Produced on 15/09/2020 with Xpress Selection V8.9.5 - database DIL 15.5.

Project name CASA ISA


Project address Peru
Reference A
Client name CASA ISA
Revision B_GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RMXYQ4AVL 1 Heat pump VRV IV S 60HZ
RMXYQ5AVL 2 Heat pump VRV IV S 60HZ
FXAQ63PVE 2 VRV AP - De Pared (Panel Plano)
FXMQ140PAVE 2 VRV M-PA - Unidad de conducto montada en el techo
KHRP26A22T 1 Refnet branch piping kit
DTA116A51 2 (DTA116A51)Home Automation Interface Adaptor - External
power supply may be required depending on the model
SVMPC1T 2 VRV Controller by tablet
BRC1E63 4 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
▼ indicates a model size down due to tolerance
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Applied indoor capacity safety factor or tolerance
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 2
2.2. VRV 1 - RMXYQ4AVL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Airflow
°F BTU/h BTU/h BTU/h BTU/h °F °F °F cfm
UE-02 FXAQ63PVE 75.2 / 62.6 15518 20984 14888 16006 42.8 53.5 68.0 671
UE-01 FXAQ63PVE 75.2 / 62.6 15518 20984 14888 16006 42.8 53.5 68.0 671

Required cooling capacity towards the outdoor unit: 31036BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UE-02 41-47 220V 1ph 0.6 1050×290×238 14
UE-01 41-47 220V 1ph 0.6 1050×290×238 14

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 3
2.3. VRV 2 - RMXYQ5AVL
Capacity data at conditions and connection ratio (112%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Airflow
°F BTU/h BTU/h BTU/h BTU/h °F °F °F cfm
UE-06 FXMQ140PAVE 75.2 / 64.0 43308 50386 42696 35135 42.8 55.5 75.0 1624

Required cooling capacity towards the outdoor unit: 50386BTU/h.


Required heating capacity towards the outdoor unit: 53779BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UE-06 43-46 220V 1ph 3.4 1400×300×700 46

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 4
2.4. VRV 3 - RMXYQ5AVL
Capacity data at conditions and connection ratio (112%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Airflow
°F BTU/h BTU/h BTU/h BTU/h °F °F °F cfm
UE-03 FXMQ140PAVE 75.2 / 64.0 43308 50386 41934 35135 42.8 55.5 75.0 1624

Required cooling capacity towards the outdoor unit: 50386BTU/h.


Required heating capacity towards the outdoor unit: 53779BTU/h.
The sum of the required indoor unit capacities is 50386BTU/h for cooling and 53779BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 45347BTU/h (= -10%) and for heating
of 48401BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UE-03 43-46 220V 1ph 3.4 1400×300×700 46

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 5
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
EER EER at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
COP COP at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 6
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC EER (*) Tmp H HC Rq HC COP (*)
% °F BTU/h BTU/h BTU/h/W °F BTU/h BTU/h W/W
VRV 1 RMXYQ4AVL 125 89.6 39239 31036 12.6 32.0 / 26.9 30788 4
VRV 2 RMXYQ5AVL ▼ 112 86.0 48763 (-3.2%) 50386 11.8 32.0 / 27.0 39112 (-27.3%) 53779 3.9
VRV 3 RMXYQ5AVL ▼ 112 86.0 48763 45347 11.8 32.0 / 27.0 39112 (-19.2%) 48401 3.9

(*) The EER and COP values are calculated at nominal conditions: nominal temperatures, 100% connection ratio
and without considering pipe length corrections.

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
VRV 1 RMXYQ4AVL 7.5 R410A 2.9 n/a
VRV 2 RMXYQ5AVL 7.5 R410A 3.4 n/a
VRV 3 RMXYQ5AVL 7.5 R410A 3.4 n/a

Name Model PS MCA WxHxD Wght


A mm kg
VRV 1 RMXYQ4AVL 220V 1ph 16.5 940×990×320 78
VRV 2 RMXYQ5AVL 220V 1ph 27 940×990×320 85
VRV 3 RMXYQ5AVL 220V 1ph 27 940×990×320 85

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 7
3.2.1. VRV 1 - RMXYQ4AVL

Model Qty Description


RMXYQ4AVL 1 Heat pump VRV IV S 60HZ
FXAQ63PVE 2 VRV AP - De Pared (Panel Plano)
KHRP26A22T 1 Refnet branch piping kit
BRC1E63 2 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 8
3.2.2. VRV 2 - RMXYQ5AVL

Model Qty Description


RMXYQ5AVL 1 Heat pump VRV IV S 60HZ
FXMQ140PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
BRC1E63 1 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 9
3.2.3. VRV 3 - RMXYQ5AVL

Model Qty Description


RMXYQ5AVL 1 Heat pump VRV IV S 60HZ
FXMQ140PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
BRC1E63 1 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 10
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping VRV 1


VRV 1
RMXYQ4AVL

⅜"×⅝" ⅜"×⅝"
KHRP26A22T

UE-02
FXAQ63PVE

⅜"×⅝"

UE-01
FXAQ63PVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 11
4.2. Piping VRV 2
VRV 2
RMXYQ5AVL

⅜"×⅝"

UE-06
FXMQ140PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 12
4.3. Piping VRV 3
VRV 3
RMXYQ5AVL

⅜"×⅝"

UE-03
FXMQ140PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 13
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring VRV 1


to centralized controller
P1,P2
VRV 1 UE-02 BRC1E63
RMXYQ4AVL FXAQ63PVE
OUT F1,F2 IN F1,F2 F1,F2
L,N 16.5A 1ph L, N 0.6A 1ph
P1,P2
UE-01 BRC1E63
FXAQ63PVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 14
5.2. Wiring VRV 2
to centralized controller
P1,P2
VRV 2 UE-06 BRC1E63
RMXYQ5AVL FXMQ140PAVE
OUT F1,F2 IN F1,F2 F1,F2
L,N 27A 1ph L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 15
5.3. Wiring VRV 3
to centralized controller
P1,P2
VRV 3 UE-03 BRC1E63
RMXYQ5AVL FXMQ140PAVE
OUT F1,F2 IN F1,F2 F1,F2
L,N 27A 1ph L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 16
6. Device Options
6.1. Centralized Controller Options
Model Description Used by
SVMPC1T VRV Controller by tablet DTA116A51 (x2)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 17
7. Centralized Controllers
7.1. Concept

Control Groups Specific Controller Models

Control group 1
Automatización en casa
VRV 1 (2) # outdoors 3
VRV 2 (1) # indoors 4 # controllers 2
VRV 3 (1)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 18
7.2. Control group 1

VRV 1 (2)
RMXYQ4AVL OUT F1,F2

VRV 2 (1) Automatización en casa


RMXYQ5AVL DTA116A51

VRV 3 (1)
RMXYQ5AVL OUT F1,F2

Automatización en casa
DTA116A51

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 19