Proper arc
chutes shall be provided to quench the arc immediately. MCBs shall be provided with magnetic fluid
plunger release for over current and short circuit protection. The overload or short circuit device shall
have a common trip bar in the case of DP and TPN miniature circuit breakers. All the MCBs shall be tested
and certified as per Indian Standards, prior to installation.
5.4 Fuse
Fuses shall be of high rupturing capacity (HRC) fuse links and shall be in accordance with IS : 9224 -1979
and having high rupturing capacity of not less than 35 MVA at 415 V. The back-up fuse rating for each
motor / equipment shall be so chosen that the fuse does not operate on starting of motors / equipment.
HRC fuses shall be of the make as specified in Make of Material. The fuse and SFU make shall be same
make.
5.5 Contactors
The contactors shall meet with the requirements of IS : 13947 and BS : 775.
The contactors shall have minimum making and breaking capacity in accordance with utilization category
AC3 and shall be suitable for minimum Class II intermittent duty.
If the contactor forms part of a distribution board then a separate enclosure is not required, but the
installation of the contactor shall be such that it is not possible to make an accidental contact with live
parts. The coil and contacts shall be easily replaceable without taking out / removal of contactor from the
panel. The contact system shall be suitable for inspection.
5. Accessories
Internal Accessories - The MCCB should have user friendly clip-fit type site fittable.
Internal accessories like shunt / Under voltage / Trip alarm contacts / auxiliary contacts etc.
shall be provided wherever required.
Internal accessories should have double insulation & No side bias.
External Accessories –
ROM – All MCCBs should be fitted with the Extended type Rotary Operating Mechanism
(ROM).
The ROM should be suitable for direct mounting on MCCB or Panel door.
The ROM should be with door interlock (with defeat feature) & padlock facility.
Terminal Shrouding – The MCCB Terminations/ Spreader links should be shrouded & touch
proof.
6. Other Features
The MCCB should be suitable for contact inspection.
The MCCB shall be suitable for both Cu and Al termination.
The MCCB shall have spreader links and phase barriers as standard feature.
5.6 Voltmeter
Voltmeter shall comply with BS : 90. The dial of the meter shall be square in shape of 96 x 96 mm. or 144
x 144 mm. size. The voltmeter shall be moving iron type, flush pattern, with dust and moisture proof
enclosure.
The voltmeter selector switch shall be arranged to provide line to line voltage reading and line neutral
voltage.
5.7 Ammeter
Ammeter shall comply with BS : 89. The dial of the ammeter shall be square in 96 x 96 mm. or 144 x 144
mm. size. The ammeter shall be moving iron type, flush pattern with dust and moisture proof enclosure.
The range of the ammeter shall be in accordance 1 to 1.5 times the feeder full load current. Separate
current transformer shall be provided for all ammeters.
Prior to fabrication of the Panels the supplier / contractor shall submit for consultant’s approval the shop
/ vendor drawing consisting of G.A. drawing, sectional elevation, single line diagram, bill of material etc.
and design calculations indicating type, size, short circuiting rating of all the electrical components used,
bus bar size, internal wiring size, Panels dimension, colour, mounting details etc.. The contractor shall
submit manufacturer’s catalogues of the electrical components installed in the Panels .
7.0 Inspection
At all reasonable times during production and prior to transport of the Panels to site, the supplier /
contractor shall arrange and provide all the facilities at their plant for inspection.
8.0 Test Certificates
Testing of Panels shall be carried out at factory and at site as specified in Indian standards in the presence
of consultant. The test results shall be recorded on a prescribed form. The test certificate for the test
carried out at factory and at site shall be submitted in duplicate to the consultant for approval.
Item No.2
Supply, Installation, testing and commissioning of Lighting/ Power Receptacles / Air conditioner power distribution
panels(MCBDCs), flush mounting, double door type dust and vermin proof, powder coated enclosure and provided
with four pole MCB as in comer in dust tight, powder coated enclosure and provided with four pole MCB as a
feeders. The panels shall be provided with the R,Y,B indicating lamps on the front door and shall be with complete
wiring and all materials as per drawings, specifications and directions of Engineer - In - Charge. 18 Ways SPN ( Total
12 Nos 1 pahse O/G circuit ), Incomer 63 A Four pole MCB- 10 kA. Out going circuits : 18 Nos 6/10/20 Amp SP
MCBs 10 kA.
Item No. 3
Providing and erecting XLPE(IS:7098)(II)-88 ISI marked Armoured cable multi staranded Copper conductor for 1.1
KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road crossing or floor of
following size of cables.A) 4 core 2.5 sq.mm 2XWY FOR HPSV Fitting figher fighter parking
4 core x 4 sq.mm 2XWY for Out door street light.
Item No.4
Supply and Installation of Approved make Four Pole LT Heavy Duty Switch Disconnector Fuse Unit Cubical type
for panel mounting complete with operating mechanism suitable to operate on 415V A.C. With HRC fuses of
suitable load confirming to IS. 13947 (Part I & III). of following capacities with weather proof, dust & vermin
proof, wall / pole mounted front operated Outdoor type box having IP-64 protection made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary
supporting angles, flats including cutting, bending, drilling, welding, riveting with internal partitions & cable alley
as per requirements & instruction of engineer-in-charge with erection . This switch shall be installed at power
supply connection from power supply authority if required and insist by power supply authority.
Item No.5
Providing and erecting XLPE(IS:7098)(II)-88 ISI marked Armoured cable multi staranded Aluminium conductor
for 1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road crossing or floor of
following size of cables.A) 3.5 core 120 Sq.mm (70 sq.mm 1/2 core A2XFY main incomer from DGVCL meter to LT
panel.
Item No.6
6a
Providing & laying of 50 MM Nominal OD Doubled Walled Corrugated Pipes (DWC) of polyethylene
(conforming to IS 14930 - II) with necessary connecting accessories like coupler, Tee, L - Bow, etc. of same
material at required depth (90 cms) including excavation for laying of cable below ground/ road surface for
enclosing cable and back filling the same to make ground as per original & as per instruction of Engineer
Incharge - for Streelight Cable of 1 x 4 core x 16 Sq. MM and Service cable of 1 x 4 core x 16 Sq. MM - Make
: Dura guard/ Carlon/ Emtell / telerex
6b
Providing & laying of 120 MM Nominal OD Doubled Walled Corrugated Pipes (DWC) of polyethylene
(conforming to IS 14930 - II) with necessary connecting accessories like coupler, Tee, L - Bow, etc. of same
material at required depth (90 cms) including excavation for laying of cable below ground/ road surface for
enclosing cable and back filling the same to make ground as per original & as per instruction of Engineer
Incharge - for Streelight Cable of 1 x 4 core x 16 Sq. MM and Service cable of 1 x 4 core x 16 Sq. MM - Make
: Dura guard/ Carlon/ Emtell / telerex
6c
Supplying following size of Light duty “A” Class G.I . Pipe & erecting as directed by Engineer-in-charge. (a)
50 mm dia. For outdoor fittings installation
Item No.7 and 8
The cable end termination is carried out by the contractor as per the schedule B.
Item No.9
Lighting Luminaries.
Item No. 10 to 16
Lighting System
(Internal Wiring)
1. Scope
This section covers, definition of point wiring, system of wiring and supply, installation, connection,
testing and commissioning of point wiring for light points, ceiling fan points, exhaust fan points,
convenience socket outlet points, power socket outlet points, bell outlet points etc. including fixing of
light fixtures, ceiling fan, exhaust fan, wall fan, bell etc. Concealed wiring shall be carried out in this
tender.
2. Standards
The following standards and rules shall be applicable :
IS : 732 Code of practice for electrical wiring installation (System voltage not exceeding
650 V)
IS : 1646 Code of practice for fire safety of buildings (General) Electrical installation.