1 About This Manual User Manual
1.4 Others
This document will take the PVS-24M-HV for example. For the installation and
use of other types of combiner boxes, please also refer to this manual.
PVS-20M-HV
PVS-16M-HV
The electrical structure, installation and use method of PVS-20M-HV are the
same with that of PVS-24M-HV. The only difference between them is the
numbers of DC input string. Please contact our after-sales service center +86
551 6532 7834 if you have any doubt.
2
User Manual 1 About This Manual
The following symbols on the device enclosure must be paid attention to.
Symbols Explanation
3
2 Safety Instructions
This chapter describes some important safety instructions about SunBox PVS.
Please read the manual carefully before installation. If any device damage
occurs when ignoring the safety instructions, our company has the right to
exclude all warranty claims.
Lethal Voltage!
Death resulting from burning and electric shock upon touching the
live components of the PVS.
Disconnect the end connection of the PV string before cable
connection;
Do not use ordinary ammeter to measure the DC voltage before
cable connection. An ammeter with withstanding voltage of 1500V is
recommended. Serious consequences may follow if otherwise.
Observe all safety instructions required by the PV cell manufacturer.
Device damage or system fault may cause fire and electric shock!
Optical check the device for any possible damages or dangerous
states before operation.
Check if other external devices or circuit connection are in safe state.
Work on the device only when it is safe to do so.
4
User Manual 2 Safety Instructions
5
2 Safety Instructions User Manual
Make sure the terminals are firmly connected during wiring. If the cable
copper core and the terminals are not connected firmly, terminals will
be over-heating and burnt. Anti-flaming cables with multi-strand are
advisable and the cable cross-sectional area should be no less than
the recommended value.
The nuts of the water-proof terminals must be firmly screwed to
prevent water leakage and PVS damages.
Pull the fuse out of the fuse holder for personal and device safety.
Lock the cabinet door and seal the water-proof cover of the lock core
after operation.
No not open the cabinet door frequently.
6
3 Product Description
3.1 System introduction
For a large-scale grid-connected PV system, it is widespread to install a DC
combining device between PV modules and inverters to minimize cable
connections, facilitate maintenance and enhance reliability.
Our SunBox PVS combiner box series (PVS) are designed for meeting these
requirements, which provides a turnkey solution for PV plant systems.
Considering different types of PVS, a certain number of PV strings can be
connected to the input side of PVS. After combining work done, at the output
side, there will be one DC+ and one DC- main line. By using of surge protection
device (SPD) and circuit breakers, the output can be connected to inverters
directly.
The PV generation system including a PVS is shown in following figure.
7
3 Product Description User Manual
PVS - XX M - HV
A B C D
A: Device name
B: Max. input number of PV strings
C: Possess the function of monitoring
D: High voltage at 1500Vdc.
Model Max. string number Monitoring function
PVS-24M-HV 24 YES
PVS-20M-HV 20 YES
PVS-16M-HV 16 YES
8
User Manual 3 Product Description
A
B
9
4 Installation Guide
4.1 Checking before installation
The delivery content of the PVS is shown below:
10
User Manual 4 Installation Guide
950
253
690
Unit: mm.
Pictures in this manual are indicative only! The real product you
receive may differ.
11
4 Installation Guide User Manual
Humidity during installation may damage the PVS. Do not install the
PVS during rainy or humidity days.
Screw the water-proof terminals tightly to prevent moisture penetration
no matter the installation is vertically or horizontally. Seal the unused
terminals after cable connection.
2X
1000
460
12
User Manual 4 Installation Guide
Strutting piece
Rooftop surface
13
4 Installation Guide User Manual
Step 3 Fix the PVS to the surface according to the sequence of bolt, spring
washer, flat washer, PVS hangers, support, and nut. Torque:18N.m.
Column-mounted steps:
Step 1 Mark position and drill holes on the frame according to the distance of
the hangers on the four corners of the PVS.
Step 2 Fix the PVS to the surface according to the sequence of bolt, spring
washer, flat washer, PVS hangers, support, and nut. Torque: 18N.m.
14
User Manual 4 Installation Guide
I
H
J K
G
L MN O
E F
B
D
C
No. Description
A DC+ fuse cartridge
B DC- fuse cartridge
C RS485 ports
D Ground copper bar
E Output of DC negative pole
F Output of DC positive pole
G DC switch
H SPD
I Protection fuse of the switching power supply
J Power board
15
4 Installation Guide User Manual
No. Description
Indicators, from left to right:
TX: transmitted communication data signal indicator;
RX: received communication data signal indicator;
K RUN: monitoring unit Run status indicator;
SPD: surge protection device Fault indicator;
CB: circuit breaker status indicator;
PWR: monitoring unit power supply status indicator.
LED display (can display current, baud rate and communication
L
address)
M Setting switch (used to set the actual input numbers of the PVS)
N Dip switch (setting communication address)
O Push switch (switch between current and communication parameter)
Pictures above are for orientative information, and some details may
not exactly correspond to the product you received. Please prevail in
kind.
16
User Manual 4 Installation Guide
A C
E
Monitor
I nput
Ou tput F
B D
Nylon terminal
A
C
E
F
B D
MC4 terminal
Note 2: the MC4 terminal and its accessories are within the scope of delivery.
User needs not to purchase.
17
4 Installation Guide User Manual
OFF
ON
Step 4 Remove fuse (Take nylon terminal for example).
Before After
18
User Manual 4 Installation Guide
Nylon terminal
Step 1 Loosen the union nut of water-proof terminals.
Step 2 Insert the “PV1+” cable through terminals of positive input area, and
connect the cable to the “PV1+” terminal inside the device. Enough wire
bending space should be ensured.
19
4 Installation Guide User Manual
No. Description
A Cable (e.g. “PV1+”, “PV2+”… “PV1-”, “PV2-” etc.)
B Conduit
Step 3 Stripped off the cable insulation layer, using wire stripper, to reveal the
copper core, length as specified in above table.
12mm
16mm2
Step 6 Follow the same procedure to connect rest cables. Comb all the input
cables together with cable ties and firm them onto the cable support bar.
Appropriate cable bending space shall be ensured.
20
User Manual 4 Installation Guide
Press the bolt toward the side with indentation during fixation. Make
sure the terminal is inserted into the PVS as much as possible.
MC4 terminal
Step 1 Strip off 7mm insulation layer from the positive and negative DC cable.
Step 2 Assemble the cable ends with crimp contacts by crimping pliers.
Step 3 Connect the cables according to the method illustrated below. Pull the
cable gently to make sure it is secured.
− Connect the positive input cable according to the figure below.
A
B
C
A B C
PVS positive input terminal positive input cable Sealing cover
21
4 Installation Guide User Manual
B
C
A B C
PVS negative input
negative input cable Sealing cover
terminal
40mm
Step 1 Insert the “DC+” cable through “DC Output (+)” terminal. Enough cable
bending space should be ensured.
Step 2 Strip off both protective and insulating layers with the help of a hand
crimping pliers. The length of cable conductor shall be approx. 25mm.
25mm
Step 3 Connect the cable to the proper DT terminal. The cable specification is
specified in "8.1 Technical Data".
Step 4 Instll the DT terminal according to the following steps.
− 1. Use hexagon spanner to remove the nut;
− 2. Insert DT terminal into the output terminal;
22
User Manual 4 Installation Guide
A
E E
D D A Copper bar
F C B DT terminal
C Bolt
D Spring washer
B E Flat washer
F Nut
Make sure that the nuts have been screwed into place. If the cable
conductor has not been connected firmly, long-time work may burn the
terminal. Stranded flame-retarded copper wire shall be used, and its size
shall be over the recommended value as described in 8.1.2.
Nuts of water-proof terminals must be screwed correctly and firmly.
Otherwise, water leakage can damage the PVS.
23
4 Installation Guide User Manual
Step 2 Insert the green-yellow wire from the device outside into the “ ”
water-proof terminal, then pull the wire and connect it to the inner
terminal. Enough wire bending space should be ensured.
Step 3 Strip off both protection and insulation layers, with approx. 12mm
conductor length.
Step 4 Connect the OT terminal.
Step 6 Tighten the nuts of water-proof terminal clockwise. Ground wirings have
been finished.
24
User Manual 4 Installation Guide
Upper layer:A1,B1,FG
Lower layer:A2,B2,FG
Step 1 Unscrew the water-proof terminals “Monitor Input” and “Monitor Output”.
Step 2 Pull the communication cable inside the PVS through the water-proof
terminals.
Step 3 Strip off the cables’ protection layer and the insulation layer until the
copper core is 8mm outside.
Step 4 Insert the screwdriver inside the input cable terminal holes. Pull the
screwdriver until the leaf spring is bounced completely.
Step 5 Insert wires into bottom of wiring holes A1, B1, and FG. Among them:
− Connect communication cable RS485-A to A1;
− Connect communication cable RS485-B to B1;
− Connect communication cable shielding layer to terminal FG.
Step 6 Loosen the screwdriver to let the leaf spring connect to the cable.
Step 7 Follow the same steps to connect the output cables to the A2 ,B2 and FG,
to finish the communication terminal connection.
25
4 Installation Guide User Manual
A1 B1 A2 B2 A1 B1 A2 B2 A1 B1 A2 B2
RS485A
120Ω resistor
RS485B
PC
SolarInfo
Logger (optional)
26
User Manual 4 Installation Guide
A
No. Name
B A Cable trench
C
D B Positive output cable supporting arm
C Negative output cable supporting arm
D Communication cable support arm
Cable trenches
Note: pictures here is indicative only, user can make adjustment according to
real needs.
27
4 Installation Guide User Manual
Note: the LED display can be divided into the first two digits and
last three digits. The first two digits is used to display the Nth
input of the PVS; the last three digits are used to display the
28
User Manual 4 Installation Guide
Item Description
current of this input.
For example: 0110.0 means that the current of the 1st input is
10A.
But when the first two digits are 00, the last three digits are the
voltage. For example: 00700 means that the present voltage is
700V.
Press K2 to turn screen once
Communication address
Communication A0 007
2
0000 0010
(1×21+0×20=2)
3
0000 0011
(1×21+1×20=3)
247
1111 0111 (1×27+1×26+1×25+1×24+0×
23+1×22+1×21+1×20=247)
29
4 Installation Guide User Manual
Binary
Dip-switch settings Decimal address
address
PVS-24M-HV
PVS-20M-HV
PVS-16M-HV
If the strings input are 24 ,20,16, there is no need to set any parameter.
This section introduces the communication setting method of the PVS when the
string inputs are 23 (the product user received is PVS-24M-HV).
If the real strings input do not correspond to the abovementioned input number,
set the parameters according to the following steps to ensure the normal
communication of the PVS.
Step 1 After power on, the monitoring board on the top left of the PVS internal
works normally.
Step 2 Set the protocol switch 2 to the ON position. If the last three digits of the
LED are “P=0” or “P=1”, the PVS is in Setting status as shown below.
ON
Step 3 Press the key switch A1 to select the input string number, for example
24.
Step 4 Press the key switch A2 and turn the last digit of the LED to “0”, i.e. “No
input”.
− “0”: “No input”
− “1”: ”Input”
30
User Manual 4 Installation Guide
Take PVS with 23 inputs for example, the 24th input needs to be set to “No
input”. The LED is shown as below.
K1 k2
Step 5 After setting, turn the protocol switch 2 to the OFF position to save the
above settings.
31
5 Commissioning
Check if the PVS can operate normally after installation:
Step 1 Connect the connection terminal of each PV string.
Step 2 Measure the input voltage of positive pole and negative pole of each
input to make sure they are basically same and the positive pole and
negative pole are connected correctly.
Step 3 Fasten the fuse holder.
Step 4 Close circuit breaker; monitoring unit power indicator “PWR” lights up
and status indicator “RUN” flashes. When push switch K1 is pressed, if
there is a value on the LED digitron, the operation is normal.
PE
NC
PV-
485A
PV+
485B
+5V
SPD GND
CB
Step 5 Lock the door, remove the key and tighten the key-hole water-proof cover.
32
6 Routine Maintenance
Due to ambient temperature, relative humidity, windblown dust and vibrations,
components of PVS will get aging. It is necessary to do the routine maintenance
work periodically on the device.
Only work on the PVS when it is switched off and voltage free. Fuses are
non-resetting once they are broken. After many times replacement, the fuse
holders will get loose. Users should fasten the fuse holders periodically to
ensure valid connections.
Once the fuse is blown, the damage is irrecoverable. Replace the fuse
by qualified operators in time.
Replace the fuse with new one with the same model and the same
grade.
Method to replace fuse:
Open the fuse cover Insert new fuse Close the fuse cover
33
7 Troubleshooting User Manual
34
7 Troubleshooting
This chapter gives the basic troubleshooting methods for customer as a
reference.
On the monitoring
unit, “RX” flashes and Use dip switch to set address
Incorrect address
“TX” does not light again.
up.
35
8 Appendix User Manual
On the monitoring
Contact us for replacement of
unit, indicator “RUN” Faulty CPU board
the monitoring unit
does not flash.
On the monitoring
Failure of surge Replace surge protection
unit, indicator “SPD”
protection device device in time
lights up.
36
User Manual 8 Appendix
PE
NC
PV-
485A
PV+
485B
+5V
SPD GND
CB
If you have any doubt during use of this product, please feel free to
contact us.
E-mail: service@sungrowpower.com
For contact, please provide the following information so that we can
provide you with help and service more quickly:
PVS model
PVS serial number
Brief description of fault information
37
8 Appendix
8.1 Technical data
Types PVS-16M-HV PVS-20M-HV PVS-24M-HV
Max. string number 16 20 24
Nominal output current 176A 220A 264A
Nominal system
1500Vdc
working voltage
Working voltage range
of the monitoring 500Vdc~1500Vdc
module
Max. detection current
15A
of the branch
Communication
RS485
connection method
Power consumption of
3W
the monitoring module
Enclosure protection
IP65
rating
Ambient temperature
-30℃~+60℃
range
Relative humidity 0~95%
Weight approx. 51kg 53kg 55kg
Dimensions (W ×D×H)
950*690*253
(mm)
Optional function
String monitoring Yes
Load switch working
Yes
state monitoring
Communication
RS485
interface
38
User Manual 8 Appendix
Evidence
Sungrow Power Supply Co., Ltd. needs the users to provide the receipt invoice
and the date you purchase. Meanwhile the trademark should be clearly legible.
Otherwise Sungrow Power Supply Co., Ltd. has the right to exclude liability
claims.
Conditions
The original unqualified product should return to Sungrow.
39
8 Appendix User Manual
Users should permit appropriate time to maintenance the device with fault for
Sungrow.
Exclusion of liability
Guarantee or liability claims for damages of any kind are excluded if they are
caused by one or more of the following: