Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
p(x)
2 As IEEE Flash uses the 2 point method, some
1 1 ln(x) − ln(xm ) (3)
= exp [− ( ) ] changes and/or simplifications were made for a
√2πxσln(x) 2 σln(x) closer similarity of the input parameters used by
where: 𝜎ln(𝑥) is the standard deviation of ln(x), and both programs: All discharges were considered
negative; the front time was fixed at 2µs and tail time
xm is the median value of x. Table 1 shows the
infinity; peak value was sorted according to a
parameters used to sort the discharges using
cumulative probability distribution given by
Equation 3 [7].
Anderson [4] (Equation 6).
Table 1: Statistical Parameters of Negative and
Positive Strokes [7]. 𝑝(𝐼) = 1/(1 + (𝐼𝑐 /31)^2.6) (6)
Negative Positive
Parameter where, Ic is the crest value of stroke current.
Median σ Median Σ
31.1 0.48 35.0 1.21 Two sets of simulations were performed to calculate
IP, kA
3.83 0.55 22.0 1.23 the lightning performance: (a) varying the tower
tf, kA footing resistance and (b) varying the number of
77.5 0.58 230.0 1.33 insulators. The results are presented in Figure 2,
th, kA
and show that, for both cases, there is a strong
Ninety percent of the discharges are considered of similarity between the algorithm proposed and the
negative polarity. Besides that, 60% of the sorted IEEE Flash.
strokes hit the tower, and 40% hit the mid-span.
3.2 Comparison with Sigma SLP
A single value for the average ground flash density To compare the proposed method with Sigma SLP,
along the line should be used. The Electrogeometric data from a 90kV shielded OHL presented in [5] was
Model [1] is used to determine the last step of each used. The lightning performance was calculated at
sorted return stroke (Equations 4 and 5). 4 different arrester configurations: (a) without any
ZnO; (b) two ZnO in all towers; (c) two ZnO in
alternate towers and (d) one ZnO in alternate
𝑟𝑐 = 10𝐼 0.65 (4)
towers. The tower footing resistance values vary
[3.6 + 1.7 ln(43 − 𝑦𝑐 )]𝐼 0.65 𝑦𝑐 < 40𝑚 from 5 to 60Ω.
𝑟𝑔 = { (5)
5.5𝐼 0.65 𝑦𝑐 ≥ 40𝑚
The OHL is composed by sixteen 150-m spans. The
typical tower is 23.3m high and has an impedance
of 175Ω. The insulator strings are composed by six
where: rc is the attractive radius of the shield and
255 x 127mm insulator units. The phase conductors
phase conductors, rg the attractive radius of earth
and shield wires data is given in Table 3 and the
and yc the height (m).
ground flash density is 2.8 discharges per km2 per
year.
3 VALIDATION
To validate the algorithm, two comparisons are
presented. First, with IEEE Flash [4] and secondly
with Sigma SLP [5].
50.0 30.00
Num Outages/100km.year 45.0
Num outages/100km.year
25.00
40.0
35.0 20.00
30.0
15.00
25.0
20.0 10.00
15.0
10.0 5.00
5.0
0.00
0.0 5.00 15.00 25.00 35.00 45.00 55.00
0.0 10.0 20.0 30.0 40.0 50.0 60.0
Tower footing resistance
Tower footing resistance Algorithm (a) Sigma LP (a)
Algorithm Flash Algorithm (b) Sigma LP (b)
(a)
25.00
Num outages/100km.year
35.0 20.00
Num Outages/100km.year
30.0
15.00
25.0
20.0 10.00
15.0
5.00
10.0
0.00
5.0
5.00 15.00 25.00 35.00 45.00 55.00
0.0 Tower footing resistance
7 8 9 10
Algorithm (c) Sigma LP (c)
Number of Insulators
Algorithm (d) Sigma LP (d)
Algorithm Flash
Number of outages/100km.year
1.00
0.80
0.60
0.40
0.20
0.00
0 10 20 30 40 50 60 70 80 90 100
Figure 4: OHL Tower Geometry. Tower
Without ZnO With ZnO 1 ZnO 2 ZnO 3 ZnO
660
600
540 Figure 6: Number of outages/100km.year per
480 tower for OHL Itutinga – Minduri.
420
Rt (Ω)
360
300
240
Finally, to evaluate the effectiveness of different
180 arrester configurations, the towers were ranked by
120
60 their performance without arresters. After that,
0 several simulations were performed considering an
1,600
increasing number of arresters installed from the
1,400
1,200
highest failure rate towers to the lowest ones. Figure
Span Length (m)
the actual outage data. A total of 65406 discharges Figure 7: Reduction in the number of outages for 3
were simulated from which approximately 10000 hit different ZnO arrester configurations, OHL Itutinga
the OHL. The obtained number of - Minduri.
outages/100km.year is presented in Table 4. As
seen, the calculated lightning performance is about As seen, if one arrester is installed per tower, the
40% higher than the observed average maximum reduction in the outage number is around
performance. These results are considered to be in 30% when all towers receive one arrester. On the
good agreement. other hand, when two arresters are installed per
tower, the outages can be reduced in 60%. The
Table 4: OHL Failure Rate number of outages can be reduced to zero only
Number of when three arresters are installed per tower and
Item
outages/100km.year every tower receives the arresters. The same
Observed 6.48 reduction in outages (30%) can be reached by
Simulated 9.11 installing sets of two arresters in 30% of the highest
failure rate towers, or installing sets of tree arresters
A further investigation on the contribution of each in 15% of the towers with worse performance.
individual tower to the number of
outages/100km.year line was performed. Figure 6 Assuming that the estimated performance without
(red line) shows the result. Additionally, an arresters (17.64 outages/100km.year) is a good
estimation of the OHL performance before the estimation for this line, the simulated failure rate
installation of the arresters was performed, reduction is 48% obtained using 140 arresters
considering the same line without any ZnO arrester. actually installed along the 103 towers. Therefore,
it can be inferred from Figure 7 that the same [1] IEEE Std. 1243-1997, “IEEE Guide for
performance improvement can be achieved by improving the lightning performance of
installing sets of tree arresters in 25% of the towers transmission lines,” 1997;
(78 arresters) or sets of two arresters in 60% of the
[2] A. R. Hileman, Insulation Coordination For
towers (124 arresters). In both cases, the total
number of ZnO arresters would be lower than the Power Systems, Marcel Dekker, 1999;
140 units actually installed. The installation of a [3] CIGRE WG 33-01, “Guide to Procedures for
single arrester per tower would not lead to an Estimating the Lightining Performance of
outage reduction of 48%. Transmission Lines”, CIGRE Brochure 63,
1991;
The curves presented in Figure 7 can be seen as a [4] Transmission Line Reference Book, 345kV
fingerprint of this specific OHL. They can be used to
and Above, 2º Ed., 1985;
find a cost effective solution on the configuration
and number of ZnO arresters needed to reach an [5] S. Sadovic, R. Joulie, S. Tartier and E. Brocard,
acceptable lightning performance of this OHL. "Use of line surge arresters for the
improvement of the lightning performance of 63
5 CONCLUSIONS kV and 90 kV shielded and unshielded
This paper presented a Monte Carlo methodology transmission lines," in IEEE Transactions on
to estimate the lightning performance of OHLs Power Delivery, vol. 12, no. 3, pp. 1232-1240,
protected by surge arresters. The methodology was Jul 1997;
implemented in MATLAB environment. The routine [6] H. W. Dommel, Electromagnetic Transients
uses the ATP to perform the electromagnetic Program. Reference Manual. Portland, OR:
transient calculations. Bonneville Power Administration, 1986;
[7] IEEE TF on Parameters of Lightning Strokes,
The methodology was compared with two well-
known lightning performance programs: IEEE Flash “Parameters of lightning
and Sigma SLP. In both cases, the results are in strokes: A review,” IEEE Trans. on Power
good agreement. Differently from IEEE Flash, the Delivery, vol. 20, no. 1, pp. 346-358, January
proposed method compares the resulting stress at 2005;
the insulator string with its supportability not only in [8] J.A. Martinez and F. Castro-Aranda, “Modeling
two points, but all the time and considers the of overhead transmission lines for line arrester
installation of line surge arresters for performance
studies,” IEEE PES General Meeting 2004,
improvement. On the other hand, the main
difference between Sigma SLP and the proposed June 2004, Denver;
method is the focus on individual tower performance [9] J.A. Martinez and F. Castro-Aranda, “Lightning
to search a better performance solution. performance analysis of overhead
Additionally, a real 138 kV OHL operated by CEMIG transmission lines using the EMTP,” IEEE
was studied. A total of 140 ZnO surge arresters Trans. on Power Delivery, vol. 20, no. 3, pp.
were installed along this line and its lightning
2200-2210, July 2005;
performance has been recorded from 2007 to 2015.
The actual performance data was compared with [10] J. A. Martinez and F. Castro-Aranda,
the proposed methodology and good results were "Lightning Flashover Rate of an Overhead
obtained. Transmission Line Protected by Surge
Arresters," Power Engineering Society
Finally, a tower by tower failure rate analysis was
proposed and performed. The approach allows the General Meeting, 2007. IEEE, Tampa, FL,
user to decide on how many ZnO arresters are 2007, pp. 1-6;
needed and in which towers the arresters are to be [11] Electro-Magnetic Transient Program (EMTP),
installed on a certain line to reach a desired lightning Theory Book;
performance. The proposed procedure can be used [12] J. A. Morales, E. A. Orduña, R. J. Cabral and
as a design tool for arrester installation to improve
A. S. Bretas, "Combined TACS-MODELS for
OHL lightning performance.
Footing Tower Resistance considering ground
ACKNOWLEDGMENTS ionization," 2014 North American Power
Symposium (NAPS), Pullman, WA, 2014, pp.
The authors thank the Brazilian agencies: CAPES,
1-5.
FAPEMIG and CNPq for the financial support
provided to this study. [13] S. C. Assis, W. C. Boaventura, J. O. S. Paulino,
R. L. Markiewicz, “Lightning Performance of
REFERENCES Transmission Line with and without Surge
Arresters: Comparison between a Monte Carlo
method and field experience”, Electric Power
Systems Research 149 (2017) 169-17;