Characteristic
Design N. 480005
Type Oil Immersed Transformer
Rated power [MVA] 16 MVA
Insulation Liquid Mineral Oil Nynas
Primary Voltage [kV] 110
Primary Tapings [%] +/-9x1.78% OLTC on HV Side
Secondary Voltage [kV] 20
Insulation Class Primary Voltage [kV] AC185 LI450
Insulation Class Primary-Neutral Voltage [kV] AC130 LI290
Insulation Class Secondary Voltage [kV] AC50 LI125
S-C apparent power of the network and duration [MVA] HV side 6000 MVA - LV side 500 MVA
S-C withstand of the transformer [sec] 2
Frequency [Hz] 50
Vector Group YNd11
Ambient Temperature [°C] -25 / +40
Altitude [m] <1000
Location Outdoor
Surface Treatment Epoxy-Polyurethane paint, 160 microns RAL
7032
Guaranteed Values
Standard and Tolerances According to IEC 60076
Temperature Rises Top oil / Windings [°K] 60 / 65
No Load Loss, P0 [kW] 12
Load Losses, Pk (at 75°C) [kW] 90
Impedance, Uk [%] 11
No load current at rated voltage and frequency [%] 0.25
Sound Pressure Level at no load, Lpa [dB(A)] 85 at 0.3 m ONAN
Type of design
Tank Vacuum proof tank, bolted cover
Cooling OFAF
Winding Conductor Material Cu
Primary side bushings 3 450kV/800A – Condenser Bushings –
ABB GOB type – brown color
Primary-Neutral side bushings 1 325kV/800A – Condenser Bushings –
ABB GOB type – brown color
Secondary side bushings 3 24kV/1000A – DIN Porcelain Bushings –
Comem type – brown color
Tap Changer Type On-load
Maker ABB UBB RN 350/150 in tank mounted
Accessories 1 Oil-air cooler with pump and fans
Core made of cold rolled grain oriented low
1
loss steel
1 Conservator complete with OLTC chamber
ABB 1/2
ABB S.p.A. TRANSFORMER DATA SHEET
Weights and dimensions – Refer to the latest revision of overall dimensions drawing for definitive values
Oil Weight [kg] 8100
Total Weight [kg] 30500
Dimensions (without separate cooler, LxWxH) [mm] 5500x3500x5500
Notes/Deviations:
1. Surge arresters, grounding resistors, remote control/signaling devices, current and/or voltage
transformers are not included.
2. Neither cables/busbars for connection with electrical networks nor wires for connection with remote
control/signaling devices are included.
3. No civil works are included in our scope of supply.
ABB 2/2