ZxF100Ax/Cx
E350 Series 2
Technical Data
Date: 05.07.2016
File name: D000027981 E350 Series 2 ZxF100Ax Cx 3-phase Technical Data en h.docx
© Landis+Gyr D000027981 en h
2/8
Revision history
Version Date Comments
d 17.03.2011 Temperature range for display operation changed from 55 °C to 70 °C.
e 01.06.2011 General load switching capacity for supply control switch added.
f 20.12.2011 Maximum cross-section of the conductor is terminal-dependent.
Document template updated.
g 12.12.2012 Company name changed to Landis+Gyr AG.
Auxiliary circuits deleted.
Suspension hanger added.
h 05.07.2016 Updated disclaimer.
Updated with firmware M29 enhancements.
Updated ingress protection rating to IP54.
Updated terminology.
Although the information contained within this document are presented in good faith and believed to be correct, Landis+Gyr (including its
affiliates, agents and employees) disclaim any and all liability for any errors, inaccuracies or incompleteness relating to the product.
Landis+Gyr makes no warranty, representation or guarantee regarding the performance, quality, durability or suitability of the products for
any particular purpose. To the fullest extent permitted by law Landis+Gyr disclaims (1) any and all liability arising out of the use of the
product, (2) any and all liability, including, but without limitation to, special, consequential and indirect damages and losses, and (3) any and
all implied warranties, including, but without limitation to, fitness for purpose and merchantability.
The information contained in this document is strictly confidential and is intended for the addressee only. The unauthorised use, disclosure,
copying, alteration or distribution of this document or the contents thereof is strictly prohibited and may be unlawful.
All product information are subject to change without notice.
MID-specific Data
Frequency
Nominal frequency fn 50 Hz
Current
Tolerance 2%
Reference current Iref selectable: 5, 10 or 20 A
IEC-specific Data
Minimum current Imin ≤ 0.05 x Iref
Terminal cover
Short no free space
Extended 40, 60 or 80 mm free space
203
Material
Housing
Polycarbonate, partly glass-fiber reinforced
140 72 Connections
176 Phase connections
Type screw-type terminals
Diameter steel-type 8.5 mm
Dimensions (with extended 60 mm terminal cover )
Diameter brass-type 9.5 mm
173 84
Minimum conductor cross-section 4 mm2
Maximum conductor cross-section
- (9.5 mm terminals) 35 mm2
- (8.5 mm terminals) 25 mm2
Wire-end ferrules must be fitted on stranded wires!
Screw dimensions M6 x 14
Maximum screw head diameter ≤ 6.6 mm
Cross-slot type Z, size 2, to ISO-4757-1983
Tightening torque < 3 Nm
260
40
140 72
176
13 16
16 13 16
19 16 13
Network type
ZFF 3-phase, 3-wire network
ZMF 3-phase, 4-wire network
Connection type
1 Direct connection
Measured quantities
A Active energy
C Active and reactive energy
Additional functionality
C Meter with communication interface
B Meter with communication interface and supply control switch
Rates
e 1 rate
d 2 rates
t Multi-rate (up to 6 rates)
Anti-tampering
- No anti-tampering
F Anti-tampering
Version
s2 Series 2