Sei sulla pagina 1di 3

Profile

TemBreak
Safety you can rely on, with choice of Protection

All TemBreak Plugin and drawout


SAFETY TRIP (STANDARD)
MCCBs are fitted with a safety trip
as standard. If an attempt is made
to remove an MCCB while ON it
will automatically trip.

The neutral pole of all TemBreak


EARLY MAKE / LATE BREAK NEUTRAL
MCCBs are of early make / late
break design.
This eliminates the risk of abnor-
mal line to neutral voltages which
may damage sensitive electronic
equipment.

TemBreak MCCBs from 125AF to


SUITABLE FOR ISOLATION
1600AF are suitable for isolation
as defined by IEC 947-2. Positive I (ON) TRIP 0 (OFF)
Contact Indication (PCI) is 400A 400A 400A
achieved via the toggle OFF
mechanism. O

Padlocks can only be installed ON


if the contacts are fully open. I

Terasaki is one of the few manufacturers who can still offer a


CHOICE OF PROTECTION
complete range of Thermal Magnetic MCCBs up to 800 AF.
Ir 0.8
Im
7.1
8.5
The thermal adjustment of the TemBreak range, 63% to 100% of the
6 nominal rating, is one of the biggest on the market.
0.63 1
5 10 This proven form of electromechanical technology still represents by
xIn
xIn
far the largest type of MCCBs sold on the European Market.
Thermal Adjustment Magnetic Adjustment Wouldn't you prefer the choice?
63% - 100% x In 500% - 1000% x In

9
Profile
TemBreak
Features

NEW! NEW!
ADD ON EARTH LEAKAGE BLOCK XMD MOTOR OPERATOR

• Wide range of current & • Positive contact indication


time adjustments
• Access to O.C.R. settings
• Trip/Non Trip option
• One stroke on/off
• Pre Trip alarm function mechanism

• Local/Remote indication • Fast closing mechanism

See page 54 for more information See page 52 for more information

10
Ratings and
Specifications 11-20

• Economical series 12
• Standard series 13-15
• High-fault level series 16
• Switch Disconnector series 17
• Mining series (1100v) 18
• D.C. Application series 19
• TZS-AD Relay and Earth Leakage Block 20

IEC