Main E-room, Secondary E-room, ACC and ROP E-room

Arrangement for Electrical Equipments

(MV switchgear, Aux. Transformers dry type, LV switchgear, DC/UPS sytem, Control cubicles & Batteries, VSD)
freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Page
Date Name Appr. GSEEE 1GP006913 1
.
Rev. Huser
.
Main E-room at +2.5 m level Platforms located above 400 mm Maximum external height of the
Segregation MV/ LV is necessary From the bottom of the module Containers is 3.6 m
Cable entry from bottom
Single access door
500 mm double floor for cabling with removable wall

Battery fusebox Access and operation


Wallmounted IP65 from outside room Stairs
H/W/D 0.8/0.6/0.3 m C Platform
Access to battery room
A A Stairs D
roof through ladder
casing C c

0.5m
0.5m
fusebox fusebox
control panel for
0.8m 0.8m HVAC Venitlation

1.2m
lighting up to 1m
Circulation 1.5 m
C Trafo

15 m
Eye wash

2.5m
station with
potable 00BFT50
water supply
1.6MVA 2m
Container G1 Container G2

12BRC10
1.2m

1.2m
1.2m
View Window

11BTL10 11BRC10

1.2m

HMI
HMI
SERVICE

12BRT10
11BRT10

0.65m 0.65m
TROLLEY

EBOP ESOP
1.2m

ST10 ST10
1.2m
5.5 m

12BTL20

0.8m
0.8m
5.5m

4.8m
Battery 00BTB10

0.6m
0.6m
11BTT&

12BTT&
11BUG

12BUG
4.8m

2.15m
88BBT

0.7m
1.9 m

VFD
1.9 m

0.7m
88BB
VFD
4.3m

00BVB10
2m

ELOP/
Battery 12BTA10

ESOP
GT12

0.65m
ELOP/
ESOP
0.65m
GT11

2.7m

6.5m
1.95m 00BVC10
TCP GT 11

12BVC10
TCP GT12
11BVC10
– 11BBA

2m

1.95m
4.3m
1.2 m

MV SWGR – 00BBB10
– 00BBA10

CONTINUE ON PAGE 3
LV – 11BHC12

2m

00BRB
12BHC11
MV SWGR

12BTL10
0.8m
11BTL20

0.8m

00BRA
GAMP
GAMP
0.85m 0.8m

0.8m

LV 00BFA50 CCW
MV SWGR

1.4m
5.5 m

5.5 m

00BRU10
0.85m

5.6m
ECS
ECS
5.6m

00BRT10
5.3m
Battery 11BTA10

1.4m

00BTM20 00BTM10
0.8m 0.8m
Battery 00BTA10

2.6m
2.6m

5.3m
LV – 11BMC10

00BVA10
2.15 m
LV – 11BHC11

GPP

GPP

LV - 12BMC10

LV - 12BHC12
SERVICE
1.2 m TROLLEY
9.85 m

0.8 m
1.4 m
10.5m

Access to battery room

00BTL10 00BTL20
11BNC10

12BNC10

0.8 m 0.8m
roof through ladder

1.95 m
casing

1.95 m
freigegeben/ Released

0.95 m 0.95 m
Air flow
direction
Eye wash 0.8m
station with
potable
Expansion

water supply 0.2m


C Circulation 1.2 m
arc duct

1.2m
0.5m
0.5m

fusebox fusebox
0.5m Container M3 Container H12 Container I1 Container H1
1.8m Container H11
0.8m 0.8m
3.2 m 3.2 m 3.2 m 3.2 m 3.2 m
B 3.2 m 3.2 m
3.5m 0.4 m
Container I2
Battery fusebox
Arc expansion channel
Wallmounted IP65
H/W/D 0.8/0.6/0.3 m
prefered side. 4m
Access and operation
clearance to other
from outside room structure at +4.5m 26.2m

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Main E-room Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Drawing number
Resp. Dept
Check. Roux
. equipment arrangement Page
Date Name Appr. GSEEE 1GP006913 2
.Rev. Huser
.
Platforms located above 400 mm
From the bottom of the module
Single access door Single access door Single access door Single access door
with removable wall with removable wall with removable wall with removable wall

D Stairs
c c c c

1.35m

1.35m

1.35m
Trafo
1.2m
Trafo Trafo Trafo
00BFU50 00BFT10 00BFV10 00BFU10
2.5m

1.6MVA 2.5MVA 2.5MVA 2.5MVA 2.2 m

Space reserved for tables


2m 2.2m 2.2m

- Local Operator Station


Transformer
View Window View Window View Window View Window Wall mounted
600x300 mm

AVR Panel
Wall mounted
750x500 mm
400 kVA
6.7 m

8.7 m
9.8 m

00BLT10

control
1.65m

0.8m
8.7 m

Trafo

Fire
0.8m
4.2m

0.8m
1m
CONTINUE ON PAGE 2

LV 00BFB50 CCW

4.8 m
400 kVA

1.6m
WSC SIL
00BNT10
Trafo

1.65m
00BFC10 – Non redundant loads
00BFA10 – Redundant loads
00BMC10 – Essential loads

TCP - ST
1.2 m
1m

2.4m
3.55 m
00BFB10 – Redundant loads

WSC
0.6m

BUS 00BLC10
480/220 VAC

2.6 m

1.6 m

1.6m
HRSG12 SIL

HRSG11 SIL
1.6m
BOP-RIO2
GPP

Stairs
2.4 m

2.4 m
2.15 m

2.4 m
Edge
BUS 00BNC10

0.8m

BOP-RIO1

HRSG 12
480/220 VAC

HRSG 11
freigegeben/ Released

TROLLEY
SERVICE

GAMP

0.8m

0.8m 0.8 m
0.8m
Circulation 1.2m 0.8m

C
Container H2 Container H3 Container H4 Container H5 Container M1 Container M2

3.2 m 3.2 m 3.2 m 3.2 m 3.2 m 3.2 m


19.2 m

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Main E-room Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Page
equipment arrangement
Date Name Appr. GSEEE 1GP006913 3
.Rev. Huser
.
Secondary E-room at +2 m level
Cable entry from bottom
500mm double floor for cabling

Secondary E-room, power island GT11


Platforms located above 400 mm
From the bottom of the module
Single access door Single access door
with removable wall with removable wall

Platform
Stairs
D
3.4m 8.2m 3.4m c
c
2.0m

1.0m
2.0m 0.6x0.2m
HP IP Feedwater Pump
DC Starter Drive -11BPA11
Wall box

3/1.5/1.5 MVA
3.2m

3/1.5/1.5 MVA
View Window
11BPA11

11BPA12
View Window
Terminal point

3.9 m
for water cooling Container F21
3.2m

Stairs
Stairs

1.2m
1.2m

1.0m
HP IP Feedwater Pump Terminal point
Drive -11BPA12 for water cooling

Fire
0.8m

11BHD10 - Secondary

0.6
11BMD10- Secondary Board
control

3.2m
Board Non-Essential Essential Transformer
5.9 m 4m Wall mounted 0.8m control panel for
600x300 mm
HVAC Venitlation

Platform
D Container H21 lighting up to 1m
C

1.5m
1.45m 11BND10 11BLD10 1.95 m 1.45m
2.65 m Trafo 1.2 m 2.4m

0.9m
Trafo
0.9m

SERVICE
11BLU10 SP & L SP & L Non- 11BNU10 BMS1 HRSG1
Platform 2m TROLLEY
250 kVA Essential Essential 250 kVA

15 m

Secondary E-room GT11


freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Secondary E-room Page
Date Name Appr.
equipment arrangement GSEEE 1GP006913 4
.Rev. Huser
.
Secondary E-room at +2 m level
Cable entry from bottom
500mm double floor for cabling

Secondary E-room, power island GT12


Platforms located above 400 mm
From the bottom of the module
Single access door Single access door
with removable wall with removable wall

Platform
Stairs
D
3.4m 8.2m 3.4m
c c
2.0m

1.0m
2.0m HP IP Feedwater Pump
0.6x0.2m
DC Starter
Drive -12BPA11
Wall box

3/1.5/1.5 MVA
3.2m

3/1.5/1.5 MVA
View Window
12BPA11

12BPA12
View Window
Terminal point

3.9 m
for water cooling Container F22
3.2m

Stairs
Stairs

1.2m
1.2m

1.0m
HP IP Feedwater Pump Terminal point
Drive -12BPA12 for water cooling

Fire
0.8m

12BHD10 - Secondary

0.6
12BMD10- Secondary Board
control

3.2m
Board Non-Essential Essential Transformer
5.9 m 4m Wall mounted 0.8m control panel for
600x300 mm
HVAC Venitlation

Platform
D Container H22 lighting up to 1m
C

1.5m
1.45m 12BND10 12BLD10 1.95 m 1.45m
2.65 m Trafo 1.2 m 2.4m

0.9m
Trafo
0.9m

SERVICE
12BLU10 SP & L SP & L Non- 12BNU10 HRSG2
Platform 2m TROLLEY
250 kVA Essential Essential 250 kVA
BMS2

15 m

Secondary E-room GT12


freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Secondary E-room Page
Date Name Appr.
equipment arrangement GSEEE 1GP006913 5
.Rev. Huser
.
ACC E-room at +2.0 m level
Cable entry from bottom ACC E-room, next to ACC
500mm double floor for cabling

Removable wall on Single access Single access Single access Single access
all transformers and door with view door with view door with view door with view
maintenance door Window Window Window Window
with window
Removable walls
In all transformers
Container H31 at ground level
Container H32 at +2.0m level c 3.75 m c c c

0.725m
2.3m 2.3m 2.3m 2.3m
Platforms located above 400 mm
Aux Trafo Aux Trafo Aux Trafo

1.32m
Aux Trafo

1.32m
1.32m
From the bottom of the module

2.5 m

1.32m
00BFT30 00BFT40 00BFU30 00BFU40
3.15MVA 3.15MVA 3.15MVA

Stairs
3.15MVA

Stairs
Container H31 0.6m

0.6
00BFA30 ACC FANS 00BFB30 ACC FANS SERVICE
6.9m 5.1 m TROLLEY

3.2 m
control panel for
Platform
2.5x2 m HVAC Venitlation
c
D Container H32 lighting up to 1m

6.9m 5.1m 2.4m Platform


00BFA40 ACC FANS 00BFB40 ACC FAN ACC RIO 1.5m
15m

ACC RIO

ACC room
Cable entry from bottom
freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Secondary E-room Page
Date Name Appr.
equipment arrangement GSEEE 1GP006913 6
.Rev. Huser
.
ROP E-room at +2.0 m level
Cable entry from bottom
500mm double floor for cabling

This container will be supplied by with gas extinguishing


system which is outside E-room supplier scope
ROP E-Room E-room supplier to bring provisions, including over
pressure flaps

15m

Platforms located above 400 mm


From the bottom of the module 3.0m

00BLA60 LV SWGR-00BFA60

0.8m
Trafo
00BLT60

LV SIDE
1.95m 7.5m
1.45m

00BFT60
2MVA

Trafo
View Window
Single access
3.2 m

door and

2m

c
Container H41 removable wall
D
Stairs

0.8m Trafo
Fire 00BNT60 1.95m 1.2m
2m

Corridor
PRS control 1.45m 00BND60
Transformer
1.95m

0.8m
Wall mounted Trafo
BOP RIO3

View Window
600x300 mm 00BLU60
1.6m 00BLB60

00BFU60
3.2 m

1.45m

2MVA

Trafo
Container H42 Single access
C

SERVICE door and


TROLLEY

c
removable wall

2m
1.9m

0.8m
Platform Platform 7.5m 1.2m
1m

0.6 Gas
1.5m 2m extinguishing 00BFB60

control panel for


HVAC Venitlation
lighting up to 1.2m

ROP E-Room
Cable entry from bottom
freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. Casal
. EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Secondary E-room Page
Date Name Appr.
equipment arrangement GSEEE 1GP006913 7
.Rev. Huser
.
All HVAC and ventilation systems design for N+1 redundancy

Side view G1-I2:


Note A: maintenance doors
Air inlet to main E-room
double maintenance door key-
locked, tag with risk of failing,
min 2x1m large, 2.3m high

HVAC units (N+1) on I2 roof

Note B: Handrail around


double door: roof of battery room
Main door min 2x1m large, 2m
high for personal access, plus
0.5m large for maintenance

Air inlet to battery room:


Access to battery room
return G1 + HVAC fresh,
roof through ladder
damper regulated
casing

Note C: Air flow with pushed-air


Personal access door with panic ventilation (on UPS),
bar, min 1m large, 2m high with H2 detectors

Note D:
HVAC main E-room and battery room: principle
double maintenance door,
min 2x1m large, 2.3m high
Personal access door with panic
bar, min 0.8m large, 2m high Secondary E-room(s): Roof top or split units or equivalent
Access with handrails in seller scope in case of required roof access for maintenance
freigegeben/ Released

Ventilation systems: pushed air with ventilators.


Maintenance possible with switching off the equipment in the room, without roof access.

Ventialtion of the battery room shall complied with IEEE 1635

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010 Resp. Dept Drawing number
Check. Roux
. Doors, HVAC, Page
Date Name Appr. Ventilation GSEEE 1GP006913 8
.Rev. Huser
.
Valid for escape way only.
For equipment arrangement refer to pages «main E-room equipment arrangement» Imposed door opening direction if 0.6m
is not achieved with 90deg -open door
Mandatory principles:
• 0.8m normal way : all panel doors closed Main E-room Escape door
• 0.6m escape way : any 1 panel door opened. Door might obstruct
the way if free to move in escape direction
• 2 escape ways when distance to door is above 10m
• Way for exceptional maintenance might be reduce down to 0.4m

Stairs
C Platform
A A Stairs D A
C

0.5m
0.5m
fusebox fusebox
control panel for
0.8m 0.8m HVAC Venitlation Circulation 1.5 m
C Trafo

1.35m
Eye wash lighting up to 1m
bottle and 00BFT50
collector
tray
1.8m

View Window
SERVICE
TROLLEY
5.5 m
5.5m

Battery 00BTB10
Battery 12BTA10

TROLLEY
SERVICE
MV SWGR – 11BBA

CONTINUE ON PAGE 3
5.5 m
5.5 m
Battery 11BTA10

Battery 00BTA10
freigegeben/ Released

0.95 m 0.95 m
Air flow
direction Eye wash
bottle and
collector
tray
0.8m 0.8m Circulation 1.2 m
C
0.5m
0.5m

fusebox fusebox
Container M3 Container H12 Container I1 Container H1
Container G1 Container G2 Container H11
B B

Container I3 7m Container I2
Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. Casal
. EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Escape ways and door openings Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 9
.Rev. Huser
.
Valid for escape way only.
For equipment arrangement refer to pages «main E-room equipment arrangement» Imposed door opening direction if 0.6m
is not achieved with 90deg -open door

Main E-room Escape door

A A A A D Stairs

control
0.8m
1.35m
1.35m

1.35m

Fire
1.35m
Trafo Trafo Trafo Trafo
00BFU50 00BFT10 00BFV10 00BFU10
2.5m

3.0m

Space reserved for tables


2.2m 2.2m 2.2 m

- Local Operator Station


1.8m
View Window View Window View Window View Window

400 kVA

00BLT10
CONTINUE ON PAGE 11

1.4m
Trafo
1m

400 kVA

00BNT10
Trafo

1.4m
1m

Stairs
freigegeben/ Released

TROLLEY
SERVICE

0.8 m
0.8 m
Circulation 1.2m

C
Container H2 Container H3 Container H4 Container H5 Container M1 Container M2

Design basis IEC 60364 Part 7-729: Low-voltage electrical installations –Requirements for special installations or locations –Operating or maintenance gangways
IEC 61936-1 Power installations exceeding 1 kV a.c. Common rules Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Escape ways and door openings Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 10
.Rev. Huser
.
Valid for escape way only.
For equipment arrangement refer to pages «main E-room equipment arrangement» Imposed door opening direction if 0.6m
is not achieved with 90deg -open door
Platform
Stairs Escape door
A D A
Secondary E-room, power
island GT11 & GT12

Stairs
Stairs

Platform
D C

Rop E-room

ACC E-room

Stairs

Corridor
0.54
C
freigegeben/ Released

Stairs

Stairs
Platform

D C
Platform

Design basis IEC 60364 Part 7-729: Low-voltage electrical installations –Requirements for special installations or locations –Operating or maintenance gangways
IEC 61936-1 Power installations exceeding 1 kV a.c. Common rules Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Escape ways and door openings Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 11
.Rev. Huser
.
Valid for transport unit coding and room designation only.
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»

Main E-room

00UBB10R522 00UBB10R523 00UBB10R524 00UBB10R525 00UBB10R526


00UBB10R511
00UBB10R531

Container H11

Container H12

Container H1
Container G2

Container H2
Container G1

Container M3

Container H4
Container H3
Container I2

Container M2
Container I1

Container H5

Container M1
00UBB10R521

Letter+number: transport unit coding


freigegeben/ Released

KKS: room designation

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Transport unit coding and Resp. Dept Drawing number
Page
room designation GSEEE 1GP006913 12
.Rev. Date Name Appr. Huser
.
Valid for transport unit coding and room designation only.
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»

Room designation:
• Secondary E-room power island GT11: 11UBB10R201
• Secondary E-room power island GT12: 12UBB10R201
• ACC E-room: 00UBB10R410
• RoP E-Room: 00UBB10R610

Secondary E-room, power Secondary E-room, power


island GT11 island GT12

Container F21 Container F22


11UBB10R203 12UBB10R203 12UBB10R204
11UBB10R204
11UBB10R202 12UBB10R202

Container H21 Container H22

11UBB10R201 12UBB10R201

ROP E-Room
ACC E-Room

Container H41 00UBB10R611


00UBB10R411 00UBB10R412 00UBB10R413 00UBB10R414
freigegeben/ Released

00UBB10R610
Container H31

Container H42
Container H32 00UBB10R612

00UBB10R410

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Transport unit coding and Resp. Dept Drawing number
Page
room designation GSEEE 1GP006913 13
.Rev. Date Name Appr. Huser
.
Weight and heat losses of equipment
Total
Use Total Container Total
Dimension Units Losses Weight equipment
Description Location Container factor losses weight weight
weight
W mm D mm H mm kW kW t t t t
11BTA10, 12BTA10 Batteries for GT Battery room I2 5500 1000 2 6 1 32.4
12 64.80 30 94.80
00BTA10, 00BTB10 Batteries for ROP Battery room I2 5500 1000 2 6 1 32.4
00BBA10 MV Switchgear Main E-room G1 10700 1800 2400 1 3.4 0.8 13.4 13.40 13.5 26.90
5.68
00BBB10 MV Switchgear Main E-room G2 9700 1800 2400 1 3.7 0.8 12.4 12.40 13.5 25.90
11BHC12 LV Switchgear Main E-room H11 4300 800 2400 1 1.4 0.8 3.225
11BHC11 LV Switchgear Main E-room H11 5300 800 2400 1 2.1 1 3.975
11BMC10 LV Switchgear Main E-room H11 5600 800 2400 1 3.1 0.8 4.2
88BT-1 VFD for GT11 Main E-room H11 610 610 1 0.2 1 0.3
11BTT10&11BUG10 DC-DC CONVERTER & DCDB Main E-room H11 600 800 2205 1 0.075 1 0.25
11BRT10 Inverter 1p 120Vac 60 Hz+Bypass Main E-room H11 1205 810 2205 1 0.96 0.8 18.843 0.9 16.87 11.5 28.37
11BTL10 Charger Main E-room H11 810 810 2205 1 7.29 0.5 0.9
11BTL20 Charger Main E-room H11 810 810 2205 1 7.29 0.5 0.9
11BRC10 Subdistribution board 120Vac 1p Main E-room H11 1200 800 2155 1 0.9 0.9 0.72
Emergency lube oil pump /
ELOP/ESOP for GT11 Main E-room H11 650 620 2150 1 8 0.5 1.5
Emergency seal oil pump starters
GPP-GT11 & GT12 Generator protection panel - GT Main E-room M3 2607 600 2 1.2 1 2
GAMP-GT11 & GT12 Gas Auxiliary Monitoring Panel - GT Main E-room M3 805 500 2200 2 1.2 1 0.966
ECS-GT11 & GT12 Main E-room M3 850 800 2 1.2 1 5.2 1.02 7.09 11.5 18.59
TCP-GT11 & GT12 Turbine control panel - GT Main E-room M3 4806 650 2 1.2 1 3
HMI-GT11 & GT12 HMI laptop type no rack Main E-room M3 2 0.4 1 0.1
12BHC12 LV Switchgear Main E-room H12 5300 800 2400 1 2.1 0.8 3.975
freigegeben/ Released

12BHC11 LV Switchgear Main E-room H12 4300 800 2400 1 1.4 1 3.225
12BMC10 LV Switchgear Main E-room H12 5600 800 2400 1 3.1 0.8 4.2
88BT-12 VFD for GT11 Main E-room H12 610 610 1 0.2 1 1
12BTT10&12BUG10 DC-DC CONVERTER & DCDB Main E-room H12 600 800 2205 1 0.075 1 0.25
12BRT10 Inverter 1p 120Vac 60 Hz+Bypass Main E-room H12 1205 810 2205 1 0.96 0.8 18.703 0.9 17.57 11.5 29.07
12BTL10 Charger Main E-room H12 810 810 2205 1 7.29 0.5 0.9
12BTL20 Charger Main E-room H12 810 810 2205 1 7.29 0.5 0.9
12BRC10 Subdistribution board 120Vac 1p Main E-room H11 1200 800 2155 1 0.9 0.9 0.72
Emergency lube oil pump /
ELOP/ESOP for GT12 Main E-room H12 650 620 2150 1 8 0.5
Emergency seal oil pump starters 1.5 Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Weight Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 14
.Rev. Huser
.
Weight and heat losses of equipment
Use Total Total Container Total
Dimension Units Losses Weight
Description Location Container factor losses weight weight weight
W mm D mm H mm kW kW t t t t
Emergency bearing oil pump /
EBOP-ST / ESOP ST Main E-room I1 16 0.5
Emergency seal oil pump starters 640 500 2000 2 1.5
00BTL10 Charger for BOP Main E-room I1 810 810 2205 1 6.08 0.5 0.9
00BTL20 Charger for BOP Main E-room I1 810 810 2205 1 6.08 0.5 0.9
00BTM10 Charger for BOP Main E-room I1 810 810 2205 1 6.08 0.5 0.9
00BTM20 Charger for BOP Main E-room I1 810 810 2205 1 6.08 0.5 0.9
00BRT10 Inverter 1p 127Vac 60 Hz Main E-room I1 1600 800 2200 1 4.5 0.8 31.96 1 12.28 11.5 23.78
00BRU10 Inverter 1p 127Vac 60 Hz Main E-room I1 1600 800 2200 1 4.5 0.8 1
00BVA10 220Vdc board Main E-room I1 2150 800 2100 1 1 0.8 1.075
00BVC10 220Vdc board Main E-room I1 2150 800 2100 1 1 1 1.075
00BVB10 220Vdc board Main E-room I1 2150 800 2100 1 1 0.8 1.075
00BRB 127Vac 60hz Main E-room I1 1950 800 2100 1 1 1 0.975
00BRA 127Vac 60hz Main E-room I1 1950 800 2100 1 1 1 0.975
00BFT50 Trafo 1.6 MVA Dry-type Main E-room H1 2000 1200 1 15.2 0.5 3.5
2.64 8.38 11.5 19.88
00BFA50 LV Switchgear CCW Main E-room H1 6500 800 1 3.3 0.8 4.875
00BFU50 Trafo 1.6 MVA Dry-type Main E-room H2 2000 1200 1 15.2 0.5 3.5
00BFB50 LV Switchgear CCW Main E-room H2 4200 800 1 2 0.8 4.24 3.15 11.68 11.5 23.18
00BMC10 LV Switchgear Essential loads Main E-room H2 6700 800 1 3.3 0.8 5.025
00BFT10 Trafo 2.5 MVA Dry-type Main E-room H3 2000 1200 1 22.1 0.5 2.5
3.9 9.03 11.5 20.53
00BFA10 LV Switchgear Non-redundant Main E-room H3 8700 800 1 3.9 1 6.525
00BFV10 Trafo 2.5 MVA Dry-type Main E-room H4 2200 1350 1 22.1 0.5 2.5
4.3 9.85 11.5 21.35
00BFC10 LV Switchgear Non-redundant Main E-room H4 9800 800 1 4.3 1 7.35
00BFU10 Trafo 2.5 MVA Dry-type Main E-room H5 2200 1350 1 22.1 0.5 2.5
00BFB10 LV Switchgear - Redundant loads Main E-room H5 8700 800 2350 1 3.9 0.8 6.525
00BNC10 Small power Main E-room H5 2150 800 2350 1 1 1 1.075
10.395 14.28 11.5 25.78
freigegeben/ Released

00BLC10 Small power Main E-room H5 3550 800 2350 1 1 1 1.775


00BNT10 Small distribution transformer Main E-room H5 1650 1000 1 4.3 0.5 1.2
00BLT10 Small distribution transformer Main E-room H5 1650 1000 1 6.25 0.5 1.2
GPP-ST Generator protection panel - ST Main E-room M1 2607 600 1 0.6 1 1.5642
GAMP-ST Gas Auxiliary Monitoring Panel - ST Main E-room M1 805 500 1 0.6 1 0.483
ECS-ST Edge panel Main E-room M1 850 800 1 0.6 1 0.51
HMI-ST Human machine interface ST Main E-room M1 1 0.2 1 0.05
4.4 7.41 11.5 18.91
WSC Controllers Water steam cycle control Main E-room M1 2400 800 1 0.6 1 1.44
BOP 1 Controllers Main E-room M1 2400 800 1 0.6 1 1.44
WSC SIL Main E-room M1 1600 800 1 0.6 1 0.96
ACC Controllers Main E-room M1 1600 800 1 0.6 1 0.96 Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Weight Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 15
.Rev. Huser
.
Weight and heat losses of equipment
Use Total Container Total
Dimension Units Losses Total weight
Description Location Container factor losses Weight weight weight
W mm D mm H mm kW kW t t t t
HRSG 11 & 12 Main E-room M2 2400 800 2 1.2 1 2.88
HRSG SIL 11 & 12 Main E-room M2 1600 800 2 1.2 1 1.92
3.6 6.78 11.5 18.28
TCP-ST Turbine control panel - ST Main E-room M2 4806 650 1 0.6 1 1.5
Fire control cabinet Fire control cabinet Main E-room M2 800 600 2102 1 0.6 1 0.48
11BPA11 & 11BPA12 Transformer for feed water pumps Secondary PI GT11 F21 2 50 0.5 26
36.00 15.00 51.00
HP IP FWP Drive 11 & 12 HP IP FWP Drives Secondary PI GT11 F21 3200 800 2 14 1 10
11BHD10 Secondary non-essential Secondary PI GT11 H21 5900 800 1 2.8 0.8 3.54
11BMD10 Secondary essential Secondary PI GT11 H21 4000 800 1 1.8 1 2.4
11BLU10 & 11BNU10 Transformers Secondary PI GT11 H21 1000 1500 2 3.8 1 2.04
44.14
BMS1 Secondary PI GT11 H21 1200 600 1 0.9 1 0.72
13.38 11.5 24.88
HRSG1 RIO Secondary PI GT11 H21 2400 600 1 1.8 1 1.44
Fire control cabinet Fire control cabinet Secondary PI GT11 H21 800 600 1 0.6 1 0.48
11BLD10 SP & L Non-essential Secondary PI GT11 H21 2650 800 1 1 0.8 1.59
11BND10 SP & L essential Secondary PI GT11 H21 1950 800 1 1 1 1.17
12BPA11 & 12BPA12 Transformer for feed water pumps Secondary PI GT12 F22 2 50 0.5 26
36.00 15.00 51.00
HP IP FWP Drive 11 & 12 HP IP FWP Drives Secondary PI GT12 F22 3200 800 2 14 1 10
12BHD10 Secondary non-essential Secondary PI GT12 H22 5900 800 1 2.8 0.8 3.54
12BMD10 Secondary essential Secondary PI GT12 H22 4000 800 1 1.8 1 2.4
12BLU10 & 12BNU10 Transformers Secondary PI GT12 H22 1000 1500 2 3.8 1 2.04
44.74
BMS2 Secondary PI GT12 H22 1200 600 1 0.9 1 0.72
13.38 11.50 24.88
HRSG2 RIO Secondary PI GT12 H22 2400 600 1 1.8 1 1.44
Fire control cabinet Fire control cabinet Secondary PI GT12 H22 800 800 1 0.6 1 0.48
12BLD10 SP & L Non-essential Secondary PI GT12 H22 2650 800 1 1 0.8 1.59
12BND10 SP & L essential Secondary PI GT12 H22 1950 800 1 1 1 1.17
00BFT30, 00BFT40,
Auxiliary transformers ACC Room H31 88 0.5 24 15 39
00BFU30, 00BFU40 2250 1350 4 24
00BFA30 LV Switchgear ACC Room H32 6900 800 1 4 0.5 4.14
00BFB30 LV Switchgear ACC Room H32 5100 800 1 4 0.5 3.06
00BFA40 LV Switchgear ACC Room H32 6900 800 1 4 0.5 9.8 4.14 15.84 11.5 27.34
freigegeben/ Released

00BFB40 LV Switchgear ACC Room H32 5100 800 1 4 0.5 3.06


ACC RIO Control ACC Room H32 2400 800 1 1.8 1 1.44
00BFT60 Transformers 2MVA ROP E-room H41 2000 1350 1 16 0.5 8 4.25
00BNT60, 00BLT60 Transformers 250 KVA ROP E-room H41 1500 100 2 7.6 1 2.06
00BFA60 LV Switchgear ROP E-room H41 7500 800 1 3.1 0.5 4.5 12.58 11.50 24.08
11.65
00BLA60 SP & L ROP E-room H41 1950 800 1 1 1 1.17
PRS Pressure reducing station cabinet ROP E-room h41 2000 600 2200 1 1.5 1 0.6
00BFU60 Transformers 2MVA ROP E-room H42 2000 1350 1 16 0.5 8 4.25
00BLU60 Transformers 250 KVA ROP E-room H42 1500 100 1 3.8 1 1.03
00BFB60 LV Switchgear ROP E-room H42 7500 800 1 3.1 0.5 4.5
13.35 11.50 24.85
00BLB60 SP & L ROP E-room H42 1950 800 1 1 1 9.35 1.17
Fire control cabinet Fire control cabinet ROP E-room H42 800 800 1 0.6 1 0.48
BOP RIO3 RIO for WSC & RIO for BOP ROP E-room H42 3200 800 1 2.4 1 1.92 Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Weight Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 16
.Rev. Huser
.
Valid for support, platforms, stairs only.
Division of scope:
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»
Scope Responsible
Containers placed and welded on steel plates at top of
concrete pillars Confirm and document Container seller
support points for containers
Civil study and work GE Power
Concrete pillar location. Steel plate LxWxD: 500x500x30mm
Stairs and platforms GE Power
Handrails on containers Container seller

Main E-room
The distance indicated in the below scketch is between pillar centers

3.1m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.2m 3.1m

3.55m
3.55m

3.55m

3.55m

3.55m

3.55m
3.55m
3.55m

3.55m
3.55m

3.55m

3.55m
3.55m
3.55m

3.75m
3.75m

3.75m

3.75m

3.75m

3.75m

3.75m
3.75m
3.75m

3.75m

3.75m
3.75m
3.75m
3.75m

3.75m
3.75m

3.75m

3.75m

3.75m
3.75m

3.75m
3.75m
3.75m

3.75m

3.75m

3.75m
3.75m

3.75m
freigegeben/ Released

3.65m

3.55m
3.55m
3.55m

3.55m

3.55m

3.55m
3.55m

3.55m

3.55m
3.55m

3.55m

3.65m
3.55m
I2 G1 G2 H11 H1
M3 H12 I1 H2 H3 H4 H5 M1 M2

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Support, platforms, stairs Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 17
.Rev. Huser
.
Valid for support, platforms, stairs only.
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»

Containers placed and welded on steel plates at top of Concrete pillar location. Steel plate LxD 500 x 500mm
concrete pillars

RoP E-room

Secondary E-room, power 3.55m 3.75m 3.55m


3.75m
island GT11 & GT12
Stairs Platform
1.2m 2m
3.1m

3.55m 3.75m 3.75m 3.55m


3.55m 3.75m 3.75m 3.55m
Stairs
1.2m

3.7m

Platform
3.1m

Stairs
3.55m 3.75m 3.75m 3.55m
3.55m 3.75m 3.75m 3.55m
Platform

Stairs
1.2m
Platform
3.0m

3.55m 3.75m 3.75m 3.55m


freigegeben/ Released

Stairs
Stairs
1.2m

3.55m 3.75m 3.75m 3.55m


Platform

2.8m
ACC E-room
3.55m 3.75m Platform
3.75m 3.55m

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Support, platforms, stairs Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 18
.Rev. Huser
.
Principles.
Valid for heat losses only Subject to adaptation to local ambiant and vendor specific solutions
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»
This page gives the heat loss of the equipment only.
Heat provided from ouside to be considered as per
local conditions

Heat losses are defined in pages 14, 15 and 16 of this


document

Air out Air out Air out Air out Air out
mounted on mounted on mounted on mounted on mounted on
vertical wall, vertical wall, vertical wall, vertical wall, vertical wall,
top part top part top part top part top part

Forced ventilation, Forced ventilation, Forced ventilation, Forced ventilation, Forced ventilation,
pushed air, pushed air, pushed air, pushed air, pushed air,
ventilation ventilation ventilation ventilation ventilation
mounted below or mounted below or mounted below or mounted below or mounted below or
HVAC C Air return side of the side of the side of the side of the side of the
container container container container container
To
atmosphere
or to I2
N+1 redundancy

HVAC B
freigegeben/ Released

HVAC A

Distribution air duct


G1 G2 H11 M3 H12 I1 H1 H2 H3 H4 H5
I2

Distribution by temp-controlled flaps Main E-room


or other agreed on L2 meeting

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. HVAC and ventilation Resp. Dept Drawing number
Page
principles proposal GSEEE 1GP006913 19
.Rev. Date Name Appr. Huser
.
Valid for heat losses only
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»
This page gives the heat loss of the equipment only.
Heat provided from ouside to be considered as per
local conditions

Heat losses are defined in pages 14, 15 and 16 of this


document

Air out
mounted on
Air out Air out
vertical wall,
mounted on mounted on
top part
vertical wall, vertical wall,
top part top part

Forced
ventilation,
Forced Roof top units or split Forced
pushed air,
ventilation, ventilation,
pushed air, unit – N+1 redundancy pushed air, ventilation
ventilation mounted below
ventilation
mounted below the container
mounted below
the container the container

Forced
ventilation,
pushed air,
Roof top units or split unit – N+1 redundancy ventilation
mounted below
the container

Secondary power island E-room ROP E-room


Air out
Air out Air out Air out Air out mounted on
mounted on mounted on mounted on mounted on vertical wall,
vertical wall, vertical wall, vertical wall, vertical wall, top part
top part top part top part top part

Forced Forced Forced Forced


freigegeben/ Released

ventilation, ventilation, ventilation, ventilation,


pushed air, pushed air, pushed air, pushed air,
ventilation ventilation ventilation ventilation
mounted below mounted below mounted below mounted below
the container the container the container the container

Roof top units or split unit – N+1 redundancy

ACC E-room
Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. HVAC and ventilation Resp. Dept Drawing number
Page
principles proposal GSEEE 1GP006913 20
.Rev. Date Name Appr. Huser
.
Valid for Interface to others – cooling and water only
For doors and equipment arrangement refer to pages «main E-room equipment arrangement» Main E-room

Rain water Rain water Rain water


interface point: interface point: interface point:
at +0.1m at +0.1m at +0.1m

Rain water collection down to


+0.1m level
in E-container seller scope
freigegeben/ Released

Rain water
interface point: Rain water Rain water
at +0.1m interface point: interface point:
at +0.1m at +0.1m

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Interface to others – Resp. Dept Drawing number
Page
cooling and water GSEEE 1GP006913 21
.Rev. Date Name Appr. Huser
.
Valid for Interface to others – cooling and water only
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»

Cooling water Secondary power island E-room


connection for VSD:
Rain water 67kW per VSD
interface point: 70kW in total
at +0.1m Rain water
interface point:
Rain water collection down to +0.1m at +0.1m
level
in E-container seller scope

Rain water
interface point:
at +0.1m

Rain water
interface point:
at +0.1m

ACC E-room
freigegeben/ Released

ROP E-room

Rain water
interface point:
at +0.1m Rain water
interface point:
at +0.1m
Rain water collection down to +0.1m
level in E-container seller scope

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Interface to others – Resp. Dept Drawing number
Page
cooling and water GSEEE 1GP006913 22
.Rev. Date Name Appr. Huser
.
Valid for lighting and small power only
For doors and equipment arrangement refer to pages «main E-room equipment arrangement» Switch on-off the marked area, power socket

Lighting supplied through the HVAC and lighting distribution panel. Power socket

400lux in normal operation (normal and essential on)


GE appliance type “LED Mariner” with GE T8 LED tube or equivalent - www.gelighting.com/eu -

Essential lighting: no
OPTION: 50lux, minimum each 3rd lamp.

Emergency lighting: using 90min integrated battery back-up to mark escape way with 2 lux minimum and in compliance with local law at installation place.

Power outlet: single phase as per “Electrical equipment for system package, technical requirements”
freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Lighting and small power Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 23
.Rev. Huser
.
Valid for lighting and small power only
For doors and equipment arrangement refer to pages «main E-room equipment arrangement»

Switch on-off the marked area, power socket

Power socket

Secondary power island E-rooms

ROP E-room ACC E-room

To be iluminated together with upstair container


freigegeben/ Released

Non-public

C 04.06.2018 Casal Date .04.06.2018 =


Prep. .
Casal EVM II GE Power Doc Code +
Gas Power Systems EVM/00/E/UBB---EP52/EA/010
Check. Roux
. Lighting and small power Resp. Dept Drawing number
Page
Date Name Appr. GSEEE 1GP006913 24
.Rev. Huser
.