Purpose
The purpose of this guide is to provide a basic overcurrent protection philosophy for transformers.
Transformer Overcurrent Protection
Time-current curve (TCC) landmarks (figure 1)
• All landmarks are based on the nominal kVA rating of the transformer
• Full load amps (FLA) – located in the upper decade
• Thermal damage curve – located in the upper 3 decades
• Mechanical damage curve – located in the middle decade
• Inrush points defined @ 12 x FLA and 0.1 seconds, and 25 x FLA and 0.01 seconds
TCC regions (figure 2)
• Equipment operating region – located at and to the left of the FLA and inrush points
• Equipment damage region – located to the right and above the damage curves
• Protective device operating region – located between the equipment operating and damage
regions
Suggested overcurrent protection (figure 3)
• Set protection above the full load amps and inrush points
• Set protection below the damage curves
Comments
• If current penetrates the limits of the thermal damage curve, insulation damage may occur.
• If current penetrates the limits of the mechanical damage curve, cumulative mechanical damage
may occur.
Fig. 1 Transformer TCC landmarks
Fig. 2 Transformer TCC regions
Fig. 3 Transformer overcurrent protection