Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1. It is required to produce an illumination of 100 lux in a factory hall 30 m by 15 m. Assume that the
maintenance factor is 0.8, coefficient of utilization is 0.4 and efficiency of lamp is 14 lm/W. Suggest
the suitable rating, the number of lamps and their possible arrangement. The sizes of the lamps
available are 100, 250, 400 and 500 W.
[40 lamps of 250 W in 5 rows]
5. A room 40 m x 15 m is to be illuminated by 1.5 m 80-W fluorescent tubes mounted 3.5 m above the
working plane on which an average illumination of 180 lux is required. Using maintenance factor of
0.8 and the utilization factor of 0.5, (a) calculate the number of tubes required, (b) sketch a suitable
layout. The 80-W fluorescent tube has an output of 4,500 lm.
[60 tubes]
6. A hall is to be provided with a lighting installation. The hall is 30- m x 20 m x 8 m (high). The
mounting height is 5 m and the required level of illumination is 110 lux. Using metal filament lamps,
determine (a) the rating of suitable lamp and (b) number of single lamp luminaries and draw their
lighting layout. Assume maintenance factor = 0.8, utilization coefficient = 0.6 and space/height ratio
= 1.
Watt: 200 300 500
Lumen/Watt: 10 12 12.3
[(a) 500 W, (b) 24 lamps,]