Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
University of Technology –
Mauritius
SCHOOL OF INNOVATIVE
TECHNOLOGIES & ENGINEERING
2.31 SOFREL PLC S50 Remote Terminal Unit and the SCADA software.............10
................................................................................................................................. 23
5.0 References:........................................................................................................ 26
Advantages Description
Economics Less costly when intended to further expand the
system (save Cost).
Speed Several nodes connected and no centralized
domain for storage of data (several memories
per nodes available).
Inherent distribution All the workstations are connected together and
each
Reliability System is much more reliable since if one
station failed there are still others from which
information can be fetched from.
Incremental growth Easier to add other processor or systems.
Disadvantages
Software Many software is needed
Network Virus on network
More components to
fail
The Grand Baie Treatment Plant is one of the three main Wastewater
Treatment Plant found in Mauritius. The wastewater is treated up to
the tertiary level at the Treatment Plant. Wastewater is collected from
This chapter gives us a clear explanation on how the communication between the different hosts
is being performed. To have a better understanding, let us consider some important aspect in our
system first. Below is some basic explanation which will help us throughout this chapter.
System Busses
The internal paths along which the digital signals flow within the PLC are called
busses.
The system has four busses:
- The CPU uses the data bus for sending data between the different elements,
- The address bus to send the addresses of locations for accessing stored data,
- The control bus for signals relating to internal control actions,
- The system bus is used for communications between the I/O ports and the I/O unit.
Memory
System (ROM) to give permanent storage for the operating system and the fixed data used by the
CPU.
RAM for data. This is where information is stored on the status of input and output devices and
the values of timers and counters and other internal devices. EPROM for ROM’s that can be
programmed and then the program made permanent.
I/O Sections
Inputs monitor field devices, such as switches and sensors.
Outputs control other devices, such as motors, pumps, solenoid valves, and lights.
Power Supply
Most PLC controllers work either at 24 VDC or 220 VAC. Some PLC controllers have electrical
supply as a separate module, while small and medium series already contain the supply module.
Programming Device
The programming device is used to enter the required program into the memory of the processor.
The program is developed in the programming device and then transferred to the memory unit of
the PLC.
• PLC – this is where all the sensors and transducer are connected
from the I/O module such as the Variable Speed Drive for speed
control of the pump, the float switches for the Start and stop of
the pump, the temperature sensor of the pump, the moisture
detector of the pump, the pressure sensor for measuring of pump
pressure, running of the generator and change-over module and
contactors for the opening and closing of the gate valve and
manual operation of the pump.
• Data logger – This stored all the events occurred throughout the
day and are being transmitted to the SCADA found at the PCs for
every Station.
Prepared by: Paraouty, Boodoo, Khodabux
Page 9
HCA3110 Embedded Distributed Systems – Distributed Processing in a box
• Printer – this print the report for the events occurred throughout
specified days.
• Input/output boards;
• A voice board.
• A PC running SOFTOOLS;
• A PC running SOFTOOLS;
• Pagers;
• Mobile telephones;
• Radio links;
• Dedicated lines
automatically. The data collected by the RTUs are logged to disk for
retrieval and further processing using popular spreadsheet packages
(EXCEL, and the like). Data may be displayed in graphic or tabular
format (mimic diagrams, trend charts, tabular reports, etc.). Many
commercially available process control systems are compatible with
S50.
Using ‘Inter-RTU’ links, RTU S50 can directly call one or more SOFREL
RTUs to transfer data and control remote sites.
Over a radio link, a single frequency can be used. RTU S50 can also
serve as a “relay station” for communicating with other stations.
Radio communication
The S50's radio functions offer a wide range of possibilities; they are
compatible with traditional radio sets as well as with the new radio sets
that do not require a license for use.
• The « Radio relay» function makes it possible for the Master station
to communicate with Station B via Station A, in which case the latter
behaves transparently.
RTU S50 can serve as a SCADA interface for monitoring and controlling
one or more PLCs. Supported protocols include:
Using the ‘INTER-SITE feature, RTU S50 can exchange snapshot data
directly with one or more other SOFREL RTUs.
This allows S50 to send its own control/setpoint and status data to
remote sites and retrieve the process data from these sites.
Over a RADIO link, RTU S50 can spontaneously transmit current data to
other stations, using a single frequency for several stations. S50 can
also be used as a “relay station” to pass data along other stations.
RS-232 transmission
The cable must be connected to earth on only one side. The maximum
length for an RS-232 cable is 15 meters.
RS-485 transmission
The RS-485 link for communicating with S50 I/O is not electrically
isolated. The following rules are to be applied:
• The RS-485 bus must have a line structure (i.e., no ring, no star
topology);
• Branches from the main bus must be kept as short as possible (less
than 10 meters);
5.0 References:
Lecture notes
http://www.sofrel.com/
http://arxiv.org/abs/1010.4065
http://www.lesman.com/unleashd/catalog /sensors_multiranger.html