SREEGIRI CONSULTANTS DESIGN OF FRICTION SLAB Rev-0

EDAPPALLY, COCHIN

Project: - FOUR LANING OF THALASSERY - MAHE BYPASS


SECTION OF NH-17 FROM KM 170.600 TO KM 189.200 UNDER
NHDP PHASE -III ON EPC MODE IN THE STATE OF KERALA.

DESIGN OF FRICTION SLAB

(Design Note No: SGC/17-18/TMB/DN-101A)


Reference drawing No: SGC/17-18/TMB/SD-101B

CLIENT:
NATIONAL HIGHWAYS AUTHORITY OF INDIA

AUTHORITY:
CHAIRMAN, NATIONAL HIGHWAYS AUTHORITY OF INDIA,
G-5 & 6, Sector 10, Dwaraka, New Delhi-110075

CONTRACTOR:
GHV (India) Pvt. Ltd - EKK Infrastructure Private Limited (JV)
AML Centre -I, 8 Mahal Industrial Area
Mahakali Caves Road, Andheri(E), Mumbai-400093

DESIGN DIRECTOR:
SREE GIRI CONSULTANTS
Ponnadi Lane
Jawans Cross Road, Cochin-41
Email – sgc.cons@gmail.com

PROOF CONSULTANT:
RUKY PROJECTS PVT. LTD

AUTHORITY'S ENGINEER:
Feedback Infra Pvt. Ltd.-
Mukesh Associates (JV)

R1 Revised Dimensions 12-04-19 APPROVED BY


R0 Initial Submission 05-04-19
Revisions Description Date
DATE DESIGNED BY CHECKED BY
Amit Joseph
12-04-19 Mohamed Sherin CP. M.Tech Shine Varghese. M.Tech
M.Tech

GHV (India) Pvt. Ltd- NATIONAL HIGHWAYS


EKK Infrastructure Pvt Ltd(JV) AUTHORITY OF INDIA 1
SREEGIRI CONSULTANTS DESIGN OF FRICTION SLAB Rev-0
EDAPPALLY, COCHIN

A Introduction
Design of friction slab to take care of dispersion of lateral load on crash barrier in case of vehicle
collision is shown below. Additional details such as design of crash barrier, etc can be found in DN-
101.

B Dimensions of Structure

Fig. Dimension details of Crash Barrier with Friction Slab

GHV (India) Pvt. Ltd- NATIONAL HIGHWAYS


EKK Infrastructure Pvt Ltd(JV) AUTHORITY OF INDIA 2
SREEGIRI CONSULTANTS DESIGN OF FRICTION SLAB Rev-0
EDAPPALLY, COCHIN

Design Data
Weight of Concrete = 2.500 t/m3
Weight of Earth = 2.000 t/m3
Weight of Wearing Coat = 2.400 t/m3
Coefficient of Friction μ = 0.500

Crash Barrier
Cross-sectional Area of Crash Barrier = 0.296 m2
Weight of Crash Barrier = 0.739 t/m
Distance of CG in Horizontal Direction from Point A = 0.169 m

Friction Slab
Cross-sectional Area of Friction Slab = 0.828 m2
Weight of Friction Slab = 2.070 t/m
Distance of CG in Horizontal Direction from Point A = 1.044 m

Earth above Friction Slab


Weight of earth above Friction Slab = 1.331 t/m
Distance of CG in Horizontal Direction from Point A = 1.671 m

Wearing Coat
Weight of wearing coat = 0.369 t/m
Distance of CG in Horizontal Direction from Point A = 1.475 m

Weight of vehicle at time of collision


Weight of vehicle at time of collision (assuming 50% load is applied) = 0.750 t/m
Distance of CG in Horizontal Direction from Point A = 0.750 m

Type of Containment = Normal


Horizontal Force assumed acting at top of crash barrier = 1.500 t/m
Lever Arm from Point A = 1.725 m
Destabilizing Moment at Point A Mo = 2.588 tm/m

Stabilizing Moments at Point A = 0.125 tm/m


+ 2.160 tm/m
+ 2.225 tm/m
+ 0.544 tm/m
+ 0.563 tm/m
Ms = 5.616 tm/m

Check for Overturning


FOSoverturning = Ms/Mo = 2.171
> 2 =>
OKAY

Check for Sliding


Sliding Force ΣH = 1.50 t/m
Restoring Force μΣF = 2.63 t/m
FOSsliding = μΣF/ΣH = 1.753
> 1.5OKAY
=>

GHV (India) Pvt. Ltd- NATIONAL HIGHWAYS


EKK Infrastructure Pvt Ltd(JV) AUTHORITY OF INDIA 3
SREEGIRI CONSULTANTS DESIGN OF FRICTION SLAB Rev-0
EDAPPALLY, COCHIN

Design for Friction Slab Section

Design Moment, Med = 38.813 kNm


Yield Strength of Steel fy = 500 N/mm2
Strength of Concrete fck = 40 N/mm2
Strength of Concrete in tension fckm = 3 N/mm2
Breadth of Section, b = 1000 mm
Depth of Section, D = 250 mm
Clear cover, c = 50 mm
Dia of Strirrup, ds = 0 mm
No. of Tension Reinf. layers = 1
Dia of Tension Rebar = 12 mm
Steel provided in spacing (S) or number (N) = S
Number/Spacing of Tension rebar in one layer = 180 /mm
No. of Comp. Reinf. layers = 1
Dia of Comp. Rebar = 12 mm
Steel provided in spacing (S) or number (N) = S
Number of Comp. rebar in one layer = 180 /mm
Ast Provided = 628.319 mm2
Asc Provided = 628.319 mm2
Effective depth, d = = 194 mm
Min. Longitudinal Steel required = 302.640 mm2
Tension steel provided is sufficient for minimum requirement.
Factor for eff. height of comp. zone, λ = 0.8
Effective strength Factor, ƞ = 1
Material safety factor for concrete, ϒc = 1.5
Material safety factor for steel, ϒs = 1.15
Design Strength of Concrete, fcd = 26.667 N/mm2
Is width of compression zone decreasing in the direction of compression zone?
= N
ƞ.fcd = 26.667 N/mm2
Neutral Axis Depth, X = 12.81 mm
X,lim/d = 0.617
X,lim = 119.65 mm
X < Xlim
Modified NA, λX = 10.24 mm
Moment of Resistance, Mrd = 51.598 kNM
Slab is safe for provided steel

GHV (India) Pvt. Ltd- NATIONAL HIGHWAYS


EKK Infrastructure Pvt Ltd(JV) AUTHORITY OF INDIA 4