Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
HANDBOOK
P&ID Guidelines
Version: 01
Date: 2017.11.28
0.1 2 (62)
Document Description:
P&ID Guidelines
CONTENT
1 Sound Engineering Practice (SEP) ....................................................................................................5
1.1 SEP for Varivent, Ecovent, Butterfly and Control Valves from GEA .........................................5
1.2 SEP for Overflow (Type Q) Valves from GEA...........................................................................6
1.3 SEP for Vacuum Relief (Type V) Valves from GEA ..................................................................7
1.4 SEP for Safety Relief (Type 488 and 483 Stericom) Valves from GEA....................................8
1.5 SEP for Centrifugal Pumps (Type TP) from GEA .....................................................................9
1.6 SEP for Piping Systems from GEA .........................................................................................10
2 Selection of Appropriate Pump Types .............................................................................................12
2.1 Overview of Pump Types, and Reference Material ................................................................12
2.2 Centrifugal Type – Where to Use it .........................................................................................14
2.3 Self-Priming Centrifugal Type – Where to Use it ....................................................................15
2.4 All centrifugal pumps from GEA Hilge.....................................................................................16
2.5 Rotary Lobe Positive Displacement Type – Where to Use it ..................................................17
2.6 Peristaltic Type – Where to Use it ...........................................................................................18
2.7 Piston Type – Where to Use it ................................................................................................19
2.8 Screw Type – Where to Use it ................................................................................................20
2.9 Twin screw Type – Where to Use it ........................................................................................21
2.10 Diaphragm Metering Type – Where to Use it .........................................................................22
2.11 Mechanical Seals ....................................................................................................................23
2.12 Design Rules for Pumps and Fail-Safe Features ...................................................................24
2.12.1 Flow ...........................................................................................................................24
2.12.2 No Flow ......................................................................................................................24
2.12.3 Reverse Flow .............................................................................................................24
2.12.4 High Pressure ............................................................................................................25
2.12.5 Low Pressure .............................................................................................................25
3 Selection of Appropriate Valve Types ..............................................................................................26
3.1 Introduction of Hygienic Design Criteria for Valves ................................................................26
3.2 Overview of Valve Configurations ...........................................................................................30
3.2.1 Overview of Valve Housing Configurations ...............................................................31
3.3 VARIVENT® Valve Selection Scheme ...................................................................................33
3.3.1 Single Seat Shut-Off Valves: Flow Stoppage ............................................................34
3.3.2 Single Seat Shuttle Valves: Changing Flow Direction ...............................................35
3.3.3 Double Seat Shut-Off Valves: Hygienic Mix-Proof Separation of Media ...................36
3.3.4 When Product Recovery (“Pigging”) is Required.......................................................47
3.4 Modulating Control Valves ......................................................................................................48
3.5 Overflow Valves ......................................................................................................................50
3.6 Safety Relief Valve ..................................................................................................................51
3.7 Vacuum Valve .........................................................................................................................52
3.8 Sampling Valves .....................................................................................................................53
3.8.1 Varivent Sample Valve Type I ...................................................................................53
3.8.2 Varivent Sample Valve Type TSVN/U .......................................................................53
3.9 Butterfly Valves .......................................................................................................................54
3.10 Mixproof butterfly valves (Type 988): ......................................................................................55
3.11 Aseptomag Valves ..................................................................................................................56
Revision: Page:
0.1 3 (62)
Document Description:
P&ID Guidelines
0.1 4 (62)
Document Description:
P&ID Guidelines
DOCUMENT HISTORY
Date Revision Change Author
2017.11.22 0.0 Update Corporate Design document Santiago
Villafñe
2017.11.28 0.1 Review and eliminate references (if proceed), Santiago
update pictures, Villafañe
Revision: Page:
0.1 5 (62)
Document Description:
P&ID Guidelines
In the following sections, the recommended good practices for engineering are described. They are related to the
different equipment used for design installation (type of valves, centrifugal pumps and piping systems from GEA).
All equipment related to a project will be listed in a PID and/or in a equipment list.
1.1 SEP for Varivent, Ecovent, Butterfly and Control Valves from GEA
SEP 1 - function Classify all these types of valves in the project (from P&IDs or equipment list) into these types:
close-off flow (type –A, -B, -C, -L, any butterfly or shuttle valve W, X, Y) or mix (type –E), or
control flow.
SEP1.1 - close-off These valves are to close against flow (minimizes water hammer) (exception: valves on tank
emptying.
If liquid will be trapped between two close-off valves, check for risk of thermal expansion /
hydraulic lock and ensure one valve can relieve (expansion pressure can lift seat) or else add a
relieving valve (type Q or safety valve if required).
SEP1.2 - mixing Minimize dead-legs by placing stop valves close to the mixing valve (at downstream, dead-leg
side).
SEP1.3 - control Control valves do not provide full shut-off. If this is necessary, add an automatic close-off valve.
Use proper manual valves to size Kv value.
SEP 2 - mix- As a minimum, CIP and product operations must be separated by mix-proof or block and bleed
proofing valves.
SEP2.1 - K or D Select K type when separating CIP detergents or CIP water, otherwise use D type.
SEP2.2 - other mix- Type C has a double seal (a pressure spike could cause mixing of incompatible stream) but it is
proof types an economical alternative, e.g. on suction side of CIP stations). Type B, with balancer, protects
against pressure spikes. Type R has radial sealing to minimize losses in valve activation. Type
T is a tank bottom valve to minimize dead legs on tanks.
SEP2.3 - VSC Connect VSC to mix-proof valves (except type K). Allow one VSC per product line, maximum
15 valves per 1” VSC on a 1” line. (NOTE in process description: VSC not allowed activate if any
of connected valves activated).
Locate VSC upstream of CIP supply valve or downstream of CIP return valve, so that dead leg
to VSC is not exposed to product or process water.
SEP2.4 - Seat lift Use seat lift if the product is sticky such as sugar or yeast, and would adhere to the seal unless
it was cleaned.
SEP 3 - line size Size the valves to the local flow to check allowable product velocities and effect on pump duty.
SEP 4 - pressure Size the actuator to keep valve close against a pressure difference.
SEP 4 - hygiene All product valves must be on a CIP route. If there is no flow through the valve on CIP, put a
note on the P&ID “minimize dead-leg”.
Tank emptying valves should be top to bottom flow, for complete draining – this is allowed to
contravene SEP1.1 since pressures are normally < 0 barg.
SEP 5 - materials Select seals according to fluid. If client requires material certificates, note requirements on valve
list sheet in equipment list and in valve order.
Revision: Page:
0.1 6 (62)
Document Description:
P&ID Guidelines
SEP 6 - electrical Configure control cap as double feed-back, AS-I connection, solenoid in valve cabinet, 24V dc,
unless client / site requirements are different. ATEX zoning affects the selection of feedback
switches and solenoids.
SEP 7 - access Valves must be located where they can be maintained, either at ground level or on a tank or
platform.
SEP 8 - noise Calculate Kv for control valves at normal flow duties. If the valve would operate < 20% of
selected Kv for the lowest normal flow, these is a danger of excessive noise.
SEP 1 - function Classify all these (Q) valves in the project (from P&IDs or equipment list) into these types: relieve
flow (type –B, -L) or bypass type (type –E), or control flow (-B).
SEP1.1 - relief For safety of personnel, (i.e. where liquid/gas is hazardous) or for cases where pressure relief
value is critical, use safety relief valve type 488 or equivalent instead; otherwise, Q type is
acceptable. Pipe relief line to ground or drain.
SEP1.2 - bypass Use at each positive pump (includes homogenizers) in process lines.
SEP1.3 - control Select a back-pressure to apply to product and note effect on pump. Note, it prevents back-flow,
and therefore acts as a non-return valve. Therefore also check for trapped liquid as per 1.1 of
Varivent valves.
SEP 3 - line size As for Varivent valves. For relief valves, the relief line and valve housing may be sized according
to the flow required to reduce the pressure in the system to safe levels.
SEP 4 - pressure Size the spring range according to the proper pressure.
SEP 4 - hygiene If it’s located on a product line, the valve must activate in CIP to clean the seats. For a relief line
allow for loss of CIP during pulsing operation.
SEP 8 - noise Select spring range so that the normal duty is mid-range on spring. If the valve would operate at
lowest spring tension, there is a danger of excessive noise.
Revision: Page:
0.1 7 (62)
Document Description:
P&ID Guidelines
SEP 1 - function Exclusively for vacuum protection of enclosed tanks. Must be protected against freezing, and
restrictions to air inflow.
SEP1.1 - relief Activates at minimum vacuum of 25mm water gauge of -2.5mbar. Normally not suitable on its
own for protection against collapse of hot CIP vapour.
SEP 3 - line size Size according to air inflow required against vacuum rating allowed for tank.
SEP 4 - hygiene If it’s located on a product tank, the valve must activate in CIP to clean the seat. Specify the
pneumatic lifting actuator (needs 5 bar air to open against maximum 3b in tank).
CIP fluid is collected in an integral drip pan. Size depends on size of valve to be collected in
funnel and drain pipe.
Allow for loss of CIP during pulsing operation.
0.1 8 (62)
Document Description:
P&ID Guidelines
1.4 SEP for Safety Relief (Type 488 and 483 Varivent ®) Valves from GEA
SEP 1 - function Protection of personnel from rupture of pipes or vessels containing hazardous fluids or gases,
or protection of equipment when pressure setting is critical.
Stericom types contain bellows-type seal, suitable for pharmaceutical application. Type 483 is
for tanks or valves. Type 484 is for dead-space free tank connection only.
Varivent type 488 is for dairy, food, beverage and brewing applications.
SEP1.1 - relief Run vent pipe to external or safe area (not linked to other vents). Observe installation guidelines
in manual to avoid a pipe layout that would allow liquid to accumulate over the lifting disk.
SEP 3 - line size Stericom Type 483 sized according to table in Components catalogue 3.2/4 (57); Stericom type
484 sized to 3.2/7 (57); Varivent type 488 sized to 3.2/11 (57).
SEP 4 - pressure Specify the pressure at which the valve must lift. This cannot be varied on site.
SEP 4 - hygiene If it’s located on a product line, the valve must activate in CIP to clean the seats. Specify the
pneumatic lifting device H8.
Allow for loss of CIP during pulsing operation.
0.1 9 (62)
Document Description:
P&ID Guidelines
SEP 1 - function These pumps add a differential pressure to liquids in a flow range 1 to 200m3/h, maximum 90m
flow head. It is for sanitary applications where the liquid is less than 500cP. The pump will operate
at a point determined by the system back pressure and the “pump curve” for the selected impeller
/ model. See SEP 2 below.
SEP1.1 - direction These pumps do not block liquid flow in either direction.
If reverse flow is a possibility, and it is fitted with a speed drive, a specific set-up configuration is
required to avoid errors in speed drive.
SEP1.2 - starting Rated for up to 15 starts per hour. It is not suitable for pulse operation.
SEP1.3 - control Pump operating flow can be controlled by speed drive or by control valve on discharge.
SEP 2 - sizing Use a pressure drop calculation tool to calculate the duty of the pump. Warning levels should be
taken in consideration where NPSH is low (redesign system / select special pump) or liquid
velocity is high (check client requirements).
Specify the duty to the pump supplier / manufacturer, who is given the responsibility to select the
correct model / impeller / motor based on this data. Check the pump type proposed by the
manufacturer – it is to be mid-range on curve and ideally be one impeller size below maximum
allowed in housing.
SEP2.1 - routes If the flow can increase due to changes in routing or operating requirements (CIP, or options),
make a separate calculation for this duty and provide all relevant information to the supplier.
SEP2.2 - motor Consider the requirements for over-sizing the motor if operating conditions allowed for “run-out”,
i.e. the pump operating at the end of the pump curve due to absence of system back-pressure.
Consider the number of starts per hour, especially for CIP supply pumps and pumps operating
to maintain a level or pressure.
SEP2.3 - sealing The seal protects the motor from the liquid in the housing; it allows part of the fluid to lubricate
the seal surface. NEVER run the pump without liquid in the line – the seal will overheat and
break.
Consider the posibility of flushed seals for CIP supply pumps and pumps where product is at
temperature >60°C, or is likely to crystallize or harden when the pump is inactive. Double or
balanced seal sets are used to prevent leakage of the fluid to the atmosphere, or for high suction
pressure.
SEP 3 - pressure Find the maximum dead-head pressure that the selected pump can generate, and check the
pressure rating of the connected piping system.
SEP 4 - hygiene Pump must be on a CIP route. Check if pump needs to operate in CIP, if not, put a note on the
process description / activation table to “jog” pump a limited number of times in CIP. If pump
housing needs to be drained (usual in pharmaceutical applications) then specify VTP drain valve)
SEP 5 - materials Select seals according to fluid media. If client requires material certificates, note requirements
on pump sheet in equipment list and in pump order.
SEP 6 - electrical Configure pump as the available Hz and voltage. Please, always verify hertz and voltage.
Standard IEC motor, with thermistors if necessary, unless client / site requirements are different.
Select stainless steel shroud. ATEX zoning affects the selection of motors, thermistors, cable
and glands.
SEP 7 - access Pump must be located where it can be maintained. There is approx. 80mm clearance under the
motor. If more is required, fit the pump to a box section frame.
0.1 10 (62)
Document Description:
P&ID Guidelines
SEP 1 - function Classify all these systems (from P&IDs) into these types: hygienic, hazardous fluids, utilities.
Note that “tubing” is the correct description for the typical stainless steel “pipe” we use in our
installations, and that “pipes” are defined by reference to schedules of pipe thicknesses.
SEP1.1 - hygienic Consider CIP as the prime requirement. CIP flow to be a minimum of 1.5m/s in any part of
hygienic pipe system.
Avoid or minimize dead-legs (Length / Diameter <= 0.5).
SEP1.2 - hazard Specify earthing at each pipe connection to dissipate static charge for hazardous fluids or
powders with risk of explosion or fire.
Concentrated detergents are hazards and must be carried in Sch. 5 pipe or double pipe, to
minimize dangers of leaks.
SEP1.3 - utilities Service pressure is outside our control; consider the available pressure and specify pressure
reducing sets, if required.
SEP 2 - line size Size the pipes to the local flow to check allowable product velocities and effect on pump duty.
SEP 3 - pressure Generally adopt 5b as the design pressure. This corresponds with the “standard” actuator
selection for GEA Flow Components valves with compressed air pressure of 6b.
Check the multiple of pipe diameter by design pressure (<5000 generally, or <2000 for
hazardous fluids).
SEP3.1 - hammer Consider any shut-off valve or positive displacement pump where liquid can suddenly stop due
to normal or fail operation of valve or pump.
Ensure valves close against flow. If no fail-safe relief is possible (given the valves as required
or used in the process), specify a Q-type valve discharging safely to drain. Specify Q-type
valves at positive displacement pumps so that discharge-line pressure can lift seat to relieve
to upstream side.
Note in process description / activation matrix – on-delay of pumps, off-delay of valves.
SEP3.2 - vacuum If due to siphoning, or collapse of vapor after CIP, or water hammer, vacuum can be created
in the system, provide vacuum break valves so as to allow the pipes to drain out.
SEP3.3 - expansion Stainless tube will expand approximately 1.7mm per meter when heated from 0°C to 100°C.
In lengths < 5m where elbows are free to move, compensation for this expansion is usually not
necessary.
The mechanical installation specification makes it the contractor’s responsibility to cater for
expansion by sliding supports, pipe loops, or compensators. It must be noted, on layout or
otherwise, the fixed points in each pipe >5m straight length (usually at equipment, or where
passing through a wall, or as designated).
SEP3.4 - safety (Pressure) Consider if the pressure can exceed the design pressure and find the weakest
equipment or tubing in the system. If this equipment or tubing is of a lower rating that the
possible maximum pressure in a system, protect the equipment with a rated safety valve.
(Temperature) If the pipe surface temperature is generally at a temperature of >60°C and is
within normal reach of operators, check the possibility of insulate the pipe, it must be marked
on the P&ID as requiring insulation.
0.1 11 (62)
Document Description:
P&ID Guidelines
SEP 4 - hygiene Line must be on a CIP route. If there is no flow through the line on CIP, put a note on the P&ID
“minimize dead-leg”.
Line must be free-draining to atmosphere. If a non-draining section (U-section) in the pipe
layout is unavoidable, add an automatic drain valve for use in CIP (and add a note to the
process description).
Specify line filters (M&S angular type), mesh 1.5mm, on delivery side of CIP pumps to trap
residual dirt or particles.
Product filters may be specified by client. Check the pressure drop, and if a proprietary filter is
specified (e.g. bag-type) note that many are not CIP cleanable and may have dead-legs. Advise
client of any breaches in hygiene or CIP due to the client specification. The responsibility for
manual cleaning will be with the client.
SEP 5 - materials Select seals according to fluid media. If client requires material certificates, note requirements
on mechanical installation specification and in contract / order.
Tubing to be AISI 316L or 304 to a defined standard (DIN 11850, or ASTM A270R.) for
pharmaceutical or high quality hygienic systems.
SEP 6 - insulation For thermal efficiency, steam, condensate, chilled water and hot water pipes must be insulated
– refer to mechanical installation specification.
SEP 7 - access Equipment must be located where it can be maintained, either at ground level or on a tank or
platform. Pipes can be carried in overhead racks.
Revision: Page:
0.1 12 (62)
Document Description:
P&ID Guidelines
Pumps are commonly grouped into 2 classes; those which produce pressure by accelerating the liquid (roto-
dynamic or centrifugal type), and those which move volume (positive displacement type).
0.1 13 (62)
Document Description:
P&ID Guidelines
The operating characteristics of each type of pump is illustrated below. A centrifugal pump has a characteristic
flat curve with the pressure (representing pressure added by the pump) decreasing with flow, whereas a positive
displacement pump typically moves the same volume flow regardless of pressure.
The “dead head” represents the pressure added by a centrifugal pump when the outlet is closed.
The “System” represents the pressure drop in the piping and equipment downstream of the pump. As flow and
velocity increase, the system pressure increases. The pressure drop at zero flow represents the static head, or
the pressure required to lift the liquid to the discharge point.
Revision: Page:
0.1 14 (62)
Document Description:
P&ID Guidelines
A centrifugal pump takes a liquid in at the center of a rotating impeller and accelerates it by moving it along the
vanes to the discharge neck at the top right of the impeller housing. The fast moving liquid is suddenly slowed
down to pass through the outlet. This is what generates the pressure at the discharge point. Looking from the
motor side, the motor and the impeller move in a clockwise direction.
Key features:
Centrifugal pumps have very wide applications in our business. They are cheaper than similarly sized positive
displacement pumps, are easy to clean, and many types have EHEDG certification.
They are not good for cases where the suction pipe is not flooded (CIP return from a tank), or for low flow-rates
(under 5m3/h requires a careful selection) or media which is sensitive to shear (because of the acceleration caused
by the impeller) or media which have a viscosity greater than 300cP (note some manufacturers will supply
centrifugal pumps for higher viscosities).
Revision: Page:
0.1 15 (62)
Document Description:
P&ID Guidelines
A self-priming centrifugal pump is a mechanical modification of the impeller housing so as to tackle one
fundamental weakness of centrifugal pumps – the requirement for flooded suction. Each manufacturer has a
different approach.
Alfa Laval developed a cartwheel type impeller to create a wide liquid ring. APV (Ws+) use an inducer (a “pre-
impeller”) to create a liquid ring, plus a small pilot pipe refilling the suction from the discharge to create a very
effective and efficient self-priming pump.
Some manufacturers put a reservoir on the outlet (to maintain prime). Fristam and Hilge have liquid ring pumps
which depend on a gradually deepening channel behind the impeller to create an enhanced suction.
Appart of Hilge, GEA have released a self-priming centrifugal based on the TP pump which has a good chance
of being the first EHEDG certified self-priming pump. It is efficient (40% compared to a typical 25% for a
conventional liquid ring pump), it uses an inducer which is eccentrically mounted to maintain a liquid “well” while
it creates a liquid ring, and does not need a pipe connection from the discharge to the suction. It does need to be
piped to be at a low point.
TPS Self-priming centrifugal pumps are almost always used ONLY for CIP return from tanks. Most types are not
designed in a hygienic way and would therefore be unsuitable for product.
Even other pumps manufacturers and the more recent GEA models (TPS and Hilge) are less efficient than
standard centrifugal motors and therefore have a high power requirement. They are not suitable for generating
high pressure – the usual limit is 4bar for “conventional”.
Revision: Page:
0.1 16 (62)
Document Description:
P&ID Guidelines
0.1 17 (62)
Document Description:
P&ID Guidelines
A rotary lobe pump draws liquid into a central inlet between two counter rotating lobes, and, as the lobes rotate,
each carries a fixed pocket of liquid around until they meet on the opposite side, where they are squeezed together
and “escape” through the centrally mounted outlet.
Note that the pump creates enough suction to prime itself, and that the flow is necessarily “pulsed” because of
the time interval between suction and delivery. Increasing the number of lobes reduces the effect of pulsation. (A
bi-lobe or scimitar type is worst for pulsation but can be selected for the most shear-sensitive products.
Conventionally we use a tri-lobe. There are 4-lobes available also, which is best at reducing pulsation).
In a lobe pump there is clearance between the lobes and the impeller casing which allows a certain amount of the
liquid to be carried back to the suction. This is called slippage and it is a consequence of having a clearance for
the lobes. Slippage decreases as viscosity increases. Pumps which are designed for viscous materials are very
poor at pumping water or CIP.
Rotary lobe pumps are used for liquids with a viscosity higher than 300cP, or for shear-sensitive liquids. They are
typically used for cold cream, flavors, colors, food oils and yeast. The Alfa Laval SRU, and the Waukesha
Universal II series are among several rotary lobe pumps with EHEDG certification.
Revision: Page:
0.1 18 (62)
Document Description:
P&ID Guidelines
A peristaltic pump is the simplest type of pump as it does not have any valve, ring or anything susceptible to
obstruction or corrosion. The fluid is just in contact with the internal wall of the hose, eliminating the risk of
contamination of the fluid from the pump or vice versa. This type of pump can run dry without any problem.
The hose is compressed by a roller against a semi-circular track. As the roller move along the track, the fluid
keeps moving until the track finishes. New fluid enters the hose and the same operation is repeated.
The material hose has to be selected according to the fluid media to be pumped.
Clean the hose may be difficult in some cases. The hose may be smaller or the pressure in the hose for cip may
be higher than the pressure design hose.
Check always the hose material and the cleanability possibilities.
Peristaltic pumps are ideals for most types of fluids, even the ones with a high viscosity, the shear-sentives, the
corrosive and the abrasive ones, or those which have suspended solids.
They are especially useful in pumping applications where hygiene is very important. These pumps are
recommended for different applications: measuring, dosing and dispensing. They are easy to install, easy to
operate and cheap to maintain.
Revision: Page:
0.1 19 (62)
Document Description:
P&ID Guidelines
The piston (D) has two rings (F) y (H), and the space created between them is called hydraulic barrier (G). This
allows the cleaning of the ring (F), which is in contact with the fluid and needs to be cleaned. During the production
phase, this ring forms a barrier between the product and the air external to the dispenser, which is contaminated,
by circulating good quality water with no pressure.
This pump is used in order to achieve a high precision injecting the fluid, for example, while packaging yogurt or
other viscous products, and it also allows to inject products with solids, like yogurt with pieces of fruit.
Revision: Page:
0.1 20 (62)
Document Description:
P&ID Guidelines
This pump is used for viscous fluids (like butter, cream, pulp fruitR) and high pressures.
Revision: Page:
0.1 21 (62)
Document Description:
P&ID Guidelines
This type consists of two screws which form chambers. These chambers are filled with the pumped fluid and, as
the pump rotate, the fluid is moved from the suction side of the pump to the higher pressure discharge side of the
pump.
While pumping there is no metal-to-metal contact within the pump housing. This allows good pumping
performance even with non-lubricating and corrosive and contaminating fluids.
Reverse flow is allowed by changing the shaft direction, so the suction becomes from discharge and vice versa.
This pump is also used for viscous fluids and high pressures, but it is more compact than the single screw type
and its pieces have a lower wear.
Revision: Page:
0.1 22 (62)
Document Description:
P&ID Guidelines
The diaphragm is actioned using compressed air, so the valves are operated by positive and negative pressure.
The fluid is sucked from the suction line into the process chamber. During the discharge, the suction valve is
closed and the discharge valve will open. The fluid is discharged from the process chamber into the discharge
line.
The diaphragm can be also actioned mechanically. In this case, they are used as dispensing pumps.
These pumps are mainly used for the transport of products, but not during processing. They are used for pumping
hot caustic and acid, and other products like fruit juices concentrates, jam, olives, honeyR
Revision: Page:
0.1 23 (62)
Document Description:
P&ID Guidelines
A mechanical seal is a device used to contain fluid within the pump, where a rotating shaft passes through its
stationary housing. The key is to allow the rotating shaft to enter the wet area of the pump without allowing the
pressurized fluid to escape. This is the reason why a mechanical seal is needed.
0.1 24 (62)
Document Description:
P&ID Guidelines
2.12.1 Flow
Ensure there is a supply of liquid to pumps before they start. Place them where there is a flow by gravity into the
suction of the pump, ensure by calculation that there will be adequate suction pressure, and control the operation
of the route so that the valves open (to allow liquid to flow) before the pump starts. Note even P.D. type pumps,
which can prime themselves, should still be governed by this rule.
2.12.2 No Flow
There are two cases; no flow due to blockage of the outlet line, and no flow because there is no liquid getting into
the pump. The control system needs to be designed to protect against these cases by generating a no flow error,
and in particular, by turning off pumps if there is a low level in the supply tank.
In the first case, there is no immediate danger for centrifugal pumps. The fluid will be heated by the pump and will
expand, and the motor will heat-up. The motor will normally NOT have a thermistor and can be damaged (usually
after more than 10 minutes) to the point of needing to be sent for rewinding.
The product, if the supply side route is open, generally will not cause damage due to expansion, but this needs to
be considered. However, there is a danger for positive displacement pumps, because the volume of liquid
displaced by the pump must go somewhere and it will rupture pipes or connections or equipment. Therefore we
must design a fail-safe protection for positive displacement pumps in the form of a pressure relief or overflow
valve.
In the second case, the pump will run dry which will cause the seal to heat up extremely quickly (a matter of
seconds). The pump must be protected by the control system!
For centrifugal pumps, even incorrect wiring (running backwards) does not cause reverse flow, just much lower
pressure. However, as the impeller housing has an open flow path, liquid can flow backwards through a centrifugal
pump if it is off. This can be a desired result (e.g. if you are washing two lines together, one in reverse flow) but if
it is not required, the best protection against it is a non-return valve.
For lobe type positive displacement pumps, incorrect wiring can cause reverse flow driven by the pump. If there
is liquid available (hence, per rule 1, always have the route open before starting the pump). However when the
pump is off, it is a blockage to flow (except for a small amount of slip). Therefore do NOT put a non-return valve
on the outlet of a P.D. pump.
Revision: Page:
0.1 25 (62)
Document Description:
P&ID Guidelines
If high pressure can be generated outside the pump in question (for example by pumps in series), then pressure
on the suction side of (typically) 3 bar or greater can force open a mechanical seal, and cause excessive leakage.
Therefore, if putting pumps in series ensure that the second pump has a balanced (double) mechanical seal. The
control of such pumps must allow for a phasing in and out to avoid sudden pressure peaks or water hammer.
A pump generates a pressure wave when it starts, which can be higher than the dead head pressure; therefore
check the actuator sizing on valves that are close to the pump delivery and ensure there is a margin of safety on
the lifting pressure (2 bar suggested). Valves further away will not see the same level of pressure due to pressure
drops in the system.
Water hammer is a well-known phenomenon caused by the sudden closing of a valve in a flowing stream of liquid.
As a rule of thumb, sudden closures can cause a pressure spike of twice the operating pressure (if lines are more
that 100m long, this effect is exacerbated). The pressure spike may need to be calculated
The control system must protect against this by turning off pumps while the route valves are still open. This is a
phased shut-down. The designer must put in additional safety for positive displacement pumps.
For centrifugal pumps, the designer must consider where extra pressure would relieve to – for example in a normal
transfer line, the weak point may be the push-out to drain valve (typically a UA type) which will open to relieve
excess pressure. Furthermore, the control system should be designed to minimize pump re-starts (pulse/pausing
of pumps is not recommended!).
It is very important to assure that there are no parts in the installation with a very low pressure because if the
pressure at any point of the circuit is lower than the vapour pressure of the liquid, cavitation will appear. This effect
will damage the pump and prevent it from priming.
In order to see if the installation is close to the effect of cavitation, the Net Positive Suction Head (NPSH) is used.
There are two types of NPSH:
- NPSHa (available): it measures how close the fluid is to cavitation
- NPSHr (required): limit value required at a specific point of the installation to avoid the cavitation of the
fluid.
The NPSHr has to be lower than the NPSHa of the centrifugal pump so that the cavitation effect does not exist
and the pump functions effectively.
There are rules of thumb regarding suction pipes sizes, for example the suction should be one size larger than
the delivery side – this may compromise the CIP velocity in each, so it is not always appropriate.
One very useful rule is to have as long as possible a straight suction pipe into the pump. This is especially relevant
for positive displacement pumps, because the pulsing flow creates an additional acceleration head (difficult to
calculate), that can affect cavitation.
Vacuum can also occur in piping if there is an intermediate high point between the pump and the outlet. This is a
risk associated with the pipe layout. If the pump stops, the liquid in the high point will drain both ways downwards,
and if BOTH sides are unable to drain out fully (thereby letting air into the line), then a vacuum break occurs. This
causes a problem on restart of water hammer and possibly even an overload on the pump (due to high initial
flow). In the piping design, select and specify routes that avoid intermediate rises with liquid trapped on both sides
– a continuous downward path on both sides is ideal.
Revision: Page:
0.1 26 (62)
Document Description:
P&ID Guidelines
The VARIVENT® Valve System is designed for process plants in which production quality, hygiene and
operational safety is a first priority. They are a classic example of “hygienic engineering” in which the principles of
“cleanability” and “drainability” are incorporated into the mechanical design.
There are certain features of the design of the VARIVENT® valves that differentiate them from other piston-type
valves, including:
- Leakage detection at the open valve lantern, which provides a hygienic design solution
- Geometry of the valve housings (no pockets, drainability, curved surfaces), which provides a hygienic
design solution.
- The seal / gasket design is such that no crevices exist where soil residues may be trapped and bacteria
can accumulate and multiply.
- The valve can be “cleaned in place“.
- Modularity / interchangeability of parts
- Standard “product contact” surface finishes of Ra </= 0.8µm, which provides better cleanability.
- The valves are EHEDG approved.
According to the EHEDG Requirement for “Leak detection”, the valve design must provide for rapid external
detection of leakage of seals between the product side and the atmosphere. In addition, it must not be possible
for fluid to transfer from actuators into product areas, and vice versa. VARIVENT® valves achieve this requirement
as follows:
- The lantern is opened, allowing the valve stem to be visible and providing immediate leak detection from
the outside.
- The opened lantern provides a break between the actuator and the valve housing, ensuring that there
can be no contamination from the actuator through to the product.
- The opened lantern also prevents temperature changes occurring in the actuator (as it is not subjected
to any changes in product temperature), thereby increasing the actuator’s lifetime.
0.1 27 (62)
Document Description:
P&ID Guidelines
The VARIVENT® valve system satisfies the EHEDG Requirement for “Geometry and Drainability” as follows:
- The clear height of the housing always conforms exactly to the size of the sockets.
- There are no domes or sumps in the valve housings.
- The housings have excellent cleaning characteristics.
The VARIVENT® valve system satisfies the EHEDG Requirement for “Seals” as follows:
- The valves utilize a V-ring type seal in a groove, and a metallic stop which limits seal deformation and
avoids uncontrolled overstress.
- This avoids any dead space behind the seal, reduces the risk of contamination and increases the lifetime
of the seals.
0.1 28 (62)
Document Description:
P&ID Guidelines
Revision: Page:
0.1 29 (62)
Document Description:
P&ID Guidelines
The EHEDG Requirement for “Cleaning in Place” lists the following methods for cleaning valve surfaces:
- Seat lifting to flush the seat, complete with a metallic stop, cavity and drain pipe.
- Cavity spray cleaning to reach the leakage chamber up to the seat seals and the drain pipe.
The VARIVENT® valve system achieves this requirement as follows:
- Cleaning by seat lifting optimizes cleaning of the cavity chamber and seal.
- The cavity outlet is small and easy to clean.
- There are no dead corners and a metallic throttling gap – no risk of contamination.
- Cleaning via the external connection achieves optimized cleaning by means of a spray nozzle.
0.1 30 (62)
Document Description:
P&ID Guidelines
The VARIVENT® valve system is modular in nature, it means valve parts are interchangeable. The high flexibility
offers many advantages. With the ability to combine all basic elements with one another, the system offers a
broad range of possible applications. Existing valve systems in process installations can be modified or adapted
without changing the current system concept.
(2) Actuator
(3) Lantern
0.1 31 (62)
Document Description:
P&ID Guidelines
The height of the dead-zone-free housing exactly corresponds to the diameter of the connection pipeline.
This avoids domes and sumps with their negative effects such as oxidization damage or cleaning problmes. The
special ball shape of the housing offers the best flow profiles without flow separation.
All valves have exchanged modules, and design offers numerous housing combinations with either clamped or
welded seats.
0.1 32 (62)
Document Description:
P&ID Guidelines
The two-letter code indicates the valve type (first letter) and the housing configuration (second letter) being used.
It is also possible to have a valve with a “mix-match” housing combination, where the upper housing is smaller
than the lower housing. In this case, the actuator size is based on the size of the upper housing. In some cases,
it is possible to have a larger housing on the upper side, e.g. the 3” / 2.5” combination, but this should always be
confirmed with Tuchenhagen prior to purchasing the valve.
• Note: Valves with mix-match housing combinations should also be considered for use in Valve Seat Cleaning
operations, in place of the more commonly used NL type valve, because there is no dead-leg associated with
its installation.
The following types of valves are manufactured within the VARIVENT® Valve System:
• Single Seat Shut-off Valves
• Single Seat Shuttle Valves
• Double Seal Valves
• Mix-proof Shut-off Valves
• Mix-proof Shuttle Valves
• Mix-proof Tank Bottom Valves
• Aseptic Valves
• Leakage Free Valves
0.1 33 (62)
Document Description:
P&ID Guidelines
The VARIVENT® Valve selection scheme is an aid to selecting the appropriate valve type for the particular
application. Please refer to the flow component catalogue for details.
When selecting the type of valve to use, it is important to bear in mind that different valve types have different
static and dynamic closing behaviours that must be taken into account when operating pipe systems.
In static pipe system conditions, it may be possible for a valve seat to open due to high pressure in the pipeline.
(Standard valve design allows the valve to be resistant to pressures of 5 bar or less).
Conversely, it may be possible for a valve seat to be “locked” into place (i.e. unable to open) if the pressure in the
pipe-line pressing down on the valve seat is greater than the compressed air pressure required to open the valve
(standard valves require 6 bar air pressure to open). Therefore, when selecting the valve type to use, it is important
to consider the orientation of the valve seats as well as the actuator size required.
In dynamic conditions, water hammer may be exacerbated during the closing action of the valve. Therefore it is
always important to ensure that the valve is installed so that its seat will close against the direction of flow of the
liquid. The diagram below shows a typical mix-proof valve, where the arrow indicates the recommended direction
of flow in order to prevent these pressure surges:
0.1 34 (62)
Document Description:
P&ID Guidelines
• Valve types N and U provide single seat shut-off (flow stoppage) within a piping system.
• Typical applications include: Drain valve (type U), bypass valve, dosing valve and tank outlet valve
• The actuator is reversible, with the normal position being spring to open, air to close.
• The direction of flow dictates whether an N or a U valve is most appropriate – pressure surges during the
closing operation of the valve should be avoided. The valve should always shut against the direction of
hydraulic flow.
• If closing against the direction of flow is not possible (e.g. emptying of the system) the valve type U should
be used.
• There is also a smaller, more economical version of the N type valve available (ECOVENT) which has no
accessories and fewer housing combinations available.
Type N Type U
Revision: Page:
0.1 35 (62)
Document Description:
P&ID Guidelines
• Valve types W and X change the direction of flow within a piping system.
• The valve switch over should always take place against the direction of flow.
• Typical applications include: CIP supply piping, CIP return piping, collecting (converging) (Type W),
separating (diverging) (Type X).
• The actuator is reversible, with the normal position being spring to open, air to close.
• There is also a smaller, more economical version of the W type valve available (ECOVENT) which has
no accessories and fewer housing combinations available.
Type W Type X
Revision: Page:
0.1 36 (62)
Document Description:
P&ID Guidelines
• The D type valve provides mix-proof separation at pipe junctions within pipe systems – stopping flow or
joining flow streams.
• Typical applications include: Valve blocks, tank outlets, units. For mix-proof separation of incompatible
media in rigid matrix-piped systems flowing through closed valve housings or for protecting already
cleaned pipes against contamination. This valve allows tanks in a common valve block to be washed
without putting the transfer operation at risk of contamination.
• The valve has an axial/axial gasket arrangement on the insert (which causes leakage of product during
switching from open to closed).
The lower seat moves up by about 2mm (allowing material in the bottom housing into the neutral area) to
join the upper seat and then both seats move up together
• The valve type D has a cleaning device for spray-cleaning of the leakage chamber. If valve seat cleaning
is required in connection with pipe cleaning, the valve must be equipped with a lifting actuator for lifting
the valve disk on the actuator side and/or on the opposite side for cleaning the leakage chamber.
• The valve should always shut against the direction of flow.
• Note: When ordering a D valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve; i.e. just cleaning
the seats is not enough because not enough flow velocity is present in the valve cavity to ensure that it is
cleaned properly. This should also be noted on the P&ID and in the FDS.
0.1 37 (62)
Document Description:
P&ID Guidelines
• Higher pressure peaks over 25 barg in the pipe system beneath the valve seat may force the lower valve
seat open. The pressure peak is then relieved via the leakage outlet.
• The B type valve provides mix-proof separation at pipe junctions within pipe systems.
• Typical applications are similar to the D valve, except they are preferred for use with expensive products
in high pressure conditions.
• The valve comes with a balancer for the lower valve seat, which provides pressure hammer safety up to
25 bar.
• The valve has an axial/axial gasket arrangement on the insert (which causes leakage of product during
switching from open to closed).
• Note: Due to its pressure resistance from the balancer, the valve has strong spring closing forces that
cause the valve to close much quicker than the valve type D without balancer. This may cause such
problems as water hammer in the piping system, or loss of feedback. The closing time of the valve can
be prolonged by throttling the exhaust air or by serial disconnection in the system via timer, first stopping
the liquid supply and then closing the valve1.
• The B type valve has the same housing combinations and sizes as the D type valve.
• Note: When ordering a B valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve; i.e. just cleaning
the seats (with the lifting actuator) is not enough because not enough flow velocity is present in the valve
cavity to ensure that it is cleaned properly. This should also be noted on the P&ID and in the FDS.
Notes:
1. “In particular for valves (type R and type B) which are balanced under the valve seat against pressure surges, it is of
utmost importance that these valves are not closed abruptly against flowing in liquid. Otherwise high dynamic
pressure forms at the valve seat, high differential pressure at the discharge side and high flow velocity occur”.
Revision: Page:
0.1 38 (62)
Document Description:
P&ID Guidelines
During opening, the lower seat moves up first, by about 2mm, to join the upper seat. This action allows liquid from
the lower pipeline to enter the neutral area of the valve. Then both seats move up together. During the closing
action of the valve, the liquid in the neutral area is discharged via the leakage port.
Pressure acts equally in all directions. Also, pressure is inversely proportional to surface area. Therefore, the
addition of the balancer to the lower part of the valve insert, increases the surface area upon which the pressure
of the liquid can act. This counteracts the pressure which is acting on the valve seat, thereby “balancing” the effect
of the pressure surge.
Revision: Page:
0.1 39 (62)
Document Description:
P&ID Guidelines
• The R type valve provides mix-proof separation at pipe junctions within pipe systems.
• Typical applications are similar to the D and B valves, except they are preferred for use with expensive
products where no losses are desired.
• The valve has an axial/radial sealing arrangement on the insert (which means it is leakage free during
switching from open to closed).
• The valve is fitted with a balancer which provides pressure hammer safety up to 30 bar.
• Due to its pressure resistance of 30 bar(g) and its quick-closing characteristic, the same conditions as
described for valve type B must be taken into account for the closing of the valve.
• Note: When ordering an R valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve; i.e. just cleaning
the seats (with the lifting actuator) is not enough because not enough flow velocity is present in the valve
cavity to ensure that it is cleaned properly. This should also be noted on the P&ID and in the FDS.
0.1 40 (62)
Document Description:
P&ID Guidelines
The radial sealing arrangement on the lower seat of the R valve means there is no leakage of product from the
neutral area during switching of the valve.
The axial-axial sealing arrangement means that the valve seal lifts as the lower part moves up, allowing liquid into
the neutral area. Whereas with the radial sealing arrangement, the seal is retained as the lower part moves up,
so that no liquid can enter the cavity.
0.1 41 (62)
Document Description:
P&ID Guidelines
• Cleaning can be achieved by means of a “valve seat cleaning” valve (typically an N type valve) which
supplies CIP solution via a flexible hose connection to the neutral area of the mix-proof valve.
• Cleaning can also be achieved through lifting (by fitting a lifting actuator onto the valve, which can lift the
individual valve seats independently of each other and of the main operation of the valve). This means:
o Optimised cleaning of cavity and gasket surfaces.
o Metallic throttling gap.
o No dead corners.
o Small and easily cleanable leakage outlet.
o No contamination risk.
0.1 42 (62)
Document Description:
P&ID Guidelines
• The K type valve provides mix-proof separation at pipe junctions within CIP or gas pipe systems – with
no cleaning of the neutral area.
• The valve type K is not designed for cleaning the leakage chamber. It is not suitable for applications in
hygienic product systems. It is preferably used in pipe systems that need not to be cleaned, but must
have mix-proof separation.
• Typical applications include mix-proof separation of CIP solutions or gas. They are also frequently used
on CIP Centres.
• The leakage chamber of the valve type K is not drained, neither in vertical nor horizontal installation
position of the valve. This should be taken into consideration when using this valve type. If draining of the
leakage chamber is required, then double-seat valves, type D, B or R should be used. The double-seal
valve, type C is also suitable for simple applications.
• The valve has an axial/axial gasket arrangement on the insert (which causes leakage of liquid during
switching from open to closed).
• The valve should always shut against the direction of flow.
• The K valve is an economic version of the D type valve, where hygiene might be less of a concern. It is
not available with a balancer.
Type K
Revision: Page:
0.1 43 (62)
Document Description:
P&ID Guidelines
• The C type valve provides double-seal separation at pipe junctions within CIP or gas pipe systems –
stopping flow or joining flow streams.
• In all installation positions of the valve type C, the leakage chamber is drained via the lateral drain valves.
• If the valve is to be mounted in horizontal position, (e.g. Gas Block) the drain valve should always be at
the lower position to ensure drainage.
• This valve is not commonly used, although one possible use is in CIP Centres, instead of using a K type
valve (the advantage being that the seals/seats of the C valve can be cleaned).
• The C valve could be used as a more economical version of the D valve, but it should be noted that it is
not as reliable, because it does not have two independent seats. (If one seat lifts due to high pressure in
the line, so does the other).
• The valve has an axial-axial sealing arrangement.
• There is only one valve disk.
• The leakage cavity is cleanable, by means of 2 rinsing valves.
• On a product or Gas Block installation, one rinsing valve should be connected to a VSC supply and the
second rinsing valve should be piped to drain via 8mm tube.
• On a CIP Plant installation, only 1 rinsing valve is needed. (No VSC) This valve should be piped to drain
via 8mm tube. The Nozzle on the valve housing for the 2nd rinsing valve should be blanked off by using a
PTFE blanking plug. This plug is “flush” with the inside wall of the housing so there is no dirt pocket.
• The valve should always shut against the direction of flow.
• Note: Make sure that both seals are in good condition, as otherwise only one seal is reliably sealing.
When changing the seals, both seals should always be replaced.
0.1 44 (62)
Document Description:
P&ID Guidelines
3.3.3.8 Double Seat Shut-Off Valve: Changing Flow Direction with Mix-Proof Protection
• The type Y valve changes flow direction with mix-proof separation of incompatible media.
• Typical applications include: Pasteurizers (pasteurised product against non-pasteurised product) and
tanks. Since the valve type Y is a mix-proof shuttle valve, it should be primarily used for flow diverging
applications.
• The Y valve is a combination of the shuttle valve X (lower part) & the mix-proof valve D (upper part).
• Note: Only the seat between the middle and upper ports is mix-proof. The lower seat, between the middle
and lower ports, is a single seat. This should be borne in mind when installing the valve and designing
the piping system.
• Cleaning of the “neutral area” is possible.
• A lifting actuator is available as an option.
• The valve should always switch against the direction of flow.
• Note: When ordering a Y valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve; i.e. just cleaning
the seats is not enough because not enough flow velocity is present in the valve cavity to ensure that it is
cleaned properly. This should also be noted on the P&ID and in the FDS.
Type Y
Revision: Page:
0.1 45 (62)
Document Description:
P&ID Guidelines
• The T type valve provides mix-proof tank outlet shut-off – stopping flow or joining flow streams.
• Typical applications include: Storage tanks (cream, milk, concentrate), process tanks (rennetting tanks,
ripening tanks, culture vessels, mixing tanks). E.g. mix-proof separation of product in the tank from CIP
in the line:
Fig 3.3.O: Mix-proof Separation of Product in Tank from CIP in the Line
• The valve has an axial-radial sealing arrangement, similar to the R valve (leakage free switching).
• It also has a balancer for the valve seat on the actuator side. This is because, after tank filling, the valve
closes with the direction of flow (contrary to our usual philosophy). The balancer on the actuator side
works against the tendency of pressure surges.
• The valve is mix-proof, and cleaning of neutral area is possible.
• A lifting actuator is available as an option.
• Horizontal installation is possible (ECO-MATRIX® principle).
• The leakage chamber of the bottom valve, type T_R is self-draining in the upside-down position only. In
case of vertical or horizontal installation position (e.g. ECO-MATRIX), the valve is equipped with an
additional drain valve.
• The valve provides a means of flush tank bottom shut-off.
• Note: When ordering a T valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve; i.e. just cleaning
the seats is not enough because not enough flow velocity is present in the valve cavity to ensure that it is
cleaned properly. This should also be noted on the P&ID and in the FDS.
Revision: Page:
0.1 46 (62)
Document Description:
P&ID Guidelines
Type UF Type NF
Revision: Page:
0.1 47 (62)
Document Description:
P&ID Guidelines
• The L type valve stops flow or joins flow streams, with mix-proof separation of incompatible media, and
is suitable for pigging (product recovery) operations.
• Typical applications include tank filling and tank emptying, with pigging of the complete product pipe.
• The valve comes with an optional lifting actuator, individually switchable for upper and lower valve seats.
• Cleaning of “neutral area” with rinsing (valve seat cleaning) valves is also possible.
• The valve has a radial seal arrangement, similar to the R type valve.
• The valve can be installed in upright, horizontal or upside-down positions.
• Note: Product recovery is only possible in one housing (the housing furthest away from the actuator), as
the other housing contains the valve insert.
• Note: When ordering an L valve with a lifting actuator for independent seat lifting, it is very important to
specify that the standard cavity cleaning connection to the valve stem is also required.
To achieve full EHEDG requirements, it must be possible to clean the cavity of the valve as well as the
individual seats; i.e. just cleaning the seats is not enough because not enough flow velocity is present in
the valve cavity to ensure that it is cleaned properly. This should also be noted on the P&ID and in the
FDS
Type L
Revision: Page:
0.1 48 (62)
Document Description:
P&ID Guidelines
These valves are used to control conditions such as flow, pressure, temperature and liquid level by fully or partially
opening or closing in response to signals received from controllers that compare a “set-point” to a “process
variable” whose value is provided by sensors that monitor changes in such conditions.
There are different valves that will be used from now on:
- Type P does not work as a regular modulating valve because it has different opening positions, so it is used
when just a complete opened or complete closed position of the valve is not what it is needed.
- Type S and A are used as a regular modulating valve. They have a fine adjustment, so they are useful for
cases where more precision is required.
Revision: Page:
0.1 49 (62)
Document Description:
P&ID Guidelines
0.1 50 (62)
Document Description:
P&ID Guidelines
• The Q valve relieves excess pressure in pipes, but is NOT a safety device.
• Typical applications include: bypass valve after positive displacement pumps, drain valve, air exhaust
valve.
• The set pressure is adjustable by means of an actuator with an adjustable spring.
• An integrated pneumatic actuator (type M) is available as an option, in order to lift the valve seat for
cleaning purposes.
• There are 6 housing combinations available, according to the VARIVENT principle.
Type Q
Revision: Page:
0.1 51 (62)
Document Description:
P&ID Guidelines
• The type 448 valve relieves excess pressure and is an approved safety device. The adjustment is factory
set and the adjustment mechanism is sealed.
• Approvals include TUV, ASME and ATEX.
• Typical application: tank pressure relief.
• Full-lift function.
• Response pressure: max. 10 bar.
• Pressure range: 0.2 to 16 bar (spring loaded actuator).
• Wetted components made of AISI 316L.
• Includes a cleanable housing, according to the VARIVENT principle.
• Manual lifting as standard, pneumatic seat lifting optional.
• Different connection types are available.
Type 448
Revision: Page:
0.1 52 (62)
Document Description:
P&ID Guidelines
Type V
Revision: Page:
0.1 53 (62)
Document Description:
P&ID Guidelines
• The type I sample valve is installed into the process system upright
• The actuator is dually configured so that the valve can be actuated pneumatically or manually.
• Due to the conical contour of the valve disc, smaller sample volumens can be tapped as well.
• It uses up to two proximity swithches, permiting the detection of the closed and/or opened positions.
0.1 54 (62)
Document Description:
P&ID Guidelines
0.1 55 (62)
Document Description:
P&ID Guidelines
0.1 56 (62)
Document Description:
P&ID Guidelines
Damaged Bellows
Advantage
• The Aseptomag Valve is hygienic. When the shaft of the valve insert moves, there is no contact with the
outside of the valve housing chamber. There is no risk of the product getting contaminated.
Disadvantage
• The Aseptomag valve Bellows is easily damaged. If the valve closes with the direction of flow, it will cause
serious damage to the Bellows.
• Replacement of the seals is not easy. They need to be melted off with a soldering iron.
• Replacement seals need to be heated in an oven.
• Tefasep seals need to be sterilized with steam to approx. 140degs for approx. 20mins, with all valves in
the open position. The valves will then need to be closed to embed the seal against the seat-ring to ensure
a proper seal of up to 6bar.
Revision: Page:
0.1 57 (62)
Document Description:
P&ID Guidelines
0.1 58 (62)
Document Description:
P&ID Guidelines
Liquid is not compressible, and in principle it must be assumed that incompressible liquids behave like a solid
body. If they are suddenly decelerated or abruptly brought to a halt, pressure surges can build up in closed pipes
(commonly known as “water hammer”) and can cause destruction (imagine a car being driven into a solid wall).
In principle, these guidelines should be applied to all valves within the VARIVENT® range, particularly where the
valve has a “shut-off” or “direction-switching” function.
Therefore, when the balanced valve closes against flow, it does so much quicker than a standard valve, almost
negating the advantage of closing against the flow. The result is a stronger water hammer and associated wear
on valve seals (in particular the radial seal in the valve type R, which is more susceptible than an axial seal).
To counteract this, balanced valves that close against flow must also have restrictors in the air exhaust,
in order to slow down the closing action.
Revision: Page:
0.1 59 (62)
Document Description:
P&ID Guidelines
The situation, where liquid may be trapped between 2 closed valves, must be avoided.
Liquid is not compressible, therefore it will not “give way” to allow the valve to open (or close) into it. The high
pressure build-up in the system means that the valve can no longer be opened by the control air pressure or that
it does not reach its non-actuated (closed) position.
Often, this high pressure build-up is caused by “thermal expansion” in the system when the liquid is at rest, i.e.
the temperature of the pipe-work, and the liquid in it, can increase over time, causing the liquid volume to expand.
0.1 60 (62)
Document Description:
P&ID Guidelines
• The C type valve can be used for double-seal separation at pipe junctions within CIP or gas pipe systems
instead of the K valve.
• Advantage
• The C valve is that the valve is cheaper than the D or K valve. It has only one disk. Less moving parts and
less seals.
• Disadvantage
• The C valve is not a true mix-proof, like the K or D valves, because it does not have two independent seats.
If one seat lifts due to high pressure in the line, so does the other.
C Valves on a Gas Block VSC hose and 8mm drain line on a C Valve
0.1 61 (62)
Document Description:
P&ID Guidelines
Although a P&ID is primarily schematic, it is often relied upon (even when layouts are available) as the guide for
placing and orienting tanks and valve blocks.
Mistakes are commonly made with valve block manufacture because the layout on the P&ID is notional and does
not reflect the actual orientation of the tanks and the valve block.
The key risks are: a tank is connected to the wrong valve row, or a valve block is constructed in the wrong
orientation, meaning pipes are crossing each other from tank to valve block. Therefore ALWAYS ensure the P&ID
reflects the planned layout of tanks and valve block.
Explanatory Note
The size this will occupy on the P&ID will be larger than a simplistic schematic layout, but this is a small price to
pay for accuracy of construction of valve block and accuracy in pipe to valve connections, with the attendant
benefits for wiring and process descriptions.
Revision: Page:
0.1 62 (62)
Document Description:
P&ID Guidelines
6 CHAPTER SUMMARY
This chapter dealt with the design of the P&ID. The designer must be familiar with our Sound engineering
practice which provides a series of checks on the selection of valves and pumps.
Specific information is provided on common pump and valve types so that the appropriate type can be selected
from suppliers documentation and Tuchenhagen flow components.