Installation and use manual

electronic controller
Logik 103
(Code 0KLC5Z5B)

ORIGINAL INSTRUCTIONS

DESCRIPTION

Logik 103 is a industrial electronic controller for the proper operation/management of a screw
compressors room with 4 units connected max. (if the alarm relay is set as operating of the 4th
compressor), working pressure up to 15 bar.
Thanks to three different operating principle selectable via software (Balance hours – Priority –
Smart), Logik 103 can meet the different needs of each installation type, always having as
main target:
1) the maximum efficiency of the system granting a constant pressure in line.
2) energy saving.
Thanks to the time-keeper assembled in, you can set 4 bands of operation and each band
programmed according two different working pressure set.

Rev. 0.5 – 24.05.2012 Page 1


INDEX

TECHNICAL FEATURES Page 3

OPERATING PRINCIPLE Page 4

CAUTIONS Page 5

MOUNTING TO THE WALL Page 6

ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS Page 7

MAIN VISUALIZATION Page 9

PROGRAMMING Page 10

1 – INFO Page 10

2 – PASSWORD Page 11

3 – VISUALIZATION SETUP Page 11

4 – PLANT SETUP Page 12

5 – PRESSURES Page 14

6 – TIMER Page 15

7 – MAINTENANCE Page 16

8 – ALARMS Page 17

9 – GSM UNIT Page 18

10 – RESET Page 19

DISPOSAL Page 19

WARRANTY Page 20

EDITION LIST Page 20

CE CONFORMITY DECLARATION Page 21

Rev. 0.5 – 24.05.2012 Page 2


TECHNICAL FEATURES

• Power supply: 230 V ~ ± 10 % - 50/60 Hz


• Consumption: ~ 25 m.A.
• Insulation class:
• Protection degree: IP30
• Working temperature: -5 ÷ 50°C with 90% RH (non condensing).
• Storage temperature: -20 ÷ + 60°C
• Grey box: ABS auto-extinguishing (V0)
• Connections: screw terminals
• Nr. 3 function key + nr. Start/Stop button
• Nr. 1 input for pressure transducer 4 ÷20 mA, working range 0 ÷ 15 bar
• Nr. 1 serial port RS232 for connection to GSM Unit (code 0JLC5L5B)
• Visualization through back-light graph LCD (128 x 64 dots)
• Nr. 1 time-keeper, accuracy 0,1% with no rechargeable buffer battery: electrical life over
10 years
• Nr. 4 relay with contact 8 (2) A- 250V~ for:
operating compressor 1-2-3
operating compressor 4 or alarm output with free contacts
• Logik 103 is provided with nr. 1 pressure transducer (working range 0 ÷ 15 bar), 4÷20 mA
2 wire with stainless steel membrane AISI 316L.
• Weight : ~ 1.200 g

The controller switches OFF due to micro-power > 300 m.sec.

Rev. 0.5 – 24.05.2012 Page 3


CAUTIONS

Logika Control informs you that:


- the controller is not a safety device and software is class A (see EN 60730-1 ed EN 60335-1)
- any changes or modifications of the LOGIK 103 and / or operations carried out in
disagreement with what is described in this manual will invalidate the warranty and void the
original Declaration of Conformity;
- the values refer to the technical LOGIK 103 (SEE TECHNICAL FEATURES - PAGE 3), drawings
and other records are the property of Logika Control s.R.L. which reserves all rights;
- the installation must be performed by qualified personnel as required by law in the country of
installation and it requires the user before installation to verify that the electrical system
corresponds to the nominal supply voltage of LOGIK 103 (SEE SPECIFICATIONS - PAGE 3);
- Logik 103 must be installed in closed ambient possibly in the compressors room;
- on Logik 103 power net you have to place an insolator switch;
- Logik 103 is not a safety device and software is Class A (see EN 60730-1 and EN 60335-1):
the installer will provide any safety devices if necessary;
- Logik 103 is not intended to be used in potentially explosive atmospheres;
- don’t wash the box oc Logik 103 by water jet.

Rev. 0.5 – 24.05.2012 Page 4


OPERATING PRINCIPLE

The panorama of compressed air systems is represented by a very large and different scenery.
Nowadays there is no industry that does not have a compressor room for which you often have
to deal with different issues related both to the expansion of facilities (ie a new machine
management needs of an ever-growing air) that the simple management of the compressors
to allow a homogeneous use.

The Logik 103 provides the ideal solution for every need with the flexibility given by three
different types of work: Balance hours - Priority - Smart.
Each of the three working principles pursues the same target, namely to ensure a constant
pressure in line to ensure optimal system performance: the Logik 103 places into service or
stop the compressor considered the most appropriate or unnecessary, depending on air
demand and this objective can be achieved just by three different principle mentioned above.

- BALANCE HOURS: for installation consisting of compressors of the same power where you
want to use the machines alternately and obtain even wear.
You can set a time after which the machine will rotate among them according to the FIFO
principle (First In First Out): the compressor, which was first placed in service will be the
first to be excluded.

- PRIORITY: for installation where the installer / end user decides the priority of the
compressor (ie the sequence of action) by assigning them a number (lower number =
higher priority).
This is a principle useful for those systems disproportionately evolved over time where an
intelligent operation would risk the exclusion of certain machines because never felt enough
or too big.
Then selecting the priority system and knowing the consumption, the Logik 103 will operate
the machines in accordance with a pre-selected setting.

- SMART: operating principle to obtain the best performance by optimizing the power
consumption (saving).
- By setting the rating system will be arrested or put into service the compressors according
to the actual air consumption; consumption detected by the fall or increased.
Thanks to other parameters in the section on programming, Logik 103 ensure significant
energy savings for a plant always reactive to any changes in the pressure.

Rev. 0.5 – 24.05.2012 Page 5


MOUNTING TO THE WALL

Use the controller as template and fix it through the 4 Fisher tiles (C) provided (tiles ∅ 5mm –
self-threading screw TC 3,5 x 38 mm).

Open the cover by the 4 screws (A), unhook the connector (B) to take the cover out and make
the electrical connection more easy.

The electrical connection must be carried out by authorized personnel according the electrical
drawing below and related legend and in power off status, so pay attention the isolator switch
that CRS1 depends on the power supply is in OFF position.

NOTE: for electrical connections, open the holes pre sliced and use the sleeves (D) provided
(∅ 16 mm) where the related rigid pipes have to be inserted to run a fixed connection
according to the current regulations.

ATTENTION: the connection to the electrical grid must be carried out as last
operation.

Rev. 0.5 – 24.05.2012 Page 6


ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS

Logik 103 is provided with nr. 6 sleeves for rigid pipe ∅16 mm to be used for the electrical
connections otherwise the protection IP30 is missed.
To grant the IP protection degree to the device, keep closed the holes unused for the electrical
connections.

NOTE: in case alarm relay is used by operating the 4th compressor, see always drawing A
or B below according the connection.

LEGEND

TRMINAL M1: alarm relay 8 (2)A. 230Vac or operating compressor 4


TERMINAL M2: relay operating compressor 1
TERMINAL M3: relay operating compressor 2
TERMINAL M4: relay operating compressor 3
TERMINAL M5: connection to GSM UNIT
TERMINAL M6: pressure transducer 4/20mA – (0÷15bar or 0÷50 bar)
(Pole1 = negative – Pole2 = positive)
TERMINAL M7: Power Supply 230Vac
TERMINAL M8: connection to control panel

Rev. 0.5 – 24.05.2012 Page 7


NOTES ON CONNECTIONS TO LOGIK 103

Before you make the connections, put the compressors OFF and check out the way of control:
if they are provided with input to remote start / stop follow connection A, on the other way act
on the electromechanical pressure switch and follow the connection B.

A-REMOTE START/STOP
With parameter 04-10 (Relay operation) set ON, connect the poles 1 and 2 of the terminal M1
(if the 4th compressor is connected) - M2 - M3 - M4 to the remote start/stop input of the
compressor; with parameter 04-10 set OFF connect the poles 1 and 3 of the terminal M1 – M2
– M3 – M4 to the remote start/stop input of the compressor (default ON).
PAY ATTENTION: decreases by 0.5 bar the start pressure and increases by 0.5 bar the Stop
pressure on the machine respect to the working pressures set on Logik 103.

B-ELECTROMECHANICAL PRESSURE SWITCH


With parameter 04-10 set ON, connect the poles 1 and 2 of the terminal M1 (if the 4th
compressor is connected) - M2 - M3 - M4 in series to the pressure switch; with parameter 04-
10 set OFF, connect the poles 1 and 3 of the terminal M1 - M2 - M3 - M4 in series to the
pressure switch (default ON).
PAY ATTENTION: decreases by 1.0 bar the start pressure and increases by 1.0 bar the Stop
pressure on the machine respect to the working pressures set on Logik 103.
NOTE: The pressure switch contact must occur electromechanical closed before
turning on the Logik 103.

SCHEMA DI COLLEGAMENTO LOGIK 103 – GSM UNIT (0JLC5L5B)

NOTE: the communication cable


between Logik103 and GSM UNIT
GND must be 4 poles, shielded (the
shield must be connected to one
NC
pole GND only) and no longer than
TX 3 meters.

M5-Logik 103 RX

1 NC

M1 – GSM Unit
NOTE ABOUT THE TRANSDUCER
The pressure transducer must be mounted on the air tank and always in an upright position to
prevent condensation. If the distance from the controller is longer than 5 meters, use a
shielded cable 2x0, 5mm ² and ground only one end of the screen.
The maximum distance should not exceed 50 m.
Note: be careful to place the pressure transducer in an upright position to prevent
condensation from getting clogged.

NOTE ABOUT THE ALARM RELAY


In case the 4th compressor is not connected, you can use the alarm relay (free contacts, output
terminal M1) to operate an alarm signal (light or siren) that will be activated permanently with
shut-off alarm and intermittently with visual warnings.

Rev. 0.5 – 24.05.2012 Page 8


MAIN VISUALIZATION

Power on and the display shows the message “Logika Control” “Logik 103” for 3 seconds
and then the following visualization:

X.Xbar Pressure detected

Menu

Pushing the start button, the display visualizes the following

1 2 3 4 According # of compressors
7,8
7.0 7.5 bar
P.Start P.Stop MENU

ESC FUNCTION: in any part of the menu, hold down the button for about 2 seconds and
you return to the main display.

QUICK SETTING START AND STOP PRESSURE


Change the Start pressure by pushing : function P.Start change into “+”, “P.Stop” into
“-” and starts blinking; change the value by and/or and confirm it by : the value
stops blinking.
Change the Start pressure by pushing : function P.Start change into “+”, “P.Stop” into
“-” and starts blinking; change the value by and/or and confirm it by : the value
stops blinking.

MEANING OF THE ICONS

= start and stop of the compressors operated by clock (visualized while activated only)

1 = comp. stop 1 = comp. Working 1 (blinking) = running upload to stop

1 =out of service for maintenance

P2 = second pressure level enabled

= alarm in

= maintenance timer expired

ANTIPANIC FUNCTION
In any settings menu and / or views, after 300 seconds from the last pushing any key, the
controller shift back to the main display without saving any changes not confirmed.

FUNCTION LCD ENERGY SAVING


After 1 minute of the last pushing any key, the backlight of the display turns off to on again by
pushing any key.

Rev. 0.5 – 24.05.2012 Page 9


PROGRAMMING (Advisable to set with controller OFF)

To enter the programming, push the button below the function “Menu” (shown in reverse) to
the left of the display so you enter the main flow which includes the following:

1 – Info To select each sub-menu always use th arrow buttons and


2 – Password-Change password confirm by to enter in.
3 – Visualization setup NOTE TO PARAMETER SETTING
4 – Plant setup To modify the parameters, select the desired one using the
5 – Pressures arrow keys and confirm by ; always with the arrow
6 – Weekly program functions select the new value and confirm it by .
7 – Maintenance
8 – Alarms Flowing down the menu and overcoming the last parameter,
9 – GSM Unit the display shift back to the previous visualization.
10 – Reset

1 – INFO

For each compressor the display visualizes in


WORKING HOURS
the following values in sequence: total working
hours – starts/hour – maintenance timer elapsed C.1 1.900 h
C.2 4.400 h
(if enabled) and software release of the controller.
Visualization comes through arrow buttons.

When the maintenance timer is elapsed the display visualizes the symbol ; enter into “Info”
menu to visualize the messages related to the maintenance timer elapsed; to reset the
message and related key symbol push when the display shows message in.
NOTE: if you reset the maintenance messages by only, they will be visualized again after 16
hours until you don’t reset them into Reset menu.

Code Meaning
M1- C.1-2-3-4 Change air filter
M2- C.1-2-3-4 Change oil filter
M3- C.1-2-3-4 Change separator filter
M4- C.1-2-3-4 Change oil
M5- C.1-2-3-4 Check compressor

NOTE: # 1-2-3-4 are related to the compressor connected

Rev. 0.5 – 24.05.2012 Page 10


2 – PASSWORD (no default code)

From main menu, selecting “Password” and pushing you enable the controller to enter the
password and protect some parameters-menu by any tampering of unauthorized personnel.
The procedure to enter the password is the following:

2 – Password 2 – Password

X-- XXX

By the arrow key select the Once you set each single
first digit and confirm by digit, the number is replaced
ENTER function and shift to automatically into X to
the second one and so the protect by unauthorized
third. views.
Once the last digit has been confirmed and the password is correct, the display shift back to
the previous menu without shown Password menu.
In case the password is not correct, the display visualizes the “PASSWORD WRONG”.
Once the password has been enabled to be able to enter into the protected setting you have to
select “Password” again and enter the code you enter previously.

PASSWORD MISSED AND/OR CHANGE PASSWORD !!!


In case you forget the password you have to disconnect the power supply to the controller,
then restore power line while holding down and for about 5 seconds.
During this time the display shows the blinking message “Reset Password”; when the
message change into “Password reset” stop holding down the arrows button.
To enter new password follow the instruction step 2.

3 – VISUALIZATION SETUP

In this menu you can set the parameters related to the visualization of the controller.
To edit the setting select the parameter desired by the arrow function and confirm by ;
always by the arrow buttons select the new value and confirm by .
3 - Visualization setup

English
BAR
- +
10:23 Gio 26/02/2011
DLS/Summer = Yes

Select language for display messages (default ITALIAN)

Pressure measurement unit: bar/psi (default bar)

Display contrast

Setting date/time and automatic change DLS/Summer time if YES has been selected

Rev. 0.5 – 24.05.2012 Page 11


4 – PLANT SETUP (Password)

Very important for optimal management and high system 4 – Plant setup
efficiency is the setting of the parameters into this menu. 1-Operating principle
Below you can find the settable parameters with related default 2–Comp. nr.
values, setting range and operating principle. 3 –Comp. parameters
Enable the editing of the parameters by selecting them with 4 –Tank capacity
Arrow keys and confirm by ; till by arrow keys select the 5–Delay stop
new value and confirm it by . 6–Delay start

1-Comp. Nr. (default 2): enter the number of compressors connected to Logik 103: setting
range 2 ÷ 4. PAY ATTENTION: parameter visualized while controller is OFF only.
NOTE: by selecting “4” the terminal M1 configures 4th compressor management automatically.
4-3-Comp. parameters
2-Compressors parameters
Comp. nr.1
By confirming this parameter the display visualizes
Comp. nr.2
Set the following parameters for each compressor: Comp. nr.3
Comp. nr.4

1 - Air flow: set the air flow of the compressor:


Air flow 50÷ 50.000 l/min. Step 50 l/min default 1.000

2 - Priority: set the priority of each compressor in the management of the plant:
Priority 1÷4 1=highest priority default 1

3 - Priority set: managing start/stop of the compressors under timer operation (see chapter 6
– TIMER) is possible to change automatically the priority of the compressor into the 4 different
working bands available (Set1 – Set2 – Set3 -Set4) where Set1 is the setting on parameter
4.2 - Priority.
Priority set Set2 – Set3 – Set4 1÷4 default 1

4 - Loading time: set the time passing from starting motor and open the load solenoid valve:
Loading time 0÷ 600 sec. Step 1 sec. default 1.000

5 - Unload time: set the unload time


Unload time 0÷ 600 sec. Step 1 sec. default 1.000

6 - Safety time: it is the time to elapse between the shutdown and subsequent restart of the
compressor:
Safety time 10÷ 300 sec. Step 1 sec. default 1.000

9 - Starts/hour (default OFF):


OFF: the starts/hour counting is just visualized on INFO menu and the following parameter is
not in.
ON: the display visualizes the following parameter where to set the max. starts/hour of the
motor allowed. If the compressor reaches the setting value, it will be operated if strictly
necessary only to keep the pressure in the working range set.
In case the compressor overcomes the setting value, the controller visualizes the related
warning (it’s not a shut-down alarm) and store it into the alarm list; once the hour is elapsed
the counting is erased and start again.
Starts/hour 6÷ 20 h. Step 1/h Default 12

Rev. 0.5 – 24.05.2012 Page 12


10 - Working hours: set the operating hours of the compressors, if existing, at the time of
installation of the controller:
Working hours 0÷ 99.000 h 100 h x passo default 0

3-Tank capacity: setting 500 ÷ 50.000 l (Step 100 litres) – default 1000.
Take into consideration further secondary tanks and plant volume, if any.

4-Delay STOP: 0 ÷ 20 seconds – default 0.


Before to stop the compressor, the controller start this timer; once the timer is elapsed if the
control algorithm till needs to stop the compressor, it will be done.

5-Delay START: 0÷20 seconds – default 0.


Before to start the compressor, the controller start this timer; once the timer is elapsed if the
control algorithm till needs to start the compressor, it will be done.
NOTE: delay stop and delay start have the function to manage dynamic control of the
compressors more reactive or slower.

6-Power ON: confirm and visualize the followings:


1 – T start comp. 2: 5 ÷ 240 seconds – default 120 seconds.
Once this timer is elapsed if the pressure has not reached the stop pressure, the controller
starts the second compressor and third one also if necessary
2 – Compressor: 1 ÷4 – select the compressor has to start every first starting of the day.

7-Restart: confirm and visualize MANUAL/AUTOMATIC – default MANUAL.


MANUAL: in case of black-out when the power is ON again, the controller keep in OFF status,
compressors are stopped and the display visualizes the code alarm AL.B.3 (POWER FAULT).
AUTOMATIC: in case of black-out when the power is ON again, the controller restart to manage
the compressors according the working pressure after a safety time of 120; during timer in
progress, the display visualizes the message “Power OFF”.

8-Balance hours: by this parameter you can balance and align the working hours of the
compressors after first starting of the controller; confirm and visualize
1-Align hours: OFF – ON / Default OFF
OFF: the alignment of the hours is not operated
ON: the compressor with less working hours has higher priority during the operation
2-Working hours: 10 ÷ 500 h – default 100
once this timer is over, the compressors rotate among them according FIFO principle, except
to start in case of need by air demand.
9-Reserve compressor: confirm and visualize NO/YES – default NO
NO: no one compressor managed as emergency unit.
YES: enter the number of the compressor you need to operate in emergency situation only; it
means while the pressure goes down the value set on P6 “low pressure alarm” or in case one
or two compressors are out for maintenance.

10-Relay operation: ON/OFF – default ON


NOTE: parameter visualized by controller in OFF only.
ON: connect the compressor to the relay in the position NC (Normally closed).
In case of failure of the Logik 103 or power failure the compressors shut down.
OFF: connect the compressor to the relay in the position NO (Normally open).
In case of failure of the Logik 103 or power failure, the compressors will continue to work
through their own pressure sensor.

Rev. 0.5 – 24.05.2012 Page 13


11-Model (default SMART) – select the operating principle amongst:
Smart – Priority – Balance hours
Once you select the operating principle, Logik 103 will visualize only the related parameters.

5 – PRESSURES

This menu allows to set all parameters related to the pressure and alarm, as reported below.
For selecting and confirm the data, use the arrow buttons and as for the other sub-menu.

Description Setting range Default Password


P1-Top range transducer 15 ÷ 16 15,0 bar X
P2-High pressure alarm (P3+0,5) ÷ (P1-0,5) 10,0 bar X
P3-Stop pressure (P4+0,2) ÷ (P2-0,2) 8,0 bar
P4-Start pressure 3 ÷ (P3-0,2) 7,0 bar
P5-Offset transducer -2,0 ÷ +2,0 0 bar X
P6-Low pressure alarm (P4-0,5) ÷ 3 6,0 bar X
P7-P. Stop 2nd level (P8+0,2) ÷ (P3+0,5) 7,5 bar
P8-P. Start 2nd level 3 ÷ (P7–0,2) 6,5 bar

NOTE: alarm P6 reset automatically while pressure overcomes the value set on P4.

Rev. 0.5 – 24.05.2012 Page 14


6 – TIMER
6 – Timer

This menu allow to manage start and stop of the compressors room 1-Timer OFF
2-2° press. level OFF
through the time-keeper in the controller. 3-Priority set OFF
Confirm the selection and visualize 1 Timer OFF: confirming 4-Programming
OFF the weekly timer is disabled and sublevels not visualized.
Confirm ON: the weekly timer is enabled and sublevels visualized.
Select 2 - 2° livello Press.: OFF: confirm OFF and the programming 6 – Timer
Of the second pressure level is not enabled. 1-Timer ON
Confirm ON: the programming of the second pressure level is enabled. 2- 2° press. Level ON
Select 3 – Priority set to enable the different priority to operate by timer 3-Priority set ON
4- Programming
set on parameter 3 – Priority set under 2 – Compressor parameters.
Select and confirm 4 – Programming to visualize the label for the
weekly timer on 4 time levels. MON
Enter the program label and “Monday” starts blinking. P1 S1 ON 07:30 OFF 12:30
Select the day of the week you need to start setting by the arrow keys P1 S1 ON 13:30 OFF 16:30
and confirm by Enter: P1 starts blinking to indicate start/stop values P1 S1 ON 16:30 OFF 18:30
are related to the parameters P3 and P4 and ON and OFF times are P1 S1 ON 18:30 OFF 20:30

related to the start and stop of the plant; if you set P2 instead of P1,
ON and OFF times you’re going to set are related to the parameters
of the 2nd pressure level P7 and P8.
After you confirm P1 or P2, the symbol S1 (visualized only if the parameter “3 – Priority set”
under menu 2 – Compressor parameters is enabled) will start blinking to indicate you can
set the priority according the related working bands: select the priority set by the arrow
buttons and confirm by Enter.
Then the first ON time starts blinking: set it by the arrow keys and confirm by Enter; now the
OFF time starts blinking and so on to the next ones; after the confirmation on the last OFF
time by Enter, the LCD shift to visualize the message below giving the possibility to copy the
setting to the next day:

COPY
PREV. DAY?

Push Enter if you need to copy the setting; if you do not want to copy and set the next day
manually push one of the two arrow button.
the next day starts blinking; by Enter you can confirm on the next days the setting already
done on first day or change a described above.
After last setting the display shift back to 5- Weekly program.
- When the weekly program is enabled, the main visualization of the display shows the clock
icon on the upper left side.
- When the 2nd pressure level is enabled, the main visualization of the display shows P2 on
the upper left side.
- When the compressors plant is under clock operation, it is possible to force stopping by
simply pushing Start/Stop: it is possible to come back to clock management by keeping
pushed 5 seconds the Start/Stop button again.
- When the compressors plant is under clock operation, it is possible to force starting by
pushing 5 the Start/Stop for 5 seconds: it is possible to come back to clock management by
simple pushing the Start/Stop button again.

Rev. 0.5 – 24.05.2012 Page 15


7 – MAINTENANCE (Password)
7 – Maintenance

By this menu is possible: 1 – Activate timer


- exclude the compressors you have to carry out service and eventual 4 – Exclude comp.
operation of the emergency compressor, if selected (see menu
Plant setup);
- set the maintenance timer of each compressor
- visualize the related counter 7-1 – Exclude comp.
Compressor - 1: ON-OFF
Confirm Maintenance and the display visualize: Compressor - 2: ON-OFF
1 Activate timer OFF Compressor - 3: ON-OFF
4 Exclude compressors Compressor - 4: ON-OFF

If you need to set the maintenance timer to get related warning messages to carry out service,
confirm “Activate timer” and change OFF into ON by visualizing the related label.
7 – Maintenance 7-2 – Set hours 7-2.1 – Comp. Nr.1
1-Activate timer ON Compressor1 M1-Change air filter 2000 h
2- Set hours Compressor2 M2-Change oil filter 2000 h
3-Counters Compressor3 M3-Change sep. filter 4000 h
4-Excude compr. Compressor4

Set the maintenance timer by selecting and confirming 2 Set hours: the display visualize the
label to select the compressor number to set the maintenance hours and shift to the related
setting label.
Maintenance parameters list settable to each compressor:

Description Setting range Deafult


M1-Change air filter 100 ÷ 3.000 h 2.000 h
M2-Change oil filter 100 ÷ 10.000 h 2.000 h
M3-Change separator filter 100 ÷ 10.000 h 4.000 h
M4-Change oil 100 ÷ 10.000 h 8.000 h
M5-Check compressor 100 ÷ 10.000 h 8.000 h

1) If the new vaule is lower than counting in progress, the counter stops.
2) The counting is related to ON time of the relay of each compressor and it comes backwards:
when the counter reaches 0, the related warning message is visualized on the display and the
timer goes on as negative counting.
3) Storage of the time comes every 15 minutes; in case of black-out during the counting, you
lost 15 minutes fraction of time.
4) If you set M5 to 9.900 the parameter is disabled and related alarm as well.
Select and confirm “Counter” to visualize the label to select and confirm the compressor
number and show the related counter in progress.
Select and confirm Exclude compressor by the label
7 – Maintenance
7 – Maintenance
or 1 – Activate timer OFF
1 – Activate timer ON 4 – Exclude compr.
2 – Set hours
3 – Counters
4 – Exclude compr.

The display shows the label to select the compressor/s to put out 7-4 – Exclude compr.
of service for eventual maintenance without any stop for the plant. Comp - 1 ON
Select and confirm the compressor/s you need to put out of service Comp - 2 ON
and by the arrow change ON into OFF. Comp - 3 ON
Remind to put compressor/s ON once maintenance is over. Comp - 4 ON

Rev. 0.5 – 24.05.2012 Page 16


8 – ALARMS

This menu displays the warning messages detected by the controller: the list contains the last
20 alarms saved; the twenty-first erases the first one and so on.
If there are no alarms in memory the displayed visualizes the message “No alarms stored”.
In case of alarm the alarm relay RL4 (if used as alarm relay) is activated (continuously for
shut-down alarm and intermittent for visual warnings and alarm messages) and the display
shows the symbol : the key switch into AL (ALARMS); push it and the display visualizes
the alarm codes detected with date and time: flow up/down them by the arrow keys.
Once the alarm cause has been settled, push to visualize the alarm list: select by the
arrow keys and confirm by to reset them; in case of automatic reset, wait for the values
comes into the working range.

Meaning of alarm codes:

System shut-down alarm: AL.B.x


Code Cause Meaning
AL.B.0 Setting data lost
AL.B.1 P. > set P2 High pressure
AL.B.2 P.1 Pressure transducer failure
AL.B.3* Power Fault Black-out

Note: AL.B.3 is visualized if parameter 07 in Plant setup is set into manual; in case of
automatic restart after power off, the alarm is not visualized and the display shows the
message “Power OFF”: once the safety timer is over the plant restart automatically.

COMPRESSOR SHUT-DOWN
In case of shut-down alarm, the controller stops the compressor and the display visualizes
“SHUT-DOWN” with related code alarm. Once the cause has been solved push to put the
controller in OFF status.

System visual (warning) alarms: AL.W.x


Code Cause Meaning
AL.W.1 P < set P6 Low pressure
AL.W.2 Time-keeper failure Start and stop not managed by clock
AL.W.3-x Starts/hour > set 04

NOTE: AL.W.01 is enabled to detect at the starting of the system once the pressure
overcomes the start setting (auto reset).
In case of AL.W.2 (time-keeper failure) the alarms report slash instead of date and time.

Rev. 0.5 – 24.05.2012 Page 17


9 – GSM UNIT
9 – GSM Unit
Select and confirm “GSM Unit” to visualize the label where
you have to select and confirm ON for GSM setting. GSM = OFF – ON

Code Meaning Setting Notes


1 Company 000000000 Set the company title where the controller is installed: 15
Title alphanumerical characters
2 GSM 000000000 SIM number into GSM module
3 N° PIN 0000 In case pin code is not enabled leave 0000 (see PIN alarm )
4 SMS Dest. 1 000000000 Phone number of the 1st mobile to send SMS
5 SMS Dest. 2 000000000 Phone number of the 2nd mobile to send SMS
6 SMS Dest. 3 000000000 Phone number of the 3rd mobile to send SMS

NOTE:
GSM set ON
When an alarm is detected by the controller, the GSM will send an SMS to the cell phones set
with the following information:
Company title – Logik 103 – numbers of compressors set – alarm codes detected.
By sending an SMS from any cell phone to the GSM module with word “STATUS” (it doesn’t
matter capital letter or note), the GSM will reply automatically with the message “NO
ALARMS”, in case of no alarm detected or related codes in case of alarm detection.

Symbols reported on the upper left corner of the display while GSM module is connected:
Antenna: the GSM is connected.
Net coverage: if this symbol is blinking, it means there is not net coverage so the
GSM module has to be placed in another position.
Max. distance between Logik 103 and GSM unit must be no longer than 3 meters.

It blinks in case you enter a wrong pin code: in this case quit the programming,
switch off and then switch on the controller, enter the pin code again to avoid after
3rd wrong attempt the SIM card lock and you have to enter the puk code to unlock.

It blinks when the SIM card is not in or it is not well placed.


General error: replace the GSM module.

Rev. 0.5 – 24.05.2012 Page 18


10 – RESET (Password)

In this menu you can reset the maintenance timer, working hours of each compressor, alarms
list and general (uploading factory data).
Confirm by and the display visualizes the following:

09 – Reset Confirm “Maintenance” and the display Change air filter


Maintenance visualizes the label to select the number Change oil filter
Working hours of compressor you need to reset; Change separator filter
Alarms confirm the number of the compressor Change oil
General and the display visualizes Check compressor

Select the data you need and push : the display visualizes the blinking message
“Resetting” to indicate reset is in progress. When the message stops blinking means reset is
over and the counting starts by the setting on menu 7-2.

Select and confirm “Working hours”: the display visualizes the label to select the number of
compressor to reset; select the data you need and push : the display visualizes the blinking
message “Resetting” to indicate reset is in progress. When the message stops blinking
means reset is over.

Select and confirm “Alarms”, push and the display visualizes the blinking message
“Resetting” to indicate reset is in progress. When the message stops blinking means reset is
over.

Select and confirm “General”, (operation enabled when the controller is OFF only)
push and the display visualizes the blinking message “Resetting” to indicate reset is in
progress. When the message stops blinking means reset is over and the controller has loaded
all factory values by losing counting in progress and alarms.

COMPRESSOR SHUT-DOWN

In case of shut-down alarm, the controller stops the compressor and the display visualizes
“SHUT-DOWN” with related code alarm. Once the cause has been solved push to put the
controller in OFF status.

DISPOSAL

Logik 103 is composed by plastic, cables, printed circuit and electrical components; for this
reason it has not to be disposal in the environment.
For a right disposal ask for specialized companies.

Rev. 0.5 – 24.05.2012 Page 19


WARRANTY

Logik 103 controller is covered by a 24-months warranty against all manufacturing defects as
from the production date printed on the label of the device identifying the year by the first 4
characters, the week by the second 2 characters and the progressive serial number with
the last 5 characters.

In the event of a defect the controller must be appropriately packaged and sent to our factory
after asked for proper authorization number to our offices.

Customers are entitled to have defective products repaired, spare parts and labour included.
Transport expenses and risk shall be met entirely by the Customer.
Repairs carried out under warranty do not prolong or renew the warranty expiration date.

The Warranty does not cover the following cases:


- Damages resulting from tampering, impact or improper installation.
- Damages caused by repairs made by unauthorized personnel.
In all above cases repair costs shall be charged fully to the Customer.

Logika Control cannot be held liable for any direct or indirect damages to animals, people or
things as a result of failure to observe all the instructions/information in the user manual,
especially instructions concerning installation, use and maintenance of the device.

For all matters not expressly indicated, the warranty is subject to the regulations contained in
the Italian Civil Code art. 1512.

The competent court for any controversies is acknowledged to be the “Foro Monza Brianza”.

Logika s.r.l. reserves the right to modify its products without prior notice as it deems
necessary without altering their main characteristics.

Each new release of Logika Control user manual replaces the previous ones.

EDITION LIST

Rev. 0: Edition
Rev. 0.1: Reworking menu flow
Rev. 0.2: Modification of electrical drawing: added serial port RS232 to connect GSM Unit.
Rev. 0.3: Upgrade through setting of “Priority set” for the operation under clock timer.
Rev. 0.4: Upgrade to GSM Unit operation.
Rev. 0.5: Upgrade to the operation of 4th unit

Rev. 0.5 – 24.05.2012 Page 20