Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
The Centralized Supervision Unit (CSU) is used to monitor and manage the DC
power system and realize the integrated management of the AC power distribution,
DC power distribution, battery, diesel generator, solar charger, and rectifiers.
Product features
04
2
CSU
Centralized Supervision Unit
CSU501B
Hardware Specifications
Input voltage 36VDC ~ 60VDC
Operating temperature range -20°C ~70°C
Operating humidity 5% ~ 95% (non-condensing)
Cooling solution Air coolant.
Installation mode 1U height
Reverse polarity protection Protect for all signal and power inputs
Transferring information to Alarm -> real time
remote monitoring sever Data -> period
Serial communication 2 x RS485 ports; 1 x RS232 port
Storage at site controller 10,000 history data, 10,000 alarms
LCD, dot matrix, 160 x 160 resolution. Able to adjust
Display type
contrast, angle and display Icon, symbol.
Display Accurary ≤ ± 0,5%
Realtime alarm by light, sound ( >60dB at 1m distance)
Alarm management
Communication failure alarm via Web function
• Shunt type
Battery Current sensor
• Measurement range 0 ~ ±200Adc
Temperature sensor
Output signal : DC current• Range: -40 ~ 150℃
(battery/environment)
Indicator
3
CSU
Centralized Supervision Unit
Physical Specifications
Dimensions CSU501B: 41.5mm *132mm * 300mm (H * W * D)
Weight <1.5 Kg (core controller unit < 0.3Kg)
Power consumption 4.5 W
Communication interface RS232/RS485/RJ45
Analog interface 3 interfaces for battery temperature
USB interface 1 USB interface
Dry contact interface SIU board: 8 for output dry contact, 4 for input dry
contact
GMU and GMUE board (Option): 8 for output dry contact,
4 for input dry contact
Functions
• Support the remote firmware update
• Support 4 languages (optional)
• Able to extend Input Output by extension modules (customize based on required)
• Able to update CSU without any affect to system operation.
• Ethernet: RJ45 support multiple monitoring network mode: IPv4/IPv6, HTTPs, SNMP
V2/V3
• MIB file is provided to collect information via SNMP protocol
• Smart charge function: fast charge, float charge, equalize charge. Suitable for many
types of Lithium LFP battery (capacity range: 50-300AH)
• Ability of connection, information display, real-time warning and control for all
connected devices
• Equipment able to be monitored:
Lead acid battery: Monitor each string via current sensor, voltage sensor, temperature
sensor with BMU(optional).
Air conditioner controller unit, solar unit, wind energy unit via RS485 (optional)
Indoor ambient temperature
Smoke, flood, Door alarm
4
CSU
Centralized Supervision Unit
Main control functions
5
CSU
Centralized Supervision Unit