1Safety Precautions
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.

01 02 03

Do not place a magnet near the Do not place the device next to
Do not install the device in an area heating equipments
product. Magnetic objects such as
subject to direct sun light, Humidity
magnet, CRT, TV, monitor or speaker
or dust
may damage the device.

04 05 06

Be careful not to let liquid like Clean the device often to remove Do not let children touch the
water, drinks or chemicals leak dust on it device without supervision.
inside the device.

2
Safety Precautions
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.

07 08 09

Do not drop the device. Do not disassemble, repair or Do not use the device for any
alter the device. other purpose than specified.

10 11 12

Do not damage the device In cleaning, do not splash water Contact your nearest dealer in
on the device but wipe it out with case of a trouble or problem.
smooth cloth or towel.

3
Product Contents
Basic Contents

Wall Mounting Screws – 2 pcs. Wall Plugs– 2 pcs. Surge Suppressing Diode– 4 pcs.

Screw Driver – 2 pcs. Software CD InBio Installation Guide

Inbio460
4
Product Contents
Optional accessories

Weigand Card Reader Prox Card FR1200 FP Reader K1-1 Exit Button

ZK4500 FP Enrollment reader Card Enroller Inbio Metal Case RS485 convertor

5
Product PIN Diagram
SD Card Slot
LED indicators
LINK LED
Aux Input 1 LED solid green indicates
Ethernet Port LINK
TCP/IP communication is
(Green)
ACT LED normal
Aux Input 4
DIP Switch
FR1200
ACT Flashing LED indicates data
Fingerprint
PC RS485 Port Reader (Yellow) communication is in progress
Aux Output 1 State Indictor
EXT RS485
#1 Door Exit Flashing LED indicates data
Button (Yellow &
communication in progress
#1 Door Card Green)
Aux Output 4 Reader
#2 Door Exit PC RS485
#1 Door Sensor Flashing LED indicates data
Button (Yellow &
#1 Door Lock communication is in progress
#2 Door Card Green)
Reader
#3 Door Exit
Button POWER Flashing LED indicates the
(Red) panel is powered on.
#3 Door Card
Reader
#4 Door Sensor Flashing LED indicates that
#4 Door Exit RUN
#4 Door Lock Button panel is in normal working
(Green)
Lock Power #4 Door Card mode
Reader
Inbio Power
CARD Flashing LED indicates that
(Yellow) the card is read by the panel.

6
Product Dimension

Inbio460

106mm 106mm
(4.17in.) (4.17in.) 36mm
(1.42in.)
Dimensions(L*W*H):226× 106× 36(mm)
226mm 8.89× 4.17× 1.42(inches)
(8.89in.)

InBio-Casing

330mm 330mm
(13.0in.) (13.0in.) 90.5mm
(3.56in.)

Dimensions(L*W*H): 400 *90.5*330(mm)


400mm 15.7× 13.0× 3.56(inches)
(15.7in.)

7
Installation of Panel & Case
Metal Case

8
Wire Legend
Detector Infrared sensors FR1200 Inbio-Box #1Exit Button #1Card Reader #4 Exit Switch #4 Card Reader

DC
12V DC
Power

12V

Network RS485 Convertor Floodlight Alarm Normally Close Lock Normally Open Lock Power Supply

9
Power wiring diagram
Without AC 110-220V
Inbio460

Backup Battery

AC

Switching power supply

With
Backup Battery
AC 110-220V
Inbio460
+
Backup Battery
-

AC

Switching power supply

10
FR1200 Connection

12V DC
12V DC

#1 FR1200 #2 FR1200 #3 FR1200 #8 FR1200

DIP Switch Setting For FR1200 Device ID Important Notes

1. There are six DIP switches on the back of FR1200 , Switches 1-4 is for RS485
address , switch 5 is reserved , switch 6 is for reducing noise on long RS485 cable.
2. Set the odd number for IN reader, and the even number for OUT reader(for eg.
For two readers for one door- the RS485 address 1 is for IN reader, RS485 address
2 is for OUT reader )
3. If FR1200 is powered from Inbio460 panel ,the length of wire should be less
than 100 meters or 330 ft.
4. The External RS485 interface can supply maximum 500mA current , The
FR1200’s startup current is 240mA. So Inbio460 only can only power two FR1200s.
5. If the cable length is more than 200 meters or 600 ft , the number 6 switch
should be ON as below

Distance

More than 200 meters

11
Weigand Connection
Beeper

Green LED

Weigand D1

Weigand D0

GND

DC+(6-14V)

Weigand Card Reader

Exit Button Connection


12V DC Power Supply

DV12V(+)

DV12V(-)

BUT
NO

GND COM

NC

ZK ABK Exit Button


Notice:

separate power supply


K1-1 Exit Switch

12
Lock Connection
For Normally Open -Lock powered from panel power supply FR107

GND
12V DC

Sensor
Sensor

GND

12V DC

FR107
For Normally Closed -Lock powered from panel power supply

12V DC
GND

Sensor
Sensor

GND

12V DC

13
Lock Connection
Switching Wet Contact to Dry Contact
Steps:
Important Notes:

InBio is set to supply lock power by default from built-in


power supply , If you want to use external power supply , Inbio460 Detach from Rail Remove Top Cover Lock Relay
you must take the following steps
1. Take apart the cover of inbio460
2. Select the desired lock relay and find its jumpers
5 1 5 1 5 1 5 1
3. Take off the jumpers and change to
4. Connect the lock as shown in the diagram below. Changed Setting Jumpers Terminals Default Setting

Connecting a Lock with External Power supply

GND

12V DC

FR107

SEN SEN GND 12V DC

14
Auxiliary Input/Output
Aux. Input Connection

Smoke Detector

12V DC
GND
COM
NO
NC

Aux. output Connection

Alarm

12V DC
GND
COM
NO
NC

15
Ethernet Connection

Important Notes:

1. Both 10Base-T and 100Base-T


TCP/IP are supported
2. The cable length must be less
ZK4500 Enrollment
than 100 meters or 330 ft.
reader
CR10 Card Issuer 3. For more than 100 meters ,
please use HUB to amplify the
The CR10 and ZK4500 are connected to the server
using USB connection. signal

Direct connection
To connect Inbio460 with a PC directly, connect both devices with a straight network cable. As the Inbio460 supports auto MDI/MDIX ,
it is not necessary to use a crossover type cable.

ZK4500 Enrollment
reader
CR10 Card Issuer

16
RS485 Connection

#63 Inbio460

RS485-
RS485+
#1 Inbio460 GND

Important Notes Do's and Dont's for RS 485 connection


1. RS485 communication wires should be a shielded or twisted pair cable.
RS485 communication wires should be connected in a bus cascade instead
of a star form, to achieve a better shielding effect by reducing signal
reflection during communications.
2. A single 485 bus can be connected with 63 access control panels at the
most, but preferably less than 32 panels should be connected.
3. To eliminate signal attenuation in communication cables and suppress
interference, if the bus is longer than 200 meters, set the number 8 DIP
switch to the ON position. This is equivalent to a parallel connection of one
120ohm resistance between the 485+ and 485- lines.

Distance

More than 200 meters

#1 Inbio460 #* Inbio460

17
DIP Switch Setting
Introduction RS485 Address

1. Number 1-6 are reserved to set the device number for RS485
communication. The code is binary, and the numbering starts from left to
right. When the switch is set to ON position, it indicates 1 (on); when the
switch is set downwards, it indicates 0 (off). For example, to set a device
number 39=1+2+4+32, which corresponds to the binary code 111001, put
number 1, 2, 3, and 6 to ON position, as illustrated below.

2. For more details, please check the table at the end of this document

Restore factory setting Terminal Resistance

1. If you forget the inBio IP address or the device does not work 1. Number 8 is for setting the RS485 termination resistance. Putting the
normally, you can use the number 7 terminal to restore inbio460 to switch to ON position is equivalent to parallel connection of a 120ohm
factory default settings. The parameters which gets reset are termination resistance between 485+ and 485-
device IP address, communication password ,gateway ,subnet mask. 2. As shown in diagram below, for more info please read RS485 connection
2. The switch is OFF by default. When it is moved upwards and important notes
downwards for three times within 10 seconds and finally returned
to OFF position, the factory settings will be restored after the
access control panel is restarted.
1 times 2 times 3 times OFF
120ohm

18
Electrical Specification

Min. Typ. Max. Notes


Working power supply
Voltage(V) 9.6 12 14.4 Use regulated DC power adaptor only
Current(A) 2
Electronic lock relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 2
Auxiliary relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 1.25
Switch Aux. input
VIH (V) TBD
VIL (V) TBD
Pull-up resistance (Ω) 4.7k The input ports are pulled up with 4.7k resistors
WEIGAND Input
Voltage(V) 10.8 12 13.5
Current(mA) 500
ZK Electronic lock
Voltage(V) 10.8 12 13.2
Current(mA) 500

19
Troubleshooting
1. Fingerprint can not be read well or it takes too long.
 Check whether a finger or fingerprint sensor is stained with sweat, water, or dust
 Retry after cleaning the finger and fingerprint sensor with dry cloth.
Reset Button
 If a finger is way too dry, rub your finger on the palm and retry.
 Try to reset fingerprint sensor by pressing the reset button at the bottom of the reader

2. Fingerprint is matched but authorization keeps failing.


 Check whether the user’ access is restricted.
 Inquire with administrator whether the enrolled fingerprint has been deleted from the device
for some reason.

3. How Many kinds of WEIGAND format can be supported.


 The panel is set to read 26 bit by default.
 However there are 9 other bit formats which can be selected from the software. In addition you
can also define your custom bit format.

4. How many verification modes can be support.


 Card Only
 Fingerprint Only
 Password Only
 Card plus fingerprint
 Card plus password
 Card or fingerprint

20
Specification
Communication RS485, Ethernet
Baud Rate for RS485 9600-115200 baud
Power Supply 12V DC, 3A
Device Capacity Card capacity 30,000 ; Log events capacity 100,000 ; Finger capacity 3,000
LED Indicator Indication for communication, power, status and prox card
Environment Operating Temp: 32-113 °F (0-45 °C) Operating Humidity: 20% to 80%
Number of doors controlled four door one way or two door two way
Number of card readers supported 4
Number of FR1200 supported 8
FR1200 Sensor Fingerprint sensor 500dpi Optical / Optical sensor
Types of readers supported 26-bit Weigand, others upon request
Number of Inputs 12 (4 Exit Device, 4 Door Status, 4 AUX)
Number of Outputs 8 (4- Form C relay for lock and 4- Form C relay for Aux output)
Weight 7.8lbs (3.55kg)
Enclosure Stainless Steel
Mounting Wall Mount
Dimensions (Bundle Only) 15.7in. × 3.56in.× 13.0in. 400mm(L) X 90.5mm(W) X 330mm(H)
Dimensions ( Board Only) 8.89in.× 4.17in.× 1.42in. 226mm(L) X 106mm(W) X 36mm(H)
CPU 32 bit 400MHz
RAM 32MB
Flash 128MB
Certified

21
PC485 Table

Switch Setting Switch Setting


Place Address Place Address
1 2 3 4 5 6 1 2 3 4 5 6

Address No. 1 2 4 8 16 32 Address No. 1 2 4 8 16 32


01 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
02 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
03 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
04 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
05 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
06 OFF ON ON OFF OFF OFF
38 OFF ON ON OFF OFF ON
07 ON ON ON OFF OFF OFF
39 ON ON ON OFF OFF ON
08 OFF OFF OFF ON OFF OFF
40 OFF OFF OFF ON OFF ON
09 ON OFF OFF ON OFF OFF
41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF
42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF
43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF
44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF
45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF
46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF
47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF
48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF
49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF
50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF
51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF
52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF
53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF
23 ON ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 55 ON ON ON OFF ON ON

25 ON OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 57 ON OFF OFF ON ON ON

27 ON ON OFF ON ON OFF 58 OFF ON OFF ON ON ON


28 OFF OFF ON ON ON OFF 59 ON ON OFF ON ON ON
29 ON OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
30 OFF ON ON ON ON OFF 61 ON OFF ON ON ON ON
31 ON ON ON ON ON OFF 62 OFF ON ON ON ON ON
32 OFF OFF OFF OFF OFF ON 63 ON ON ON ON ON ON

22
Functions and specifications of the product are subject to change without notice due to quality enhancement or function update. For any inquiry
for the product, please contact ZKTeco Inc .
ZK China :
ZK Building, Wuhe Road, Gangtou,
Bantian, Buji Town, Longgang District,
Copyright 2013 ZKTeco Inc. All right reserved. Shenzhen China.
ZKTeco May, at any time and without notice , Make changes or Tel.: +86 755-89602345
improvements to the product and services offered and/or cease sales@zkteco.com
producing or commercializing them. zkteco.com

Potrebbero piacerti anche