Sei sulla pagina 1di 6

Active Filter Control Methods Based on Different Power Theories

Viktor Valouch
Institute of Electrical Engineering
Academy of Sciences of the Czech Republic
DolejSkova 5, (32-18202 Prague, Czech Republic
valouch @ iee.cas.cz

Abstract - A few different power theories are presented and main classes of the methods may be viewed: an analysis in
used in the control strategies of the shunt active filter in case the time or frequency domain, respectively. Both the
of the unsymmetrical supply voltage system. The time principles exhibit some lines of contact. The use of both an
responses of the currents, instantaneous powers and losses, algebraic and geometrical approach to the mathematical
obtained by the simulation, are shown and compared. foundations of the instantaneous power concepts has been
Although for the symmetrical voltage system with only the
reported. In spite of an intensive research in the field, some
fundamental harmonic different power theories provide
effectively the same results, those may differ substantially for questions still remain open or some confusions
unsymmetrical supply systems with harmonics. disseminated in papers.
The results, summarised in the table, show that the applied Apparatus for the improvement of power quality are
power theories influence substantially the basic performance mainly based on pulse width modulated (PWM) voltage-
criteria: the shapes of the supply currents, instantaneous or current-type inverters and may be used for the
powers, and losses. With regard to the purpose of the use of a compensation of hgh harmonics and/or laggng power
device for power quality improvement an appropriate control factor (active filters, power quality conditioners), as
strategy must be implemented. voltage stabilisers or power flow controllers [2]. The
voltage-type PWM inverters are preferred to current-type
I. INTRODUCTION inverters because of their better efficiency and dynamics.
The active filters are connected in parallel or series with
The power analysis in multiphase systems has belonged loads. They can be used standing alone as well as with
among the most discussed topics in power engineering for conventional passive filters in hybrid configurations.
many years. Nowadays, the huge boom of the power Together with the type of the active (hybrid) filter and its
electronics brings about the use of different non-linear internal control strategy, the way. of the generation of its
loads, for example single-phase loads, arc furnaces, diode reference voltages or currents determines main
and thyristor rectifiers, etc. These loads are often performance indexes of the filter.
characterised by dynamic or stochastic changes in the In the power flow controllers, the reference phase
consumption of energy in terms of active and reactive currents are calculated to deliver demanded active and
powers, and by the large spectrum of voltage or current reactive powers from the PWM rectifier to the mains.
high harmonics. The development of power analysis The reference phase currents for the voltage stabilisers
methods has been provoked by demands to model power are determined to stabilise the supply voltage in the
systems, measure and display consumed electrical energy, coupling point by changing the reactive component of the
filter high harmonics, and especially lately, this current produced by the stabiliser.
development has been inspired by the research of active Different modifications of the power theories have just
filters and power quality conditioners used for the been used for calculating the reference variables.
compensation of voltage and current components andor A few power theories applied to the control of a shunt
lagging power factor in the mains. active filter are reported in the paper. The function of the
Conventional power theories have been based on the active filter in case of unsymmetrical supply voltage and
ideas valid for single-phase systems and for integral load current systems with high harmonics was studied by
values, and have been gradually extended to the field of the siniulation. Although for the symmetrical voltage
three-phase systems where unsynimetrical and unbalanced system with only the fundamental harmonic different
systems must be also considered. let alone dfferences power theories provide effectively the same results, those
between three- and four-wire (generally ni- and (m+l)- may differ substantially for unsymmetrical supply systems
wire) three-phase (m-phase) systems. with harmonics.
With regard to the wide voltage and current harmonic
spectra in dynamic systems with power converters and, at 11. POWER THEORIES
the same time, with possibilities to compensate for
undesirable phenomena actively, the attention has been As a case of study, we shall consider the shunt active
recently focused on the methodology of the so-called filter depicted in Fig. 1. The active filter delivers to the
“instantaneous” powers. Questions of the so-called wattles point of coupling such a compensating current i, in order
(imaginary, reactive, non-active or passive) powers, which that the mains current i may be free of harmonics and with
increase losses and lower performance criteria of apparatus demanded power factor, no matter how shaped is the load
and distribution networks without providing loads with current iL. Power conditions may be characterised by the
active powers, are broadly discussed [I]. The aim of the values of the instantaneous active p and reaclive q power.
methods, being developed, is the effective compensation of The supply voltage as well as load current system is
the harmonics and reactive powers in places of their unsymmetrical with high liarmonics. We shall consider
sources or at coupling points of distribution networks. Two three-phase four-wire system in the simulation.

0-7803-5662-4/99/$10.00 01999 IEEE 521 ISIE’99 - Bled, Slovenia


In case of the symmetrical voltage system without high
harmonics in steady states the instantaneous power p is
equal P and instantaneous reactive power q equals Q.
The IRP theory may be also used without the three-
phase to quadrature transformation of phase voltages and
currents [4]. Using (9, the following equations may be
deduced

ACTIVE
FILTER
(7)
C
and for the so-called instantaneous complex power it holds
Fig. 1 . Circuit diagram ofthe implemenlalion of an active filter

A . Instantaneous Reactive Power (IRP) theory (Pq theory)


-Review

The phase voltages and currents may be transformed If we substitute instantaneous powers p, q in (6), (7) by
into the stationary reference frame with the axes a (real), p the common average values P, Q, we obtain dc current
(imaginary). Holding the principle of power invariance, the components
transformation matrix is as follows
(9)

The differences between ip and iP; i, and i,- respectively


are then ac (fluctuating) components
where, for a simplification, the zero-sequence component . . - &. , .1 - = 1 . - 1 -. (1 0)
is not considered. For the transformations holds P P 4 4 4

These components may be just compensated for by using


appropriate active filters. The components ip-,iQ represent
the reference current vectors, which should be followed by
In addition to the instantaneous (active) power of the 3- the actual currents (vector ic in Fig. 1). As we can observe
phase system in egs. (6), (7), (9), (lo), both instantaneous powers p , q of
p = v , i , +v,i, +v,ic =v,i, +vaia =Re{vi*} p=p-P,q =q-Q
- (11)
(3)
the load and their average values P, Q must be calculated.
where v, i are space vectors, the instantaneous reactive Instead of using (lo), the components
power was introduced may be calculated and then ip', i,l directly determined by
similar relations as (6), (7).
q = -v,ig +v,i, = Im{vi *> (4) It is evident that in case of the symmetrical voltage
system of only fundamental harmonics, we can derive from
Contrary to [3], we define that q is positive for the lagging (6),(7) the phase currents
current. The implementation of the instantaneous power po
= voioof the zero-sequence components into the IRP theory
is quite easy [3].
On the ground of egs. (3), (4), currents i,, i p may be
expressed in the form 4
,i (t)= -v (t - 72/24 ) (13)

;:[=I I,:: [;I= -1 ly12


and by the same way the equations for other phases or
components according to (9), (10).
If the reactive power Q of the load should be also
compensated for, not only i; (4-), but the total current i,(q)
must be injected by the filter into the point of coupling.
The IRP theory has been widely used in many
where ,i iap are instantaneous active components of i,, i p applications. Nevertheless, if the supply voltage system is
while ,i ips are instantaneous reactive (passive) unsymmetrical, the use of the IRP concept leads to that the
components. mains current become non-sinusoidal in spite of the

522
compensation of p-, q-. Therefore some modifications or The equal current SD (CSD) method is based on the
extensions of the IRP have been searched for to overcome assumption that all supply phase currents after
this disadvantage. compensation should be equal in amplitudes Iam=Ibm=
=I,= I,. For demanded compensated supply currents the
B. ModGed IRP theories following relations may be derived
P
A possible extension of the IRP theory has been i, (t)= -vu (t), I , = &P / V,
suggested in [ 5 ] , [6]. It is based on a different definition of VTa‘
P
4 ib (t)= -v, (t)
VT Vb
q = v,’i, +vb’ib+ v,’i, = (vaf- vc’)i,+ (v,’ - vc’)ib (14) P
i, (t)= -v, (t)
T‘ ‘c
where v,’, vb’, v,’ lag v,, vb, v, respectively by 90 degrees.
If the instantaneous power p is also expressed through where V, = V, + Vb + V, is the sum of the RMS values of
phase currents and line-to-line voltages, the reference the phase voltages.
compensating currents may be expressed, contrary to the In case of the equal resistance SD (RSD) method, the
paragraph A, directly in phase quantities without any amplitudes of the compensated phase currents will be Imj=
transformation
=42PV, /(V: + V: + V:), j = a, b, c instead of those in
(18).
The reference compensating currents are determined as
follows
j = a,b,c
ijc(t)=iJL(t)-ij(t), (1 9)
D’= (v, - v, [v,’ - vc’) - (vat- v.’) (v, - v,)
It is evident that in addition to the calculation 01 the
It is proved in [6] that both the theories IRP, 161 give the average value P of the load consumption, the RMS (or
same results if the following relations hold maximum) values of the supply phase voltages must be
detected. Note that i, + ib + i, f 0 if the voltage system is
not symmetrical (vu+ vb + v, f 0), so the zero-sequence
(16) current component io exists, which restricts the use of the
SD methods to four-wire systems.
which is true only in symmetrical voltage systems. Thus, The CSD method presented in [7] can be modified to be
the IRP theory may be viewed as a particular case of this applicable also in three-phase three-wire systems. The
extended theory. The use of the extended pq theory (15) modification is based on the additional two assumptions
preserves the sinusoidal supply currents also in (besides lorn = l b m = I , = Im): i) the phase currents are
unsymmetrical voltage systems. Also the extended p q sinusoidal, ii) the angles among all three currents amount
theory may be applied in three-phase four-wire systems. to 120 degrees. In addition to that, let us admit llial a
If the original IRP theory is used and we need to preserve certain angle (pl between the current i and the positive-
the supply currents sinusoidal also in unsymmetrical sequence symmetrical voltage v1 is possible, not to say
systems, another option is viable. The reference even demanded. Instead of (18) the following equations
compensating currents i;, i; (and corresponding phase hold
ones) may be calculated as follows

where the positive-sequence symmetrical component vI is


i, (t)= -io (t)- i, (t)
used instead of the whole supply voltage v as in (6), (10).

C. Synchronous Detection (SO) methods Note that as a pilot for the demanded compensated current
system serves the original phase voltage vu.Nevertheless,
the amplitude VI of the positive-sequence voltage system
The SD method has been recently developed to
must be calculated for the determination of V,
overcome disadvantages of the original IRP theory if it is
If the time courses of the compensated currents are to
applied to unsymmetrical voltage systems 171. Three
be derived exactly from the positive-sequence voltage
different strateges have been formulated: equal power SD
system, which is the case of very unsymmetrical voltage
(PSD) method, equal current SD (CSD) method and equal
systems, the smtegy (20) must be modified as follows
resistance SD (RSD) method. It was found that the RSD
results in minimum supply line losses, although for most i,(t)= &qJ(t -pi /mi), j = a,b,c ( 21)
conditions, the use of the RSD and CSD methods results in VI
very close line losses. All the methods are intended for where vI,,j = a, b, c are the time responses of the phase
four-wiresystems to achieve the sinusoidal supply currents voltages of the positive-sequence system, which must be
(if voltages are sinusoidal), in phase with supply voltages. estimated now. The strategy (21) is the same as that

523
described in the vector notation (9), while the voltage v is (vu = 200 v,
= 0'; v b = 220 v , (pb = 140"; v,= 210 v,
(po
substituted by vl as in (17) for the compensating currents. cpc = -135'). At the time 0.22 s of the simulation the
The reference compensating currents for (20) or (21) are reference angle (pl is changed from 0" to 45O, and at the
again calculated by (19). time 0.26 s the 5* and 7* harmonics are imposed on the
supply voltages. The instants of the changes are indicated
111. SIMULATION AND RESULTS by the symbol V. Also the load currents involve the 3d, 5*
and 7' harmonics and are not symmetrical (35A, 0"; 45A,
Figs. 2 - 6 show the time responses of the main 110"; 25A, 130" for the fundamental harmonics). The
variables of the system in Fig. 1: the supply phase voltages losses are calculated for the resistance Rs = 0.02 0 of the
and currents, instantaneous powers p, q and Joule losses dp feeding line.
in the individual phases and their total values, the The Czarnecki's concept of the Running Values [SI is
trajectories of the vectors of filtered supply voltages v and used for the calculation of the positive-sequence voltage
currents i as well as of the compensating currents io The symmetrical components and average values P, Q of p, q.
following strategies are considered: i) the IRP theory (9) - In addition to the compensation of the load current
(10); ii) the extended IRP theory (15); iii) the modification harmonics, the consumption of 5000 W from the dc side of
(17) based on the IRP theory; iv) the RSD method the P W M inverter is assumed. The effects of the P W are
(modified (18) and (19); v) the modification (20) of the not considered in the figures: all actual currents are
CSD method (for the three-wire system). supposed to be same as the related references.
The supply voltage system is supposed unsymmetrical

..................................................

Fig. 2. The IRP-theory (9)-(IO)is used in the control strategy ofthe active filter.

- II _-.I
1

wa. 750 300 . 130 . '00 _...__.- 3

............

m.n.0 -,oo '-3.0 ' -3.30

524
01
.......................... 1

!
........................

- ...............

Fig. 4. The modification (17) ofthe IRP theory is used in the control strategy.
.I- .................

.......... .......... ..........

Fig. 5 . The RSD method (modified (18 and (19)) is used in the control strategy.

............. ..............

I , .
"In. - 7 3 o P :

525
TABLE I
COMPARISON OF THE USE OF DIFFERENT POWER THEORIES IN THE SHUNT ACTIVE FILTER
(UNSYMMETRICAL SUPPLY VOLTAGE SYSTEM)

Supply phase
Criteria Phe q/inc

Method

ii) EIRP 1 no I yes I const


I Yes higher higher
I I I
---------It
no lower

~~)RSD
I
I no
I
I yes
I
I var 1I const Yes lower lower

Yes * *

* the items can not be compared with those above because ofthree-wire system considered here (without zero-sequence load currents)

Tab. 1 summarizes the results in terms of the shapes of REFERENCES


the supply currents (symmetrical, sinusoidal) and
insvtaneous powers p, q (constant, variable for constant Depenbrock, M., Marshall, D.A., van Wyk, J.D.: Formulating
Requirements for a Universally Applicable Power Theory as
P, Q of the load), and the display of supply voltage high Control Algorithm in Power Compensators. ETEP Vo1.4, No.6,
harmonics in the phase currents. The average total Joule 1994,445-455.
losses dplincas well as the peak values of i, are compared Akagi, H.: New Trends in Active Filters for Power Conditioning.
IEEE Transactions on 1A-32, No.6, 1996, 1312-1322.
(hgher or lower) with those for the I W theory as Akagi, H., Nabae, A.: The p-q Theory in Three-phase Systems
references. In case of symmetrical voltage systems all the under Non-Sinusoidal Conditions. ETEP Vo1.3, No. 1, 1993,27-31.
methods yield the same results. Rossetto, L., Tenti, P.: Using AC-fed PWM Converters as
Instantaneous Reactive Power Compensators. IEEE Transactions
on PE-7, No.1, 1992,224-229.
IV. CONCLUSION Komatsu, Y., Kawabata, T.: A Control Method of Active Power
Filter in Unsymmetrical Voltage System. Proc. of EPE’95, Sevilla,
A few different power theories have been presented and Spain, 1995, 1.904-1.907.
used in tlie control strategies of the shunt active filter in Komatsu, Y., Kawabata, T.: Characteristics of Three Phase Active
Power Filter Using Extension pq Theory. Proc. of ISIE’97,
case of the unsymmetrical supply voltage system. The time Guimarases, Portugal, 1997, 302-307.
responses of the currents, instantaneous powers and losses, Chen, C.L., Lin, C.E., Huang, C.L.: Reactive and Harmonic
obtained by the simulation, have been compared. Current Compensation for Unbalanced Three-phase Systems Using
The results, summarised in the table, show that the the Synchronous Detection Method. Electric Power System
Research (26), 1993, 163-170.
applied power theories influence substantially the basic Czarnecki, L.S.: Power Theory of Electrical Circuits with Quasi-
performance criteria: the shapes of the supply currents, Periodic Waveforms of Voltages and Currents. ETEP Vo1.6, No.5,
instantaneous powers, losses, etc. With regard to the 1996,321-328.
purpose of the use of a device for power quality
improvement (as an active filter, voltage stabiliser, power ACKNOWLEDGEMENT
flow controller), an appropriate control strategy must be
implemented. The work was supported by the Grant Agency of the
Academy of Sciences of the Czech Republic under contract
A 2057901.

526

Potrebbero piacerti anche