Pipe Clamps
OVERVIEW
Properties:
System MS-L
Installation
FRSH Material Steel DD11 (material no. 1.0332)
acc. to DIN EN 10111
Zinc plating Electro zinc plated, 5 - 9 µm
Connecting nut (up to FRSH 59 - 63) Resistance welded, M 8, SW 13
Locking screw Flat head screw with combination recessed head
Installation
System MS
Sound insulation insert Material: silicone
Sound insulation for DIN 4109
Temperature range -50° to +220°C
Hardness 60 ± 5° Shore A
Fire behavior DIN 4102: class B2
System FUS
Installation
Description INSTALLATION
Installation Grid
▪ Two-screw pipe clamp with high temperature resistant
sound insulation insert.
Advantages / Benefits
Sliding Elements
Fixpoint and
▪ Use for steam up to max. +220 °C.
▪ Simple installation due to large opening angle.
▪ Locking screw secured against loss.
▪ Reinforcement bead in clamp band.
Accessories
Installation System
Stainless Steel
Type Art. No. Qty. per box Max. recom. Size Clamping range Locking screw Thread Connecting nut Width x Width Height Height Height
static load height thickness clamp
(centr. tension) band
Nrecom. D A bxs B H Z Z1
pcs. [kN] [inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] Air conditioner
fixings
FRSH 15 - 19 063490 100 1.00 3/8” 15 - 19 M 5 x 20 M8 6.8 20 x 1.25 62 38 23 16
FRSH 20 - 24 063492 100 1.00 1/2” 20 - 24 M 5 x 20 M8 6.8 20 x 1.25 68 44 26 19
FRSH 25 - 30 063494 100 1.00 3/4” 25 - 30 M 5 x 20 M8 6.8 20 x 1.25 75 50 29 22
FRSH 32 - 37 063495 100 1.00 1” 32 - 37 M 5 x 20 M8 6.8 20 x 1.25 80 56 32 25
Electrical fixings
FRSH 121 - 127 063525 10 2.00 - 121 - 127 M 8 x 30 M 8 / M 10 21 25 x 2.5 192 175 85 77
FRSH 133 - 141 063537 10 2.00 5” 133 - 141 M 8 x 35 M 8 / M 10 21 25 x 2.5 198 180 88 80
FRSH 159 - 162 091507 8 2.00 - 159 - 162 M 8 x 30 M 8 / M 10 21 25 x 2.5 218 206 101 93
FRSH 165 - 168 091508 8 2.00 6” 165 - 168 M 8 x 30 M 8 / M 10 21 25 x 2.5 226 212 104 96
Plugs and