PROPOSE PACKAGE OPTION-01

PROJECT : QPMO RENOVATION WORK


LOCATION: TRAILER 5990
PRODUCT : DX AHU PACKAGE UNIT
S.No COMPLIANCE COMPLY REMARKS

The contractor shall supply and install the necessary breakers at the existing electrical
1 panels including all wiring required for the function of the two AHU package units. Yes

2 The two AHU package units shall have electric heating coil in order to maintain the No Proposed with Duct heaters, capacity 3 Kw
required indoor temperature

3 The AHU package unit shall provide an amount of conditioned air at 10,320 CFM No Proposed with 12,500 CFM

4 The AHU package unit shall provide approximately 30 ton cooling, R410 No Proposed with 33.7 ton & R22 refrigerant

PROPOSE PACKAGE OPTION-01


PROJECT : QPMO RENOVATION WORK
LOCATION: TRAILER 5991

PRODUCT : DX AHU PACKAGE UNIT


S.No COMPLIANCE COMPLY REMARKS

1 The contractor shall supply and install the necessary breakers at the existing electrical Yes
panels including all wiring required for the function of the two AHU package units.

The two AHU package units shall have electric heating coil in order to maintain the
2 required indoor temperature No Proposed with Duct heaters, capacity 3 Kw

3 The AHU package unit shall provide an amount of conditioned air at 7,610 CFM No Proposed with 11,000 CFM
4 The AHU package unit shall provide approximately 25 ton cooling, R410 No Proposed with 27.4 ton & R22 refrigerant
PROPOSE PACKAGE OPTION-02
PROJECT : QPMO RENOVATION WORK
LOCATION: TRAILER 5990
PRODUCT : DX AHU PACKAGE UNIT

S.No COMPLIANCE COMPLY REMARKS

The contractor shall supply and install the necessary breakers at the existing
1 electrical panels including all wiring required for the function of the two AHU Yes
package units.
The two AHU package units shall have electric heating coil in order to maintain
2 the No Proposed Duct heaters with capacity 3
Kw
required indoor temperature

3 The AHU package unit shall provide an amount of conditioned air at 10,320 No Proposed two units of flow 7000 &
CFM 8000 CFM
4 The AHU package unit shall provide approximately 30 ton cooling, R410 No Proposed two units of capacity 17 ton
& 13 ton, R410A refrigerant

PROPOSE PACKAGE OPTION-02


PROJECT : QPMO RENOVATION WORK
LOCATION: TRAILER 5991
PRODUCT : DX AHU PACKAGE UNIT
S.No COMPLIANCE COMPLY REMARKS

The contractor shall supply and install the necessary breakers at the existing
1 electrical panels including all wiring required for the function of the two AHU Yes
package units.
The two AHU package units shall have electric heating coil in order to maintain
2 the No Proposed Duct heaters with capacity 3
required indoor temperature Kw

Proposed two units of flow 7000 &


3 The AHU package unit shall provide an amount of conditioned air at 7,610 CFM No 8000 CFM in term to achive specified
cooling
4 The AHU package unit shall provide approximately 25 ton cooling, R410 No Proposed two units of capacity 17 ton
& 13 ton, R410A refrigerant