation button ON/OFF status. program or Section 19.20
information
monitor
Changes the display format of the current values and 18
Hexadecimal current value setting values for the timer, counter, data register, Requires
Options
Units and
Other Extension
Section 19.21
display setting extended register, and extended file register to a program *2
hexadecimal display format.
Display screen protect Enables all functions, prohibits change (test) Requires
Section 19.22
function functions, and protects the top screen (time display). program
The following codes saved at the display device can 19
be used as display commands:
Requires
Display Module
User message display Alphanumeric: 20H to 7DH ASCII code Section 19.23
program
Katakana: A1H to DFH ASCII code
Japanese character: Shift JIS Level-1, 2
353
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.5 Procedure for Accessing the Menu Screen from the Title Screen
19.5 Procedure for Accessing the Menu Screen from the Title Screen
All operation explanations and display screen examples in this manual are in English. When the menu display
language is set to Japanese, please convert the screen messages to their Japanese translations.
→ Refer to Section 19.25 for the Japanese & English display character correspondence table.
→ Refer to Section 19.10 for menu display language setting.
A user screen can also be displayed by using the user message display function.
→ Refer to Section 19.23 for user message display function.
Although the year displays in a 2-digit format (05), this can be changed to a 4-digit format (2005) by revising
the program.
→ Refer to Subsection 19.12.3 for the 2-digit year to 4-digit year change procedure.
354
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.6 Menu Structure
11
19.6 Menu Structure
Counters
High-Speed
Title screen
Operation keys
ME L S E C - F OK Press the [OK] button 12
FX3U Se r i e s ESC
Output Wiring
Press the [ESC] button
Ve r . 2 . 00
- + The [+] / [-] button are used to move
the cursor and switch between display
screens.
Approx. 1.5 secs.
Top screen (Time display) Menu screen 13
Various Uses
Wiring for
OK Mo n i t o r / T e s t OK D( 16b i t )
31 . 5 . 05 ESC ESC DD ( 3 2 b i t )
23 : 59 : 59 [ Tue ] T
C
R( 16b i t ) 14
Troubleshooting
Maintenance,
Test Run,
Switched by system information setting DR ( 3 2 b i t )
ER ( 1 6 b i t )
User message display function DER ( 3 2 b i t )
<P r o d u c t i o n> OK X
Ta r ge t 10000 ESC Y 15
Pr oduc t i on 100 M
Extension Units
Powered
IInput/Output
R ema i n i n g 9900 S
Display example
E r r o r Ch e c k OK E r r o r Ch e c k
16
Blocks
Extension
Input/Output
ESC No e r r o r s
17
OK
Unit
Power Supply
Extension
L A NGU A G E L A NG U A G E
ESC
Eng l i s h
18
Display example
Options
Units and
Other Extension
Co n t r a s t OK Co n t r a s t
ESC 0
( - 5 ~ 10 )
19
Display Module
C l o c kMe n u OK Cu r r e n t t i me
ESC Cl ock Se t t i ng
20
Terminal Block
355
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.6 Menu Structure
Display example
En t r yCo d e OK The En t r y Co d e
ESC I s no t se t
C l e a r A l l De v OK Cl ea r
ESC a l l dev i ces
OK Execu t e
ESC Ca n c e l
Display example
PLC S t a t u s OK PLC S t a t u s ( 1 / 3 )
ESC Ve r . 2 . 0 0
The En t r y Co d e
i s no t se t
- +
Display example
ESC PLC S t a t u s ( 2 / 3 )
Memo r y casse t t e
Pr o t ec t i on OF F
Ca p a c i t y 64K
- +
Display example
ESC PLC S t a t u s ( 3 / 3 )
Ba t t e r y 2 . 9V
C o mm e n t s
0 / 0
Display example
S c a n T i me OK S c a n T i me
ESC Cu r r : 0 . 5ms
Ma x : 0 . 8ms
Mi n : 0 . 3ms
Display example
Ca s s e t t e OK Memo r y Ca s s e t t e
ESC C a s s e t t e R AM
Ca s s e t t e R AM
C a s s e t t e : R AM
356
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
11
19.7 Monitor/Test Mode [Excluding User-Registered Devices]
Counters
High-Speed
19.7.1 Relevant devices
Monitoring and testing can be performed from the "Monitor/Test" menu for the devices listed below. 12
(Monitoring/testing is not possible for the file register (D) and the index register (V/Z)).
Output Wiring
: Possible : Possible under certain conditions
: Not possible −: Item not supported by this device
Monitored Items Test Items
Forced Current
Device
Contact Reset
Operation Current Setting
Direction Value Value
ON/ Value
Setting
Change
13
OFF Change
Various Uses
Wiring for
Input [X] − − − − − − −
Output [Y] − − − − *1 − −
Auxiliary relay [M] − − − − *1 − −
State [S]
Timer [T]
− −
−
− − *1 − −
*2*3
14
Troubleshooting
Maintenance,
Test Run,
Counter [C] *4 *2*3
Extension Units
Powered
IInput/Output
Index register (V,Z) − − − − − −
*1. A forced ON or OFF is executed for only one operation cycle, and therefore has a considerable effect
on the SET/RST and self retaining circuits when the PLC is running.
Moreover, a forced ON/OFF result is retained for devices (Y,M,S) which are not being driven by an
OUT instruction, etc., in the program. 16
Blocks
Extension
Input/Output
*2. Setting values of timer and counter can be changed when the PLC status is as shown below.
Program Memory Type RUN/STOP Status Setting Change Enabled/Disabled
RUN Enabled
Internal RAM
STOP Enabled
PROTECT switch ON
RUN Disabled 17
STOP Disabled
Unit
Power Supply
Extension
Memory cassette
RUN Enabled
PROTECT switch OFF
STOP Enabled
*4. The C200 to C255 32-bit up/down counters and the high-speed counters have counting directions.
*5. Enabled only when a memory cassette is installed.
357
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
3) Press [OK] to display the monitor screen for the device which was
selected for monitoring. D 0 0
To cancel the operation and return to the "device selection screen",
D 1 0
press [ESC].
After the power is turned on, the number of the device to be D 2 0
displayed is shown as follows. D 3 0
a) The first time the power is turned on, the display begins with
device No.1.
b) At subsequent power ONs, the device which was being
monitored at the previous operation is displayed (they are saved D 34 0
in memory for each device type). D 35 0
4) Use the [+] and [-] buttons to move the cursor or the screen to the D 36 0
until the device to be monitored is displayed.
D 37 0
→ Refer to Subsection 19.7.3 for status display.
358
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
11
19.7.3 Monitor screen & status display
Counters
High-Speed
→ Refer to Section 19.21 for the procedure used to display the current values as hexadecimal values.
1. Data register [D (16-bit)] / extended register [R (16-bit)] / extended file register [ER (16-bit)]
D 0 0
12
Display Content [1]
Output Wiring
[1] Device No. D 1 0 [2]
[2] Current value D 2 0
D 3 0
2. Data register [DD (32-bit)] / extended register [DR (32-bit)] / extended file register [DER (32-bit)]
13
Various Uses
Wiring for
Display Content
D 1 D 0 [1]
Device No.
[1] [Upper 16-bit device No. (odd number)] 0 [2]
[Lower 16-bit device No. (even number)] D 3 D 2
14
[2] Current value 0
Troubleshooting
Maintenance,
Test Run,
File register (D):
The file register (D) current value cannot be directly monitored at the
display module. 15
Extension Units
Powered
IInput/Output
3. Timer (T)
[2] [3]
Display Content
[1] Device No. T 0 P R 16
Contact image 0 [4]
Blocks
Extension
Input/Output
[2] ON: [5]
1000
OFF: Blank
Reset image
[3] ON:
[1] [2] [3]
OFF: Blank
17
[4] Current value T 1 P R
Unit
Power Supply
Extension
Setting value or device specified by setting value (if an index 0 [4]
[5]
modifier is present, the index register’s device is also displayed).
D 0 [5]
[6] Current value of device specified by setting value.
1000 [6]
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
359
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
4. Counter [C]
[1] [2] [3]
Display Content C0 to C199
[1] Device No. C 0 P R
Contact image 0 [5]
[2] ON: [6]
100
OFF: Blank
Reset image
[3] ON:
[1] [2] [3]
OFF: Blank C0 to C199
Count direction display
C 1 P R
UP count:
[4] 0 [5]
DOWN count: Blank
(32-bit up/down counter and high-speed counter only) D 0 [6]
[5] Current value 1000 [7]
Setting value or device specified by setting value (if an index
[6] [1] [2] [3] [4]
modifier is present, the index register’s device is also displayed). C200 to C255
[7] Current value of device specified by setting value.
C2 0 0 P R U
0 [5]
-1 [5]
[6]
360
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
11
19.7.4 Test mode operation
Counters
High-Speed
There are 3 types of test mode operations, depending on the device type. The 3 operations are explained
below.
→ Refer to Subsection 19.7.1 for test mode subject devices.
1. Data registers [D: D (16-bit), DD (32-bit)] / extended registers [R: R (16-bit), DR (32-bit) / 12
Output Wiring
extended file registers [ER: ER (16-bit), DER (32-bit)] / user-registered devices
Various Uses
Wiring for
D6 2 0 3 0
2) Hold the [OK] button for 1 second or longer to switch to the test
mode. The current value begins blinking (refer to fig. at right). D6 2 0 0 0
D6 2 0 1 0 14
D6 2 0 2 0
Troubleshooting
Maintenance,
Test Run,
D6 2 0 3 0
Extension Units
Powered
IInput/Output
Cancels the operation and returns to the "monitor D6 2 0 3
ESC
screen".
Reduces the value. Hold for 1 second or longer for high-
-
speed reduction.
+
Increases the value. Hold for 1 second or longer for 16
high-speed increase.
Blocks
Extension
Input/Output
Registers the current value and returns to the "monitor
OK
screen".
4) Press [OK] to register the current value and return to the "monitor screen".
Unit
Power Supply
Extension
The display module’s test function cannot be used to change the current value of the file register (D) which
is stored in the program memory.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
361
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
2) Press the [OK] button to display the cursor, then select the "test
subject selection screen". [Test subject selection screen]
To cancel the operation and return to the "monitor screen", press T 0 P R
[ESC]. 0
1000
4) Hold the [OK] button for 1 second or longer to register the test
subject selection, and switch to the test mode.
T 0 P R
To cancel the operation and return to the "test subject selection
screen", press [ESC]. 0
Test Subject Status when [OK] is hold for 1 second or longer 1000
[1] No change
[2]
Numeric value begins blinking.
[3]
362
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
11
1 Use the [+] / [-] buttons to select the desired setting method (refer to table below), then press [OK]
Counters
High-Speed
to register this selection.
Changeable
Selectable Setting Values Setting Description
Content
Direct setting (without index modifier) The directly specified value becomes the setting
[Direct (K,H)] Direct value. 12
Direct setting (with index modifier) numeral The [directly specified numeicral value] + [index
Output Wiring
[direct (K,H) + index register (V0 to V7, Z0 setting register’s current value] becomes the setting
to Z7)] value.
Indirect setting (without index modifier) The specified device’s current value becomes the
[data register (D), extended register (R)] setting value.
Indirect setting (with index modifier) Indirectly
The [directly specified device No.] + [index
13
[data register (D) + index register (V0 to specified
Various Uses
Wiring for
device No. register’s current value] becomes the device No.
V7, Z0 to Z7)],
specified by the setting value. That device’s
[Extended register (R) + index register (V0
current value becomes the setting value.
to V7, Z0 to Z7)]
Troubleshooting
Maintenance,
Test Run,
Use the [+] / [-] buttons to change the value as desired, then press [OK] to register the changed
value.
- For "indirect setting" or "indirect setting + index register" method:
Use the [+] / [-] buttons to change the device No. as desired, then press [OK] to register the
setting value. 15
6) After the setting operation is completed, return to the "test subject selection screen", where the [ESC]
Extension Units
Powered
IInput/Output
button can then be pressed to return to the "monitor screen".
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
363
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.7 Monitor/Test Mode [Excluding User-Registered Devices]
3. Output [Y] / auxiliary relay [M] / special auxiliary relay [M] / state [S]
Forced ON/OFF operations are possible for the output [Y] / auxiliary relay [M] / special auxiliary relay [M] /
state [S] contacts.
2) Hold the [OK] button for 1 second or longer to switch to the test
mode. The device then begins blinking (refer to figure at right). Y000
To cancel the operation and return to the "test subject selection
Y010
screen", press [ESC].
Y020
Y030
3) Use the [+] / [-] buttons to move the blinking position to the device
where a forced ON/OFF is desired. Y000
To cancel the operation and return to the "monitor screen", press
Y010
[ESC].
Y020
Button Operation Description
Y030
ESC Cancels the operation and returns to the "monitor screen".
Moves in the lower device No. direction (for forced ON/OFF
- subject selection).
Hold for 1 second or longer for high-speed scrolling.
Moves in the higher device No. direction (for forced ON/OFF
+ subject selection).
Hold for 1 second or longer for high-speed scrolling.
OK Highlights the contact’s ON/OFF status.
364
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.8 Monitor/Test Mode [User-Registered Devices]
11
19.8 Monitor/Test Mode [User-Registered Devices]
Counters
High-Speed
Regarding user-registered devices at "Monitor/Test" menu, monitor and test operations can be performed for
a maximum of 4 data registers (16-bit/32-bit) specified by the system information.
→ Refer to Section 19.19 for the user-registered device setting procedure.
12
19.8.1 Monitor mode operation
Output Wiring
1) At the menu screen, use the [+] and [-] buttons to move the cursor
to the "Monitor/Test" item, then press [OK] to display the "device D( 16b i t )
selection screen" shown to the right.
To cancel the operation and return to the "top screen (time
DD ( 3 2 b i t )
T
13
display)", press [ESC] at the menu screen
Various Uses
Wiring for
2) "Use the [+] and [-] buttons to move the cursor to the "User" item. C
To cancel the operation and return to the "device selection screen", R( 16b i t )
press [ESC].
DR ( 3 2 b i t )
ER ( 1 6 b i t )
14
DER ( 3 2 b i t )
Troubleshooting
Maintenance,
Test Run,
X
Y
M
S
Us e r
15
Extension Units
Powered
IInput/Output
3) Press [OK] to display the data registers specified by the system
information. H a l t t i me r [1]
The first time the power is turned on, the display begins with device D 1 0 0 [2]
No.1 of the "user-registered devices". At subsequent power ONs,
10
the device which was being monitored at the previous operation is [3]
16
displayed.
Blocks
Extension
Input/Output
If a specified user-registered device has been changed, the newly
specified device is displayed.
To cancel the operation and return to the "device selection screen", press [ESC].
Display Content
[1]
Device comments (registered at the PLC) are displayed together with the devices. 17
If no device comment has been registered, the device comment area is left blank.
Unit
Power Supply
Extension
[2] Device included in the user-registered devices
[3] Current value
4) Use the [+] and [-] buttons to scroll the user-registered devices
screen.
To cancel the operation and return to the "device selection screen",
18
D 103 D 104
Options
Units and
Other Extension
press [ESC].
0
365
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.9 Error Check
2) Hold the [OK] button for 1 second or longer to switch to the test
mode. The current value then begins blinking (refer to fig. at right). Ha l t t i me r
3) Use the [+] / [-] buttons to change the value as desired. To cancel D 100
the operation and return to the "monitor screen", press [ESC]. 10
Button Operation Description
Cancels the operation and returns to the "monitor
ESC
screen".
Ha l t t i me r
Reduces the value.
- D 100
Hold for 1 second or longer for high-speed reduction.
20
Increases the value.
+
Hold for 1 second or longer for high-speed increase.
Registers the current value and returns to the "monitor
OK
screen".
4) Press [OK] to register the current value and return to the "user registered devices screen".
366
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.10 LANGUAGE (Menu Display Language Setting)
11
19.10 LANGUAGE (Menu Display Language Setting)
Counters
High-Speed
The language used at the display module menus is specified at the "LANGUAGE" menu. The language
setting procedure is described below.
All operation explanations and display screen examples in this manual are in Japanese. When the menu
display language is set to English, please convert the screen messages to their English translations.
→ Refer to Section 19.25 for the Japanese & English display character correspondence table.
12
Output Wiring
19.10.1 Changing to Japanese menus
The procedure for changing from English menus to Japanese menus is described below.
1) Turn the PLC power on.
Following a brief title screen display (1.5 seconds), the "current time
Title screen 13
Various Uses
Wiring for
screen" or a "user message" is displayed. ME L S E C - F
FX3U Se r i e s
Ve r . 2 . 00
Approx. 14
1.5 secs.
Troubleshooting
Maintenance,
Test Run,
Top screen (Time display)
05 . 5 . 31
23 : 59 : 59 [ Tue ]
15
Extension Units
Powered
IInput/Output
or
User creation screen (example)
<P r o d u c t i o n>
Ta r ge t
Pr oduc t i on
10000
100
16
Blocks
Extension
Input/Output
R ema i n i n g 9900
2) Press the [OK] button to display the menu screen shown to the right
(4 lines of the menu display). Monitor/Test
ErrorCheck 17
Unit
Power Supply
Extension
LANGUAGE
Contrast
ClockMenu
EntryCode
ClearAllDev
18
Options
Units and
Other Extension
PLC Status
ScanTime
Cassette
3) At the menu screen, use the [+] / [-] buttons to move the cursor to the
"LANGUAGE" item, then press [OK] to display the "display language
19
L A NGU A G E
Display Module
selection screen".
To cancel the operation and return to the "top screen (time display)",
En g l i s h
press [ESC].
20
Terminal Block
367
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.10 LANGUAGE (Menu Display Language Setting)
4) Use the [+] / [-] buttons to move the cursor to " ".
To cancel the operation and return to the "menu screen", press [ESC].
Button Operation Description
ESC Cancels the operation and returns to the "menu screen".
- Moves the cursor upward.
+ Moves the cursor downward.
OK Registers the selected display language and returns to the "menu screen".
5) Press [OK] to register the selected display language and return to the "menu screen".
3) Press [OK] to register the selected display language and return to the "menu screen".
368
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.11 Contrast
11
19.11 Contrast
Counters
High-Speed
The liquid crystal display contrast setting is specified at the "Contrast" menu. Selections made at this menu
are saved at D8302. A contrast setting of "0" is specified at factory default.
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "Contrast" item, then press [OK] to display the "contrast Co n t r a s t
12
adjustment screen".
Output Wiring
0
To cancel the operation and return to the "top screen (time
display)", press [ESC]. ( - 5 ~ 10 )
Various Uses
Wiring for
[ESC]. 3
( - 5 ~ 10 )
14
Button Operation Description
Troubleshooting
Maintenance,
Test Run,
ESC Cancels the operation and returns to the "menu screen".
Lowers the contrast
-
(decreases the numeric value. The value can be decreased to -5.)
Increases the contrast
+
(increases the numeric value. The value can be increased to +10.) 15
OK Registers the selected setting and returns to the "menu screen".
Extension Units
Powered
IInput/Output
3) Press the [OK] button to register the selected setting and return to the "menu screen".
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
369
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.12 Clock Menu (Current Time Setting)
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "ClockMenu" item, then press [OK] to display the selection Cu r r e n t t i me
screen shown at right. Cl ock se t t i ng
To cancel the operation and return to the "top screen (time
display)", press [ESC].
2) Use the [+] / [-] buttons to move the cursor to the "Clock setting"
item. Cu r r e n t t i me
To cancel the operation and return to the "menu screen", press Cl ock se t t i ng
[ESC].
4) Use the [+] / [-] buttons to change the blinking data as desired, then
press [OK] to register the change. Cl ock se t t i ng
Settings are performed in the following sequence: Year → Month → 31 . 1 . 2004 *
Day → Hours → Minutes → Seconds.
23 : 59 : 59 [ Sa t ]
After pressing [OK] to register the final "seconds" setting, a "Current
time is set" message is displayed, completing the current time
setting procedure. The default "Year" display is a
Button Operation Description 2-digit value indicating the
Western calendar year.
Returns to the previous setting item.
ESC Returns to the "selection screen", when at the "Year"
item ("Year" is blinking) position.
Reduces the value.
-
Hold for 1 second or longer for high-speed reduction.
Increases the value.
+
Hold for 1 second or longer for high-speed increase.
Proceeds to the next setting item.
OK "Current time is set" message displays if pressed at the
"Seconds" item ("Seconds" is blinking).
370
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.12 Clock Menu (Current Time Setting)
11
19.12.2 Displaying the current time
Counters
High-Speed
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "ClockMenu" item, then press [OK] to display the selection Cu r r e n t t i me
screen shown to the right. Cl ock se t t i ng
To cancel the operation and return to the "top screen (time 12
display)", press [ESC].
Output Wiring
2) Use the [+] / [-] buttons to move the cursor to the "Current time"
item. To cancel the operation and return to the "menu screen",
press [ESC].
3) Press the [OK] button to display the current time.
To cancel the operation and return to the "selection screen", press 2-digit display 13
[ESC].
Various Uses
Wiring for
Button Operation Description 31 . 1 . 04
ESC Returns to the "selection screen". 23 : 59 : 59 [ Sa t ]
- Disabled
+
OK
Disabled
Returns to the "selection screen".
4-digit display 14
Troubleshooting
Maintenance,
Test Run,
4) Press [OK] or [ESC] to return to the "selection screen".
31 . 1 . 2004
5) Press [ESC] to return to the "menu screen".
23 : 59 : 59 [ Sa t ]
15
Extension Units
Powered
IInput/Output
19.12.3 Changing the current time’s "Year" from 2-digit format to 4-digit format
The "Year" data displays as 2-digit value with a default. This can be changed to a 4-digit display by the
following programming.
M8002
16
Blocks
Extension
Input/Output
MOV K2000 D8018
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
371
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.13 Entrycodes
19.13 Entrycodes
Entry codes registered at the PLC can be canceled from the "EntryCode" menu.
When canceled, all operations are enabled.
Registering or changing entry codes is not possible at the display module.
The programming tool must be used in advance to register new entry codes.
372
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.13 Entrycodes
11
19.13.2 Level-specific restrictions screen list
Counters
High-Speed
: Function enabled
: Timer and counter setting values cannot be changed.
−: Function disabled
Entry Code: 8 digits
Entry Code: 16 digits 12
Label entered as the first
Selected at GX Developer setting screen
Output Wiring
character at Entry Code input
Function name None
All online Reading/
Writing
A B C operations writing
prohibited
prohibited prohibited
Top screen (time display)
13
Device − −
Various Uses
Wiring for
Monitor/
Test User (User-registered
− −
device)
ScanTime (Scan time display) − −
PLC status − −
ErrorCheck − − 14
Troubleshooting
Maintenance,
Test Run,
User message display
Display screen protect function − − − −
Menu display language setting − −
Contrast adjustment − −
Display 15
Time
Extension Units
Powered
IInput/Output
Setting − −
Entry Code (cancel) −
Clear all device
− −
(Device all-clear)
Memory cassette transfer − − − − 16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
373
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.13 Entrycodes
En t r yCo d e The En t r y Co d e
C l e a r A l l De v i s no t se t
PLC S t a t u s
S c a n T i me
Registered
Entry code If entry code is correct
When switching to menu
prohibited by entry code occurs P l ease , Al l ope r a t i on
i npu t En t r y Co d e i s poss i b l e
Registered 0
En t r y Co d e er ror Registered
Entry code + 2nd entry code If entry code is incorrect
P l ease , I ncor r ec t
i npu t En t r y Co d e En t r y code !
0
Canceled
Ma k e En t r y Co d e
va l i d?
OK Execu t e
ESC Ca n c e l
374
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.13 Entrycodes
11
19.13.5 Canceling an entry code
Counters
High-Speed
1) At the menu screen, use the [+] / [-] buttons to move the cursor to the "EntryCode" item, then press [OK]
to display the "entry code input screen".
If an entry code has been registered, one of the following screens is displayed.
- If a 16-digit entry code is registered, an 8-digit × 2-line screen (shown at left below) is displayed. 12
- If an 8-digit entry code is registered, an 8-digit × 1-line screen (shown at right below) is displayed.
Output Wiring
16-digit entry code 8-digit entry code
P l ease , Entry code P l ease ,
i npu t En t r y Co d e i npu t En t r y Co d e
0 0 13
2nd entry code
Various Uses
Wiring for
2) Use the [+] / [-] buttons to specify the first digit of the entry code, then press [OK] to proceed to the next
digit. To cancel the operation and return to the "menu screen", press [ESC].
16-digit entry code 8-digit entry code
14
P l ease , P l ease ,
Troubleshooting
Maintenance,
Test Run,
i npu t En t r y Co d e i npu t En t r y Co d e
6 7 2 3B9 6 7 01234567
AF2C4 5B0
15
Lowest order digit Lowest order digit
Extension Units
Powered
IInput/Output
(final digit) (final digit)
Blocks
Extension
Input/Output
Reduces the value (F→E...2→1→0).
-
Hold for 1 second or longer for high-speed reduction.
Increases the value (0→1→2...E→F).
+
Hold for 1 second or longer for high-speed increase.
Highest order
Registers the specified value and moves to the next digit input position. 17
If [OK] is pressed at the lowest order digit, and if the entered entry code is correct, the
Unit
Power Supply
Extension
digit to 2nd digit
Entry Code is canceled.
OK
An "All operation is possible" message appears, and the Entry
Lowest order Correct Entry Code Code is canceled.
digit (final digit)
Incorrect Entry Code A "Incorrect Entry Code" message appears.
3) If the [OK] button is pressed at the lowest order position, the entered
18
If entry code is correct
Options
Units and
Other Extension
20
Terminal Block
375
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.14 Device All-Clear
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "EntryCode" item, then press [OK] to display the "enable entry Ma k e En t r y Co d e
code" screen. va l i d?
2) Press the [OK] button to enable the entry code. Or, to retain the OK Execu t e
entry code’s canceled status, press [ESC]. ESC Ca n c e l
Button Operation Description
ESC Cancels the operation and returns to the "menu screen".
- Disabled
+ Disabled
Enables the Entry Code and returns to the "menu
OK
screen".
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "ClearAllDev" item, then press [OK] to display the "Clear all C l ea r
devices" screen.
a l l dev i ces
To cancel the operation and return to the "top screen (time
display)", press [ESC]. OK Execu t e
E SC Ca n c e l
2) Press the [OK] button to initialize the subject devices. Or, to cancel
the operation, press [ESC].
If the PLC is running at this time, a "PLC is running" message is Al l dev i ce
displayed and the all-clear is not executed. In this case, press [OK] we r e c l ea r d
or [ESC] to return to the "menu screen".
Button Operation Description
ESC Cancels the operation and returns to the "menu screen".
When PLC is running
- Disabled
+ Disabled PLC i s r unn i ng
Initializes the subject devices and returns to the "menu
OK
screen".
376
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.15 PLC Status
11
19.15 PLC Status
Counters
High-Speed
The PLC statuses shown below can be displayed from the "PLC Status" menu.
→ Refer to Subsection 19.15.2 for display details.
Page Title Display Item
• Version
12
PLC Status(1/3)
Output Wiring
• Entry code status
• Program memory type
PLC Status(2/3) • Memory cassette’s write protect status
• Program memory capacity
PLC Status(3/3)
• Battery voltage
• Number of registered comments
13
Various Uses
Wiring for
19.15.1 Display operation
1) At the menu screen, use the [+] / [-] buttons to move the cursor to the
"PLC Status" item, then press [OK] to display the "PLC Status (1/3)"
screen.
PLC S t a t u s ( 1 / 3 ) 14
Ve r . 2 . 00
Troubleshooting
Maintenance,
Test Run,
To cancel the operation and return to the "top screen (time display)",
press [ESC]. Al l ope r a t i on
i s un r es t r i c t ed
PLC S t a t u s ( 1 / 3 ) 15
Ve r . 2 . 00
Extension Units
Powered
IInput/Output
PLC ope r a t i on
i s l imi t ed
2) Use the [+] / [-] buttons to switch between the PLC Status screen
pages. PLC S t a t u s ( 2 / 3 ) 16
Press [OK] or [ESC] to return to the "menu screen". I n t e r na l Memo r y
Blocks
Extension
Input/Output
Button Operation Description Pr o t ec t i on - -
ESC Returns to the "menu screen". Ca p a c i t y 64K
Returns to the previous page.
-
PLC Status(3/3) PLC Status(2/3) PLC Status(1/3) PLC S t a t u s ( 3 / 3 ) 17
Proceeds to the next page.
Unit
Power Supply
Extension
Ba t t e r y 3 . 2V
+
PLC Status(1/3) PLC Status(2/3) PLC Status(3/3) C o mm e n t s
19
Display Module
20
Terminal Block
377
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.15 PLC Status
PLC S t a t u s ( 1 / 3 )
Ve r . 2 . 00 [1]
Al l ope r a t i on
[2]
i s un r es t r i c t ed
Display Content
[1] Main unit’s version information.
Indicates the PLC’s entry code registration status.
Messages vary according to the entry code status.
When a 16-bit entry code status is "all online operations prohibited", and when an 8-bit entry code status is
"level A", the entry code must be canceled in order to view the PLC information.
Displayed message PLC status
• For 16-bit entry code:
A "writing prohibit" or "reading/writing prohibit" entry code is
[2] PLC operation is limited registered.
• For 8-bit entry code:
A "Level B" or "Level C" entry code is registered.
The registered entry code has been canceled by an "entry code" menu
All operation is unrestricted
operation.
The Entry Code is not set No entry codes have been registered.
Fatal error occurred → Refer to Subsection 19.24.1 for details.
PLC S t a t u s ( 2 / 3 )
I n t e r na l Memo r y [1]
Pr o t ec t i on - - [2]
Ca p a c i t y 64K [3]
Display Content
Program memory type
Displayed message Program memory type
[1] Internal Memory PLC internal RAM memory
Memory Cassette Memory cassette flash memory
378
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.16 Scan Time (Scan Time Display)
11
3. PLC Status 3/3
Counters
High-Speed
PLC S t a t u s ( 3 / 3 )
Ba t t e r y 3 . 2V [1]
C o mm e n t s
1000 / 2000
[2] 12
Output Wiring
Display Content
[1] Battery voltage
Number of registered comments
[2]
([number of registered comments] / [number of parameter-specified comments])
13
Various Uses
Wiring for
19.16 Scan Time (Scan Time Display)
The scan time’s current value, minimum value, and maximum value can be displayed from the "ScanTime"
menu.
14
19.16.1 Scan time display operation
Troubleshooting
Maintenance,
Test Run,
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "ScanTime" item, then press [OK] to display the "scan time
S c a n T i me
screen".
To cancel the operation and return to the "top screen (time Cu r r : 0 . 7ms 15
display)", press [ESC]. Ma x : 5 . 6ms
Extension Units
Powered
IInput/Output
2) Press [OK] or [ESC] to return to the "menu screen". Mi n : 0 . 6ms
Blocks
Extension
Input/Output
cassette can be performed from the "Cassette" menu when the PLC is in a STOP state.
This menu is disabled, however, if an entry code is registered in the internal RAM. In this case, remove the
memory cassette and use the programming tool to cancel the internal RAM’s entry code.
Item Operation Description
Cassette←RAM Copies internal program memory (RAM) data to a connected memory cassette. 17
Cassette→RAM Copies data from a connected memory cassette to the internal program memory (RAM).
Unit
Power Supply
Extension
Performs a consistency check of the connected memory cassette data and the internal
Cassette : RAM
program memory (RAM) data.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
379
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.17 Cassette (Memory Cassette Transfers)
19.17.1 Transfer from internal RAM to memory cassette (Cassette <- RAM)
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "Cassette" item, then press [OK] to display the "memory Memo r y Ca s s e t t e
cassette transfer screen".
C a s s e t t e R AM
To cancel the operation and return to the "top screen (time
display)", press [ESC]. Ca s s e t t e R AM
C a s s e t t e : R AM
2) Use the [+] / [-] buttons to move the cursor to the "Cassette ← RAM"
item, then press [OK] to display the screen shown to the right. C a s s e t t e R AM
To cancel the operation and return to the "memory cassette transfer
( Wr i t e )
screen", press [ESC].
OK Execu t e
E SC Ca n c e l
• Caution:
Do not turn the PLC power off or perform writing from the programming tool while a program is being
transferred by a "memory cassette transfer" menu operation, as these actions could destroy the program,
causing incorrect operation of the PLC.
380
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.17 Cassette (Memory Cassette Transfers)
11
19.17.2 Transfer from memory cassette to internal RAM (Cassette -> RAM)
Counters
High-Speed
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "Cassette" item, then press [OK] to display the "memory Memo r y Ca s s e t t e
cassette transfer screen". C a s s e t t e R AM
To cancel the operation and return to the "top screen (time
Ca s s e t t e R AM
12
display)", press [ESC].
Output Wiring
C a s s e t t e : R AM
2) Use the [+] / [-] buttons to move the cursor to the "Cassette → RAM"
item, then press [OK] to display the screen shown to the right. Ca s s e t t e R AM
To cancel the operation and return to the "memory cassette transfer ( Re a d )
screen", press [ESC].
OK Execu t e
13
Various Uses
Wiring for
E SC Ca n c e l
Troubleshooting
Maintenance,
Test Run,
- Disabled
+ Disabled
OK Executes the transfer.
• Caution: 15
Do not turn the PLC power off or perform writing from the programming tool while a program is being
Extension Units
Powered
IInput/Output
transferred by a "memory cassette transfer" menu operation, doing so may destroy the program and
disorder the PLC.
Blocks
Extension
Input/Output
- The transfer is not executed if a "PLC is running" message
appears. PLC i s r unn i ng
In this case, set the PLC to the STOP state, then perform the step
3) operation described above.
17
Unit
Power Supply
Extension
- The transfer is not executed if a "Transfer failed" message
appears. Ca s s e t t e R AM
In this case, turn the power off, check the memory cassette ( Re a d )
connection, then attempt the operation again from the first step.
Tr ans f e r
f a i l ed 18
Options
Units and
Other Extension
20
Terminal Block
381
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.17 Cassette (Memory Cassette Transfers)
19.17.3 Memory cassette & internal RAM consistency check (Cassette : RAM)
1) At the menu screen, use the [+] / [-] buttons to move the cursor to
the "Cassette" item, then press [OK] to display the "memory Memo r y Ca s s e t t e
cassette transfer screen". C a s s e t t e R AM
To cancel the operation and return to the "top screen (time
Ca s s e t t e R AM
display)", press [ESC].
C a s s e t t e : R AM
2) Use the [+] / [-] buttons to move the cursor to the "Cassette : RAM"
item, then press [OK] to display the screen shown at right. C a s s e t t e : R AM
To cancel the operation and return to the "memory cassette transfer ( Ve r i f y )
screen", press [ESC].
OK Execu t e
E SC Ca n c e l
C a s s e t t e : R AM
( Ve r i f y )
P r o g r ams
don ' t ma t c h
382
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.18 System Information (Restrictions From PLC)
11
19.18 System Information (Restrictions From PLC)
Counters
High-Speed
Some of the display module functions require system information settings in order to enable program control
of these functions. Functions which require the use of system information are listed below.
• Monitor/test function • Display screen protect function
- For hexadecimal display of current value: → Refer to Section 19.22 for details. 12
Output Wiring
→ Refer to Section 19.21 for the setting • Operation button ON/OFF information
procedure. → Refer to Section 19.20 for details.
- To use user-registered devices: • User message display function
→ Refer to Section 19.19 for the setting → Refer to Section 19.23 for details.
procedure.
13
Various Uses
Wiring for
19.18.1 System information list
Special data register D8300 and D8301 devices with first numbers specified are assigned as system
information devices (data register, auxiliary relay). The data register (excluding special data register) should
be specified at the system information’s "system signal 1", and the auxiliary relay (excluding special auxiliary
relay) should be specified at the system information’s "system signal 2". Both D8300 and D8301 have default 14
settings of "-1".
Troubleshooting
Maintenance,
Test Run,
→ Refer to Section 19.19 to 19.23 for explanations of each system signal.
1. System signal 1
Special data System
Description Reference
register Information 15
D User-registered device 1 type
Extension Units
Powered
IInput/Output
D +1 User-registered device 1 No.
D +2 Devices for user-registered device User-registered device 2 type
D +3 settings User-registered device 2 No.
Only data registers can be Section 19.19
D8300 = K
D
D
+4
+5
specified for user-registered
devices.
User-registered device 3 type
User-registered device 3 No.
16
Blocks
Extension
Input/Output
Occupies 41 D +6 User-registered device 4 type
points
D +7 User-registered device 4 No.
D +8 Device for display screen protect function Section 19.22
D +9 Device where user message display character strings are saved.
Use either character data or the data shown below.
Section 19.23
17
∼
Unit
Power Supply
Extension
D +40 • Japanese: Shift JIS code
2. System signal 2
Special data System
register Information
Description Reference
18
M [OK] button ON/OFF
Options
Units and
Other Extension
M +5 Section 19.21
setting the value display format (hexadecimal or decimal).
ON during "user-registered device Section 19.19
Display screen
M +6 monitoring screen" or "user message" and
information
display. Section 19.23
20
Terminal Block
383
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.18 System Information (Restrictions From PLC)
END
384
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.19 User (User-Registered Device Setting)
11
19.19 User (User-Registered Device Setting)
Counters
High-Speed
The procedure for specifying the devices which display as "User" at the "Monitor/Test" menu is explained
below. The user-registered devices are specified by writing the "device type" and "device No." at "D to
D +7" in the system information (system signal 1).
→ Refer to Section 19.8 for operation. 12
→ Refer to Section 19.18 for system information setting.
Output Wiring
→ Refer to Subsection 19.19.3 to 19.19.5 for program examples.
1. System signal 1 13
Various Uses
Wiring for
User-Registered System
Description Setting Value
Device No. Information
D = K7: Data register [D] (16-bit)
D Device type
D = K8: Data register [D] (32-bit)
1
D +1 Device No.
When D
When D
= K7, D
= K8, D
+ 1 = K0 to K8511
+ 1 = K0 to K7998, K8000 to K8510
14
Troubleshooting
Maintenance,
Test Run,
D +2= K7: Data register [D] (16-bit)
D +2 Device type
D +2= K8: Data register [D] (32-bit)
2
When D = K7, D + 3 = K0 to K8511
D +3 Device No.
When D = K8, D + 3 = K0 to K7998, K8000 to K8510
D +4 Device type
D
D
+4= K7: Data register [D] (16-bit)
+4= K8: Data register [D] (32-bit)
15
3
Extension Units
Powered
IInput/Output
When D = K7, D + 5 = K0 to K8511
D +5 Device No.
When D = K8, D + 5 = K0 to K7998, K8000 to K8510
D +6= K7: Data register [D] (16-bit)
D +6 Device type
D +6= K8: Data register [D] (32-bit)
4
D +7 Device No.
When D
When D
= K7, D
= K8, D
+ 7 = K0 to K8511
+ 7 = K0 to K7998, K8000 to K8510
16
Blocks
Extension
Input/Output
2. System signal 2
System Setting
Display Screen Status
Information Content
M +6
ON
OFF
"User-registered device" screen, or "user message" screen is displayed.
Other screen is displayed.
17
Unit
Power Supply
Extension
19.19.2 Precaution when setting 3 or fewer devices
When 3 or fewer devices are set as user-registered devices, the "type" setting for unused devices should be
set to a value other than 7 and 8.
→ Refer to Subsection 19.19.4 for a program example.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
385
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.19 User (User-Registered Device Setting)
1. Operation
In this program example, the 4 devices shown in the table below are set as user-registered devices, with a
hexadecimal format specified for the current value display.
1) The hexadecimal display format applies only to current values which display at the "user-registered
device" menu. Other current values display in a decimal format.
2) In this program example, system information is assigned from D50 to D90 and from M50 to M56.
2. Program
M8002
MOV K50 D8300 System information (system No.1) is set at D50 to D90.
Initial pulse
MOV K50 D8301 System information (system No.2) is set at M50 to M56.
M8002
MOV K8 D50
Initial pulse User-registered device 1 is set as 32-bit data at "D101, D100".
MOV K100 D51
MOV K7 D52
User-registered device 2 is set as 16-bit data at "D102".
MOV K102 D53
MOV K7 D54
User-registered device 3 is set as 16-bit data at "D103".
MOV K103 D55
MOV K7 D56
User-registered device 4 is set as 16-bit data at "D104".
User- MOV K104 D57
registered
device
monitoring User message
in progress display command
M56 M54
SET M55
User- Hexadecimal current value appears while user-registered device
registered
device monitoring screen is displayed.
monitoring in User message At other Monitor/Test screens, the current values and setting values
progress display command are displayed in a decimal format.
M56 M54
RST M55
END
386
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.19 User (User-Registered Device Setting)
11
19.19.4 Program example 2 (when 3 or fewer devices are displayed as user-registered devices)
Counters
High-Speed
Use this program example as a reference when setting 3 or fewer devices as user-registered devices.
Output Wiring
2. Operation
In this program example, the 3 devices shown in the table below are set as user-registered devices, with a
hexadecimal format specified for the current value display.
1) The hexadecimal display format applies only to current values which are displayed at the "user-registered 13
device" menu. Other current values are displayed in a decimal format.
Various Uses
Wiring for
2) In this program example, system information is assigned from D50 to D90 and from M50 to M56.
Troubleshooting
Maintenance,
Test Run,
2 D102 16-Bit Hexadecimal
3 D103 16-Bit
3. Program
M8002 15
MOV K50 D8300 System information (system No.1) is set at D50 to D90.
Extension Units
Powered
IInput/Output
Initial pulse
MOV K50 D8301 System information (system No.2) is set at M50 to M56.
M8002
MOV K8 D50
User-registered device 1 is set as 32-bit data at "D101, D100".
Initial pulse
MOV K100 D51 16
Blocks
Extension
Input/Output
MOV K7 D52
User-registered device 2 is set as 16-bit data at "D102".
MOV K102 D53
MOV K7 D54
User-registered device 3 is set as 16-bit data at "D103".
17
Unit
Power Supply
Extension
MOV K103 D55
20
Terminal Block
387
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.19 User (User-Registered Device Setting)
19.19.5 Program example 3 (when 5 or more devices are displayed as user-registered devices)
Use this program example as a reference when setting 5 or more devices as user-registered devices.
1. Operation
In this program example, the 7 devices shown in the table below are set as user-registered devices, with the
current value display format set individually for each device.
1) The display formats specified here apply only to current values which appear at the "user-registered
device" menu. Other current values appear in a decimal format.
2) In this program example, system information is assigned from D50 to D90 and from M50 to M56.
User-Registered Device Devices Set As User- Display
Data Length
No. Registered Devices Format
1 D100 (D101) 32-Bit Hexadecimal
2 D102 16-Bit Decimal
3 D103 16-Bit Decimal
4 D104 16-Bit Decimal
5 D200 16-Bit Hexadecimal
6 D210 16-Bit Decimal
7 D201 16-Bit Hexadecimal
2. Program
M8002
System information (system No.1) is
MOV K50 D8300
set at D50 to D90.
Initial pulse
System information (system No.2) is
MOV K50 D8301
set at M50 to M56.
Sets "K-1" at D52 to D57 because user-
FMOV K-1 D52 K6
registered devices 2 to 4 are unused.
At Monitor/Test screens other than
M8002 the "user-registered device" screen,
RST M55 the current values and setting values
Initial pulse are displayed in a decimal format.
ZRSTP M58 M67 Initialization of the user-registered
User- screen's scroll flag.
registered User
device message Setting of flag that specifies the
monitoring display SET M60
in progress command [+] button ON default user-registered devices.
M56 M54 M53
SFTLP M60 M61 K7 K1
M61
RST M60
M67
User- SET M60
registered User
device message
monitoring display User-registered device screen scroll
in progress command [-] button ON RST M67 program (by [+] and [-] buttons).
M56 M54 M52
SFTRP M58 M59 K8 K1
M59
RST M59
SET M66
M60
MOV K8 D50 Sets the first device which appears at
the user-registered device screen as
MOV K100 D51 a "D101, D100" 32-bit device, with a
hexadecimal current value display
SET M55 format.
388
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.19 User (User-Registered Device Setting)
11
Continued from previous page
Counters
High-Speed
M61
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K102 D51 the 2nd displayed device as a "D102"
16-bit device, with a decimal current 12
RST M55 value display format.
Output Wiring
M62
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K103 D51 the 3rd displayed device as a "D103"
16-bit device, with a decimal current
value display format.
13
RST M55
Various Uses
Wiring for
M63
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K104 D51 the 4th displayed device as a "D104"
16-bit device, with a decimal current
value display format.
14
RST M55
Troubleshooting
Maintenance,
Test Run,
M64
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K200 D51 the 5th displayed device as a "D200"
16-bit device, with a hexadecimal
current value display format.
15
SET M55
Extension Units
Powered
IInput/Output
M65
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K210 D51 the 6th displayed device as a "D210"
16-bit device, with a decimal current
value display format.
16
RST M55
Blocks
Extension
Input/Output
M66
MOV K7 D50 At user-registered device screen
scrolling (by [+] and [-] buttons), sets
MOV K201 D51 the 7th displayed device as a "D201"
SET M55
16-bit device, with a hexadecimal
current value display format. 17
Unit
Power Supply
Extension
END
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
389
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.20 Operation Button ON/OFF Information
1. System signal 1
System signal 1 has no system information related to this function.
2. System signal 2
System
Status Description
Information
ON [OK] button is pressed.
M
OFF [OK] button is not pressed.
ON [ESC] button is pressed.
M +1
OFF [ESC] button is not pressed.
ON [-] button is pressed.
M +2
OFF [-] button is not pressed.
ON [+] button is pressed.
M +3
OFF [+] button is not pressed.
390
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.21 Specifying a Hexadecimal Current Value Display Format
11
19.21 Specifying a Hexadecimal Current Value Display Format
Counters
High-Speed
The procedure for specifying a hexadecimal display format for current values which display at the "Monitor/
Test" menu explained below. The display format is specified by the system information’s (system signal 2)
"M +5" ON/OFF status.
The display formats which correspond to the ON and OFF statuses are shown in Subsection 18.21.1 below. 12
The display format should either be fixed as decimal or hexadecimal. Switching between the two should be
Output Wiring
possible by an external operation.
→ Refer to Section 19.18 for system information setting.
Various Uses
Wiring for
System signal 1 is unrelated to this function.
2. System signal 2
System Setting Display
Information Content Format
Display Subjects
14
Hexadecimal Timer (T) [current value], counter (C) [current value], data register (D) [16-
Troubleshooting
Maintenance,
Test Run,
ON
M +5 bit/32-bit], extended register (R) [16-bit/32-bit], and extended file register
OFF Decimal (ER) [16-bit/32-bit]
Extension Units
Powered
IInput/Output
which display at the "Monitor/Test" screen. In this program example, system information is assigned from D50
to D90 and from M50 to M56.
M8002
MOV K50 D8300 System information (system No.1) is set at D50 to D90.
Initial pulse 16
MOV K50 D8301 System information (system No.2) is set at M50 to M56.
Blocks
Extension
Input/Output
M8000
Specifies a hexadecimal display format for current values which appear
M55
at the Monitor/Test screen.
RUN monitor
END
17
Unit
Power Supply
Extension
19.21.3 Program example 2 (specifying a decadal data display format)
The following program example specifies a decimal display format for current values and setting values which
appear at the "Monitor/Test" screen. In this program example, system information is assigned from D50 to
D90 and from M50 to M56.
18
M8002
Options
Units and
Other Extension
MOV K50 D8300 System information (system No.1) is set at D50 to D90.
Initial pulse
MOV K50 D8301 System information (system No.2) is set at M50 to M56.
M8000
Specifies a decimal display format for current values which appear at
RUN monitor
M55
the Monitor/Test screen. 19
Display Module
20
Terminal Block
391
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.22 Display Screen Protect Function
19.22.1 Entry code & display screen protect function levels and corresponding restrictions
If an entry code has been registered, that entry code related restriction takes priority over the "display screen
protect function"
: Usable
: Timer and counter settings cannot be changed
: Only monitor function is usable (test function is not available)
: Unusable
Function Name Entry code Display Screen Protect
All online Reading/
Writing
16-digit entry code setting--> operations writing
prohibited
prohibited prohibited
None B (Read/ None 1 2
A (All C (Erroneous
Incorrect
8-digit entry code setting (level) --> operations write
write
prohibited) prohibited)
protection)
Top screen (time display)
Device
Monitor/Test User (User-
registered device)
ScanTime (Scan time display)
PLC status
ErrorCheck
User message display
Display screen protect function
Menu display language setting
Contrast adjustment
Display
Time
Setting
Entry code (cancel) −
Clear all device (Device all-clear)
Memory cassette transfer
19.22.2 Relationship between entry code & display screen protect function
If the PLC’s entry code registration function is used, that entry code related restriction takes priority over the
display module’s "display screen protect function". The relationship between entry codes and the display
screen protect function is shown below.
Entry code Entry code Display Screen Protect
Function Restrictions
registration Status Status
Entry code is Entry code is being used Restriction of functions is according to the entry code
Entry code is not canceled Entry code is not being used level.
registered Entry code is Entry code is being used
All functions are enabled (no restrictions).
canceled Entry code is not being used
Restriction of functions is according to the display
Entry code is being used
Entry code is not registered screen protect function.
Entry code is not being used All functions are enabled (no restrictions).
392
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.22 Display Screen Protect Function
11
19.22.3 Entry code levels
Counters
High-Speed
1. For versions prior to Ver.2.20
8-Digit Entry code Level Entry code Content Entry code Input Example
Output Wiring
8-digit hexadecimal value beginning B1234567
B (Read/Incorrect write protection)
with "B". BABCDEF7
8-digit hexadecimal value beginning C8904567
C (Erroneous write prohibited)
with "C". CDEF567F
Various Uses
Wiring for
16-digit entry codes are used.
If an 8-digit entry code is specified, processing occurs in the same manner as in versions prior to Ver.2.20.
16-Digit Entry code Setting
Entry code Content Entry code Input Example
Content
All online operations prohibited "A to F", "0 to 9" 16-digit value.
0ABCDEF262297529 14
AABCDEBF34523724
Troubleshooting
Maintenance,
Test Run,
B123456789012345
Writing prohibited "A to F", "0 to 9" 16-digit value.
7ABCDEF73DAEB93A
2890445234817567
Reading/writing prohibited "A to F", "0 to 9" 16-digit value.
CDEF567FABDFEA46
15
19.22.4 System information - display screen protect function
Extension Units
Powered
IInput/Output
1. System signal 1
Setting
System
Information
Content
(Level)
Function Restriction Summary 16
Blocks
Extension
Input/Output
All functions except the "user message display"
1
and "top screen (time display)" functions are disabled.
The following functions are disabled: "monitor/test’s ’test’ function", "device all-clear",
D +8 2 "time change", "contrast setting", "memory cassette transfer",
and "menu display language setting".
Other
17
All functions are enabled.
Unit
Power Supply
Extension
values
2. System signal 2
System signal 2 is unrelated to this function.
In this program example, the display screen protect function is set to "level 2". Use this program as a
reference when other level settings are specified.
In this program example, system information is assigned from D50 to D90 and from M50 to M56.
M8002
MOV K50 D8300 System information (system No.1) is set at D50 to D90. 19
Display Module
Initial pulse
System information (system No.2) is set at M50 to
MOV K50 D8301
M56.
MOV K2 D58 Sets the display screen protect function to "level 2".
END 20
Terminal Block
393
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.22 Display Screen Protect Function
• The protect function is enabled by using the display module’s "monitor/test function" to change the system
information’s (system signal 1) "D +8" current value to "1" or "2".
• Once the setting is made, it cannot be canceled from the display module.
• To cancel the setting, use the programming tool to change the system information’s (system signal 1)
"D +8" current value to a value other than "1" and "2".
If the system information’s (system signal 1) "D +8" is set in a general purpose data register, however,
the display screen protect function can be canceled by turning the power off, then on again.
394
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
11
19.23 User Message Display Function
Counters
High-Speed
The user message display function allows a user-prepared message to appear in place of the "top screen
(time display)".
The [OK] button is then pressed to switch from the "user message screen" to the "menu screen".
If using fixed user messages, the messages (created in GX Developer’s "device memory" window) should be 12
saved individually at D +9 to D +40 of the file register (D), extended register (R), and extended file
Output Wiring
register (ER).
→ Refer to Section 19.18 for system information setting.
→ Refer to Subsection 19.23.7 for character data input.
Various Uses
Wiring for
1. System signal 1
System Information Description
D +9
Device where the user message character string is saved.
14
~
D +40
Troubleshooting
Maintenance,
Test Run,
1) Displayable Characters & Codes
Character Type Code
Alphanumeric 20H to 7DH, A1H to DFH ASCII code
Japanese Shift JIS Level 1-, 2
15
2) System information’s (system signal 1) D +9 to D +40 and display position
Extension Units
Powered
IInput/Output
Row (horizontal character position)
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16]
D +9 D +10 D +11 D +12 D +13 D +14 D +15 D +16
Line (vertical character position)
1 Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher
order order order order order order order order order order order order order order order order 16
Blocks
Extension
Input/Output
D +17 D +18 D +19 D +20 D +21 D +22 D +23 D +24
2 Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher
order order order order order order order order order order order order order order order order
D +25 D +26 D +27 D +28 D +29 D +30 D +31 D +32
3 Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher
order order order order order order order order order order order order order order order order 17
D +33 D +34 D +35 D +36 D +37 D +38 D +39 D +40
Unit
Power Supply
Extension
4 Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher Lower Higher
order order order order order order order order order order order order order order order order
2. System signal 2
System Setting
Screen Display
18
Information Content
Options
Units and
Other Extension
will display at those positions. Therefore, the use of full-size characters (shift JIS code) should be avoided at
the shaded areas shown in the above table.
395
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
1. Operation
The 3 messages shown below appear in accordance with the auxiliary relay M100 to M102 ON/OFF
statuses.
When auxiliary relays are ON simultaneously, the messages appear in the No.1 --> No.2 --> No.3 order.
The following is a program example in which the system information has been assigned from D50 to D90 and
from M50 to M56.
2. Character data
User message data to be displayed is created in GX Developer, and is assigned to the file registers shown
below.
→ Refer to Subsection 19.23.7 for character data input.
File Register Where
Message No.
Saved
1 D1000 to D1031
2 D1032 to D1063
3 D1064 to D1095
3. Program
M8002
Sets system information (system
MOV K50 D8300
signal 1) at D50 to D90.
Initial puls
Sets system information (system
MOV K50 D8301
signal 2) at M50 to M56.
Message No.1 display
M100
BMOV D1000 D59 K32
Message No.2 display
M100 M101 Sets character data at D59 to D90,
BMOV D1032 D59 K32 depending on conditions.
Message No.3 display
M100 M101 M102
BMOV D1064 D59 K32
M100
Displays character data saved at D59
M54
to D90.
M101
M102
END
396
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
11
19.23.5 Program example 2 ([+] / [-] buttons of user messages switching)
Counters
High-Speed
The following is a program example in which the [+] / [-] buttons are used to switch the displayed user message.
Note that user messages do not appear when a screen other than the "top screen (time display)" is displayed.
1. Operation
The No.1 message shown below appears when auxiliary relay M100 switches on, and the [+] / [-] buttons can
12
Output Wiring
be used at that time to switch to the other messages as shown below.
The system information is assigned from D50 to D90 and from M50 to M56.
No.1 No.2 No.3
P L CS <Se t t i ng up> <Op e r a t i n g >
Pr ocess i ng un i t + Now wa rm i n g up + Pr ocess 05 13
- -
Various Uses
Wiring for
Ve r . 2 . 0 Dr i l l i ng ho l es
2. Character data
User message data to be displayed is created in GX Developer, and is assigned to the file registers shown below. 14
→ Refer to Subsection 19.23.7 for character data input.
Troubleshooting
Maintenance,
Test Run,
Message No. File Register Where Saved
1 D1000 to D1031
2 D1032 to D1063
3 D1064 to D1095
15
3. Program
Extension Units
Powered
IInput/Output
M8002
Sets system information (system
MOV K50 D8300
signal 1) at D50 to D90.
Initial pulse
Sets system information (system
MOV K50 D8301
M100
signal 2) at M50 to M56.
16
Blocks
Extension
Input/Output
M54 User message display command.
M100
Initializes the user message selection
ZRST M58 M63
flag.
"User
message
displayed" flag [+] button ON
SET M60 Sets the user message initial screen.
17
Unit
Power Supply
Extension
M100 M56 M53
SFTL M60 M61 K3 K1
M61
RST M60
M63
"User
SET M60 18
User message selection flag control in
Options
Units and
Other Extension
message
displayed" flag [-] button ON RST M63 accordance with [+] / [-] button
M100 M56 M52 operation.
SFTR M58 M59 K4 K1
M59
SET M62
19
RST M59
Display Module
M60
BMOV D1000 D59 K32
M61
BMOV D1032 D59 K32
Sets user message data at D59 to
M62
BMOV D1064 D59 K32
D90. 20
Terminal Block
END
397
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
1. Operation
The message shown below appears when auxiliary relay M100 switches on.
In this program example, the system information is assigned from D50 to D90 and from M50 to M56.
<P r o d u c t i o n >
Ta r ge t *1
Pr oduc t i on *1
R ema i n i n g *1
*1. The current values of the devices shown below appear as the target quantity, the production quantity,
and the remaining quantity.
Item Device Remarks
Target D200 Specifies the C0 setting.
Production C0 Counts the number of M101 ON operations.
Remaining D201 Remaining (D201) = target (D200) - production (C0).
3. Character data
User message data to be displayed is created in GX Developer, and is assigned to file registers D1000 to D1031.
→ Refer to Subsection 19.23.7 for character data input.
4. Program
M8002
Sets system information (system
MOV K50 D8300
signal 1) at D50 to D90.
Initial pulse
Sets system information (system
MOV K50 D8301
signal 2) at M50 to M56.
Specifies "10000" as the target
MOV K10000 D200
quantity
D200
M101 Production quantity count setting is
C0 specified indirectly by D200.
M8000
SUB D200 C0 D201 Remaining quantity
RUN monitor
M100
M54 User message display command.
398
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
11
Continued from previous page
Counters
High-Speed
Starts a sub-routine program that
MOV D201 D104 adds a space (20H) to the
remaining quantity (D201) current
value (max. 5 digits) to generate 6-
CALL P0 character data. 12
Saves the generated character
Output Wiring
BMOV D160 D88 K3 data at the user message display
position.
FEND
P0 M8000
INC D106 13
RUN
Various Uses
Wiring for
monitor
= K1 D106 MOV K0 Z0
MOV K0 Z1
= K2 D106 MOV K2 Z0
14
Troubleshooting
Maintenance,
Test Run,
MOV K10 Z1
= K3 D106 MOV K4 Z0
Processing preparation program
MOV K20 Z1 for data generating program.
15
RST D106
Extension Units
Powered
IInput/Output
M8000
RST D101
RUN
monitor
RST D103
RST D105
16
Blocks
Extension
Input/Output
RST V0
Unit
Power Supply
Extension
"D109, D108" to ASCII code which
ASCI D108 D111 K5 is saved at the D111 to D115
M8000 lower order bytes.
M8161
399
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
M8000
BMOV D130 D140Z1 K3
RUN monitor
SRET
END
400
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
11
19.23.7 Character data input procedure
Counters
High-Speed
User messages are entered and assigned to file registers in advance, using GX Developer.
Messages are displayed by a file register → data register transfer, with the message being created in place of
the numeric values, etc.
32 data register points are assigned to each message. 12
1
Output Wiring
Starting GX Developer
To start up GX Developer, click the Windows® [Start] button, then click [Programs] - [MELSOFT
Application] - [GX Developer].
13
2 Setting The PLC Model Name
Various Uses
Wiring for
Set the "PLC series" and the "PLC Type" settings as
shown below.
Required Setting Items Setting Content
PLC series FXCPU 14
Troubleshooting
Maintenance,
Test Run,
PLC Type FX3U(C)
15
Extension Units
Powered
IInput/Output
3 Parameter Settings
To specify the parameter settings, select "PLC parameter" from the project
data list. 16
Blocks
Extension
Input/Output
If the project data list does not display, click the toolbar’s [Display] - [Project
data list] items.
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
401
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
4. At the 2 selection boxes next to the input area, select "16-bit integer" and "HEX".
402
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.23 User Message Display Function
11
5
Counters
High-Speed
Entering User Messages
As shown in the illustration below, the dialog box for character string inputs is opened by double-
clicking on GX Developer’s character string display area or the data register display area.
When entering Japanese scripts (Chinese characters, etc.), data input automatically occurs in the
lower order → higher order sequence, and the input can therefore be used as it is at the display 12
Output Wiring
module’s user message display.
The GX Developer screen’s character string shown below is for "program example 1".
→ Refer to Subsection 19.23.4 for "program example 1" details.
13
Various Uses
Wiring for
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
GX Developer character arrangement precautions:
A single line is comprised of 8 data registers. 17
To prevent garbled characters when a 2-byte character (shift JIS code) arrangement extends into the next
Unit
Power Supply
Extension
line, the system replaces those characters with 2 spaces.
([Ex] spaces display at the end of the 1st line and at the beginning of the 2nd line.)
The condition of the display module line must therefore be considered when entering the characters.
Moreover, the 1st character device should be specified for displaying a 1-line character input.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
403
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.24 Operation Error Messages & Corrective Actions
404
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.24 Operation Error Messages & Corrective Actions
11
19.24.1 When a "Fatal error occurred" message appears
Counters
High-Speed
Operation is possible with the "Level C" or "Level B" entry code function restrictions.
However, the system is probably in one of the statuses described below. Check these statuses in the order
shown below, and take the appropriate corrective action.
1. Perform an error check at the display module, and if an error is active, take the appropriate 12
Output Wiring
corrective action.
→ Refer to Section 19.9 for the error check procedure.
Various Uses
Wiring for
→ Refer to Subsection 14.5.3 for watchdog timer error corrective actions.
Troubleshooting
Maintenance,
Test Run,
3) Stop the PLC, turn the power ON, display the "PLC Status (1/3)" screen and check to refer to if the "Fatal
error occurred" message appears.
- If the "Fatal error occurred" message appears, perform the corrective action described at item "2" below.
- If the "Fatal error occurred" message does not appear, set the PLC to a RUN state, then check again if
the message appears. 15
If the message appears, a watchdog timer error has probably occurred. In this case, the program should
Extension Units
Powered
IInput/Output
be re-examined.
→ Refer to Subsection 14.5.3 for watchdog timer error corrective actions.
2. If the "Fatal error occurred" message still appears after performing the corrective actions
described in item 1 above, perform the following procedure to check for symptom changes.
16
Turn the power OFF and disconnect all extension devices.
Blocks
Extension
Input/Output
(extension connectors, extension cables, and expansion board connectors)
Turn the power ON again at the main unit, display the "PLC Status(1/3)" screen again, and check if the
"Fatal error occurred" message appears.
1) If the "Fatal error occurred" message appears: 17
The main unit hardware may have failed. Contact your local Mitsubishi Electric distributor.
Unit
Power Supply
Extension
2) If the "Fatal error occurred" message does not appear:
Turn the power OFF, connect the extension devices, then operate the system again to check for errors.
If the problem persists, there may be main unit or extension device hardware failure. Contact your local
Mitsubishi Electric distributor.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
405
FX3U Series Programmable Controllers 19 FX3U-7DM (Display Module)
User’s Manual - Hardware Edition 19.25 Menu Display Characters - Japanese & English Display Character Correspondence Table.
PLC Status
is unrestricted
No errors PLC operation
ErrorCheck ErrorCheck is unavailable
PLC Status(2/3)
Error code
Internal Memory
LANGUAGE PLC status(2) Memory Cassette
(Menu display Protection --
language setting)
Capacity --K
Contrast Contrast
PLC Status(3/3)
Current time
Clock setting PLC status(3) Battery -.-V
ClockMenu
(Current time Clock setting Comments
setting) Current time ScanTime
is set ScanTime Curr: -.-ms
(Scan time display) Max : -.-ms
Please,
Min : -.-ms
input Entry Code
Memory Cassette
Cassette
******** Cassette←RAM
(Memory cassette
Cassette→RAM
Make Entry Code transfer)
Cassette:RAM
valid?
EntryCode OK→Execute Cassette←RAM
Cassette
ESC→Cancel (Write)
←RAM
All operation Please wait...
is possible Cassette→RAM
Cassette
Incorrect (Read)
→RAM
Entry Code Please wait...
Cassette Transfer
Clear
→RAM completed
all devices
OK→Execute Cassette Transfer
ClearAllDev
ESC→Cancel ←RAM failed
(Device all-clear)
All device Cassette:RAM
were cleard (Verify)
Please wait...
Cassette:RAM
Programs match
Programs
don't match
406
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition
11
Counters
High-Speed
20. FX-16/32E*-*-TB (Terminal Block)
12
DESIGN PRECAUTIONS
Output Wiring
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
13
Various Uses
Wiring for
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the 14
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
Troubleshooting
Maintenance,
Test Run,
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case. 15
Extension Units
Powered
IInput/Output
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
16
Blocks
Extension
Input/Output
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
INSTALLATION PRECAUTIONS
17
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Unit
Power Supply
Extension
Failure to do so may cause electric shock.
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
407
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition
INSTALLATION PRECAUTIONS
• Use the product within the generic environment specifications described in Section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S,
SO2 or NO2), flammable gas, vibration or impacts, or exposed to high temperature, condensation, or rain and
wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
• Do not touch the conductive parts of the product directly to avoid failure or malfunctions.
• Install the product securely using a DIN rail or mounting screws.
FX2N-10GM, FX2N-20GM, and terminal block DIN rail only
Main unit, FX2N Series I/O extension unit/block, and FX0N/FX2N/
DIN rail or direct mounting
FX3U Series special extension block/special adapter
WIRING PRECAUTIONS
• Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the
product or electric shock.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX Series terminal blocks in accordance with the precautions below in order to
prevent electric shock, a short-circuit, wire breakage, or damage to the product:
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
408
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.1 Overview
11
20.1 Overview
Counters
High-Speed
A terminal block is used to convert connector type input/output terminals into a terminal block.
Moreover, dedicated input and output terminal blocks (built-in element types) can be used to receive AC input
signals for conversion to relay / transistor / triac output types.
12
Output Wiring
13
Various Uses
Wiring for
Optional cable or
user-fabricated cable
14
Troubleshooting
Maintenance,
Test Run,
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
409
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.1 Overview
*1. A power supply for the input circuit is required when connected to the FX2N-16EX-C.
The current consumption is shown in the table below.
Power Supply Voltage Current Consumption
FX2N-16EX-C 24V DC 112 mA
*4. A power supply for the input circuit is required when connected to the FX2N-16EX-C.
The current consumption is shown in the table below.
Power Supply Voltage Current Consumption
FX2N-16EX-C 24V DC 160 mA
410
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.2 External Dimensions & Component Names
11
20.2 External Dimensions & Component Names
Counters
High-Speed
FX-16E-TB FX-32E-TB
Output Wiring
55(2.17")
55(2.17")
13
Various Uses
Wiring for
FX-16EYR-TB
FX-16EX-A1-TB FX-16EYS-TB
FX-16EYT-TB, FX-16EYT-H-TB
150(5.91") 150(5.91")
14
55(2.17")
55(2.17")
Troubleshooting
Maintenance,
Test Run,
Units: mm (inches) 15
Accessories: Input/output No. labels, terminal block arrangement
Extension Units
Powered
IInput/Output
cards
Blocks
Extension
Input/Output
Present at FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB, FX-
[3] Operation indicator LED
16EYT-H-TB.
[4] POWER LED Present at FX-16EX-A1-TB.
[5] CN2 terminal block (M3.5 screws) Present at FX-32E-TB.
[6] CN1 terminal block (M3.5 screws) −
17
Unit
Power Supply
Extension
[7] Nameplate −
DIN rail mounting groove
[8] −
(DIN rail width: 35mm(1.38"))
[9] DIN rail mounting hook −
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
411
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.3 Terminal Arrangement
1. FX-16E-TB
When connected to the FX2N-16EYT-C
FX-16E-TB
24+ 1 3 5 7 1 3 5 7
24+ 0 2 4 6 0 2 4 6
2. FX-32E-TB
When connected to the FX2N-16EYT-C
Lower numbers Higher numbers
CN2 24+ 1 3 5 7 1 3 5 7
24+ 0 2 4 6 0 2 4 6
CN1 CN2
CN1 24+ 1 3 5 7 1 3 5 7
24+ 0 2 4 6 0 2 4 6
412
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.3 Terminal Arrangement
11
3. FX-16EX-A1-TB
Counters
High-Speed
12
Output Wiring
Lower numbers Higher numbers
Various Uses
Wiring for
Lower numbers Higher numbers 14
Troubleshooting
Maintenance,
Test Run,
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4
24- 0 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
15
Extension Units
Powered
IInput/Output
16
Blocks
Extension
Input/Output
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
413
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.4 Installation Work
20.4.1 Mounting
20.4.2 Removal
Input/output cable
Terminal block
414
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.4 Installation Work
11
20.4.4 Connection to terminal block
Counters
High-Speed
1. The product terminal screws are as shown in the table below.
Model Name Terminal Screw Size
• FX-16E-TB, FX-32E-TB 12
• FX-16EX-A1-TB
Output Wiring
• FX-16EYR-TB M3.5
• FX-16EYS-TB
• FX-16EYT-TB, FX-16EYT-H-TB
13
2. Crimp terminal sizes vary according to the wiring method.
Various Uses
Wiring for
Use the sizes shown below.
• When 1 wire is connected to 1 terminal:
Use a crimp terminal of the size shown below, and install it as shown in the lower right figure.
Terminal Crimp
φ 3.7(0.15") screw terminal 14
6.8mm(0.27")
Troubleshooting
Maintenance,
Test Run,
or less
φ 3.7(0.15")
6.8mm(0.27") Terminal
or less
15
• When 2 wires are connected to 1 terminal:
Extension Units
Powered
IInput/Output
Use a crimp terminal of the size shown below, and install it as shown in the lower right figure.
φ 3.7(0.15")
6.8mm(0.27") Terminal Crimp
or less screw terminal
6.0mm(0.24")
or more
16
Blocks
Extension
Input/Output
φ 3.7(0.15")
6.8mm(0.27") Terminal
or less 6.0mm(0.24")
or more
17
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
415
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.5 FX-16E-TB, FX-32E-TB
*1 *1
(20) (10)
COM (19) (9) COM
*2 *2
7 (18) (8) 7
6 (17) (7) 6
5 (16) (6) 5
4 (15) (5) 4
3 (14) (4) 3
2 (13) (3) 2
1 (12) (2) 1
0 (11) (1) 0
0 2 4 6
FX-32E-TB
1 3 5 7
0 2 4 6
CN1 1 3 5 7
*1
(20) (10) *1
COM (19) (9) COM *2
FX-16E-TB
*2
7 (18) (8) 7
6 (17) (7) 6
5 (16) (6) 5
4 (15) (5) 4
3 (14) (4) 3
2 (13) (3) 2
1 (12) (2) 1
*1 *2 *2 *2 *2
0 (11) (1) 0
1 3 COM 5 7 COM 1 3 COM 5 7 COM
0 2 COM 4 6 COM 0 2 COM 4 6 COM
*1 *2 *2 *2 *2
416
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.5 FX-16E-TB, FX-32E-TB
11
20.5.2 Example of input external wiring
Counters
High-Speed
WIRING PRECAUTIONS
Output Wiring
Doing so may damage the product.
Various Uses
Wiring for
Input numbers
in the FX2N-
16EX-C 1 3 5 7 1 3 5 7
24+ 0 2 4 6 0 2 4 6
24+
24+ 1 3 5 7 1 3 5 7
14
Troubleshooting
Maintenance,
Test Run,
24+ 0 2 4 6 0 2 4 6
24V
DC
15
Extension Units
Powered
IInput/Output
20.5.3 Output external wiring
16
Blocks
Extension
Input/Output
WIRING PRECAUTIONS
Unit
Power Supply
Extension
0 to 7 (Lower Nos.) 0 to 7 (Higher Nos.)
PLC's COM
output No.
1 3 5 7 1 3 5 7 18
Options
Units and
Other Extension
Vacant 0 2 4 6 0 2 4 6
terminal COM
20
24V
Terminal Block
DC
417
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.6 FX-16EX-A1-TB
20.6 FX-16EX-A1-TB
The FX-16EX-A1-TB is used by connecting it to the FX2N series input extension block (24V DC).
Input Connector
Connectable models FX2N-16EX-C (sink input)
20.6.1 Specifications
0 to 7
Photocoupler
CN1 100V
Input/output circuitry Connector AC
side
Fuse
COMn
Terminal block
External wiring
*1. This response time does not include the response delay at the PLC.
*2. 3.9W (160mA, 24V DC) is required when connected to the FX2N-16EX-C.
418
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.6 FX-16EX-A1-TB
11
20.6.2 Internal circuit
Counters
High-Speed
CN1
(20) (10) 12
COM (19) (9) COM
Output Wiring
7 (18) (8) 7
Photo- 6 (17) (7) 6 Photo-
coupler 5 (16) (6) 5 coupler
4 (15) (5) 4
3 (14) (4) 3
2 (13) (3) 2
1
0
(12) (2)
(11) (1)
1
0
13
Photo- Photo-
Various Uses
Wiring for
coupler coupler
0 to 3 4 to 7 0 to 3 4 to 7
14
Troubleshooting
Maintenance,
Test Run,
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4
15
Extension Units
Powered
IInput/Output
24- 0 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
16
20.6.3 Example of input external wiring
Blocks
Extension
Input/Output
PLC input
No. 0 to 3 4 to 7 0 to 3 4 to 7
17
Unit
Power Supply
Extension
18
Photo-coupler
Options
Units and
Other Extension
power supply
100 to
24V
+10%
DC -15%
120V AC 19
Display Module
20
Terminal Block
419
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.7 FX-16EYR-TB
20.7 FX-16EYR-TB
The FX-16EYR-TB is used by connecting it to the FX2N series output extension block (transistor).
Output Connector
Connectable models FX2N-16EYT-C (sink output)
20.7.1 Specifications
24V DC
5mA 0 to 7
24+
Input/output
circuitry LED
CN1 Fuse
Connector side COMn
External wiring
*1. This response time does not include the response delay at the PLC.
420
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.7 FX-16EYR-TB
11
20.7.2 Internal circuit
Counters
High-Speed
(20) (10)
COM
7
(19) (9) COM
(18) (8) 7 12
6 (17) (7) 6
Output Wiring
5 (16) (6) 5
4 (15) (5) 4
3 (14) (4) 3
2 (13) (3) 2
1 (12) (2) 1
0 (11) (1) 0
13
Various Uses
Wiring for
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Troubleshooting
Maintenance,
Test Run,
24- 0 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
Extension Units
Powered
IInput/Output
0 to 7 Lower numbers 0 to 7 Higher numbers
PLC output
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
No.
Relay
16
power
Blocks
Extension
Input/Output
supply
17
Unit
Power Supply
Extension
Fuse Fuse
24V
18
DC
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
421
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.7 FX-16EYR-TB
2) AC circuit
Connect the surge absorber (combined CR
components such as a surge killer and spark killer, inductive load
etc.), parallel to the load.
PLC output
Select the rated voltage of a surge absorber that is contact
suitable for the load being used. Refer to the table Surge
absorber
below for other specifications.
Item Guide
Static electricity capacity Approx. 0.1µF
Resistance value Approx. 100 to 200Ω
Reference
Manufacturer Model name Manufacturer Model name
Okaya Electric Industries Co., Ltd. CR-10201 Rubycon Corporation 250MCRA104100M B0325
3. Interlock
For loads such as forward/reverse contactors, etc., where Interlock Forward limit
a hazardous condition could result if switched ON PLC output
simultaneously, an external interlock should be provided contact
for interlocking the PLC’s internal programs as shown to Reverse limit
PLC output
the right. contact
4. In-phase
PLC output contacts (*) should be used in an "in-phase" *
manner.
Bad *
*
Good *
422
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.7 FX-16EYR-TB
11
20.7.5 Product life of relay output contacts
Counters
High-Speed
The product life of relay contacts varies considerably depending on the load type used. Take care that loads
generating reverse electromotive force or rush current may cause poor contact or deposition of contacts
which may lead to considerable reduction of the contact product life.
1. Inductive load 12
Output Wiring
Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause
arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller,
the arc energy gets larger.
The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000
operations at 35 VA.
The following table shows the approximate life of a relay based on the results of an operation life test. 13
Various Uses
Wiring for
Test conditions: 1 sec. ON / 1 sec. OFF
Load Capacity Contact Life
0.35 A / 100V AC
35VA 3,000,000 times
0.17 A / 200V AC
0.8 A / 100V AC
14
80VA 1,000,000 times
Troubleshooting
Maintenance,
Test Run,
0.4 A / 200V AC
1.2 A / 100V AC
120VA 200,000 times
0.6 A / 200V AC
The product life of relay contacts becomes considerably shorter than the above conditions when the rush
overcurrent is shut down. 15
→ For precautions on inductive loads, refer to Subsection 20.7.4 2
Extension Units
Powered
IInput/Output
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make
sure that the rush current does not exceed the current corresponding to the maximum specified resistance
load.
2. Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush
16
Blocks
Extension
Input/Output
current does not exceed the current corresponding to the maximum specified resistance load.
3. Capacitive load
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load. Capacitive
loads such as capacitors may be present in electronic circuit loads including inverters. 17
→ For the maximum specified resistance load, refer to Subsection 20.7.1
Unit
Power Supply
Extension
18
Options
Units and
Other Extension
19
Display Module
20
Terminal Block
423
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.8 FX-16EYT-TB, FX-16EYT-H-TB
20.8.1 Specifications
Transistor output
Item
FX-16EYT-TB FX-16EYT-H-TB
Fuse Fuse
Photo- Photo-
3.3kΩ coupler 0 to 7 3.3kΩ coupler 0 to 7
24+ 24+
Input/output circuitry
LED 5 to 30V LED 5 to 30V
CN1 CN1
Connector 24V DC DC 24V DC DC
Connector
side 7mA COMn side 7mA COMn
External External
wiring wiring
*1. This response time does not include the response delay at the PLC.
424
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.8 FX-16EYT-TB, FX-16EYT-H-TB
11
20.8.2 Internal circuit
Counters
High-Speed
Photo- (20) (10)
3.3kΩ coupler COM
7
(19) (9) COM
(18) (8) 7
3.3kΩ
12
6 (17) (7) 6 Photo-
Output Wiring
5 (16) (6) 5 coupler
4 (15) (5) 4
3 (14) (4) 3
Photo- 2 (13) (3) 2
3.3kΩ coupler 1 (12) (2) 1 3.3kΩ
0 (11) (1) 0
Photo-
coupler 13
Various Uses
Wiring for
0 to 7 Lower numbers 0 to 7 Higher numbers
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
* * * * 14
Troubleshooting
Maintenance,
Test Run,
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4
24- 0 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
* For the FX-16EYT-H-TB, the output transistor elements are as shown in the figure below. 15
Extension Units
Powered
IInput/Output
20.8.3 Example of output external wiring
16
Blocks
Extension
Input/Output
PLC output
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
No.
* * * *
Photo-coupler
power supply 17
Unit
Power Supply
Extension
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4
24- 0 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
18
Options
Units and
Other Extension
Fuse Fuse
24V
DC
* For the FX-16EYT-H-TB, the output transistor elements are as shown in the figure below.
19
Display Module
20
Terminal Block
425
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.8 FX-16EYT-TB, FX-16EYT-H-TB
3. Interlock
For loads such as forward/reverse contactors, etc., where Forward
limit Interlock
a hazardous condition could result if switched ON
simultaneously, an external interlock should be provided
for interlocking the PLC’s internal programs as shown to
the right. Reverse PLC output
limit element
426
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.9 FX-16EYS-TB
11
20.9 FX-16EYS-TB
Counters
High-Speed
The FX-16EYS-TB is used by connecting it to the FX2N series output extension block (transistor).
Output Connector
Connectable models FX2N-16EYT-C (sink output)
12
The applications shown below are not supported.
Output Wiring
Unsupported Applications
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width
modulation (PWM) instruction, DOG search zero return (DSZR) instruction, interruption positioning
Pulse
(DVIT) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS)
outputs
instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to 13
increment (DRVI) instruction, drive to absolute (DRVA) instruction
Various Uses
Wiring for
Time division Input matrix (MTR) instruction, hexadecimal input (HKY) instruction, digital switch (DSW) instruction,
inputs arrow switch (ARWS) instruction
Time division
Seven segment with latch (SEGL) instruction, print (ASCII Code) (PR) instruction
outputs
14
20.9.1 Specifications
Troubleshooting
Maintenance,
Test Run,
Item TRIAC output
24+
3.3kΩ 7mA
0 to 7
Fuse 15
2.2Ω
Extension Units
Powered
IInput/Output
Input/output
circuitry U
LED 0.015
CN1 µF
connector
Photo- COMn
side
thyristor
External wiring 16
Blocks
Extension
Input/Output
Load voltage 85 to 242V AC
The total load current of resistance loads per common terminal should be the
Resistance
0.3 A / point*1 following value.
Max. load • 4 output points/common terminal: 0.8A or less
load
Inductive
load
15 VA / 100V AC
36 VA / 200V AC
17
Unit
Power Supply
Extension
0.4 VA / 100V AC
Min. load
1.6 VA / 200V AC
Open-circuit 1 mA / 100V AC
leakage current 2 mA / 200V AC
*1. In systems where frequent large-load ON/OFF switching occurs due to rush currents, the root mean square 19
current should be 0.2 A or less.
Display Module
<Example>
0.4A
4A
42 0.02 + 0.42 0.7
= 0.2A
0.02 + 0.7 + 10
0.02
sec
0.7
sec
10
sec
20
Terminal Block
*2. This response time does not include the response delay at the PLC.
427
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.9 FX-16EYS-TB
(20) (10)
3.3kΩ COM (19) (9) COM 3.3kΩ
7 (18) (8) 7
6 (17) (7) 6 Photo-
Photo- 5 (16) (6) 5 thyristor
thyristor 4 (15) (5) 4
3 (14) (4) 3
2 (13) (3) 2
3.3kΩ 1 (12) (2) 1 3.3kΩ
0 (11) (1) 0
Photo-
Photo- thyristor
thyristor
U U U U
Photo-coupler U U U U
power supply
24V Load
DC
428
FX3U Series Programmable Controllers 20 FX-16/32E*-*-TB (Terminal Block)
User’s Manual - Hardware Edition 20.9 FX-16EYS-TB
11
20.9.4 External wiring precautions
Counters
High-Speed
1. Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause Load
burnout at the output element or the PCB. To prevent this, a 0 to 7
protection fuse should be inserted at the output. Fuse 12
Output Wiring
COMn
Terminal block
Various Uses
Wiring for
100V AC or less or 1.6 VA/200V AC or less", please connect a
surge absorber parallel to the load. U Surge
absorber
Select the rated voltage of a surge absorber that is suitable for the
load being used. Refer to the table below for other specifications.
Item Guide 14
Static electricity capacity Approx. 0.1µF
Troubleshooting
Maintenance,
Test Run,
Resistance value Approx. 100 to 200Ω
Reference
Manufacturer Model name Manufacturer Model name
Okaya Electric Industries Co., Ltd. CR-10201 Rubycon Corporation 250MCRA104100M B0325 15
Extension Units
Powered
IInput/Output
3. Interlock
For loads such as forward/reverse contactors, etc., where Interlock Forward limit
Forward
a hazardous condition could result if switched ON
simultaneously, an external interlock should be provided
16
U
for interlocking the PLC’s internal programs as shown to Reverse
the right. Reverse limit
Blocks
Extension
Input/Output
U
PLC output
element
4. In-phase
PLC output contacts (*) should be used in an "in-phase" *
17
manner.
Unit
Power Supply
Extension
Bad U
*
18
U
*
Options
Units and
Other Extension
Good
U
U
19
Display Module
20
Terminal Block
429
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.1 Specifications
21.1 Specifications
Max.
Memory PROTECT Loader Compatible
Model Name Max. Memory Capacity Allowable
Type Switch Function Versions
Write
64000 steps Flash 10,000
FX3U-FLROM-64L Provided Provided
(2k/4k/8k/16k/32k selectable) memory times
64000 steps Flash 10,000 1st article
FX3U-FLROM-64 Provided NA
(2k/4k/8k/16k/32k selectable) memory times (Ver.2.20)
16000 steps Flash 10,000
FX3U-FLROM-16 Provided NA
(2k/4k/8k selectable) memory times
1. FX3U-FLROM-64L
[1] RD LED
[2] RD key
(Reading: PLC ⇒ memory cassette)
20(0.79")
[3] WR LED
[4] WR key
(writing: memory cassette ⇒ PLC)
[5] Prevent reverse installation slot
37(1.46") 6.1(0.25") [6] PROTECT switch
Units: mm (inches) [7] Main unit connector
[8] Detachment lever
2. FX3U-FLROM-64, FX3U-FLROM-16
[1] Prevent reverse installation slot
[2] PROTECT switch
[3] Main unit connector
20(0.79")
37(1.46") 6.1(0.25")
Units: mm (inches)
430
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.2 Installation & Removal
21
21.2 Installation & Removal
Cassette
Memory
If a display module (FX3U-7DM) and a display module holder (FX3U-7DM-HLD) are installed, remove these
items before installing or removing the memory cassette. Be sure that the power is OFF when installing/
removing the memory cassette.
22
21.2.1 Memory cassette installation
Battery
1 Remove the top cover.
While pressing the top cover hook ("A"), remove the top A
cover ("B") as shown in the figure to the right.
(M8000-,D8000-)
Special Devices
B
Instruction List
2 Raise the memory cassette detachment lever.
C
Raise the memory cassette detachment lever ("C").
Character-code
C 2
D
3
models
Discontinued
Install the memory cassette.
Align the cassette with the "prevent reverse installation slot"
("D"), then press it all the way in (when pressed all the way
in, the cassette is approx. 0.4mm (0.02") lower than the
surrounding surface.)
Installation
precaution
• Connect the memory cassette securely to the prescribed
connector. A poor connection can cause malfunctions.
Installing the cassette in a raised or tilted posture can also cause
malfunctions.
Memory
Good cassette
PLC body
Memory Raised cassette
Bad cassette
posture
Memory
Bad cassette Tilted cassette posture
431
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.2 Installation & Removal
Caution:
Take care to avoid twisting the detachment lever when removing
the memory cassette.
432
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.3 Saved Data Content
21
21.3 Saved Data Content
Cassette
Memory
The following data is saved on the memory cassette.
Item Description Saving Method
• Memory capacity setting
- Memory capacity (default setting: 16k steps)
22
Battery
2k/4k/8k/16k steps (FX3U-FLROM-16)
2k/4k/8k/16k/32k/64k steps (FX3U-FLROM-64/64L)
- Comment capacity
- File register capacity
Parameters - Buffer memory initial setting capacity
• Device latch range settings (keep device)
• Modem initializing settings, battery-free operation, RUN terminal
A
(M8000-,D8000-)
Special Devices
settings
Program • RS/RS2 instructions / computer link function communication settings Programming
Memory • Positioning settings tool *2
• BFM default settings
Sequence
programs
User-created sequence programs B
Instruction List
Max. 6350 points Comments and file registers can
Comments (0 to 127 blocks, be created in the memory by
1 block = 50 points / 500 steps) setting them in the parameter
Max. 7000 points memory capacity.*1
File registers (0 to 14 blocks,
1 block = 500 points / 500 steps) C
• Sequence
Character-code
program
Extended file registers ER0 to ER32767 (32768 points)
• GX
Developer
*1. The total size of the programs + comments + file registers must not exceed the maximum capacity of
the memory cassette.
D
models
Discontinued
*2. The maximum number of points for the memory capacity, comments, and file registers, can be
specified when the FX3U(C) programming tool is selected. The maximum number of points cannot be
specified when a programming tool other than the FX3U(C) is selected.
433
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.4 PROTECT Switch
OFF ON OFF ON
• Leaving the switch knob at an intermediate position for an extended period can cause an equipment
failure.
• Also use care to avoid scratching the PCB when setting the switch.
434
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.5 Memory Cassette <-> PLC (RAM Memory) Transfers by Loader Function
21
21.5 Memory Cassette <−> PLC (RAM Memory) Transfers by Loader Function
Cassette
Memory
The FX3U-FLROM-64L loader function ([WR] and [RD] key operation) is explained in this section.
• Program transfers (reading/writing) are possible between the memory cassette and the PLC’s internal
RAM memory.
• The loader function is enabled while the PLC is stopped.
22
Battery
21.5.1 Tool for pressing the [WR] and [RD] keys
Use an insulator tool (plastic, ceramic, etc.) to press the [WR] and [RD] keys. The area around the keys is not
insulated. Using a metal screwdriver, etc can cause equipment damage.
A
(M8000-,D8000-)
Special Devices
21.5.2 Writing (WR: 64L −> PLC)
A memory cassette program is written to the PLC’s internal RAM memory.
Required condition: The PLC must be stopped.
Instruction List
(Setting the PROTECT switch to ON (on memory cassette’s rear face) prevents accidental overwriting of
memory cassette program.)
→ Refer to Subsection 21.2.1 for the installation procedure.
• Verify that the PLC power is OFF, then install the memory cassette on the PLC.
• Turn the PLC power ON.
[WR] LED [WR] key
C
• Raise the memory cassette’s eject lever.
Character-code
2 Press the [WR] key 1 time. WR(64LJPLC)
RD(64LIPLC)
The [WR] LED lights, and a preparation status is established.
• To cancel, press the [RD] key.
D
models
Discontinued
3 Press the [WR] key again.
Writing is executed, and the [WR] LED goes off.
27
26
25
24
23
R
E
22
N
21
U
R
20
27
TT
A
7
26
B
24 R
6
17
23 RO
25
5
R
16
22 E
4
15
3
14
2
13
21
1
12
17 20
0
11
16 7
15 6
IN
14 5
13 4
12 3
11 2
10 1
T 0
U
O
FX
ST
OP
After turning the PLC power OFF, remove the memory cas-
sette from the PLC.
→ Refer to Subsection 21.2.2 for the removal procedure.
435
FX3U Series Programmable Controllers 21 FX3U-FLROM-16/64/64L (Memory Cassette)
User’s Manual - Hardware Edition 21.6 Transfers By Display Module Operation
1 Turn the PROTECT switch OFF at the rear face of the memory cassette.
The memory cassette must be removed from the PLC in order to turn the PROTECT switch OFF.
→ Refer to Subsection 21.2.2 for the removal procedure.
27
26
25
24
4
23
R
E
22
W
O
N
21
U
R
20
27
TT
A
7
26
B
24 R
6
17
25
23 RO
5
R
16
22 E
4
15
Press the [RD] key again.
14
2
13
21
1
12
17 20
0
11
16 7
10
15 6
IN
14 5
13 4
12 3
11 2
10 1
T 0
U
O
Reading is executed, and the [RD] LED blinks. -48
MR
/ES
3U
FX
ST
OP
436
FX3U Series Programmable Controllers 22 FX3U-32BL (Battery)
User’s Manual - Hardware Edition 22.1 Battery Purpose
21
Cassette
Memory
22. FX3U-32BL (Battery)
Battery
PRECAUTIONS
• Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is
attached or detached while the PLC's power is on, the data in the memory may be destroyed, or the memory
cassette may be damaged.
A
(M8000-,D8000-)
Special Devices
TRANSPORTATION PRECAUTIONS
• Before transporting the PLC, turn on the power to the PLC to check that the BATT LED is off.
If the PLC is transported with the BATT LED on or the battery exhausted, the battery-backed data may be
unstable during transportation.
B
The main unit of the PLC has a built-in battery.
Instruction List
When the battery voltage drops, the BATT LED lights, and the special auxiliary relay (M8005 or M8006) turns
on. In this case, replace the battery FX3U-32BL.
Character-code
The battery is required to retain (backup) program memory and "keep device" data and maintain clock
operation in the event of a power outage.
Data Retained By Backup Battery
Program memory Internal RAM parameters, programs, device comments, file registers
• Auxiliary relay, state (for annunciator included), timer (cumulative type), counter, data D
register keep device
models
Discontinued
Device memory
• Extended register
• Sampling trace result
Current time Current time clock
22.2 Specifications
Item Specifications Remarks
Nominal voltage 3V Battery voltage can be monitored with PLC data register D8005.
22.2.1 Differences between main unit’s internal battery and the optional battery
Although the optional battery (FX3U-32BL) serves as the same as the main unit’s internal battery, they differ in
the ways described below.
They may also have different external colors due to dates of manufacture.
Main Unit Internal Battery Optional Battery (Spare)
A nameplate label indicating the product model
and lot No. is affixed.
Connector Connector
External 410 0 1
FX3U-32BL
0
appearance
LOT.44
............
0
41 0 01
Nameplate
437
FX3U Series Programmable Controllers 22 FX3U-32BL (Battery)
User’s Manual - Hardware Edition 22.3 Battery Handling
Bttery Life(years)
5
according to the graph to the right and order the replacement batteries in
advance. 4
3
2
1
0
0 10 20 30 40 50
22.3.2 Reading the date of manufacture Ambient temperature(°C)
L OT.4 4
FX3U-32BL
Year (Example: 2004) Month (Example: Apr) LOT.44
Last digit of calendar 1 to 9 : Jan to Sept. ............
year X : Oct, Y : Nov, Z : Dec
001 Connector
41
0
0 4 1 0 0 1
0
41
001
Ref. No.
Month (Example: Apr)
1 to 9 : Jan to Sept.
0 : Oct, Y : Nov, Z : Dec
Year (Example: 2004) Last 2 digits of Western-calendar year
• M8006
Battery low-voltage is latched.
• D8005
Battery voltage can be monitored.
438
FX3U Series Programmable Controllers 22 FX3U-32BL (Battery)
User’s Manual - Hardware Edition 22.4 Battery-Free Operation
21
22.4 Battery-Free Operation
Cassette
Memory
FX3U series operation is possible without a battery (PLC’s internal battery removed) when the following
conditions are satisfied.
→ Refer to the FX3U / FX3UC Programming Manuals for details concerning battery-free operation.
22
1. A memory cassette must be installed.
Battery
2. The following devices must not be used as "keep" devices.
Auxiliary relays, state (for annunciator included), timers (cumulative type), counters, data register "keep"
device, extended registers.
(M8000-,D8000-)
Special Devices
4. The clock function must be disabled.
Instruction List
C
Character-code
D
models
Discontinued
439
FX3U Series Programmable Controllers 22 FX3U-32BL (Battery)
User’s Manual - Hardware Edition 22.5 Battery Replacement
Step 4 of the replacement procedure (below), must be performed within 20 seconds after step 3, or
the memory content could be lost.
1) Battery replacement requires users to verify data integrity such as the PLC program (when a memory
cassette is not attached), latched (battery backed) device values and RTC values. Before switching the
PLC to RUN, ensure the safety of the operation.
2) If the battery backed data becomes unstable, clear the latched (battery backed) devices, and transfer the
data again. Set the RTC and default values again if necessary.
→ For the clear method of keeping devices, refer to the programming manual.
1. The FX3U series uses a different battery type than those used for the FX2N (F2-40BL) and
FX2NC (FX2NC-32BL) series.
• Not for use with the FX3U series.
2. When performing battery-free operation, the clock stops when the main unit power is turned
OFF.
440
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
21
Cassette
Memory
Appendix A: Operation of Special Devices (M8000 -, D8000 -)
The device numbers and functions of the special auxiliary relays (indicated as "special M" in tables) and 22
special data registers (indicated as "special D" in tables) are shown below.
Battery
Note that functions of certain devices vary depending on the series of the PLC.
Do not use the undefined / blank special auxiliary relays and special data registers in the sequence program
since they are occupied by the CPU.
In addition, do not activate or write to the devices with brackets on the first letter such as [M]8000 or [D]8001
in the program.
→ For detailed explanation, refer to the Programming Manual. A
(M8000-,D8000-)
Special Devices
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
Correspond- Correspond-
Number and Number and
Operation and function ing special
name
Operation and function ing special
device
name
device B
Clock
Instruction List
PLC Status
[M]8010 Not used –
[M]8000
RUN [M]8011 ON and OFF in 10 ms cycle
RUN monitor input – –
10 ms clock pulse (ON: 5 ms, OFF: 5 ms)
NO contact
M8061 [M]8012
ON and OFF in 100 ms cycle
[M]8001
RUN monitor
Error occurrence
–
100 ms clock
pulse
(ON: 50 ms, OFF: 50 ms)
–
C
Character-code
NC contact M8000 [M]8013 ON and OFF in 1 sec cycle
–
1 sec clock pulse (ON: 500 ms, OFF: 500 ms)
[M]8002 M8001 [M]8014 ON and OFF in 1 min cycle
Initial pulse – –
1 min clock pulse (ON: 30 sec, OFF: 30 sec)
NO contact M8002 Clock stop and preset
M 8015 –
[M]8003
Initial pulse
M8003
–
For real time clock
Time read display is stopped
D
1 scan time M 8016 –
For real time clock
models
Discontinued
NC contact
±30 seconds correction
ON when either M8060, M8061, M 8017 –
[M]8004 For real time clock
M8064, M8065, M8066, or M8067 D8004
Error occurrence Installation detection (Always ON)
is ON. [M]8018 –
For real time clock
[M]8005 Real time clock (RTC) error
ON when battery voltage is below M 8019 –
Battery voltage D8005 For real time clock
the value set in D8006.
low
Flag
[M]8006 It is set when battery voltage low is
D8006 [M]8020 ON when the result of addition/
detected.
Battery error latch –
Zero subtraction is 0.
ON for 1 scan, when detecting [M]8021 ON when the result of subtraction is
momentary power failure –
[M]8007 Borrow less than the min. negative number.
Even if M8007 turns ON, PLC D8007
Momentary power ON when 'carry' occurs as a result
continues to RUN mode in case D8008 M 8022
failure of addition or when an overflow –
duration of power loss is within Carry
occurs as a result of shift operation.
period of time specified in D8008.
[M]8023 Not used –
It is set when momentary power
BMOV direction specification
failure is detected. M 8024*1 (FNC 15)
–
[M]8008
If power loss time is longer than
Power failure D8008 HSC mode
period of time specified in D8008, M 8025*1 (FNC 53 to 55)
–
detected
M8008 is reset and PLC is turned
RAMP mode
in STOP mode.(M8000=OFF). M 8026*1 (FNC 67)
–
[M]8009 ON when 24V DC power fails in
D8009 PR mode
24V DC down either powered extension unit M 8027*1 (FNC 77)
–
441
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
Correspond- Correspond-
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
PLC Mode Interrupt Disable
*1 When M8030 set to ON, LED on M8050
M 8030 PLC is not lit even if low battery – (input interrupt) –
Battery LED OFF voltage is detected.
I00 disable*4
• If an input interrupt or timer
M 8031*1 If this special auxiliary relay is M8051 interrupt occurs while a special
Non-latch activated, the ON/OFF image – (input interrupt) –
auxiliary relay for that interrupt
memory all clear memory of Y, M, S, T, and C, and I10 disable*4 (M8050 - M8058) is ON, the
present values of T, C, D, special
M8052 interrupt will not operate.
data registers and R are cleared to
(input interrupt) For example, turning M8050 ON –
M 8032*1 zero.
disables the I00 interrupt;
Latch memory However, file registers (D) in – I20 disable*4
hence, the interrupt routine is not
all clear program memory, and extension M8053 processed even in an allowable
file registers (ER) in the memory (input interrupt) –
program area.
cassette are not cleared.
I30 disable*4
M 8033 When PLC is switched from RUN • If an input interrupt or timer
M8054
Memory hold to STOP, image memory and data – interrupt occurs while a special
(input interrupt) –
STOP memory are retained. auxiliary relay for that interrupt
I40 disable*4 (M8050 - M8058) is OFF,
M 8034*1 All external output contacts of PLC
–
are turned OFF. M8055 a) The interrupt will be
All outputs disable
(input interrupt) accepted. –
M 8035
– I50 disable*4 b) The interrupt routine will be
Forced RUN mode processed promptly if it is
M8056
M 8036 →Refer to Programming Manual permitted by the EI (FNC
– (Timer interrupt) –
Forced RUN signal for details. 04) instruction. However, if
I6 disable*4 the DI (FNC 05) instruction
M 8037
– M8057 disables interrupts, the
Forced STOP signal
(Timer interrupt) interrupt program will not –
[M]8038 Communication parameter setting D8176 to be processed until EI (FNC
Parameter setting flag (for N:N network setting) D8180 I7 disable*4
04) permits the interrupts.
M 8039 When M8039 is ON, PLC waits until M8058
Constant scan scan time specified in D8039 and D8039 (Timer interrupt) –
mode then executes cyclic operation. I8 disable*4
M8059
*1. Executed at END instruction
Counter interrupt Interrupt of I010 to I060 disabled –
disable*4
Step Ladder and Annunciator
M 8040 While M8040 is turned ON, transfer *4. Cleared when PLC switches from RUN to STOP.
–
Transfer disable between states is disabled.
Error Detection
[M]8041*2 Transfer from initial state is enabled
–
Transfer start in automatic operation mode. [M]8060 I/O configuration error D8060
[M]8042 Pulse output is given in response [M]8061 PLC hardware error D8061
–
Start pulse to a start input. [M]8062 Not used –
M 8043*2 Set this in the last state of zero [M]8063*5*6 Serial communication error 1 [ch1] D8063
Zero return –
return mode. [M]8064 Parameter error D8064
complete
D8065
M 8044*2 Set this when machine zero return
– D8069
Zero point condition is detected. [M]8065 Syntax error
D8314
M 8045 Disables the ’all output reset’ D8315
All output reset function when the operation mode – D8066
disable is changed. D8069
[M]8066 Ladder error
ON when M8047 is ON and either D8314
[M]8046*3 of S0 to S899 or S1000 to S4095 is M8047 D8315
STL state ON active. D8067
M 8047*3 D8069
D8040 to D8047 are enabled when D8040 to [M]8067*7 Operation error
D8314
STL monitoring M8047 is ON. D8047
enable D8315
D8068
[M]8048*3 ON when M8049 is ON and either M 8068 Operation error latch D8312
Annunciator –
of S900 to S999 is ON. D8313
operate
M 8069*8 I/O bus check –
M 8049*2 D8049 is enabled when M8049 is D8049
Annunciator ON. M8048 *5. Not cleared PLC.
enable
*6. Serial communication error 2 [ch2] PLC is detected by
*2. Cleared when PLC switches from RUN to STOP. M8438.
*3. Executed at END instruction. *7. Cleared when PLC switches from STOP to RUN.
*8. When M8069 is ON, I/O bus check is executed.
442
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
Parallel Link Memory Information
*1 Parallel link Set M8070 when [M]8101 –
M 8070 –
using master station.
Parallel link Set M8071 when
[M]8102
[M]8103
Not used
–
–
22
M 8071*1 –
Battery
using slave station. [M]8104 –
[M]8072 Parallel link ON when operating – [M]8105 ON when writing to flash memory –
Parallel link [M]8106 Not used –
[M]8073 ON when M8070 or M8071 setting –
[M]8107 Device comment registration check D8107
is incorrect
*1. Cleared when PLC switches from STOP to RUN.
[M]8108 Not used
Output Refresh Error
–
A
(M8000-,D8000-)
Special Devices
Sampling Trace [M]8109 Output refresh error –
[M]8074 Not used – [M]8110 –
[M]8075 Ready request for sampling trace [M]8111 –
[M]8076 Start request for sampling trace M 8112 –
[M]8077 ON during sampling trace D8075 to M 8113 –
[M]8078
ON when sampling trace is D8098 M 8114
Not used
– B
completed M 8115 –
Instruction List
[M]8079 Sampling trace system area M 8116 –
[M]8080 – M 8117 –
[M]8081 – [M]8118 –
[M]8082 – [M]8119 –
[M]8083 – RS (FNC 80) and Computer Link [ch1] C
[M]8084 – [M]8120 Not used –
Character-code
Not used
[M]8085 – RS (FNC 80) instruction:
[M]8121*3 Send wait flag
–
[M]8086 –
[M]8087 – *3 RS (FNC 80) instruction:
M 8122 D8122
[M]8088 – Send request
[M]8089
Flag
–
M 8123*3
RS (FNC 80) instruction:
Receive complete flag
D8123 D
models
Discontinued
BKCMP (FNC194 to FNC199) RS (FNC 80) instruction:
[M]8124 –
[M]8090 instructions - Block comparison – Carrier detection flag
signal [M]8125 Not used –
COMRD (FNC182) and BINDA [M]8126 Computer link [ch1]: Global ON
M 8091 (FNC261) instructions - Output – Computer link [ch1]:
[M]8127
character quantity selector signal On-demand send processing
[M]8092 – Computer link [ch1]: D8127
M 8128
[M]8093 – On-demand error flag D8128
Computer link [ch1]: D8129
[M]8094 –
[M]8095 Not used – On-demand Word/Byte changeover
M 8129
RS (FNC 80) instruction:
[M]8096 –
Time-out check flag
[M]8097 –
[M]8098 – *3. Cleared when PLC switches from RUN to STOP or RS
instruction is OFF.
High Speed Ring Counter
High speed ring counter operation
M 8099*2 (in units of 0.1ms, 16 bits)
D8099
443
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
Correspond- Correspond-
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
High Speed Counter Comparison, High Speed Table, and Positioning Advanced Function
HSZ (FNC 55) instruction: M 8160*2 SWAP function of XCH (FNC 17) –
M 8130
Table comparison mode *2*3
M 8161 8-bit process mode –
HSZ (FNC 55) instruction: D8130
[M]8131 Table comparison mode M 8162 High speed parallel link mode –
completion flag [M]8163 –
Not used
HSZ (FNC 55) and PLSY (FNC 57) M 8164 –
M 8132
instructions: Speed pattern mode SORT2 (FNC149) instruction:
HSZ (FNC 55) and PLSY (FNC 57) D8131 to M 8165*2 Sorting in descending order
–
instructions: D8134
[M]8133 [M]8166 Not used –
Speed pattern mode completion
flag HKY (FNC 71) instruction:
M 8167*2 HEX data handling function
–
[M]8134 –
[M]8135 – SMOV (FNC 13) instruction:
Not used M 8168* HEX data handling function
–
[M]8136 –
[M]8169 Not used –
[M]8137 –
HSCT (FNC280) instruction: *2. Cleared when PLC switches from RUN to STOP.
[M]8138 D8138
Instruction execution complete flag *3. Applicable to ASC (FNC 76), RS (FNC 80), ASCI (FNC
HSCS(FNC 53), HSCR(FNC 54), 82), HEX (FNC 83), CCD (FNC 84), and CRC (FNC188)
HS2(FNC 55), HSCT(FNC280) instructions.
[M]8139 instructions: D8139
High speed counter comparison
instruction executing Pulse Catch
ZRN (FNC156) instruction: M 8170*4 Input X000 pulse catch –
M 8140 –
CLR signal output function enable M 8171 *4 Input X001 pulse catch –
[M]8141 –
M 8172*4 Input X002 pulse catch –
[M]8142 –
Not used *4 Input X003 pulse catch –
M 8173
[M]8143 –
*4 Input X004 pulse catch –
[M]8144 – M 8174
M 8145 [Y000] Pulse output stop command – M 8175*4 Input X005 pulse catch –
M 8146 [Y001] Pulse output stop command – M 8176*4 Input X006 pulse catch –
[Y000] Pulse output monitor
[M]8147 – M 8177*4 Input X007 pulse catch –
(BUSY/READY)
[Y001] Pulse output monitor *4. Cleared when PLC switches from STOP to RUN.
[M]8148 – EI (FNC 04) instruction is necessary.
(BUSY/READY)
[M]8149 Not used –
Inverter Communication Function Communication Port Channel Setting
[M]8150 Not used – Parallel link channel switch (OFF:
M 8178 –
Inverter communication in ch1/ON: ch2)
[M]8151 *1 D8151
execution [ch1] M 8179 N:N network channel switch*5 –
*1 Inverter communication error [ch1] D8152
[M]8152 *5. The channel is specified by either creating or not creating
*1 Inverter communication error latch M8179 in setting program.
[M]8153 D8153
[ch1] •ch1: not creating M8179 in setting program
IVBWR (FNC274) instruction error •ch2: creating M8179 in setting program
[M]8154*1 [ch1]
D8154
444
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
N:N Network Counter Up/down Counter Counting Direction
[M]8180 – M 8200 C200 –
[M]8181
[M]8182
Not used –
–
M 8201
M 8202
C201
C202
–
–
22
Battery
Data communication error M 8203 C203 –
[M]8183
(Master station) M 8204 C204 –
Data communication error M 8205 C205 –
[M]8184
(Slave station No.1) M 8206 C206 –
Data communication error
[M]8185
(Slave station No.2)
M 8207
M 8208
C207
C208
–
–
A
Data communication error
(M8000-,D8000-)
Special Devices
[M]8186 M 8209 C209 –
(Slave station No.3)
D8201 to M 8210 C210 –
Data communication error
[M]8187 D8218 M 8211 C211 –
(Slave station No.4)
Data communication error M 8212 C212 –
[M]8188 M 8213 C213 –
(Slave station No.5)
Data communication error M 8214 C214 – B
[M]8189
(Slave station No.6) M 8215 C215 When M8 –
Instruction List
is ON, the
Data communication error M 8216 C216 corresponding C is –
[M]8190
(Slave station No.7) M 8217 C217 changed to down mode. –
[M]8191 Data communication in execution M 8218 C218 • ON: Down count operation –
[M]8192 – M 8219 C219 • OFF: Up count operation –
[M]8193 – M 8220 C220 – C
[M]8194 – M 8221 C221 –
Character-code
Not used
[M]8195 – M 8222 C222 –
[M]8196 – M 8223 C223 –
[M]8197 – M 8224 C224 –
High Speed Counter Edge Count Specification M 8225 C225 –
M 8198*1*2
C251, C252, C254: 1/4 edge count
selector
– M 8226 C226 – D
M 8227 C227 –
models
Discontinued
C253, C255, or C253 (OP): 1/4 M 8228 C228 –
M 8199*1*2 edge count selector
–
M 8229 C229 –
*1. OFF: 1 edge count M 8230 C230 –
ON: 4 edge count M 8231 C231 –
*2. Cleared when PLC switches from RUN to STOP. M 8232 C232 –
M 8233 C233 –
M 8234 C234 –
High Speed Counter Up/down Counter Counting Direction
M 8235 C235 –
M 8236 C236 –
M 8237 C237 –
M 8238 C238 When M8 is ON, the –
M 8239 C239 corresponding C is –
M 8240 C240 changed to down mode. –
M 8241 C241 • ON: Down count operation –
M 8242 C242 • OFF: Up count operation –
M 8243 C243 –
M 8244 C244 –
M 8245 C245 –
445
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
Correspond- Correspond-
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
High Speed Counter Up/down Counter Monitoring Timing Clock and Positioning
[M]8246 C246 – DUTY (FNC186) instruction:
[M]8330 D8330
[M]8247 C247 – Timing clock output 1
When C of 1-phase
[M]8248 C248 – DUTY (FNC186) instruction:
2-input or 2-phase [M]8331 D8331
[M]8249 C249 2-input counter is in down – Timing clock output 2
[M]8250 C250 mode, the – DUTY (FNC186) instruction:
[M]8332 D8332
Timing clock output 3
[M]8251 C251 corresponding M8 –
DUTY (FNC186) instruction:
[M]8252 C252 turns ON. – [M]8333 D8333
• ON: Down count operation Timing clock output 4
[M]8253 C253 –
• OFF: Up count operation DUTY (FNC186) instruction:
[M]8254 C254 – [M]8334 D8334
Timing clock output 5
[M]8255 C255 – [M]8335 Not used –
[M]8256 to [M]8259 Not used – DVIT (FNC151) instruction:
Analog Special Adapter M 8336*4 Interrupt input specification D8336
M 8260 to M 8269*1 1st special adapter – function enabled
[M]8337 Not used –
M 8270 to M 8279*1 2nd special adapter –
PLSV (FNC157) instruction:
M 8280 to M 8289*1 3rd special adapter –
M 8338 Acceleration/deceleration –
*1 4th special adapter – operation
M 8290 to M 8299
[M]8339 Not used –
*1. The number of connected FX3U-4AD-ADP, FX3U-4DA-
ADP, FX3U-4AD-TC-ADP and FX3U-4AD-PT-ADP units is [Y000] Pulse output monitor (ON:
[M]8340 –
BUSY/ OFF: READY)
counted from the main unit side.
*4 [Y000] Clear signal output function
M 8341 –
enable
Flag
[Y000] Zero return direction
[M]8300 to [M]8303 Not used – M 8342*4 specification
–
Turns ON when the multiplication
[M]8304*2 Zero or division result is 0.
– M 8343 [Y000] Forward limit –
M 8344 [Y000] Reverse limit –
[M]8305 Not used –
Turns ON when the division result M 8345*4 [Y000] DOG signal logic reverse –
[M]8306*2 Carry overflows. –
[Y000] Zero point signal logic
M 8346*4 reverse
–
[M]8307 to [M]8315 Not used –
*2. Supported in Ver. 2.30 or later [Y000] Interrupt signal logic
M 8347*4 reverse
–
446
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Operation and function ing special Operation and function ing special
name name
device device
Positioning High Speed Counter Function
[Y001] Pulse output monitor Operation status of C235, C241,
[M]8350 –
(ON: BUSY/ OFF: READY)
[Y001] Clear signal output function
[M]8380*3 C244, C246, C247, C249, C251,
C252, and C254
–
22
M 8351*1 –
Battery
enable [M]8381*3 Operation status of C236 –
[Y001] Zero return direction Operation status of C237, C242,
M 8352*1 specification
– [M]8382*3 –
and C245
M 8353 [Y001] Forward limit – Operation status of C238, C248,
M 8354 [Y001] Reverse limit – [M]8383*3 C248 (OP), C250, C253, and C255
–
M 8355*1 [Y001] DOG signal logic reverse – [M]8384*3 Operation status of C239 and C243 – A
[Y001] Zero point signal logic [M]8385*3
(M8000-,D8000-)
Special Devices
Operation status of C240 –
M 8356*1 reverse
–
[M]8386*3 Operation status of C244 (OP) –
[Y001] Interrupt signal logic
M 8357*1 reverse
– [M]8387 *3 Operation status of C245 (OP) –
[Y001] Positioning instruction Contact for high speed counter
[M]8358 – [M]8388 –
M 8359*1
activation
[Y001] Pulse output stop command – M 8389
function change
External reset input logic reverse –
B
Instruction List
[Y002] Pulse output monitor Function changeover device for
[M]8360 – M 8390 –
(ON: BUSY/ OFF: READY) C244
[Y002] Clear signal output function Function changeover device for
M 8391 –
M 8361*1 enable
– C245
[Y002] Zero return direction Function changeover device for
M 8392 –
M 8362*1 specification
– C248 and C253 C
M 8363 [Y002] Forward limit – *3. Cleared when PLC switches from STOP to RUN.
Character-code
M 8364 [Y002] Reverse limit –
Interrupt Program
M 8365*1 [Y002] DOG signal logic reverse –
[M]8393 Contact for delay time setting D8393
[Y002] Zero point signal logic
M 8366*1 reverse
– HCMOV (FNC189):
[M]8394 –
M 8367*1
[Y002] Interrupt signal logic
reverse
– [M]8395
Drive contact for interrupt program
–
D
models
Discontinued
[Y002] Positioning instruction [M]8396 Not used –
[M]8368 –
activation [M]8397 –
M 8369*1 [Y002] Pulse output stop command – Ring Counter
[Y003] Pulse output monitor Ring counter operation D8398,
[M]8370*2 – M 8398
(ON: BUSY/ OFF: READY) (in units of 1ms, 32 bits)*4 D8399
[Y003] Clear signal output function [M]8399 Not used –
M 8371*1*2 –
enable
*4. 1ms ring counter (D8399, D8398) will operate after M8398
[Y003] Zero return direction turns ON.
M 8372*1*2 –
specification
M 8373*2 [Y003] Forward limit – RS2 (FNC 87) [ch1]
M 8374*2 [Y003] Reverse limit – [M]8400 Not used –
M 8375*1*2 [Y003] DOG signal logic reverse – [M]8401*5 RS2 (FNC 87) [ch1] Send wait flag –
[Y003] Zero point signal logic *5 RS2 (FNC 87) [ch1] Send request D8402
M 8376*1*2 – M 8402
reverse
RS2 (FNC 87) [ch1]
[Y003] Interrupt signal logic M 8403*5 D8403
M 8377*1*2 – Receive complete flag
reverse
RS2 (FNC 87) [ch1]
[Y003] Positioning instruction [M]8404 –
[M]8378*2 – Carrier detection flag
activation
RS2 (FNC 87) [ch1]
M 8379*1*2 [Y003] Pulse output stop command – [M]8405*6 Data set ready (DSR) flag
–
447
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-1 Special Auxiliary Relay (M8000 to M8511)
Correspond-
Number and
Operation and function ing special
name
device
RS2 (FNC 87) [ch2] and Computer Link [ch2]
[M]8410 to [M]8420 Not used –
[M]8421*1 RS2 (FNC 87) [ch2] Send wait flag –
M 8422*1 RS2 (FNC 87) [ch2] Send request D8422
RS2 (FNC 87) [ch2]
M 8423*1 Receive complete flag
D8423
Error Detection
[M]8430 to [M]8437 Not used –
M 8438 Serial communication error 2 [ch2] D8438
[M]8439 to [M]8448 Not used –
[M]8449 Special block error flag D8449
[M]8450 to [M]8459 Not used –
Positioning
DVIT (FNC151) instruction [Y000]
M 8460 D8336
User interrupt input command
DVIT (FNC151) instruction [Y001]
M 8461 D8336
User interrupt input command
DVIT (FNC151) instruction [Y002]
M 8462 D8336
User interrupt input command
DVIT (FNC151) instruction [Y003]
M 8463*3 User interrupt input command
D8336
448
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
21
Appendix A-2 Special Data Register (D8000 to D8511)
Cassette
Memory
Correspond- Correspond-
Number and Number and
Content of register ing special Content of register ing special
name name
device device
PLC Status Clock 22
[D]8010 Accumulated instruction-execution
Battery
Default value is shown on the right
(in 1ms steps) Present scan time time from 0 step –
(Writes from system ROM at power *2 (in units of 0.1 ms)
D 8000
ON) – [D]8011
Watchdog timer Minimum value of scan time
Value overwritten by program is Minimum scan –
(in units of 0.1 ms)
valid after END or WDT instruction
execution.
time*2
[D]8012
A
Maximum value of scan time
(M8000-,D8000-)
Special Devices
BCD converted Maximum scan –
2 4 2 2 0 (in units of 0.1 ms)
[D]8001 value time*2
PLC type and Version 2.20 D8101 D 8013 0 to 59 seconds
system version –
FX3U, FX3UC, FX2N, FX2NC Second data (for real time clock)
Series
D 8014 0 to 59 minutes
• 2...2K steps Minute data (for real time clock)
– B
• 4...4K steps
Instruction List
D 8015 0 to 23 hours
[D]8002 • 8...8K steps –
D8102 Hour data (for real time clock)
Memory capacity • If 16K steps or more
"K8" is written to D8002 and "16" D 8016 1 to 31 days
–
or "64" is written to D8102. Day data (for real time clock)
Character-code
–
Year data (for real time clock)
BCD converted D 8019
8 0 6 0 value 0 (Sunday) to 6 (Saturday)
[D]8004 Day-of-the-week –
M8004 (for real time clock)
Error number M data
8060 to 8068
(when M8004 is ON) *2. Indicated value includes waiting time of constant scan D
operation (when M8039 is activated).
models
Discontinued
BCD converted
[D]8005 3 0 value
(in units of 0.1V) M8005 Input Filter
Battery voltage
Battery voltage present value
(Example: 3.0V) D 8020
Input filter value of X000 to X017*3
Input filter –
[D]8006 (Default: 10 ms)
Default: adjustment
Low battery
(Writes from system ROM at power M8006 [D]8021 –
voltage detection
ON) [D]8022 –
level
[D]8007 Operation frequency of M8007 is [D]8023 –
Momentary power stored. M8007 [D]8024 Not used –
failure count Cleared at power-off.
[D]8025 –
D 8008
Default: [D]8026 –
Power failure M8008
10 ms (AC power supply type) [D]8027 –
detection
Minimum input device number of Index Register Z0 and V0
[D]8009
extension units and extension [D]8028 Value of Z0 (Z) register*4 –
24V DC failed M8009
power units in which 24V DC has
device [D]8029 Value of V0 (V) register*4 –
failed.
*1. D8003 becomes the undermentioned content. *3. X000 to X007 in FX3U-16M .
Present value Type of memory Protect switch *4. The values of Z1 to Z7 and V1 to V7 are stored in D8182
to D8195.
02H Flash memory cassette OFF
0AH Flash memory cassette ON
10H Built-in memory in PLC –
449
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
Correspond- Correspond-
Number and Number and
Content of register ing special Content of register ing special
name name
device device
Constant Scan Error Detection
[D]8030 – If the unit or block corresponding to
[D]8031 – a programmed
I/O number is not actually loaded,
[D]8032 – M8060 is set to ON and the first
[D]8033 – device number of the erroneous
[D]8034 Not used – block is written to D8060.
[D]8035 – [D]8060 Example:If X020 is unconnected. M8060
[D]8036 – BCD converted
1 0 2 0 value
[D]8037 –
Device number
[D]8038 – 10 to 337
Default: 0 ms (in 1 ms steps) 1: Input X
D 8039 0: Output Y
(Writes from system ROM at power
Constant scan M8039
ON) [D]8061 Error code for PLC hardware error M8061
duration
Can be overwritten by program
Error code for PLC/PP
Stepladder and Annunciator [D]8062 M8062
communication error
*1
[D]8040 Error code for serial
[D]8063 M8063
ON state number communication error 1 [ch1]
1 [D]8064 Error code for parameter error M8064
[D]8041*1 [D]8065 Error code for syntax error M8065
ON state number
[D]8066 Error code for ladder error M8066
2
[D]8067*2 Error code for operation error M8067
[D]8042*1
ON state number Operation error step number
D 8068*2 M8068
3 latched*3
The smallest number out of active
[D]8043*1 Error step number of M8065 to M8065 to
state ranging from S0 to S899 and [D]8069*2
ON state number S1000 to S4095 is stored in D8040 M8067*4 M8067
4 and the second-smallest state
M8047 *2. Cleared when PLC switches from STOP to RUN.
[D]8044 *1 number is stored in D8041.
*3. In case of 32K steps or more, step number is stored in
ON state number Active state numbers are then [D8313, D8312].
5 sequentially stored in registers up
to D8047 (Max. 8 points). *4. In case of 32K steps or more, step number is stored in
[D]8045*1 [D8315, D8314].
ON state number
6
Parallel Link (Refer to Data Communication Edition for details.)
[D]8046*1 Parallel link error time-out check
ON state number [D]8070 –
time: 500 ms
7
[D]8071 –
[D]8047*1 [D]8072 Not used –
ON state number
8 [D]8073 –
[D]8048 Not used –
When M8049 is ON, the smallest
[D]8049*1 number out of active annunciator
On state minimum relay ranging from S900 to S999 is M8049
number stored in D8049.
[D]8050 to [D]8059 Not used –
450
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Content of register ing special Content of register ing special
name name
device device
Sampling Trace*1 Output Refresh Error
[D]8074 Y number where output refresh
[D]8109 M8109
[D]8075
error occurs 22
[D]8110 to [D]8119 Not used –
Battery
[D]8076
RS (FNC 80) and Computer Link [ch1]
[D]8077
RS (FNC 80) instruction and
[D]8078
D 8120*3 computer link [ch1] –
[D]8079 Communication format setting
[D]8080
D 8121*3
Computer link [ch1]
Station number setting
– A
[D]8081
(M8000-,D8000-)
Special Devices
[D]8082 RS (FNC 80) instruction:
[D]8122*4 Remaining points of transmit data
M8122
[D]8083
RS (FNC 80) instruction:
[D]8084 [D]8123*4 Monitoring receive data points
M8123
These devices are occupied by the
[D]8085 PLC system when the sampling
[D]8086 trace function is used in the M8075 to
M8079
D 8124
RS (FNC 80) instruction:
Header <Default: STX>
– B
A6GPP, A6PHP, A7PHP, or
Instruction List
[D]8087 *1 RS (FNC 80) instruction:
personal computer . D 8125 –
[D]8088 Terminator <Default: ETX>
[D]8089 [D]8126 Not used –
[D]8090 Computer link [ch1]
D 8127 Specification of on-demand head
[D]8091
[D]8092
device register C
Computer link [ch1]
Character-code
[D]8093 M8126 to
D 8128 Specification of on-demand data
M8129
[D]8094 length register
[D]8095 RS (FNC 80) instruction, computer
[D]8096 D 8129*3 link [ch1]
[D]8097
Time-out time setting
D
[D]8098 *3. Latch (battery backed) device
models
Discontinued
*4. Cleared when PLC switches from RUN to STOP.
*1. The sampling trace devices are used by peripheral
equipment.
*2. 0.1ms high speed ring counter D8099 will operate after
M8099 turns ON.
Memory Information
451
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
Correspond- Correspond-
Number and Number and
Content of register ing special Content of register ing special
name name
device device
High Speed Counter Comparison, High Speed Table, and Positioning Error code for inverter
[D]8157*1 communication [ch2]
M8157
HSZ (FNC 55) instruction:
[D]8130 High speed comparison table M8130 Inverter communication error step
counter [D]8158 number latched [ch2] M8158
HSZ (FNC 55) and PLSY (FNC 57) Default: -1
[D]8131 instructions: M8132 Parameter number when error
Speed pattern table counter occurs during IVBWR (FNC274)
[D]8159 M8159
[D]8132 Lower HSZ (FNC 55) and PLSY instruction [ch2]
(FNC 57) instructions: M8132 Default: -1
[D]8133 Upper Speed pattern frequency
*1. Cleared when PLC switches from STOP to RUN.
[D]8134 Lower HSZ (FNC 55) and PLSY
(FNC 57) instructions: Advanced Function
M8132
[D]8135 Upper Number of target pulses for
speed pattern [D]8160 –
D 8140 Lower Accumulated number of *2. Access restriction status by 2nd keyword
pulses output to Y000 for Program Present
PLSY (FNC 57) and PLSR Present Access restriction Monitor-
– value
value status Read Write ing
D 8141 Upper (FNC 59) instructions, or change
current address of Y000 for H0000 2nd keyword is not set. *3 *3 *3 *3
positioning instruction
H0010 Write protection –
D 8142 Lower Accumulated number of
H0011 Read / write protection – –
pulses output to Y001 for
PLSY (FNC 57) and PLSR All online operation
– H0012 – – – –
protection
D 8143 Upper (FNC 59) instructions, or
current address of Y001 for H0020 Keyword cancel
positioning instruction
*3. The accessibility is restricted depending on the keyword
[D]8144 to [D]8149 Not used –
setting status.
Inverter Communication Function
Response wait time of inverter
D 8150 –
communication [ch1]
Step number of instruction during
[D]8151 inverter communication [ch1] M8151
Default: -1
Error code for inverter
[D]8152*1 communication [ch1]
M8152
452
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Content of register ing special Content of register ing special
name name
device device
N:N Network (setting) N:N Network (monitoring)
[D]8170 – [D]8200 Not used –
[D]8171 Not used – [D]8201 Current link scan time – 22
[D]8172 – [D]8202 Maximum link scan time –
Battery
[D]8173 Station number – Number of communication error at
[D]8203
[D]8174 Total number of slave stations – master station
(M8000-,D8000-)
Special Devices
D 8178 Refresh range setting M8038 Number of communication error at
[D]8206
D 8179 Retry count setting slave station No.3
D 8180 Comms time-out setting Number of communication error at
[D]8207
[D]8181 Not used – slave station No.4
Index Register Z1 to Z7 and V1 to V7 [D]8208
Number of communication error at
slave station No.5
B
[D]8182 Value of Z1 register –
Instruction List
Number of communication error at
[D]8183 Value of V1 register – [D]8209
slave station No.6
[D]8184 Value of Z2 register –
Number of communication error at
[D]8185 Value of V2 register – [D]8210
slave station No.7 M8183 to
Code of communication error at M8191
[D]8186
[D]8187
Value of Z3 register
Value of V3 register
–
–
[D]8211
master station C
Character-code
[D]8188 Value of Z4 register – Code of communication error at
[D]8212
slave station No.1
[D]8189 Value of V4 register –
Code of communication error at
[D]8190 Value of Z5 register – [D]8213
slave station No.2
[D]8191 Value of V5 register –
Code of communication error at
[D]8192 Value of Z6 register – [D]8214
slave station No.3 D
[D]8193 Value of V6 register – Code of communication error at
models
Discontinued
[D]8215
[D]8194 Value of Z7 register – slave station No.4
[D]8195 Value of V7 register – Code of communication error at
[D]8216
slave station No.5
[D]8196 –
Code of communication error at
[D]8197 – [D]8217
Not used slave station No.6
[D]8198 –
Code of communication error at
[D]8199 – [D]8218
slave station No.7
[D]8219 to [D]8259 Not used –
Analog Special Adapter
D 8260 to D 8269 1st special adapter*1
D 8270 to D 8279 2nd special adapter*1
D 8280 to D 8289 3rd special adapter*1
D 8290 to D 8299 4th special adapter*1
453
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
Correspond- Correspond-
Number and Number and
Content of register ing special Content of register ing special
name name
device device
Display Module Function FX3U-7DM D 8342 [Y000] Bias speed Default: 0 –
Control device (D) for display module D 8343 Lower [Y000] Maximum speed
D 8300 – –
• Default: K-1
D 8344 Upper • Default: 100000
Control device (M) for display module
D 8301 – [Y000] Creep speed
• Default: K-1 D 8345 –
• Default: 1000
Language display setting
D 8346 Lower [Y000] Zero return speed
[D]8302*1 • Japanese: K0 – –
• English: Other than K0 D 8347 Upper Default: 50000
LCD contrast setting value [Y000] Acceleration time
[D]8303 – D 8348 –
• Default: K0 • Default: 100
[D]8304 to [D]8309 – [Y000] Deceleration time
D 8349 –
• Default: 100
[D]8305 –
D 8350 Lower [Y001] Current value register
[D]8306 – –
Not used D 8351 Upper • Default: 0
[D]8307 –
D 8352 [Y001] Bias speed Default: 0 –
[D]8308 –
D 8353 Lower [Y001] Maximum speed
[D]8309 – –
D 8354 Upper • Default: 100000
*1. Latch (battery backed) device
[Y001] Creep speed
D 8355 –
RND (FNC184) • Default: 1000
[D]8310 Lower RND (FNC184) instruction: D 8356 Lower [Y001] Zero return speed
–
Data for generating random D 8357 Upper • Default: 50000
–
[D]8311 Upper number
• Default: K1 [Y001] Acceleration time
D 8358 –
• Default: 100
Syntax, Circuit, Operation, or Unconnected I/O Designation Error
Step Number [Y001] Deceleration time
D 8359 –
• Default: 100
D 8312 Lower Operation error step
M8068 D 8360 Lower [Y002] Current value register
D 8313 Upper number latched (32-bit) –
D 8361 Upper • Default: 0
*2 Lower Error step number of
[D]8314 M8065 to D 8362 [Y002] Bias speed Default: 0 –
[D]8315 *2 Upper M8065 to M8067 (32-bit) M8067
D 8363 Lower [Y002] Maximum speed
–
[D]8316 Lower Step number of instruction D 8364 Upper • Default: 100000
specifying an unconnected
M8316 [Y002] Creep speed
[D]8317 Upper I/O number (directly or D 8365 –
indirectly using index register) • Default: 1000
BFM initialization function: D 8366 Lower [Y002] Zero return speed
[D]8318 M8318 –
Error unit number D 8367 Upper • Default: 50000
BFM initialization function: [Y002] Acceleration time
[D]8319 M8318 D 8368 –
Error BFM number • Default: 100
[D]8320 to [D]8328 Not used – [Y002] Deceleration time
D 8369 –
• Default: 100
*2. Cleared when PLC switches from STOP to RUN.
D 8370*3 Lower [Y003] Current value register –
Timing Clock and Positioning
D 8371*3 Upper • Default: 0 –
[D]8329 Not used –
D 8372*3 [Y003] Bias speed Default: 0 –
DUTY (FNC186) instruction:
[D]8330 M8330
Scan counting for timing clock output 1 D 8373*3 Lower [Y003] Maximum speed –
[D]8331
DUTY (FNC186) instruction:
M8331 D 8374*3 Upper • Default: 100000 –
Scan counting for timing clock output 2
D 8375*3 [Y003] Creep speed Default: 1000 –
DUTY (FNC186) instruction:
[D]8332 M8332 D 8376*3 Lower [Y003] Zero return speed –
Scan counting for timing clock output 3
DUTY (FNC186) instruction: D 8377*3 Upper • Default: 50000 –
[D]8333 M8333
Scan counting for timing clock output 4
[Y003] Acceleration time
DUTY (FNC186) instruction: D 8378*3 • Default: 100
–
[D]8334 M8334
Scan counting for timing clock output 5
[Y003] Deceleration time
DVIT (FNC151) instruction: D 8379*3 • Default: 100
–
D 8336 M8336
Specification of interrupt input
[D]8380 to [D]8392 Not used –
[D]8337 to [D]8339 Not used –
*3. Available only when two FX3U-2HSY-ADP adapters are
D 8340 Lower [Y000] Current value register connected to an PLC.
–
D 8341 Upper • Default: 0
454
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-2 Special Data Register (D8000 to D8511)
21
Correspond- Correspond-
Cassette
Memory
Number and Number and
Content of register ing special Content of register ing special
name name
device device
Interrupt Program [D]8424 Not used –
D 8393 Delay time M8393 Communication parameter display
[D]8425 –
[D]8394 –
[ch2]
22
[D]8426 Not used –
[D]8395 –
Battery
Not used Computer link [ch2]
[D]8396 –
D 8427 Specification of on-demand head
[D]8397 – device register
Ring Counter Computer link [ch2]
M8426 to
D 8428 Specification of on-demand data
D 8398 Lower Up-operation ring counter
of 0 to 2,147,483,647 M8398
length register
M8429
A
D 8399 Upper (in units of 1ms, 32-bit)*1 RS2 (FNC 87) [ch2], computer link
(M8000-,D8000-)
Special Devices
D 8429 [ch2]
*1. 1ms ring counter (D8399, D8398) will operate after M8398 Time-out time setting
turns ON. RS2 (FNC 87) [ch2]
D 8430 –
Header 1 and 2 <Default: STX>
RS2 (FNC 87) [ch1]
RS2 (FNC 87) [ch2]
D 8400
RS2 (FNC 87) [ch1]
Communication format setting
–
D 8431
Header 3 and 4
–
B
RS2 (FNC 87) [ch2]
Instruction List
[D]8401 Not used – D 8432 –
Terminator 1 and 2 <Default: ETX>
RS2 (FNC 87) [ch1] RS2 (FNC 87) [ch2]
[D]8402*2 Remaining points of transmit data
M8402 D 8433 –
Terminator 3 and 4
RS2 (FNC 87) [ch1] RS2 (FNC 87) [ch2]
[D]8403*2 Monitoring receive data points
M8403 [D]8434 –
Receive sum (received data)
[D]8404 Not used – RS2 (FNC 87) [ch2]
C
[D]8435 –
Receive sum (calculated result)
Character-code
Communication parameter display
[D]8405 –
[ch1] [D]8436 RS2 (FNC 87) [ch2] Send sum –
[D]8406 – [D]8437 Not used –
[D]8407 Not used –
*3. Cleared when PLC switches from RUN to STOP.
[D]8408 –
RS2 (FNC 87) [ch1]
Error Detection D
D 8409 –
Time-out time setting Error code for serial
models
Discontinued
[D]8438 M8438
communication error 2 [ch2]
RS2 (FNC 87) [ch1]
D 8410 – RS2 (FNC 87) [ch2] and Computer Link [ch2]
Header 1 and 2 <Default: STX>
RS2 (FNC 87) [ch1] [D]8439 Operation mode display [ch2] –
D 8411 –
Header 3 and 4 Error Detection
RS2 (FNC 87) [ch1] [D]8440 to [D]8448 Not used –
D 8412 –
Terminator 1 and 2 <Default: ETX>
[D]8449 Special block error code M8449
RS2 (FNC 87) [ch1]
D 8413 – [D]8450 to [D]8459 Not used –
Terminator 3 and 4
RS2 (FNC 87) [ch1] Positioning [FX3U and FX3UC PLCs]
[D]8414 –
Receive sum (received data) [D]8460 to [D]8463 Not used –
RS2 (FNC 87) [ch1] DSZR (FNC150) and ZRN
[D]8415 –
Receive sum (calculated result) (FNC156) instructions:
D 8464 M8464
[D]8416 RS2 (FNC 87) [ch1] Send sum – [Y000] Clear signal device
specification
[D]8417 –
Not used DSZR (FNC150) and ZRN
[D]8418 – (FNC156) instructions:
D 8465 M8465
[D]8419 Operation mode display [ch1] – [Y001] Clear signal device
specification
*2. Cleared when PLC switches from RUN to STOP. DSZR (FNC150) and ZRN
RS2 (FNC 87) [ch2] and Computer Link [ch2] (FNC156) instructions:
D 8466 M8466
[Y002] Clear signal device
RS2 (FNC 87) [ch2] specification
D 8420 –
Communication format setting
DSZR (FNC150) and ZRN
Computer link [ch2] Station *4 (FNC156) instructions:
D 8421 – D 8467 M8467
number setting [Y003] Clear signal device
specification
RS2 (FNC 87) [ch2] Remaining
[D]8422*3 points of transmit data
M8422
[D]8468 to [D]8511 Not used –
*3 RS2 (FNC 87) [ch2] Monitoring *4. Available only when two FX3U-2HSY-ADP adapters are
[D]8423 M8423
receive data points connected to an PLC.
455
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-3 Analog special adapters [M8260 to M8299 and D8260 to D8299]
Appendix A-3 Analog special adapters [M8260 to M8299 and D8260 to D8299]
When analog special adapters are connected, operations and functions are assigned to the devices shown in
the tables below in accordance with the number of connected analog special adapters.
Devices which cannot be written are shaded in "Operation and function" column.
→ For details, refer to the manual of each product.
456
FX3U Series Programmable Controllers A Operation of Special Devices (M8000 -, D8000 -)
User’s Manual - Hardware Edition A-3 Analog special adapters [M8260 to M8299 and D8260 to D8299]
21
Appendix A-3-2 Special data registers (D8260 to D8299)
Cassette
Memory
Operation and function
Number
FX3U-4AD-ADP FX3U-4DA-ADP FX3U-4AD-PT-ADP FX3U-4AD-TC-ADP
1st analog special adapter
D 8260 Input data Ch1 Output data Ch1 Measured temperature Ch1 Measured temperature Ch1 22
D 8261 Input data Ch2 Output data Ch2 Measured temperature Ch2 Measured temperature Ch2
Battery
D 8262 Input data Ch3 Output data Ch3 Measured temperature Ch3 Measured temperature Ch3
D 8263 Input data Ch4 Output data Ch4 Measured temperature Ch4 Measured temperature Ch4
Number of averaging times for Number of averaging times for Number of averaging times for
D 8264 Ch1 (1 to 4095)
Not used Ch1 (1 to 4095) Ch1 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8265 Ch2 (1 to 4095)
Number of averaging times for
Not used Ch2 (1 to 4095) Ch2 (1 to 4095)
Number of averaging times for Number of averaging times for
A
D 8266 Not used
(M8000-,D8000-)
Special Devices
Ch3 (1 to 4095) Ch3 (1 to 4095) Ch3 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8267 Ch4 (1 to 4095)
Not used Ch4 (1 to 4095) Ch4 (1 to 4095)
D 8268 Error status Error status Error status Error status
D 8269 Model code: K1 Model code: K2 Model code: K20 Model code: K10
2nd analog special adapter
D 8270 Input data Ch1 Output data Ch1 Measured temperature Ch1 Measured temperature Ch1
B
Instruction List
D 8271 Input data Ch2 Output data Ch2 Measured temperature Ch2 Measured temperature Ch2
D 8272 Input data Ch3 Output data Ch3 Measured temperature Ch3 Measured temperature Ch3
D 8273 Input data Ch4 Output data Ch4 Measured temperature Ch4 Measured temperature Ch4
Number of averaging times for Number of averaging times for Number of averaging times for
D 8274 Ch1 (1 to 4095)
Not used Ch1 (1 to 4095) Ch1 (1 to 4095)
D 8275
Number of averaging times for
Ch2 (1 to 4095)
Not used
Number of averaging times for Number of averaging times for
Ch2 (1 to 4095) Ch2 (1 to 4095)
C
Character-code
Number of averaging times for Number of averaging times for Number of averaging times for
D 8276 Ch3 (1 to 4095)
Not used Ch3 (1 to 4095) Ch3 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8277 Ch4 (1 to 4095)
Not used Ch4 (1 to 4095) Ch4 (1 to 4095)
D 8278 Error status Error status Error status Error status
D 8279 Model code: K1
3rd analog special adapter
Model code: K2 Model code: K20 Model code: K10
D
models
Discontinued
D 8280 Input data Ch1 Output data Ch1 Measured temperature Ch1 Measured temperature Ch1
D 8281 Input data Ch2 Output data Ch2 Measured temperature Ch2 Measured temperature Ch2
D 8282 Input data Ch3 Output data Ch3 Measured temperature Ch3 Measured temperature Ch3
D 8283 Input data Ch4 Output data Ch4 Measured temperature Ch4 Measured temperature Ch4
Number of averaging times for Number of averaging times for Number of averaging times for
D 8284 Ch1 (1 to 4095)
Not used Ch1 (1 to 4095) Ch1 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8285 Ch2 (1 to 4095)
Not used Ch2 (1 to 4095) Ch2 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8286 Ch3 (1 to 4095)
Not used Ch3 (1 to 4095) Ch3 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8287 Ch4 (1 to 4095)
Not used Ch4 (1 to 4095) Ch4 (1 to 4095)
D 8288 Error status Error status Error status Error status
D 8289 Model code: K1 Model code: K2 Model code: K20 Model code: K10
4th analog special adapter
D 8290 Input data Ch1 Output data Ch1 Measured temperature Ch1 Measured temperature Ch1
D 8291 Input data Ch2 Output data Ch2 Measured temperature Ch2 Measured temperature Ch2
D 8292 Input data Ch3 Output data Ch3 Measured temperature Ch3 Measured temperature Ch3
D 8293 Input data Ch4 Output data Ch4 Measured temperature Ch4 Measured temperature Ch4
Number of averaging times for Number of averaging times for Number of averaging times for
D 8294 Ch1 (1 to 4095)
Not used Ch1 (1 to 4095) Ch1 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8295 Ch2 (1 to 4095)
Not used Ch2 (1 to 4095) Ch2 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8296 Ch3 (1 to 4095)
Not used Ch3 (1 to 4095) Ch3 (1 to 4095)
Number of averaging times for Number of averaging times for Number of averaging times for
D 8297 Ch4 (1 to 4095)
Not used Ch4 (1 to 4095) Ch4 (1 to 4095)
D 8298 Error status Error status Error status Error status
D 8299 Model code: K1 Model code: K2 Model code: K20 Model code: K10
457
FX3U Series Programmable Controllers B Instruction List
User’s Manual - Hardware Edition B-1 Basic Instructions
Mnemonic Function
458
FX3U Series Programmable Controllers B Instruction List
User’s Manual - Hardware Edition B-3 Applied Instructions ... in Ascending Order of FNC Number
21
Appendix B-3 Applied Instructions ... in Ascending Order of FNC Number
Cassette
Memory
FNC No. Mnemonic Function FNC No. Mnemonic Function
Program Flow Data Operation
00 CJ Conditional Jump 40 ZRST Zone Reset
22
01 CALL Call Subroutine 41 DECO Decode
Battery
02 SRET Subroutine Return 42 ENCO Encode
03 IRET Interrupt Return 43 SUM Sum of Active Bits
04 EI Enable Interrupt 44 BON Check Specified Bit Status
45 MEAN Mean
05
06
DI
FEND
Disable Interrupt
Main Routine Program End 46 ANS Timed Annunciator Set
A
(M8000-,D8000-)
Special Devices
07 WDT Watchdog Timer Refresh 47 ANR Annunciator Reset
08 FOR Start a FOR/NEXT Loop 48 SQR Square Root
09 NEXT End a FOR/NEXT Loop 49 FLT Conversion to Floating Point
Move and Compare High Speed Processing
10 CMP Compare 50 REF Refresh B
Instruction List
11 ZCP Zone Compare 51 REFF Refresh and Filter Adjust
12 MOV Move 52 MTR Input Matrix
13 SMOV Shift Move 53 HSCS High Speed Counter Set
14 CML Complement 54 HSCR High Speed Counter Reset
15 BMOV Block Move 55 HSZ High Speed Counter Zone Compare C
56 SPD Speed Detection
Character-code
Move and Compare
16 FMOV Fill Move 57 PLSY Pulse Y Output
17 XCH Exchange 58 PWM Pulse Width Modulation
18 BCD Conversion to Binary Coded Decimal 59 PLSR Acceleration/Deceleration Setup
19 BIN Conversion to Binary Handy Instruction
D
Arithmetic and Logical Operation (+, –, ×, ÷) 60 IST Initial State
models
Discontinued
20 ADD Addition 61 SER Search a Data Stack
21 SUB Subtraction 62 ABSD Absolute Drum Sequencer
22 MUL Multiplication 63 INCD Incremental Drum Sequencer
23 DIV Division 64 TTMR Teaching Timer
24 INC Increment 65 STMR Special Timer
25 DEC Decrement 66 ALT Alternate State
26 WAND Logical Word AND 67 RAMP Ramp Variable Value
27 WOR Logical Word OR 68 ROTC Rotary Table Control
28 WXOR Logical Exclusive OR 69 SORT SORT Tabulated Data
29 NEG Negation External FX I/O Device
Rotation and Shift Operation 70 TKY Ten Key Input
30 ROR Rotation Right 71 HKY Hexadecimal Input
31 ROL Rotation Left 72 DSW Digital Switch (Thumbwheel Input)
32 RCR Rotation Right with Carry External FX I/O Device
33 RCL Rotation Left with Carry 73 SEGD Seven Segment Decoder
34 SFTR Bit Shift Right 74 SEGL Seven Segment With Latch
Rotation and Shift Operation 75 ARWS Arrow Switch
35 SFTL Bit Shift Left 76 ASC ASCII Code Data Input
36 WSFR Word Shift Right 77 PR Print (ASCII Code)
37 WSFL Word Shift Left 78 FROM Read From A Special Function Block
38 SFWR Shift Write [FIFO/FILO Control] 79 TO Write To A Special Function Block
39 SFRD Shift Read [FIFO Control]
459
FX3U Series Programmable Controllers B Instruction List
User’s Manual - Hardware Edition B-3 Applied Instructions ... in Ascending Order of FNC Number
123 EDIV Floating Point Division 167 TWR Set RTC data
460
FX3U Series Programmable Controllers B Instruction List
User’s Manual - Hardware Edition B-3 Applied Instructions ... in Ascending Order of FNC Number
21
FNC No. Mnemonic Function FNC No. Mnemonic Function
Cassette
Memory
Others Data Comparison
181 – 220 to
–
182 COMRD Read Device Comment Data 223
Battery
185 – 226 LD< Load Compare S1 < S2
186 DUTY Timing Pulse Generation
227 –
187 –
228 LD<> Load Compare S1 ≠ S2
188
189
CRC
HCMOV
Cyclic Redundancy Check
High Speed Counter Move
229 LD<= Load Compare S1 ≤ S2 A
(M8000-,D8000-)
Special Devices
Block Data Operation 230 LD>= Load Compare S1 ≥ S2
Instruction List
194 BKCMP= Block Data Compare S1 = S2
235 –
195 BKCMP> Block Data Compare S1 > S2 236 AND<> AND Compare S1 ≠ S2
196 BKCMP< Block Data Compare S1 < S2 237 AND<= AND Compare S1 ≤ S2
197 BKCMP<> Block Data Compare S1 ≠ S2 238 AND>= AND Compare S1 ≥ S2 C
198 BKCMP<= Block Data Compare S1 ≤ S2
Character-code
239 –
199 BKCMP>= Block Data Compare S1 ≥ S2 Data Comparison
Character String Control 240 OR= OR Compare S1 = S2
200 STR BIN to Character String Conversion 241 OR> OR Compare S1 > S2
201 VAL Character String to BIN Conversion
242 OR< OR Compare S1 < S2
D
202 $+ Link Character Strings
models
Discontinued
243 –
203 LEN Character String Length Detection
244 OR<> OR Compare S1 ≠ S2
Extracting Character String Data from the
204 RIGHT
Right 245 OR<= OR Compare S1 ≤ S2
Extracting Character String Data from the
205 LEFT 246 OR>= OR Compare S1 ≥ S2
Left
247 to
206 MIDR Random Selection of Character Strings –
249
Random Replacement of Character
207 MIDW Data Table Operation
Strings
250 to
208 INSTR Character string search –
255
209 $MOV Character String Transfer
256 LIMIT Limit Control
Data Operation 3
257 BAND Dead Band Control
210 FDEL Deleting Data from Tables
258 ZONE Zone Control
211 FINS Inserting Data to Tables
259 SCL Scaling (Coordinate by Point Data)
212 POP Shift Last Data Read [FILO Control]
260 DABIN Decimal ASCII to BIN Conversion
Data Operation 3
261 BINDA BIN to Decimal ASCII Conversion
213 SFR Bit Shift Right with Carry
262 to
214 SFL Bit Shift Left with Carry –
268
215 to 269 SCL2 Scaling 2 (Coordinate by X/Y Data)
–
219
461
FX3U Series Programmable Controllers B Instruction List
User’s Manual - Hardware Edition B-3 Applied Instructions ... in Ascending Order of FNC Number
462
FX3U Series Programmable Controllers C Character-code
User’s Manual - Hardware Edition C-1 ASCII Code Table
21
Cassette
Memory
Appendix C: Character-code
22
Appendix C-1 ASCII Code Table
Battery
• (ASCII Code: 5C) symbol is displayed as " " even if the language display setting at FX3U-7DM is set to
English (LANGUAGE: ENGLISH).
• The Character at ASCII Code: 7E "~" is not displayed.
A
1. ASCII code table (7-bit code expressed in hexadecimal)
(M8000-,D8000-)
Special Devices
Example . "A " becomes 41H(hexadecimal number) by ASCII code.
Hexadecimal 0 1 2 3 4 5 6 7 8 9 A B C D E F
0 SP 0 @ P p
´
1 ! 1 A Q a q
B
2 ” 2 B R b r
Instruction List
3 # 3 C S c s
4 $ 4 D T d t
5 % 5 E U e u
6 & 6 F V f v
7 ’ 7 G W g w As for this range, the C
Japanese syllabary is
Character-code
8 ( 8 H X h x displayed.
9 ) 9 I Y i y
A * : J Z j z
B + ; K [ k {
C , < L l D
D – = M ] m }
models
Discontinued
E . > N ˆ n
F / ? O _ o
463
FX3U Series Programmable Controllers D Discontinued models
User’s Manual - Hardware Edition
464
FX3U Series Programmable Controllers D Discontinued models
User’s Manual - Hardware Edition
21
MEMO
Cassette
Memory
22
Battery
A
(M8000-,D8000-)
Special Devices
B
Instruction List
C
Character-code
D
models
Discontinued
465
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition Warranty
Warranty
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range 2. Onerous repair term after discontinuation of
If any faults or defects (hereinafter "Failure") found to be production
the responsibility of Mitsubishi occurs during use of the 1) Mitsubishi shall accept onerous product repairs for
product within the gratis warranty term, the product shall be seven (7) years after production of the product is
repaired at no cost via the sales representative or discontinued.
Mitsubishi Service Company. However, if repairs are Discontinuation of production shall be notified with
required onsite at domestic or overseas location, expenses Mitsubishi Technical Bulletins, etc.
to send an engineer will be solely at the customer's
discretion. Mitsubishi shall not be held responsible for any 2) Product supply (including repair parts) is not available
re-commissioning, maintenance, or testing on-site that after production is discontinued.
involves replacement of the failed module. 3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local
[Gratis Warranty Term]
overseas FA Center. Note that the repair conditions at
The gratis warranty term of the product shall be for one
each FA Center may differ.
year after the date of purchase or delivery to a designated
place. Note that after manufacture and shipment from 4. Exclusion of loss in opportunity and secondary
Mitsubishi, the maximum distribution period shall be six (6) loss from warranty liability
months, and the longest gratis warranty term after Regardless of the gratis warranty term, Mitsubishi shall not
manufacturing shall be eighteen (18) months. The gratis be liable for compensation of damages caused by any
warranty term of repair parts shall not exceed the gratis cause found not to be the responsibility of Mitsubishi, loss
warranty term before repairs. in opportunity, lost profits incurred to the user or third
person by Failures of Mitsubishi products, special
[Gratis Warranty Range]
damages and secondary damages whether foreseeable or
1) The range shall be limited to normal use within the not , compensation for accidents, and compensation for
usage state, usage methods and usage environment, damages to products other than Mitsubishi products,
etc., which follow the conditions and precautions, etc., replacement by the user, maintenance of on-site
given in the instruction manual, user's manual and equipment, start-up test run and other tasks.
caution labels on the product.
5. Changes in product specifications
2) Even within the gratis warranty term, repairs shall be
The specifications given in the catalogs, manuals or
charged for in the following cases.
technical documents are subject to change without prior
a) Failure occurring from inappropriate storage or
notice.
handling, carelessness or negligence by the user.
Failure caused by the user's hardware or software 6. Product application
design. 1) In using the Mitsubishi MELSEC programmable logic
b) Failure caused by unapproved modifications, etc., controller, the usage conditions shall be that the
to the product by the user. application will not lead to a major accident even if any
c) When the Mitsubishi product is assembled into a problem or fault should occur in the programmable
user's device, Failure that could have been logic controller device, and that backup and fail-safe
avoided if functions or structures, judged as functions are systematically provided outside of the
necessary in the legal safety measures the user's device for any problem or fault.
device is subject to or as necessary by industry
2) The Mitsubishi programmable logic controller has
standards, had been provided.
been designed and manufactured for applications in
d) Failure that could have been avoided if
general industries, etc. Thus, applications in which the
consumable parts (battery, backlight, fuse, etc.)
public could be affected such as in nuclear power
designated in the instruction manual had been
plants and other power plants operated by respective
correctly serviced or replaced.
power companies, and applications in which a special
e) Relay failure or output contact failure caused by
quality assurance system is required, such as for
usage beyond the specified Life of contact
Railway companies or Public service purposes shall
(cycles).
be excluded from the programmable logic controller
f) Failure caused by external irresistible forces such
applications.
as fires or abnormal voltages, and failure caused
In addition, applications in which human life or
by force majeure such as earthquakes, lightning,
property that could be greatly affected, such as in
wind and water damage.
aircraft, medical applications, incineration and fuel
g) Failure caused by reasons unpredictable by
devices, manned transportation, equipment for
sc ientific tec hnol ogy s tanda rds a t tim e of
recreation and amusement, and safety devices, shall
shipment from Mitsubishi.
also be excluded from the programmable logic
h) Any other failure found not to be the responsibility
controller range of applications.
of Mitsubishi or that admitted not to be so by the
However, in certain cases, some applications may be
user.
possible, providing the user consults their local
Mitsubishi representative outlining the special
requirements of the project, and providing that all
parties concerned agree to the special circumstances,
solely at the users discretion.
466
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition Revised History
Revised History
Date Revision Discription
7/2005 A First Edition
2/2006 B • The following products are added:
- Main unit of transistor output type
FX3U-16MT/ES, FX3U-16MT/ESS, FX3U-32MT/ES, FX3U-32MT/ESS,
FX3U-48MT/ES, FX3U-48MT/ESS, FX3U-64MT/ES, FX3U-64MT/ESS,
FX3U-80MT/ES, FX3U-80MT/ESS
Contents are added to product introduction (Chapter 3), specifications, external
dimensions, terminal layout (Chapter 4), examination of system configuration
(Chapter 6), wiring examples for each purpose (Chapter 13), etc.
- Main unit of AC power type
FX3U-128MR/ES, FX3U-128MT/ES, FX3U-128MT/ESS
- Main unit of DC power type
FX3U-16MR/DS, FX3U-16MT/DS, FX3U-16MT/DSS
FX3U-32MR/DS, FX3U-32MT/DS, FX3U-32MT/DSS
FX3U-48MR/DS, FX3U-48MT/DS, FX3U-48MT/DSS
FX3U-64MR/DS, FX3U-64MT/DS, FX3U-64MT/DSS
FX3U-80MR/DS, FX3U-80MT/DS, FX3U-80MT/DSS
Contents are added to product introduction (Chapter 3), specifications, external
dimensions, terminal layout (Chapter 4), examination of system configuration
(Chapter 6), installation in enclosure (Chapter 8), example of power supply wiring
(Chapter 9), example of input wiring (Chapter 10), example of output wiring
(Chapter 12), etc.
- Input/output powered extension unit of DC power type
FX2N-48ER-DS, FX2N-48ET-DSS, FX2N-48ER-D, FX2N-48ET-D
Contents are added to product introduction (Chapter 3), examination of system
configuration (Chapter 6), installation in enclosure (Chapter 8), example of power
supply wiring (Chapter 9), input/output powered extension units (Chapter 15), etc.
- 8-point type input/output extension block
FX2N-8ER-ES/UL, FX2N-8ER, FX2N-8EX-ES/UL, FX2N-8EX, FX2N-8EX-UA1/UL,
FX2N-8EYR-ES/UL, FX2N-8EYR, FX2N-8EYT-ESS/UL, FX2N-8EYT,
FX2N-8EYT-H
Contents are added to product introduction (Chapter 3), examination of system
configuration (Chapter 6), input/output extension block (Chapter 16), etc.
- Special function blocks
FX3U-4AD, FX3U-4DA, FX3U-20SSC-H
Contents are added to product introduction (Chapter 3), examination of system
configuration (Chapter 6), installation in enclosure (Chapter 8), other extension
devices (Chapter 18), etc.
- Extension power supply unit
FX3U-1PSU-5V
Contents are added to product introduction (Chapter 3), examination of system
configuration (Chapter 6), installation in enclosure (Chapter 8), example of power
supply wiring (Chapter 9), etc.
Chapter 17 added for Extension power supply unit
• Ver. 2.30 is supported.
- Two types of instructions are added (Appendix B-1).
For the details of instructions, refer to the programming manual.
- Special auxiliary relays and special data registers are added (Appendix A).
• Cautions on write during RUN are added (Subsection 5.2.4).
• The applicability of other peripheral equipment is added (Section 5.5).
5/2006 C • EN61131-2:2003 added to EMC directive and LVD directive in FX2N series.
467
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition Revised History
468
MITSUBISHI ELECTRIC
HEADQUARTERS EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES EURASIAN REPRESENTATIVES
MITSUBISHI ELECTRIC EUROPE B.V. GEVA Beijer Electronics UAB Kazpromautomatics Ltd.
German Branch Wiener Straße 89 Savanoriu Pr. 187 2, Scladskaya str.
Gothaer Straße 8
Phone: +43 (0)2252 / 85 55 20 Phone: +370 (0)5 / 232 3101 Phone: +7 3212 / 50 11 50
Phone: +49 (0)2102 / 486-0 Fax: +43 (0)2252 / 488 60 Fax: +370 (0)5 / 232 2980 Fax: +7 3212 / 50 11 50
Fax: +49 (0)2102 / 486-1120 TEHNIKON INTEHSIS srl ELEKTROSTILY
MITSUBISHI ELECTRIC EUROPE B.V. Oktyabrskaya 16/5, Off. 703-711 bld. Traian 23/1 Rubzowskaja nab. 4-3, No. 8
French Branch
25, Boulevard des Bouvets Phone: +375 (0)17 / 210 46 26 Phone: +373 (0)22 / 66 4242 Phone: +7 495 / 545 3419
Fax: +375 (0)17 / 210 46 26 Fax: +373 (0)22 / 66 4280 Fax: +7 495 / 545 3419
Phone: +33 (0)1 / 55 68 55 68 Koning & Hartman B.V. Koning & Hartman B.V. ICOS
Fax: +33 (0)1 / 55 68 57 57 Industrial Solutions Haarlerbergweg 21-23 Industrial Computer Systems ZAO
MITSUBISHI ELECTRIC EUROPE B.V. Woluwelaan 31 Ryazanskij Prospekt, 8A, Office 100
Irish Branch Phone: +31 (0)20 / 587 76 00
Westgate Business Park, Ballymount Phone: +32 (0)2 / 257 02 40 Fax: +31 (0)20 / 587 76 05 Phone: +7 495 / 232 0207
Fax: +32 (0)2 / 257 02 49 Beijer Electronics AS Fax: +7 495 / 232 0327
Phone: +353 (0)1 4198800 AKHNATON Postboks 487 NPP “URALELEKTRA”
Fax: +353 (0)1 4198890 4 Andrej Ljapchev Blvd. Pb 21 Sverdlova 11A
MITSUBISHI ELECTRIC EUROPE B.V. Phone: +47 (0)32 / 24 30 00
Italian Branch Phone: +359 (0)2 / 97 44 05 8 Fax: +47 (0)32 / 84 85 77 Phone: +7 343 / 353 2745
Viale Colleoni 7 Fax: +359 (0)2 / 97 44 06 1 MPL Technology Sp. z o.o. Fax: +7 343 / 353 2461
INEA CR d.o.o. Ul. Krakowska 50
Phone: +39 039 / 60 53 1 Losinjska 4 a
Fax: +39 039 / 60 53 312 Phone: +48 (0)12 / 630 47 00
MITSUBISHI ELECTRIC CORPORATION Phone: +385 (0)1 / 36 940 - 01/ -02/ -03 Fax: +48 (0)12 / 630 47 01 MIDDLE EAST
Office Tower “Z” 14 F Fax: +385 (0)1 / 36 940 - 03 SIRIUS TRADING & SERVICES SRL REPRESENTATIVE
AutoCont Control Systems, s.r.o. Aleea Lacul Morii Nr. 3 TEXEL ELECTRONICS Ltd.
Tokyo 104-6212 Jelinkova 59/3
Phone: +81 3 622 160 60 2 Ha´umanut, P.O.B. 6272
Phone: +40 (0)21 / 430 40 06
Fax: +81 3 622 160 75 Phone: +420 (0)59 / 5691 150 Fax: +40 (0)21 / 430 40 02 Phone: +972 (0)9 / 863 08 91
MITSUBISHI ELECTRIC EUROPE B.V. Fax: +420 (0)59 / 5691 199 CRAFT Consulting & Engineering d.o.o. Fax: +972 (0)9 / 885 24 30
UK Branch AutoCont Control Systems, s.r.o. Bulevar Svetog Cara Konstantina 80-86
Travellers Lane Technologická 374/6
Phone: +381 (0)18 / 292-24-4/5 , 523 962
Phone: +44 (0)1707 / 27 61 00 Phone: +420 595 691 150 Fax: +381 (0)18 / 292-24-4/5 , 523 962
Fax: +44 (0)1707 / 27 86 95 AFRICAN REPRESENTATIVE
Fax: +420 595 691 199 INEA SR d.o.o.
MITSUBISHI ELECTRIC EUROPE B.V. B:TECH, a.s. Karadjordjeva 12/260 CBI Ltd.
Spanish Branch Na Ostrove 84 Private Bag 2016
Carretera de Rubí 76-80 Phone: +381 (0)26 / 617 163
Phone: +420 (0)569 / 408 841 Fax: +381 (0)26 / 617 163 Phone: + 27 (0)11 / 928 2000
Phone: +34 93 / 565 3131 Fax: +420 (0)569 / 408 889 Fax: + 27 (0)11 / 392 2354
Fax: +34 93 / 589 1579 CS MTrade Slovensko, s.r.o.
B:TECH, a.s. Vajanskeho 58
MITSUBISHI ELECTRIC AUTOMATION USA Headoffice
500 Corporate Woods Parkway U Borové 69 Phone: +421 (0)33 / 7742 760
Fax: +421 (0)33 / 7735 144
Phone: +1 847 478 21 00 Phone: +420 569 777 777
Fax: +1 847 478 22 83 INEA d.o.o.
Fax: +420 569 777 778 Stegne 11
Beijer Electronics A/S
Lautruphoj 1-3 Phone: +386 (0)1 / 513 8100
Fax: +386 (0)1 / 513 8170
Phone: +45 (0)70 / 26 46 46 Beijer Electronics Automation AB
Fax: +45 (0)70 / 26 48 48 Box 426
Beijer Electronics Eesti OÜ
Pärnu mnt.160i Phone: +46 (0)40 / 35 86 00
Fax: +46 (0)40 / 35 86 02
Phone: +372 (0)6 / 51 81 40 ECONOTEC AG
Fax: +372 (0)6 / 51 81 49 Hinterdorfstr. 12
Beijer Electronics OY
Jaakonkatu 2 Phone: +41 (0)44 / 838 48 11
Fax: +41 (0)44 / 838 48 12
Phone: +358 (0)207 / 463 500 GTS
Fax: +358 (0)207 / 463 501 Darulaceze Cad. No. 43 KAT. 2
UTECO A.B.E.E.
5, Mavrogenous Str. Phone: +90 (0)212 / 320 1640
Fax: +90 (0)212 / 320 1649
Phone: +30 211 / 1206 900 CSC Automation Ltd.
Fax: +30 211 / 1206 999 15, M. Raskova St., Fl. 10, Office 1010
MELTRADE Ltd.
Fertő utca 14. Phone: +380 (0)44 / 494 33 55
Fax: +380 (0)44 / 494-33-66
Phone: +36 (0)1 / 431-9726
Fax: +36 (0)1 / 431-9727
Beijer Electronics SIA
Vestienas iela 2
Phone: +371 (0)784 / 2280
Fax: +371 (0)784 / 2281
MITSUBISHI
ELECTRIC Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Straße 8 /// D-40880 Ratingen /// Germany
FACTORY AUTOMATION Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// info@mitsubishi-automation.com /// www.mitsubishi-automation.com
Specifications subject to change /// Art. no. 168590-E /// 06.2007