Sei sulla pagina 1di 4

Industry Application IA04008002en Effective November 2012

Variable frequency drives: energy


savings for pumping applications
Tom Neuberger and Steven B. Weston,
Eaton Corporation Valve

Variable frequency drives


application and use kW Meter

In the early days of variable frequency drive (VFD)


technology, the typical application was in process VFD
control for manufacturing synthetic fiber, steel bars, kW Meter
and aluminum foil. Because VFDs improved process
performance and reduced maintenance costs, they Figure 1: A Mechanical Throttling Device
replaced motor generator sets and DC drives. When versus a VFD
the energy crisis occurred in the early 1970s, saving
energy became a critical goal, and the use of VFDs
quickly spread into large pump applications and If a throttling device is employed to control flow,
eventually into HVAC fan systems. energy usage is shown as the upper curve in
Figure 2, while the lower curve demonstrates
energy usage when using a VFD. Because a VFD
Variable frequency drives compared alters the frequency of an AC motor, speed, flow,
to throttling devices and energy consumption are reduced in the system.
The energy saved is represented by the green
In many flow applications, a mechanical throttling shaded area.
device is used to limit flow. Although this is an
effective means of control, it wastes mechanical and
electrical energy. Figure 1 represents a pumping 100
system using a mechanical throttling valve and the Throttling
same system using a VFD.
Power Consumption (%)

80 Device

60

Energy VFD
40 Savings

20

0
0 20 40 60 80 100
Flow (%)

Figure 2: The Amount of Energy Saved by


Using a Variable Frequency Drive (versus a Valve)
to Control Flow
IA04008002 Variable frequency drives: energy savings for pumping applications

Graph A Graph B Graph C

Flow or Pressure or Power or Energy


Volume (%) Head (%) Consumption (%)

Speed (%) Speed (%) Speed (%)

2 3
Flow1 RPM1 Head1 RPM1 Power1 RPM1
= = =
Flow2 RPM2 Head2 RPM2 Power2 RPM2

Figure 3: The Affinity Laws

Variable frequency drives theory In Figure 4, the static head, friction head, and resulting
system curve are shown for a typical pumping system. In
The affinity laws can determine the system performance for this example, the maximum flow rate required is 160 liters
centrifugal devices, including theoretical load requirements per minute (lpm). This information helps to determine the
and potential energy savings. Represented in Figure 3 are the required pump and impeller size for the system to provide
three affinity laws: the maximum required flow. Based on the system curve in
1. Flow or volume varies linearly with speed. If speed Figure 4, the pump should develop at least 120 meters of
decreases by 50%, flow decreases by 50% (Graph A). pressure.

2. Pressure or head varies as a square of the speed.


If speed decreases by 50%, the pressure decreases
180
to 25% (Graph B).
System Curve
3. Power or energy consumption varies as a cube of the 160
speed. If speed decreases by 50%, power consumption
140
decreases to 12.5% (Graph C). The potential of energy
savings is available as the flow requirement is reduced. 120
Head or Pressure (m)

100
Pumping system characteristics Friction
Head
Determining the system curve, which describes what flow will 80
occur given a specific pressure, is critical to selecting the 60
appropriate pump for a system. To determine an accurate
system curve, two elements must be known: 40
• Static head or lift — The height that the fluid must be
20 Static Head or Lift
lifted from the source to the outlet.
• Friction head — The power required to overcome the 0
0 40 80 120 160 200
losses caused by the flow of fluid in the piping, valves,
Flow Rate (lpm)
bends, and any other devices in the piping. These losses
are completely flow-dependent and are nonlinear.
Figure 4: Elements of a System Curve

2
Variable frequency drives: energy savings for pumping applications IA04008002

In Figure 5, the system curve and pump performance curve Variable frequency drives application
intersect at the desired operating point of 120 m of pressure in a pump system
and 160 lpm of flow. The system will have a single operating
point unless a device is added, and rarely does a pumping Applying a VFD to the pump allows control of the pump’s
application require the pump to produce maximum flow. speed electrically while using only the energy needed to
produce a given flow. This is similar to applying a new pump
with a smaller impeller. Figure 7 demonstrates the new
180
pump curve and the energy consumed by this method. Also,
Pump Performance Curve
at Full Speed
the pressure is reduced, which helps reduce the mechanical
160 stresses generated by
140 throttling devices.
Head or Pressure (m)

120
100
180
80
160
60
140

Head or Pressure (m)


System Curve
40
120 System Curve
20
100
0
0 40 80 120 160 200 80
Flow Rate (lpm) 60 Pump Performance Curve
40 at Reduced Speed (VFD)
Figure 5: A Combination of the System and Pump Curves Required hp at
20 Reduced Speed
0
Throttling device application 0 40 80 120 160 200
in a pump system Flow Rate (lpm)

A throttling device is often used as a mechanical method to


reduce the flow rate in a pumping system. Applying a throttling Figure 7: System Characteristics Using a Variable Frequency
device to the system changes the pump curve, as shown in Drive
Figure 6. This reduces the flow of the system, but the pump
curve is not altered and continues to operate at full speed. Overlaying the two previous graphs, the difference is obvious
This creates mechanical stresses — excessive pressure in Figure 8. The blue shaded area is the energy saved by using
and temperature — on the pump system, which can cause a VFD instead of a throttling device.
premature seal or bearing failures. More importantly, this
also consumes a tremendous amount of energy. The energy
comsumed is represented by the blue shaded area 180
in Figure 6. Pump Performance Curve
160 at Full Speed
Required hp at
140
Head or Pressure (m)

Full Speed
180 System Curve
Pump Performance Curve 120 (Throttling
at Full Speed
160 100 Device)
140 Required hp
Head or Pressure (m)

80 System Curve
at Full Speed
120 60
System Curve
100 (Throttling Device) Pump Performance Curve
40 at Reduced Speed (VFD)
80 Required hp at
20 Reduced Speed
60 0
40 0 40 80 120 160 200
Flow Rate (lpm)
20
0
0 40 80 120 160 200 Figure 8: The Difference in Energy Consumption Using a
Throttling Device versus a Variable Frequency Drive
Flow Rate (lpm)

Figure 6: System Characteristics Using a Mechanical


Throttling Device

3
IA04008002 Variable frequency drives: energy savings for pumping applications

Valve Control Speed Control


Valve Turndown Losses
Flow (15 kW) Head Flow Head
Detection (50 kW) V Detection (50 kW)
F
D
(15 kW) (10 kW)
90 P 75 P
kW kW
Piping Losses
AC Pump (10 kW) AC Pump Piping Losses
Motor Control Motor (8 kW)
Valve

Losses: 15 kW Valve Turndown Losses: 0 kW Valve Turndown


10 kW Piping 8 kW Piping
15 kW Pump 10 kW Pump
50 kW Head (Load) 50 kW Head (Load)
Requires: 90 kW Requires: 68 kW

Figure 9: Energy Savings Can Be Calculated with a


Computerized Analysis

Variable frequency drives Because of these losses and the internal pump loss, to obtain
a head equivalent to 50 kW, an equivalent of a 90 kW pump
for further cost savings and a 90 kW motor is required. With the use of the VFD, there
The use of VFDs can bring further total system cost are no valve or pipe losses due to bends or additional piping,
reductions, due to the elimination of components required for thus reducing the piping losses to 8 kW. With the reduction of
valve control only. In a valve flow control system, there are these losses, a smaller pump can be used with lower losses.
losses in the valve and additional piping required to bring the For the same equivalent of 50 kW of head, only a 75 kW pump
valve to a height where it can be adjusted. In the previous and a 75 kW motor are required. This results in a substantial
example, the piping loss is 10 kW, and the valve loss is 15 kW. system cost and installation savings, further economically
justifying the use of the VFD.

Eaton Industries GmbH Eaton is a registered trademark of Eaton


Hein-Moeller-Str. 7–11 Corporation
D-53115 Bonn / Germany
All other trademarks are property of their
© 2015 by Eaton Corporation respective owners.
All rights reserved
Publication No.: IA04008002en SmartWire-DT® is a registered trademark of
ip June 2015 Eaton Corporation.

Potrebbero piacerti anche