Sei sulla pagina 1di 87

CONTROLS & NORMAL ABNORMAL

AIR CONDITIONING 1 of 77 OVERVIEW


INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Welcome to this presentation


covering the Air Conditioning
system on A320 Series
aircraft.
Like the majority of the aircraft
systems, the air conditioning
system is fully automated and
requires minimal attention.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 2 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Two computers carry out the


air conditioning system Sensors and Controls
automation.
These computers are referred
to as air conditioning system
controllers.
They receive inputs from
aircraft sensors and cockpit
and cabin controls to maintain
the desired temperature
throughout the aircraft.
LANE 1 LANE 2 LANE 1 LANE 2
They then issue instructions to
various valves and their
respective pack.

Each controller has two


independent channels to
provide redundancy.
They are referred to as lanes.
One lane is active, the other PACK 1 PACK 2
lane is available as a backup.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 3 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

A320 Series aircraft are


equipped with two air
conditioning packs located in
the belly, just forward of the
main landing gear bay.

NOTE: It is a little known


fact that PACK is an
acronym for Pneumatic
Air Conditioning Kit.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 4 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Each air conditioning system


controller is responsible for its
associated pack.
We will primarily cover only
those elements of the packs
that you can control or
monitor.
LANE 1 LANE 2

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 5 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


We will start with the pack flow
control valves. Hot bleed air Pack Bypass
from the pneumatic system Pack Flow Valve

enters each pack via these Control Valve


Temp
valves. These valves adjust Compressor
Bleed To Mixing
the rate of air flow through the Primary
Air Turbine Unit
packs. Temp
Heat Temp
Main
Exchanger Heat
These valves are normally
controlled by the respective Exchanger
air conditioning system
controller but can also be Pack Air Pack Air
controlled by the crew. Inlet
Outlet

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 6 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


After the bleed air passes
through the pack flow control Pack Bypass
valve it enters the primary Pack Flow Valve

heat exchanger. Control Valve


Temp
Compressor
The heat exchanger uses Bleed To Mixing
ambient air to cool the bleed Air Primary Turbine Unit
air. Temp Temp
Heat
Main
Exchanger Heat
Exchanger

Pack Air Pack Air


Inlet
Outlet

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 7 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


The air conditioning system
controllers control the pack Pack Bypass
outlet temperature by Pack Flow Valve

modulating the pack air inlets Control Valve


Temp
on the belly of the aircraft. Compressor
Bleed To Mixing
This adjusts the amount of Air Primary Turbine Unit
ambient air flowing through Temp Temp
Heat
the pack heat exchangers. Main
Exchanger Heat
The ambient air is expelled Exchanger
through the outlet located
further aft on the belly of the Pack Air Pack Air
aircraft. Inlet
The crew can neither monitor Outlet
nor directly control the inlets
or outlets from the cockpit.
To avoid ingestion of foreign
objects, the inlets and outlets
automatically close during
takeoff and landing.

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 8 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The cooled bleed air then


Pack 1 Anti-Ice Valve
enters a compressor where it
is compressed and the Pack Bypass
Valve
temperature increases. Pack Flow
Control Valve
The air is cooled again in the Compressor
Temp
main heat exchanger and Bleed To Mixing
enters the turbine section Air Primary Turbine Unit
Temp
where it is allowed to expand, Heat Temp
cooling the air even further. Main
Exchanger Heat
The energy extracted by the Exchanger
expansion is transmitted by a
shaft to spin the compressor. Pack Air Pack Air
Inlet
The removal of heat during
Outlet
this process reduces the
temperature of the air,
resulting in a very low pack
outlet temperature.
A ground cooling fan mounted
on the turbine shaft ensures
air flow through the heat
exchangers when ram air flow
is not sufficient (e.g., ground
operations).
LANE 1 LANE 2
It is not depicted here and this
is the last time it will be
mentioned.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 9 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


The compressor and turbine
are sometimes referred to Pack Bypass
collectively as the Air Cycle Pack Flow Valve

Machine (ACM). Control Valve


Temp
Compressor
Bleed To Mixing
Air Primary Turbine Unit
Temp Temp
Heat
Main
Exchanger Heat
Exchanger

Pack Air Pack Air


Inlet Air Cycle Machine
Outlet

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 10 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


A key tool used by each
controller to control the output Pack Bypass
Valve
temperature of each pack is Pack Flow
Control Valve
the bypass valve. Temp
Compressor
The more warm air that this Bleed To Mixing
valve allows to flow around Air Primary Turbine Unit
Temp
the air cycle machine, the Heat Temp
warmer the pack outlet Main
Exchanger Heat
temperature will be.
Exchanger

Pack Air Pack Air


Inlet
Outlet

LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 11 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The BLEED page can be used


to monitor the operation of key
components of the pack.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 12 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


The position of the pack flow
control valve and the flow rate Pack Bypass
Valve
are depicted. Pack Flow
Control Valve
Even though the valve Compressor
Temp
modulates as necessary to Bleed To Mixing
provide the appropriate flow, Air Primary Turbine Unit
Temp
the valve is either depicted as Heat Temp
open, closed, or in transit. Main
Exchanger Heat
Exchanger
Because it is the area most
prone to overheat, the pack Pack Air Pack Air
compressor outlet Inlet
temperature is also displayed. Outlet

Pack Flow

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 13 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 Anti-Ice Valve


Pack bypass valve position is
displayed. This valve is Pack Bypass
Valve
commonly misunderstood. Pack Flow
Control Valve
Basically, if it is cold outside Temp
Compressor
and a warm cabin is selected, Bleed To Mixing
the valve moves to the open Air Primary Turbine Unit
Temp
position (H – hot) to allow Heat Temp
some of the warm (not hot) Main
Exchanger Heat
bleed air to bypass some of
the cooling cycle. Exchanger

If it is hot outside and a cool Pack Air Pack Air


cabin is selected, the valve Inlet
moves to the closed position Outlet
(C – cold) to allow the
maximum amount of air to be
cooled by the pack.

And finally, the pack outlet


temperature is also displayed
on the BLEED page.
This is the temperature of the
air as it exits the pack.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 14 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now that you are familiar with


basic pack operation, we will
discuss how the air is used.
Conditioned air from the
packs is provided to a mixing
unit.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 15 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The mixing unit in turn feeds


three separate aircraft zones:
the cockpit, the forward cabin,
and the aft cabin.

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 16 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The air conditioning system


controllers monitor the
temperatures in the three
zones and use this
information to control the
outlet temperature of the
packs.
The controllers determine the
coldest required zone
temperature and command
both packs to provide air that
is that temperature.

LANE 1 LANE 2 LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 17 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Because the packs produce


the coldest air required, the
controllers must use another
tool to control the temperature
in the three zones. TRIM TRIM TRIM
Hot air is tapped directly from
the pneumatic system and
routed through a hot air
pressure regulating valve.
HOT AIR
PRESSURE
This hot air is then provided to
three trim air valves that are REGULATING
also controlled by the air VALVE
conditioning system controllers.
The trim air valves open and
close as necessary to warm the
cold pack air to reach the
desired temperature in each
zone.

LANE 1 LANE 2 LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 18 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The system also incorporates


two cabin fans. They provide
recirculation airflow from the
cabin back to the mixing unit.
This reduces the bleed air
demand through the packs
resulting in fuel savings.

An emergency ram air inlet is


located on the belly of the
aircraft. It can be used to
direct external air directly into
the mixing unit.
It may be used for cabin
ventilation if both packs fail or
to assist in clearing cabin
smoke.
Now that you are familiar with
the basic design of the air
conditioning system we will
move on to the controls and
indicators. LANE 1 LANE 2 LANE 1 LANE 2

EXIT TO
SECTION - OVERVIEW MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 19 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Air conditioning system


indications are provided on
four different ECAM pages.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 20 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

On the CRUISE page the


temperature in each of the
three zones is displayed in
degrees Fahrenheit.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 21 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

On the CAB PRESS page the


packs are represented at the
bottom of the page.
They are normally shown in
green and white.

If a pack flow control valve is


closed and the associated
engine is running, the
respective pack is displayed in
amber.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 22 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now we move on to the


BLEED page where there is
much more to talk about.

The lower half of this page is


dedicated to the pneumatic .
system and is discussed in
the Pneumatics lesson.
Indications for the packs,
mixing unit, aircraft zones,
and ram air inlet are displayed
on the upper half.
Let’s take a closer look.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 23 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Both packs are shown. We’ll


take a closer look at them.

PACK 1 PACK 2

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 24 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The pack flow control valve


and pack bypass valve are
displayed at the bottom of the
pack.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 25 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

If the valve is normally closed,


it is depicted cross-line green.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 26 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

If the valve is closed but its


position disagrees with the
commanded position, it is
depicted cross-line amber.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 27 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

If the valve is normally open, it


is depicted in-line green.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 28 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

If the valve is open but its


position disagrees with the
commanded position, it is
depicted in-line amber.
This valve is unique amongst
air related valves in that the
ECAM also shows the amount
that a pack flow control valve
is open using the pack flow
indicator.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 29 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The pack flow indicator is


depicted on the BLEED page
as you see here.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 30 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The digital pack compressor


outlet temperature readout is
normally green.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 31 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

It changes to amber if the


pack compressor outlet
temperature is excessive.
An ECAM message would
also be displayed.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 32 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

You can monitor the operation


of the bypass valve. This
needle is always green.
If the needle is more to the
left, the valve is more closed
resulting in colder pack
output.
The more to the right the more
open the valve, allowing more
hot air to bypass the air cycle
machine resulting in hotter
pack output.
Just remember C for cold and
H for hot.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 33 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The digital readout of the pack


outlet temperature is normally
green.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 34 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

It changes to amber if pack


outlet temperature is
excessive.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 35 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The mixing unit and the three


zones are depicted at the top
of the BLEED page.
They are normally green.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 36 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The mixing unit is displayed in


amber if both pack flow
control valves and the ram air
inlet are closed.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 37 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The ram air inlet is also


depicted on the BLEED page.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 38 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The various possible RAM


AIR valve indications are
displayed here.
Even if the inlet is open and in
agreement with switch
position it is displayed in
amber.
This highlights the fact that a
deployed ram air inlet is not a
normal aircraft configuration.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 39 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The lower half of the COND


page displays information
relating to the cargo hold
ventilation.
It is discussed in the
Ventilation lesson.
The upper half of the COND
page displays the hot air
pressure regulating valve, trim
air valves, zone duct inlet
temperatures, and zone
temperatures.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 40 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The hot air pressure


regulating valve is labeled
HOT AIR.
It can be displayed in the
various ways you see here.
The valve is displayed in
amber when selected closed
by the crew.
Although it is in agreement
with switch position, it remains
amber to highlight that this is
an abnormal configuration.

NORMAL OPEN, DISAGREES


OPEN WITH CONTROLLED
POSITION

NORMAL FULLY CLOSED, DISAGREES


FULLY WITH CONTROLLED POSITION
CLOSED OR SELECTED OFF BY PILOT

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 41 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The trim air valves are depicted


to the left of the HOT AIR
valve.
Let’s assume the crew has set
the controls for 70° in the
cockpit and 72° in the forward
and aft cabin.
The packs will provide 70° air
because that is the coldest
temperature requested.
The trim air valves add hot air
to increase the temperature as
necessary. Closed. Only cold pack air Partially open. Adding hot air to cold
is directed to the cockpit. pack air to warm the aft cabin.
In this example, the FWD and
AFT trim air valves are partially
open to warm the respective
zones to 72°F.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 42 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The COND page also displays


the zone duct temperature.
This is the temperature of the
air as it enters the zone.
The COND page also displays
the actual temperature in each
zone.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 43 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Zone inlet duct temperatures


are normally shown in green.

They change to amber if the


zone inlet duct temp exceeds
a preset limit.

The actual temperature in


each zone is always displayed
in green.

FAN is displayed if the


respective recirculation fails.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 44 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

We now move on to the


overhead AIR COND panel.

Most of the controls on the


bottom of the panel are
associated with the pneumatic
system and are discussed in
the Pneumatic lesson.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 45 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The guarded RAM AIR pb is


used to open the ram air inlet.
Advance to open the ram air
inlet.

The ram air valve will be


discussed in more detail in the
ABNORMAL OPERATION
section.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 46 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The PACK 1 and PACK 2 pbs


control the associated pack
flow control valve.
Advance to select pack 1
OFF.
Pack 1 is now OFF and the
valve is indicated closed.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 47 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The FAULT light in a PACK


pb illuminates if any of the
following occur:
• Pack flow control valve
position disagrees with the
commanded position.
• A pack compressor overheat
is detected.
• A pack outlet temperature
overheat is detected.
The valve closes automatically
if an overheat is detected.
In this example, a pack
compressor overheat has
been detected.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 48 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The PACK flow selector


allows the crew to select a
desired pack flow.
Three settings are available:
LO = 80% of normal flow
NORM = normal flow
HI = 120% of normal flow
This information is provided to
the air conditioning system
controllers, not directly to the
pack flow control valves.
We will look at the use of this
selector in more detail in the
NORMAL OPERATION
section.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 49 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The three zone temperature


selectors are used to adjust the
desired temperature in the
respective zone.
For reference only:
COLD = 64°F
12 o’clock = 76°F
HOT = 86°F
This information is provided to
the air conditioning system
controllers, not directly to the
trim air valves.
Individual cabin zone
temperatures can be adjusted
via the forward attendant panel
+/-5°F from the cockpit
selected temperatures.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 50 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The hot air pressure


regulating valve may be
closed using the HOT AIR pb.
Advance to see an example.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 51 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The hot air pressure


regulating valve is now
closed.
This causes all the trim air
valves to also close, thus
limiting the ability of the
controllers to adjust the
temperature in the zones.
The HOT AIR pb should only
be used when directed by a
specific procedure.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 52 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The FAULT light in the HOT


AIR pb illuminates if a duct
overheat is detected.
If that occurs, the valve closes
automatically, causing the trim
air valves to also close.
One of the ECAM steps would
be to select the pb OFF.
Advance to select the HOT
AIR pb OFF.

With the pb selected OFF, the


FAULT light extinguishes
when the overheat condition
no longer exists.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 53 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The last air conditioning


control we will discuss is on
the VENTLATION panel. OFF

The CAB FANS pb can be


used to control the
recirculation fans.
The cabin fans run any time
AC power is established.
Advance to select the CAB
FANS pb OFF.

Both recirculation fans have


stopped and are displayed in
amber on the COND page.
This completes the CONTOLS
& INDICATORS section.

EXIT TO
SECTION - CONTROLS & INDICATORS MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 54 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

You have just arrived at the


aircraft. The APU is running
and powering the aircraft.
APU bleed air is not being
used.
During the preflight of the
overhead panel it is normal to
see the FAULT lights in the
PACK pbs illuminated.
This is because the pack flow
control valves are closed due
to lack of air flow.
That is currently the case
since the engines are not
running and APU bleed is not
being used.

You should also see lights out


on the VENTILATION panel
during the preflight.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 55 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now let’s provide some air to


the packs.
You wouldn’t normally do this,
but we will display the BLEED
page for academic purposes.
Notice that both pack flow
control valves are closed due
to the lack of air.
Advance to select the APU
BLEED pb ON.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 56 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The APU bleed valve opens


and immediately supplies the
left side of the system.

Normally, after a brief delay,


the crossbleed valve would
open automatically to provide
air to the right side of the
system.

We have stopped the process


here to point out a few things.
Pack 1 is now operating and
the FAULT light in the PACK 1
pb has extinguished.
The mixing unit changes from
amber to green.
Advance to observe the right
side being supplied.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 57 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The crossbleed valve is now


open.
Pack 2 is operating.

Notice that both packs are


providing high flow, even
though the PACK FLOW
selector is in the NORM
position.
The air conditioning system
controllers automatically
command high flow when only
APU bleed air is being used or
if operating on one pack,
regardless of PACK FLOW
selector position.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 58 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

We will now display the COND


page and discuss how the
system controls the
temperature in the zones.
Current temperature
throughout the aircraft is 65°F.

The requested temperature is


76°F in all three zones with
the zone temperature
selectors in the twelve o’clock
position.
The air conditioning system
controllers react to this
situation by opening the trim
air valves to provide warmer
air to the zones.

In this example, the cockpit


has reached the desired
temperature first and the trim
air valve has partially closed
to reduce the amount of hot
air added to the pack flow.
Trim air valve operation will
continue in this manner to
maintain the desired
temperatures.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 59 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

We now move on to starting


the engines, reminding you
again that the BLEED page
would not normally be
displayed.
Advance to rotate the ENG
MODE selector to the
IGN/START position.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 60 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

When the engine mode


selector is rotated to
IGN/START, the pack flow
control valves close.
This ensures all APU bleed air
is available for engine start.
If an engine is not started
within approximately thirty
seconds, the pack flow control
valves will reopen.
They will close again when an
engine master switch is
selected ON.
Advance to start engine 2.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 61 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now let’s start engine 1.

When engine start is


complete, the pack flow
control valves open and the
APU bleed air supplies the
packs.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 62 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Using APU bleed air during


takeoff increases takeoff
performance because engine
bleed air is not being used to
operate the packs.

Normally, the APU is shut


down shortly after engine
start.
Advance to select the APU
BLEED pb OFF and shut
down the APU.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 63 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The engines bleed valves


open automatically.
The engines will provide bleed
air to the packs for the
remainder of the flight,
assuming no malfunctions
occur.
Notice that pack flow is
reduced now that the engines
are providing air to the packs.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 64 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

On flights with low passenger


counts, the PACK FLOW
selector may be set to LO.
This reduces engine bleed
demand and conserves fuel.

With a high passenger count


and high ambient temperature
it may be necessary to select
HI flow and COLD zone
temperatures.
More fuel will be used. Return
to the selector to NORM as
soon as possible.
Refer to your aircraft manuals
for specific procedures.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 65 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

We have completed our flight


and are about to leave the
aircraft.
To conserve fuel, the APU
has been shut down.
To maintain a comfortable
cabin temperature in
preparation for the next flight
the ground crew has
connected an external air
conditioning unit.
It is connected via a low
pressure connection point on
the underside of the aircraft.
Air is provided directly to the
mixing unit and then into the
three zones.
There are no direct indications
in the cockpit of whether or
not external conditioned air is
connected.
This completes the NORMAL
OPERATION section of this
lesson.

EXIT TO
SECTION - NORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 66 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now let’s take a look at some


air conditioning system
abnormals.

Anti-Ice Valve

Pack Bypass
Pack Flow Valve
Control Valve
Temp
Compressor

Primary Turbine
Temp Temp
Heat
Main
Exchanger Heat
Exchanger

Pack Air
Inlet

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 67 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

A pack 1 overheat has been


detected.
We have cancelled the
MASTER CAUT lights for you.
The BLEED page is displayed
automatically.
The pack compressor outlet
temperature is displayed in
amber.

The pack 1 flow control valve


closed automatically. It is
displayed in amber because
its position disagrees with the
switch position.

Pack 2 goes to high flow with


only one pack operating.
The first ECAM step is to
select the PACK 1 pb OFF.
Advance to perform that step.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 68 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Now the valve and switch


positions agree, so the valve
is displayed in green.
The OFF light in the PACK 1
pb is now illuminated.
The FAULT light remains
illuminated as long as the
overheat condition exists.
The ECAM procedure
includes a white condition
statement informing you know
that you may attempt to
operate the pack when the
overheat subsides.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 69 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The FAULT light has


extinguished.
The temperature indication on
the BLEED page is now
displayed in green.
Advance to select the PACK 1
pb ON.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 70 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Pack 1 is now operating.


The ECAM message is no
longer displayed and the
CRUISE page has replaced
the BLEED page.
If the overheat returns, it may
be necessary to discontinue
operating the pack.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 71 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Remember that the air


conditioning system controllers
are equipped with two
channels, referred to as lanes.
If one lane fails, it has no
impact on system operation.
The other lane can provide all
necessary functions.
Advance to fail lane 2 and
watch what happens.
HOT AIR
If both lanes of the same PRESSURE
controller fail, the associated
REGULATING
pack is lost and the hot air
pressure regulating valve VALVE
closes automatically.
This results in the trim air
valves also closing.
Temperature regulation is
degraded and is now
performed by the remaining AIR PACK 1 FAULT
controller by adjusting the flow
and outlet temperature of the
remaining pack.
That concludes the LANE 1 LANE 2
ABNORMAL OPERATION
section.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 72 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

In this example, pack 1 and 2


have failed.
The ECAM directs you to
select the packs OFF.
Advance to select the PACK 1
and 2 pbs OFF.
If you haven’t already, you
should initiate a descent.
Let’s assume ΔP is less than
+1.0psi.
Advance to select the RAM
AIR pb ON.

External air is now directed to


AIR PACK 1 + 2 FAULT
the mixing unit for cabin
PACK 1DIFF
WHEN . . . .PR
. . .<1PSI
. . . . . AND
. . . . .FL
. . <100:
. . OFF
ventilation.
PACKFL
RAM
MAX AIR
2 . . . . . . . . . . . . . . . . . .100/MEA
. . . OFF
. ON
Selecting the RAM AIR pb ON WHEN
MAX FLDIFF
. . . .PR
. . .<1PSI
. . . . . AND
. . . . FL
. 100/MEA
<100:
sends a signal to the outflow RAM AIR . . . . . . . . . . . . . . . . . . . . . ON
valve and the ram air valve to MAX FL . . . . . . . . . . . . . . . . . 100/MEA
open if ΔP is less than
+1.0psi.
If ΔP is greater than +1.0psi, NOTE: The ram air valve will not open if the DITCHING
neither valve will open. pb is selected ON. The outflow valve will not open if
the MODE SEL pb is selected to MAN.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 73 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Let’s look at some of the air


conditioning system
differences.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 74 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Some A321s have a zone


controller that oversees the Sensors and Controls
operation of the air conditioning
system.
Sensors and controls provide
Sensors and Controls
inputs to the zone controller
which sends signals to pack
controllers. PRIMARY SECONDARY
CHANNEL CHANNEL
The pack controllers then send
signals to their respective pack.
Newer aircraft have air
conditioning system controllers. LANE 1 LANE 2 LANE 1 LANE 2
Aircraft with a zone controller
do not have cabin temperature
controls on the forward
PRIMARY SECONDARY PRIMARY SECONDARY
attendant panel. CHANNEL CHANNEL CHANNEL CHANNEL

PACK 1 PACK 2

PACK 1 PACK 2

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 75 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The zone controller has two


channels, a primary and a Sensors and Controls
secondary.
The primary channel controls
the air conditioning system.
The secondary channel
provides some control if the PRIMARY SECONDARY
primary channel fails and also CHANNEL CHANNEL
provides temperature
indications on the COND page

PRIMARY SECONDARY PRIMARY SECONDARY


CHANNEL CHANNEL CHANNEL CHANNEL

PACK 1 PACK 2

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 76 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The pack controllers also


have two channels, a primary Sensors and Controls
and a secondary.

The primary channel controls


its respective pack.
The secondary channel
provides some control if the PRIMARY SECONDARY
primary channel fails and also CHANNEL CHANNEL
provides indications on the
BLEED page.

PRIMARY SECONDARY PRIMARY SECONDARY


CHANNEL CHANNEL CHANNEL CHANNEL

PACK 1 PACK 2

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING 77 of 77 OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Some A321s
Instead of a PACK FLOW
ECON FLOW
selector, some A321s have an
ECON FLOW pb.

Selecting the pb ON may


reduce pack flow up to 20%.

On all aircraft, the air


conditioning system will
command a higher flow than
that selected by the crew if it is
necessary for system
operation.

For example, in single pack


operations the remaining pack
A319, A320 and some A321s
will go to high flow regardless
of switch position.

EXIT TO
SECTION - ABNORMAL OPERATION MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The temperature of each aircraft zone


is optimized using….. ?

A HOT AIR valve.

A ZONE control valve.

A PACK FLOW valve.

A TRIM AIR valve.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The temperature of each aircraft zone


is optimized using….. ?

A HOT AIR valve.

A ZONE control valve.

A PACK FLOW valve.

A TRIM AIR valve.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Under what conditions should the


PACK FLOW selector be moved to the
LO position?

With a low passenger load to reduce


bleed air demand and improve fuel
efficiency.

With a low passenger load to increase


cabin temperature.

With a high passenger load to reduce


cabin temperature.

In cold conditions to achieve a higher


cabin temperature range.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Under what conditions should the


PACK FLOW selector be moved to the
LO position?

With a low passenger load to reduce


bleed air demand and improve fuel
efficiency.

With a low passenger load to increase


cabin temperature.

With a high passenger load to reduce


cabin temperature.

In cold conditions to achieve a higher


cabin temperature range.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Under what conditions should the


PACK FLOW selector be moved to the
HI position?

In cold conditions to achieve a higher


cabin temperature range.

With a low passenger load to increase


cabin air flow.

With a high passenger load in hot


conditions in order to help reduce the
cabin temperature.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

Under what conditions should the


PACK FLOW selector be moved to the
HI position?

In cold conditions to achieve a higher


cabin temperature range.

With a low passenger load to increase


cabin air flow.

With a high passenger load in hot


conditions in order to help reduce the
cabin temperature.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The PACK FLOW selector is set to


NORM and yet the BLEED page
displays HI pack flow. How is this
possible?

Pack flow remains at the last setting until


engine start.

The valves are spring loaded to the full


position until engine start.

HI flow is automatically selected


regardless of PACK FLOW selector
position because air is supplied by the APU.

With cold outside air conditions, pack flow


is automatically increased to help
increase the cabin temperature.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

The PACK FLOW selector is set to


NORM and yet the BLEED page
displays HI pack flow. How is this
possible?

Pack flow remains at the last setting until


engine start.

The valves are spring loaded to the full


position until engine start.

HI flow is automatically selected


regardless of PACK FLOW selector
position because air is supplied by the APU.

With cold outside air conditions, pack flow


is automatically increased to help
increase the cabin temperature.

EXIT TO
SECTION - QUIZ MAIN MENU
CONTROLS & NORMAL ABNORMAL
AIR CONDITIONING OVERVIEW
INDICATORS OPERATION OPERATION
DIFFERENCES QUIZ

You have completed the


Air Conditioning lesson.

Click here to
exit to the main menu.

EXIT TO
SECTION - QUIZ MAIN MENU

Potrebbero piacerti anche