Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Adequate clearances around the unit(s) are required for Place each mount in its correct position and lower the
the unrestricted airflow for the air-cooled condenser coils unit carefully onto the mounts ensuring the mount en-
and to prevent re-circulation of warm discharge air back gages in the mounting holes in the unit base frame.
onto the coils. If clearances given are not maintained,
airflow restriction or re-circulation will cause a loss of On adjustable mounts, transfer the unit weight evenly to
unit performance, an increase in power consumption, the springs by turning the mount adjusting nuts (located
and may cause the unit to malfunction. Consideration just below the top plate of the mount) counterclockwise
should also be given to the possibility of down drafts, to raise and clockwise to lower. This should be done
caused by adjacent buildings, which may cause re-cir- two turns at a time until the top plates of all mounts are
culation or uneven unit airflow. between 1/4” and 1/2” (6 and 12 mm) clear of top of
their housing and the unit base is level.
For locations where significant cross winds are expected,
such as exposed roof tops, an enclosure of solid or lou- A more detailed installation instruction
ver type is recommended to prevent wind turbulence is provided on Pages 128-132.
interfering with the unit airflow.
INSTALLATION OF VIBRATION ISOLATORS The liquid must enter the cooler at the
inlet connection. The inlet connection
Optional sets of vibration isolators can be supplied loose for the cooler is at the control panel
with each unit.
end of the cooler.
Using the Isolator tables shipped with the unit in the
information pack, refer to the Dimension Section (Pages
66-121), Weight Distribution and Isolator Mounting
Position Section (Pages 124-127) and Isolator types
(Pages 128-132). Identify each mount and its correct
location on the unit.
30 JOHNSON CONTROLS
FORM 201.21-NM1 (616)
A flow switch must be installed in the customer pip- Thermometer and pressure gauge connections should
ing at the outlet of the cooler and wired back to the be provided on the inlet and outlet connections of each
control panel using shielded cable. cooler. Gauges and thermometers are not provided
with the unit.
There should be a straight run of piping of at least 5
pipe diameters on either side. The flow switch should be Drain and air vent connections should be provided at all
wired to Terminals 2 and 13 on the 1TB terminal block low and high points in the piping to permit drainage of
(See FIG. 17, Page 141). A flow switch is required to the system and to vent any air in the pipes.
prevent damage to the cooler caused by the unit operat-
ing without adequate liquid flow. Liquid system lines at risk of freezing, due to low ambi- 4
ent temperatures should be protected using insulation
The flow switch used must have gold plated contacts for and heater tape and/or a suitable glycol solution. The
low voltage/current operation. Paddle type flow switches liquid pump(s) may also be used to ensure liquid is
suitable for 150 PSIG (10 bar) working pressure and hav- circulated when the ambient temperature approaches
ing a 1” N.P.T. connection can be obtained from YORK freezing point.
as an accessory for the unit. Alternatively, a differential
pressure switch fitted across an orifice plate may be used, Insulation should also be installed around the cooler
preferably of the high/low limit type. nozzles. Heater tape of 21 watts per meter under the
insulation is recommended, supplied independently and
The chilled liquid pump(s) installed in the piping controlled by an ambient temperature thermostat set
system(s) should discharge directly into the unit cooler to switch on at approximately 4°F, above the freezing
section of the system. The pump(s) may be controlled temperature of the chilled liquid.
by the chiller controls or external to the unit. For de-
tails, refer to “Electrical Elementary and Connection Evaporator heater mats are installed under the insula-
Diagrams.” tion, and are powered from the chiller's control panel.
In sub-freezing conditions, unless the evaporator has
Pipework and fittings must be separately supported to been drained or an appropriate water-to-glycol con-
prevent any loading on the cooler. Flexible connections centration is maintained, high voltage power to the
are recommended which will also minimize transmis- chiller must be kept on to ensure the heater mats assist
sion of vibrations to the building. Flexible connections in evaporator freeze protection. If there is a potential
must be used if the unit is mounted on anti-vibration for power loss, Johnson Controls recommends that the
mounts, as some movement of the unit can be expected evaporator is drained or that water in the chilled water
in normal operation. circuit be replaced with an appropriate water-to-glycol
concentration.
Piping and fittings immediately next to the cooler should
be readily de-mountable to enable cleaning before opera-
tion, and to facilitate visual inspection of the exchanger Any debris left in the water piping
nozzles. between the strainer and cooler could
cause serious damage to the tubes in
The cooler must be protected by a strainer, prefer- the cooler and must be avoided. Be
ably of 40 mesh, fitted as close as possible to the sure the piping is clean before connect-
liquid inlet connection, and provided with a means ing it to the evaporator. Keep evapo-
of local isolation.
rator nozzles and chilled liquid piping
capped prior to installation to assure
The cooler must not be exposed to flushing velocities or
debris released during flushing. It is recommended that a construction debris is not allowed to
suitably sized bypass and valve arrangement is installed enter.
to allow flushing of the piping system. The bypass can
be used during maintenance to isolate the heat exchanger The installer/user must also ensure that
without disrupting flow to other units. the quality of the water in circulation is
adequate, without any dissolved gases,
which can cause oxidation of steel
parts within the cooler.
JOHNSON CONTROLS 31
INSTALLATION
FORM 201.21-NM1 (616)
The unit performance provided in the Design Guide For connection sizes relevant to individual models refer
is based on a fouling factor of 0.0001 ft2hr°F/Btu to the Technical Data Section.
(0.018m2/hr °C/kW). Dirt, scale, grease and certain
types of water treatment will adversely affect the heat
exchanger surfaces and therefore the unit performance. COOLER CONNECTIONS
Foreign matter in the water system(s) can increase the
heat exchanger pressure drop, reducing the flow rate and Standard chilled liquid connections on all coolers are of
causing potential damage to the heat exchanger tubes. the Victaulic Groove type (See FIG. 4).
PIPEWORK ARRANGEMENT
-Flanged Connection
-Pipework
WELD FLANGE VICTAULIC ADAPTER
32 JOHNSON CONTROLS
FORM 201.21-NM1 (616)
REFRIGERANT RELIEF VALVE PIPING When ducting is to be fitted to the fan discharge it is
recommended that the duct should be the same cross-
The evaporator is protected against internal refrigerant sectional area as the fan outlet and straight for at least
overpressure by refrigerant relief valves. A pressure three feet (1 meter) to obtain static regain from the fan.
relief valve is mounted on each of the main refrigerant Ductwork should be suspended with flexible hangers
lines connecting the cooler to the compressors. to prevent noise and vibration being transmitted to the
structure. A flexible joint is also recommended between
A piece of pipe is fitted to each valve and directed so that the duct attached to the fan and the next section for the
when the valve is activated the release of high pressure same reason. Flexible connectors should not be allowed
gas and liquid cannot be a danger or cause injury. For to concertina. 4
indoor installations, pressure relief valves should be
piped to the exterior of the building. The unit is not designed to take structural loading. No
significant amount of weight should be allowed to rest
The size of any piping attached to a relief valve must on the fan outlet flange, deck assemblies or condenser
be of sufficient diameter so as not to cause resistance to coil module. No more than 3 feet (1 meter) of light
the operation of the valve. Unless otherwise specified construction ductwork should be supported by the unit.
by local regulations. Internal diameter depends on the Where cross winds may occur, any ductwork must be
length of pipe required and is given by the following supported to prevent side loading on the unit.
formula:
If the ducts from two or more fans are to be combined
D 5
= 1.447 x L into a common duct, back-flow dampers should be fitted
in the individual fan ducts. This will prevent re-circula-
Where: tion of air when only one of the fans is running.
D = minimum pipe internal diameter in cm
L = length of pipe in meters Units are supplied with outlet guards for safety and to
prevent damage to the fan blades. If these guards are
If relief piping is common to more than one valve, its removed to fit ductwork, adequate alternative precau-
cross-sectional area must be at least the total required tions must be taken to ensure persons cannot be harmed
by each valve. Valve types should not be mixed on a or put at risk from rotating fan blades.
common pipe. Precautions should be taken to ensure the
outlets of relief valves or relief valve vent pipes remain
clear of obstructions at all times. ELECTRICAL CONNECTION
JOHNSON CONTROLS 33
INSTALLATION
FORM 201.21-NM1 (616)
Voltage free contacts are rated at 115VAC, 100VA re- A Remote Run/Stop input is available for each pair of
sistive load only. Inductive loads must be suppressed systems (1/3 & 2/4). These inputs require a dry contact
across the coil. to start and stop the system. System 1/3 remote dry
contacts are connected between Terminals 2 and 15 of
Chilled Liquid Pump Starter 1TB (FIG. 17, Page 141) and System 2/4 dry contacts
are connected between Terminals 2 and 16 of 1TB (FIG.
Terminals 23 and 24 on 1TB close to start the chilled 17, Page 141). If remote start/stop is not utilized, a
liquid pump. This contact can be used as a master start/ jumper must be paced across the terminals to allow the 4
stop for the pump in conjunction with the daily start/ system to run. The remote run/stop circuitry is a 115VAC
stop schedule. Cycle the pumps from the unit panel if circuit. Contacts must be rated for low current (10ma).
the unit will be operational or shut-down during sub- Gold contacts should be used.
freezing conditions. Refer to the Evaporator Pump
Control on Page 170 for more information on testing Remote Print
the pumps.
Closure of suitable contacts connected to Terminals 2
and 14 of 1TB (FIG. 17, Page 141) will cause a hard
Run Contact copy printout of Operating Data/Fault History to be
made if an optional printer is connected to the RS-232
Terminals 21 and 22 on 1TB (FIG. 17, Page 141) close port. The remote print circuitry is a 115VAC circuit.
to indicate that a system is running. Contacts must be rated for low current (10ma). Gold
contacts should be used.
Alarm Contacts
JOHNSON CONTROLS 35
COMMISSIONING
FORM 201.21-NM1 (616)
COMMISSIONING
PREPARATION Service and Oil Line Valves
Commissioning of this unit should only Open each compressor suction, economizer, and dis-
be carried out by YORK Authorized charge service valve. If valves are of the back-seat type,
personnel. open them fully (counterclockwise) then close one turn
of the stem to ensure operating pressure is fed to pressure
transducers. Open the liquid line service valve and oil
return line ball valve fully in each system.
Commissioning personnel should be thoroughly familiar
Compressor Oil
with the information contained in this literature, in ad-
dition to this section.
To add oil to a circuit - connect a YORK hand oil pump
(Part No. 470-10654-000) to the 1/4” oil charging valve
Perform the commissioning using the detailed checks
on the oil separator piping with a length of clean hose
outlined in the EQUIPMENT START-UP CHECK
or copper line, but do not tighten the flare nut. Using
SHEET on Page 152 as the commissioning procedure
clean oil of the correct type (“L” oil), pump oil until
is carried out.
all air has been purged from the hose then tighten the
nut. Stroke the oil pump to add oil to the oil system.
PREPARATION – GENERAL
The oil level should be between the middle of the lower
The following basic checks should be made with the and middle of the upper sight glasses of the oil separa-
customer power to the unit switched OFF. tor. Approximately 4-5 gallons is present in the each
refrigerant system, with typically 1-2 gallons in each oil
separator. Oil levels in the oil separators above the top
Proper electrical lock out and tag pro-
sight glass in either oil separator should be avoided and
cedures must be followed. may cause excessive oil carryover in the system. High
oil concentration in the system may cause nuisance trips
resulting from incorrect readings on the level sensor and
temperature sensors. Temperature sensor errors may
result in poor liquid control and resultant liquid overfeed
Inspection and subsequent damage to the compressor.
Do not liquid charge with static water in the cooler. Check the panel to see that it is free of foreign materials
Care must also be taken to liquid charge slowly to avoid (wire, metal chips, etc.) and clean out if required.
excessive thermal stress at the charging point. Once the
vacuum is broken, charge into the condenser coils with
the full operating charge as given in the Technical Data
Section.
36 JOHNSON CONTROLS
FORM 201.21-NM1 (616)
Verify a chilled water flow switch is correctly fitted in FIRST TIME START-UP
the customer’s piping on the cooler outlet, and wired
into the control panel correctly using shielded cable. During the commissioning period there
should be sufficient heat load to run the
There should be a straight run of at least 5 pipe diam-
unit under stable full load operation
eters on either side of the flow switch. The flow switch
should be connected to terminals 2 and 13 in the panel. to enable the unit controls, and system
operation to be set up correctly, and a
Temperature Sensor(s) commissioning log taken. Be sure that
the chiller is properly programmed and
Ensure the leaving liquid temperature sensor is coated the System Start-up Checklist (Page 152)
with heat conductive compound (Part No. 013-00890- is completed.
000) and is inserted to the bottom of the water outlet
sensor well in the evaporator. This sensor is part of the
JOHNSON CONTROLS 37
COMMISSIONING
FORM 201.21-NM1 (616)
38 JOHNSON CONTROLS
FORM 201.21-NM1 (616)
General Operation
JOHNSON CONTROLS 39
TECHNICAL DATA
FORM 201.21-NM1 (616)
50
A
40
Pressure Drop (ft H2O)
30
D
20
10
0
0 100 200 300 400 500 600 700 800 900 1000
Water Flow Rate (GPM) LD10497
180
B
160
140
C
Pressure Drop (kPa)
120
A
100
D
80
60
40
20
0
0 5 10 15 20 25 30 35 40 45 50
Water Flow Rate (l/s)
40 JOHNSON CONTROLS