exida hereby confirms that the software library:

OGP REUSE Solutions for AC 800M HI


used with the ABB AC 800M
High Integrity Controller
The manufacturer
may use the mark:

ABB AS IAEN
Oslo, Norway
Has been assessed per the relevant requirements of:

IEC 61508:2010 Parts 1 – 3


IEC 61511:2003 Chapters 12.4.5 and 12.4.6
and meets requirements providing a level of integrity to:

Systematic Capability: SC 3 (SIL 3 Capable)


Revision 1.0 January 14, 2020
Surveillance Audit Due
February 15, 2023 Safety Function:
The OGP REUSE Solutions for AC 800M HI provides non-SIL,
SIL 2 and SIL 3 compliant application building blocks (Function
Block Types and Control Module Types) intended for Fire & Gas
(F&G), Process Shutdown (PSD) and Emergency Shutdown
(ESD) application building, using the AC 800M HI Controller.
Application Restrictions:
The application building blocks must be properly integrated,
configured and validated in a Safety Application per the
requirements in the Safety Manual.

Place embossed
seal here for
Evaluating Assessor
originals, lining it
up at the bottom

ANSI Accredited Program Certifying Assessor


ISO/IEC 17065
PRODUCT CERTIFICATION BODY
#1004 Page 1 of 2
Certificate / Certificat / Zertifikat /
ABB REUSE 1710051 P0005 C011
Systematic Capability: SC 3 (SIL 3 Capable)
Systematic Capability:
The application building blocks marked SIL 1-2 and SIL 3 has met manufacturer
design process requirements of Safety Integrity Level (SIL) 2 and 3 respectively.
These are intended to achieve sufficient integrity against systematic errors of
design by the manufacturer. A safety application utilizing these application
OGP REUSE Solutions building blocks must not claim a Safety Integrity Level higher than the statement.
for AC 800M HI,
used with the SIL Verification:
ABB AC 800M High
The Safety Integrity Level (SIL) of Safety Functions provided by Safety
Integrity Controller Instrumented Systems (SIS) utilizing application building blocks from OGP
REUSE Solution for AC 800M HI must be verified by an assessment of the safety
application software and by a calculation of PFH / PFDAVG. This assessment must
consider the architecture, proof test interval, proof test effectiveness, any
automatic diagnostics, average repair time and the specific failure rates of all
components included in the SIS. Each part must be checked to assure compliance
with minimum hardware fault tolerance (HFT) requirements.

Library content:
The OGP REUSE Solutions for AC 800M HI consist of the following libraries:
REUSEcommon, REUSEfg, REUSEfgCommonLib, REUSEFuncElmentLib,
REUSEsignallib and REUSEVoteLib.
From REUSE 8.5-0 the following libraries have been added:
REUSEIACLib and REUSEProtetctionLib.
From REUSE 8.6-0 the following library has been added:
REUSEProtectionSignalLib

The following documents are mandatory parts of this certificate:


REUSE REV 8.4-0: ABB 1405-115-C R026 V1 R0 Assessment Report
REUSE Core Libraries Safety Manual Version 8.4-0
REUSE 8.5-0: ABB 1502-024-C R031 V1 R1 Assessment Report
REUSE Core Libraries Safety Manual Version 8.5-0
REUSE 8.5-1: ABB 1601-100-C R035 V1 R0 Assessment Report
REUSE Core Libraries Safety Manual Version 8.5-1
REUSE 8.6-0: ABB 1612-090-C R039 V1 R0 Assessment Report
REUSE Core Libraries Safety Manual Version 8.6-0
REUSE 8.6-1: ABB 1710-051-C R043 V1 R0 Assessment Report
REUSE Core Libraries Safety Manual Version 8.6-1
REUSE 8.7-0: ABB 1710-051-C R047 V1 R0 Assessment Report
REUSE Core Libraries Safety Manual Version 8.7-0

80 N Main St
Sellersville, PA 18960

T-013, V5R1
Page 2 of 2