SCHEDULE OF LOADS

AMPERES CIRCUIT BREAKER


CKT NO. DESCRIPTION QTY VA VOLTS CONDUCTOR SIZE CONDUIT SIZE
ABC AB BC CA AT KAIC POLE
C1 40 HP FIRE PUMP 1 41382 230 104 150 5 3 3 - 50mm THHN (P)+ 1 -14mm2 THHN (G)
2
25mm Ø IMC
C2 5 HP FIRE JOCKEY PUMP 1 6049 230 15.2 50 5 3 3 - 8.0mm2 THHN (P)+ 1 - 5.5mm2 THHN (G) 15mm Ø IMC
TOTAL 47431 119.2
COMPUTATION :
MAIN FEEDER
IT= ((119.2) + (104 x 0.25))(0.8DF) USE : 225 AT, 3P, 10 KAIC, 60 HZ, BOLT ON TYPE
IT = 116.16 Amperes SERVICE WIRES: 3 - 60mm2 THHN(P) + 1 - 14mm2 THHN(G) IN 32mmØ CONDUIT RSC

EE SCHEDULE OF LOADS
00 00 SCALE: NTS

TAP TO EXISTING
POWER SUPPLY

150 AT, 3P 50 AT, 3P


NEMA 1 NEMA 1

40 HP 5 HP FIRE
250 AT, 3P FIRE PUMP JOCKEY PUMP
NEMA 3R

GROUND ROD GROUND ROD

GROUND ROD EE SINGLE LINE DIAGRAM


00 00 SCALE: NTS