Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
*To request individual Sporlan Product Bulletins, contact your nearest Sporlan Sales Office or Wholesaler, write Parker Hannifin, Sporlan Division, Washington,
Missouri or visit our website at www.sporlan.com.
Brazed Plate
Oil Differential Heat Exchange
Pressure Valve
CO2 Condenser
Check
Oil Oil Valve
Reservoir Separator Replaceable
Catch-All
Receiver SA-
See•All
SER
RSF-
Replaceable Liquid Line
Suction Filter CDS-7
Step Motor Evaporator Solenoid Valve
Control Valve
Oil Level
Control
SEI
Suction Header
CDS-9 Liquid Line
Step Motor Evaporator Solenoid Valve
Control Valve
Receiver Replaceable
Pump Catch-All
SA-
See•All
Supply Header
Evaporators
Liquid
Solenoid Valve
Liquid
Solenoid Valve
Return Header
Note: No pressure relief or ball valves shown. Relief valves must be present where liquid CO2 can be trapped.
All components must be properly pressure rated and protected for safe installation.
CATALOG 744 — Page 3
UL Guidelines CO2
Use this table to determine the maximum start to discharge pressure relief valve setting for each component in the system. It is the system
designers responsibility to determine the correct pressure relief valve setting. The pressures listed are NOT the maximum rated pressure of
the product.
Failure or improper selection or improper use of the products described herein or related items can cause death, personal injury
and property damage.
This document and other information from Parker-Hannifin Corporation, its subsidiaries and authorized distributors provide product or system
options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is soley responsible for making the final selection of the system and components and assuring that
all performance, endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the
application, follow applicable industry standards, and follow the information concerning the products in the current product catalog and in any
other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications
provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and
reasonably forseeable uses of the components or systems.
Page 4 — CATALOG 744
Distributors CO2
All Sporlan distributors are ready for service with CO2 . The follow- 1126
ing tables are provided for making selections based on procedure
explained in Bulletin 20-10.
1651
Quick Reference
CONNECTION SIZE TYPICAL EEV DISTRIBUTOR MAXIMUM NUMBER OF CIRCUITS NOZZLE SIDE
MATERIAL
Inches TYPES TYPE 3/16 1/4 5/16 3/8 TYPE CONNECTION
1613 6 4 – – PERM. –
SER 1.5 - 20 1616 8 6 4 – PERM. –
1/2 ODM
SEI 0.5 - 11 D260 6 4 – – L –
D262 9 6 4 – L –
SER 1.5 - 20 1620 6 4 – – J –
5/8 ODM SERI G 1622 9 7 4 – J –
SEI 30 1651(R) 7 5 – – J (R) 3/8 or 1/2 ODF
#360 BRASS
SER 20 1112 7 6 4 2 G –
7/8 ODM SERI G, J 1113 12 8 6 4 G –
SEI 30, 50 1653(R) 12 9 6 4 G (R) 3/8 or 1/2 ODF
SER 20 1115 15 10 9 6 E –
1-1/8 ODM SERI J, K 1116 20 15 – – E –
SEI 30, 50 1655 (R) 20 12 10 7 E (R) 1/2 or 5/8 ODF
1117 18 15 9 7 C –
1126 24 18 15 12 C –
1-3/8 ODM SEI 50 #377 BRASS
1128 28 25 21 16 C –
1657(R) 26 18 14 11 C (R) 5/8 or 7/8 ODF #360 BRASS
Dimensions
A A
D
C B C B
Specifications
NUMBER OF NOZZLE DIMENSIONS
NOZZLE & INLET
CIRCUITS & ORIFICE
RETAINER CONNECTION DISTRIBUTOR Inches mm
TUBING SIZES NUMBERS
RING SIZE Inches
AVAILABLE AVAILABLE A B C D A B C D
Type D260 Net Weight - Approximately 2 oz. (60 g)
.497 12.6
2 to 6 3/16” 1/2 ODM 1.96 0.81 0.82 49.8 21 21
1/9 thru 8 L .503 12.8
2 to 4 1/4” Solder
Type D262 Net Weight - Approximately 3 oz. (80 g)
7 to 9 3/16” .497 12.6
1/2 ODM 2.44 1.00 0.81 62.0 25.4 21
5 to 6 1/4” 1/9 thru 8 L .503 12.8
Solder
2 to 4 5/16”
Type 1613 Net Weight - Approximately - Approximately 2 oz. (60 g)
2 to 7 5/32” .498 12.6
1/2 ODM 1.17 0.81 0.50 29.7 21 13
2 to 6 3/16” 1/2 thru 5 PERM. .500 12.7
Solder
2 to 4 1/4”
Type 1616 Net Weight - Approximately - Approximately 3 oz. (80 g)
8 to 10 5/32”
.498 12.6
7 to 8 3/16” 1/2 ODM 1.55 1.00 0.50 39.4 25.4 13
1/2 thru 5 PERM. .500 12.7
5 to 6 1/4” Solder
2 to 4 5/16”
Type 1620 Net Weight - Approximately 2 oz. (60 g)
.623 15.8
2 to 6 3/16” 5/8 ODM 1.14 0.81 0.69 29.0 21 18
1/9 thru 8 J .625 15.9
2 to 4 1/4” Solder
CATALOG 744 — Page 5
Distributors CO2
Specifications
NUMBER OF NOZZLE DIMENSIONS
NOZZLE & INLET
CIRCUITS & ORIFICE
RETAINER CONNECTION DISTRIBUTOR Inches mm
TUBING SIZES NUMBERS
RING SIZE Inches
AVAILABLE AVAILABLE A B C D A B C D
Type 1622 Net Weight - Approximately 3 oz. (80 g)
7 to 9 3/16” .623 15.8
5/8 ODM 1.63 1.00 0.63 41.4 25.4 16
1/9 thru 8 J .625 15.9
5 to 7 1/4”
Solder
2 to 4 5/16”
Type 1112 Net Weight - Approximately 4 oz. (110 g)
5 to 7 3/16” 22.2
.873
4 to 6 1/4” 7/8 ODM 1.72 0.91 1.00 43.7 23 +/– 25.4
1/6 thru 20 G .875 0.03
2 to 4 5/16” Solder
2 3/8”
Type 1113 Net Weight - Approximately 5 oz. (140 g)
8 to 12 3/16” 22.2
.873
7 to 8 1/4” 7/8 ODM 1.78 1.16 0.88 45.2 29.5 +/– 22
1/6 thru 20 G .875 0.03
5 to 6 5/16” Solder
3 to 4 3/8”
Type 1115 Net Weight - Approximately 9 oz. (250 g)
11 to 15 3/16”
1.123 28.52
9 to 10 1/4” 1-1/8 ODM 2.44 1.50 1.12 62.0 38.1 28.4
2 thru 30 E 1.125 28.58
7 to 9 5/16” Solder
5 to 6 3/8”
Type 1116 Net Weight - Approximately 9 oz. (250 g)
1.123 28.52
16 to 20 3/16” 1-1/8 ODM 2.44 1.75 1.12 62.0 44.4 28.4
2 thru 30 E 1.125 28.58
11 to 15 1/4” Solder
Distributors CO2
Capacities Tons psi °F kW bar °C
■ ■ ■ ■
TYPE NUMBER
CONNECTIONS PORT TONS OF REFRIGERATION
“E” Series Extended Connections
ODF SOLDER Cv SIZE
Without Manual Lift Stem With Manual Lift Stem Inches Inches PRESSURE DROP — psi*
Normally Closed Normally Closed 1 2 3 4 5
E2S120-HP – 1/4 0.15 0.075 0.66 0.95 1.16 1.34 1.51
E5S130-HP – 3/8 0.53 0.150 2.34 3.33 4.09 4.73 5.30
E6S130-HP ME6S130-HP 3/8
0.93 3/16 4.20 5.90 7.21 8.30 9.26
E6S140-HP ME6S140-HP 1/2
E9S240-HP ME9S240-HP 1/2
1.53 9/32 6.84 9.64 11.8 13.6 15.2
E9S250-HP – 5/8
E10S240-HP –
1/2 2.10 5/16 9.35 13.2 16.2 18.7 20.9
E10S250-HP –
E14S250-HP ME14S250-HP 5/8 2.98 7/16 13.3 18.8 23.0 26.5 29.6
E19S270-HP ME19S270-HP 7/8 4.57 19/32 20.3 28.8 35.3 40.8 45.6
E25S270-HP – 7/8
7.81 25/32 34.7 49.1 60.2 69.6 77.9
E25S290-HP ME25S290-HP 1-1/8
– ME35S190-HP 1-1/8
13.3 1 56.3 82.2 103 120 136
– ME35S1110-HP 1-3/8
Ratings based on 20°F liquid, -20°F evaporator temperature.
kW bar °C
■ ■
TYPE NUMBER
CONNECTIONS PORT kW OF REFRIGERATION
“E” Series Extended Connections
ODF SOLDER Kv SIZE
Without Manual Lift Stem With Manual Lift Stem Inches mm PRESSURE DROP — bar*
Normally Closed Normally Closed 0.07 0.1 0.2 0.3 0.4
E2S120-HP – 1/4 0.13 1.9 2.31 2.76 3.93 4.84 5.60
E5S130-HP – 3/8 0.46 3.8 8.12 9.73 13.9 17.0 19.7
E6S130-HP ME6S130-HP 3/8
0.81 4.8 14.6 17.4 24.4 29.8 34.3
E6S140-HP ME6S140-HP 1/2
E9S240-HP ME9S240-HP 1/2
1.32 7.1 23.7 28.3 39.9 48.8 56.3
E9S250-HP – 5/8
E10S240-HP –
1/2 1.81 7.9 32.5 38.8 54.8 67.1 77.4
E10S250-HP –
E14S250-HP ME14S250-HP 5/8 2.57 11 46.1 55.1 77.8 95.2 110
E19S270-HP ME19S270-HP 7/8 3.95 15 70.4 84.3 119 147 169
E25S270-HP – 7/8
6.75 20 120 144 204 250 289
E25S290-HP ME25S290-HP 1-1/8
E35S190-HP ME35S190-HP 1-1/8
11.5 26 196 238 347 433 506
– ME35S1110-HP 1-3/8
Ratings based on -5°C liquid, -30°C evaporator temperature.
* Do not use below 1 psi (0.07 bar) pressure drop.
For other liquid line temperatures use liquid correction factors below. Maximum Operating Pressure Differential (MOPD) for the AC coil is 450 psi (31.0 bar). Maximum Rated
Pressure (MRP) = 700 psig (48.3 barg).
Disclaimer: Some CO2 systems do not use oil or lubrication in their systems. If so, the lack of lubrication in the system may cause
the internal components of the valve to wear prematurely resulting in eventual failure of the valve. This disclaimer is for solenoid
valves only.
Page 8 — CATALOG 744
Dimensions
D E 1.56” 2.92”
VALVE FITTING 40 mm Coil Removal 74 mm
OFFSET
TYPE A B C
SERIES DEPTH
ODF
Approved
Inches
E2 E2S120-HP 4.63 0.55 1.96 0.29 C
0.31
E5 E5S130-HP 4.56 0.53 2.48 0.23
E5 Series
mm
D
E2 E2S120-HP 118 14 50 7.4 E
8 B
E5 E5S130-HP 116 13 63 6
A
COIL RATINGS
STANDARD WATTS
VOLTS/CYCLES AC DC
24/50-60
120/50-60
10 15
208-240/50-60
120-208-240/50-60
CONNECTIONS
CAPACITIES CAPACITIES
ODF - Inches
ODF - Inches
MOPD MOPD
PORT SIZE
PORT SIZE
Inches
TYPE Cv TYPE Kv
SERIES REFRIGERATION SERIES REFRIGERATION
PRESSURE DROP PRESSURE DROP
AC DC AC DC
3 psi 0.2 bar
E2 E2S120-HP 1/4 0.15 0.075 1.16 E2 E2S120-HP 1/4 0.13 1.9 3.93
450 400 31.0 27.6
E5 E5S130-HP 3/8 0.53 0.150 4.09 E5 E5S130-HP 3/8 0.46 3.8 13.9
■ Capacities based on 20°F (-6.7°C) liquid temperature, -20°F (-29°C) evaporator ■ Dual voltage 4-wire coils, 120-208-240/50-60 are available at slight additional cost.
temperature. For other liquid line temperatures use liquid correction factors below. For other voltages and cycles, consult Sporlan Division of Parker, Washington, MO.
Maximum Operating Pressure Differential (MOPD) for the AC coil is 450 psi (31 ■ Available with conduit boss, junction box, or DIN at no extra charge.
bar). Maximum Rated Pressure (MRP) = 700 psig (48.3 barg). ■ For capacity at other pressure drops, see page 7 and 8.
■ See disclaimer on page 7.
Page 10 — CATALOG 744
Dimensions
D E 1.56” 2.92”
40 mm Coil Removal 74 mm
VALVE FITTING
OFFSET
TYPE A B* C
SERIES DEPTH
ODF Approved
Inches
C
E6S130-HP 4.63 0.31
E6 0.75 2.44 0.31
E6S140-HP 5.00 0.38 E6 Series
mm
E6S130-HP 118 7.9
E6 19 62 7.9 E
E6S140-HP 127 9.7
*B
* Add 1.12” (28 mm) for valves with Manual Lift Stem.
D
A
1.64”
COIL RATINGS 42 mm
STANDARD WATTS
VOLTS/CYCLES AC DC
24/50-60
120/50-60
10 15
208-240/50-60 Optional 1/2”
120-208-240/50-60 Conduit Boss
CONNECTIONS
CAPACITIES CAPACITIES
ODF - Inches
ODF - Inches
MOPD MOPD
PORT SIZE
PORT SIZE
Inches
TYPE Cv TYPE Kv
SERIES REFRIGERATION SERIES REFRIGERATION
PRESSURE DROP PRESSURE DROP
AC DC AC DC
3 psi 0.2 bar
E6S130-HP E6S130-HP
3/8 3/8
E6 ME6S130-HP 0.93 3/16 450 400 7.21 E6 ME6S130-HP 0.81 4.8 31.0 27.6 24.4
ME6S140-HP 1/2 ME6S140-HP 1/2
■ Capacities based on 20°F (-6.7°C) liquid temperature, -20°F (-29°C) evaporator ■ Available with conduit boss, junction box, or DIN at no extra charge.
temperature. For other liquid line temperatures use liquid correction factors below. ■ For mounting holes and/or bracket information, see Bulletin 30-11
Maximum Operating Pressure Differential (MOPD) for the AC coil is 450 psi (31 ■ E6 series with mounting holes are NOT standard.
bar). Maximum Rated Pressure (MRP) = 700 psig (48.3 barg). ■ For capacity at other pressure drops, see page 7 and 8.
■ Dual voltage 4-wire coils, 120-208-240/50-60 are available at slight additional cost. ■ See disclaimer on page 7.
For other voltages and cycles, consult Sporlan Division of Parker, Washington, MO.
CATALOG 744 — Page 11
Dimensions
C D E 1.75” 3.17”
FITTING 44 mm Coil Removal 81 mm
NORMALLY
VALVE DEPTH
CLOSED
OFFSET
TYPE A *B
SERIES
Approved
ODF Listed
Inches C
E9S230-HP 4.63 0.69 2.65 0.31 0.39
E9 E9S240-HP 5.00 0.75 2.70 0.38 0.33
E9S250-HP 6.50 0.69 2.74 0.50 0.31
E10 Series
E10S240-HP
E10 5.00 0.85 3.13 0.38 0.38
E10S250-HP
E14 E14S250-HP 6.88 0.46 3.26 0.50 – E
E19 E19S270-HP 7.13 0.81 3.41 0.75 –
*B
E25 E25S270-HP 7.50 0.72 3.81 0.75 – D
E25S290-HP 8.50 0.72 3.81 0.91 –
A
mm
E9S230-HP 118 18.0 67 7.9 9.9 COIL RATINGS 1.89”
48 mm
E9 E9S240-HP 127 9.7 69 9.7 7.9 WATTS
STANDARD
E9S250-HP 165 12.7 69 13.0 9.7
VOLTS/CYCLES AC DC
E10S240-HP
E10 127 9.7 80 9.7 9.7
E10S250-HP
24/50-60
E14 E14S250-HP 175 11.7 83 13.0 –
120/50-60
E19 E19S270-HP 181 21.0 87 19.0 – 15 18
208-240/50-60
E25S270-HP 191 18.0 97 19.0 – Optional 1/2”
E25 120-208-240/50-60
E25S290-HP 216 18.0 97 23.0 – Conduit Boss
* Add 1.12” (28 mm) for valves with Manual Lift Stem.
CONNECTIONS
CAPACITIES CAPACITIES
ODF - Inches
ODF - Inches
MOPD MOPD
PORT SIZE
PORT SIZE
Inches
TYPE Cv TYPE Kv
SERIES REFRIGERATION SERIES REFRIGERATION
PRESSURE DROP PRESSURE DROP
AC DC AC DC
3 psi 0.2 bar
E9S230-HP 3/8 E9S230-HP 3/8
E9 E9S240-HP 1/2 1.53 9/32 11.8 E9 E9S240-HP 1/2 1.32 7.1 39.9
E9S250-HP 5/8 E9S250-HP 5/8
E10S240-HP 1/2 E10S240-HP 1/2
E10 2.10 5/16 16.2 E10 1.81 7.9 54.8
E10S250-HP 5/8 450 400 E10S250-HP 5/8 31.0 27.6
E14 E14S250-HP 5/8 2.98 7/16 23.0 E14 E14S250-HP 5/8 2.57 11 77.8
E19 E19S270-HP 7/8 4.57 19/32 25.3 E19 E19S270-HP 7/8 3.95 15 119
E25S270-HP 7/8 E25S270-HP 7/8
E25 7.81 25/32 60.2 E25 6.75 20 204
E25S290-HP 1-1/8 E25S290-HP 1-1/8
■ Capacities based on 20°F (-6.7°C) liquid temperature, -20°F (-29°C) evaporator ■ Dual voltage 4-wire coils, 120-208-240/50-60 are available at slight additional cost.
temperature. For other liquid line temperatures use liquid correction factors below. For other voltages and cycles, consult Sporlan Division of Parker, Washington, MO.
Maximum Operating Pressure Differential (MOPD) for the AC coil is 450 psi (31 ■ Available with conduit boss, junction box, or DIN at no extra charge.
bar). Maximum Rated Pressure (MRP) = 700 psig (48.3 barg). ■ For capacity at other pressure drops, see page 7 and 8.
■ See disclaimer on page 7.
Page 12 — CATALOG 744
1.56”
Dimensions 40 mm Coil Removal
C D *E Approved
FITTING
Listed
NORMALLY
NORMALLY
DEPTH
VALVE
CLOSED
OFFSET
TYPE A B
OPEN
SERIES
ME35 Series C
ODF
Inches
E35S190-HP 10.06 5.03 0.91 0.84
E35 4.81 5.94
E35S1110-HP 11.06 5.53 0.97 0.84
E
mm D D
E35S190-HP 256 128 23 21
E35 122 151
E35S1110-HP 281 140 25 21 B B
* Add 1.12” (28 mm) for valves with Manual Lift Stem. A
24/50-60
120/50-60
10 15
208-240/50-60
120-208-240/50-60 Optional 1/2”
Conduit Boss
CONNECTIONS
CAPACITIES CAPACITIES
ODF - Inches
ODF - Inches
MOPD MOPD
PORT SIZE
PORT SIZE
Inches
TYPE Cv TYPE Kv
SERIES REFRIGERATION SERIES REFRIGERATION
PRESSURE DROP PRESSURE DROP
AC DC AC DC
3 psi 0.2 bar
ME35S190-HP 1-1/8 ME35S190-HP 1-1/8
E35 13.3 1 450 400 103 E35 11.5 26 31.0 27.6 347
ME35S1110-HP Q1-3/8 ME35S1110-HP Q1-3/8
■ Capacities based on 20°F (-6.7°C) liquid temperature, -20°F (-29°C) evaporator ■ Dual voltage 4-wire coils, 120-208-240/50-60 are available at slight additional cost.
temperature. For other liquid line temperatures use liquid correction factors below. For other voltages and cycles, consult Sporlan Division of Parker, Washington, MO.
Maximum Operating Pressure Differential (MOPD) for the AC coil is 450 psi (31 ■ Available with conduit boss, junction box, or DIN at no extra charge.
bar). Maximum Rated Pressure (MRP) = 700 psig (48.3 barg). ■ For capacity at other pressure drops, see page 7 and 8.
■ See disclaimer on page 7.
CATALOG 744 — Page 13
M E 10 S 2 5 0 S
*Connections
Coil Connection
Manual Design Port Size Connections Coil Size Connection 0 - ODF X ODF
1 - ODF X ODM S- Spade
Lift Stem Series in 1/32” Solder Q, W Size in 1/8” E - DIN 43650A
2 - ODM X ODF
3 - ODM X ODM
Type “E” series is identified by an expanded nomenclature. The sys- Q The MKC-1, OMKC-1, MKC-2 and OMKC-2 are fun-
tem of valve identity based on port size. In addition, the “E” series gus proof and meet MIL-I-631C.
identifies the connection size and type. The advantage of the “E” W The standard MKC-1 and MKC-2 are class “F” rated.
series nomenclature system is that it allows ease in valve identifica-
tion of the standard line and can provide considerable information * Standard connections are ODF inlet x ODF outlet
about special valves supplied to manufacturers. on ‘’E” Series valves. Minimum quantities may be
required for other connections.
Application
Compressor Capacity Reduction Service Transformer Selection for Low-Voltage Control Systems
Sporlan Solenoid Valves may be used in conjunction with Sporlan Dis- Many systems utilize low voltage controls, requiring the use of a
charge Bypass Valves for capacity reduction service. For capacity infor- transformer for voltage reduction, normally to 24 volts. The selec-
mation and further details on the Discharge Bypass Valves see pages tion of a transformer is not accomplished by merely selecting one that
36 to 39 or consult Sporlan Division of Parker, Washington, MO. has the proper voltage requirements. The volt-ampere (VA) rating is
equally important. To determine the VA requirement for a specific
Filter-Driers are Essential solenoid valve, refer to the chart below. It should be noted, that insuf-
Dirt and other system contaminants present a problem for refrigera- ficient transformer capacity will result in reduced operating power or
tion and air conditioning controls. Since pilot operated solenoid valves lowering of the MOPD value.
operate with rather close tolerances, system cleanliness is imperative.
The Sporlan Catch-All® Filter-Drier filters out minute particles of If more than one solenoid valve and/or other accessories are operated
dirt and other foreign matter, thus protecting the valve. from the same transformer, then the transformer VA rating must be
determined by adding the individual accessories’ VA requirements.
Sporlan recommends using a Catch-All® Filter-Drier ahead of every
solenoid valve on all refrigeration and air conditioning applications. Fusing
Contact Sporlan before adding a Catch-All® Filter-Drier in the dis- Sporlan Solenoid Valves are not supplied with fuses. Fusing should
charge line. be according to local codes. We recommend fusing the hot leg of the
valve wiring with fast acting fuses and the valve should be grounded
either through the fluid piping or the electrical conduit.
MKC-1
1.9 0.63 0.39 0.14 0.19 0.09 60
OMKC-1
MKC-2
3.1 1.4 0.60 0.26 0.31 0.13 100
OMKC-2
■ All current values are based on 60 cycles.
■ Volt-ampere ratings are based on inrush currents.
■ Above values are based on the most severe conditions. — Consult Sporlan Division of Parker, Washington, MO for coil characteristics on specific valve types.
Page 14 — CATALOG 744
Filter-Driers CO2
UL and ULC Listed – Guide SMGT-File No. SA-1756. Maximum Rated Pressure of 650 psig.
CATALOG 744 — Page 15
Filter-Driers CO2
adsorption of moisture. Tests have demonstrated that the Catch- Special Applications – A special “HH” core Catch-All Filter-
All Filter-Drier has superior acid removal ability when compared Drier is available to remove wax which frequently causes difficulty
to competitive driers. This ability, along with its excellent ability to on low temperature refrigeration systems. For cap tube systems, use
clean up the oil, is responsible for the excellent field performance in the C-032-CAP or C-032-CAP-T Catch-All which has fittings suit-
cleaning up severely contaminated systems. able for attaching to any size capillary tube.
Oil, Sludge and Varnish – Even the best refrigeration oils Remember...It’s the CORE that counts!
break down to produce varnish, sludge and organic acids. Only the
Catch-All Filter-Drier is capable of removing these products of oil
decomposition.
UL and ULC Listed – Guide SMGT-File No. SA-1756. Maximum Rated Pressure of 44.8 barg.
Page 16 — CATALOG 744
Filter-Driers CO2
Sealed Type
Liquid Line Ratings and Selection Recommendations
Tons °F psi
■ ■ kW °C bar
■ ■
Filter-Driers CO2
Specifications
CONNECTIONS OPTIONAL NUMBER of VOLUME of FILTER OVERALL
CORE PART DESICCANT MOUNTING LENGTH
TYPE ODF SOLDER SECONDARY CORES or ELEMENT
NUMBER BRACKETS
Inches FILTER* FILTER ELEMENTS Cubic Inches cm3 PART NUMBER Inches mm
C-R424-G 1/2 9.00 229
C-R425-G 5/8 — 1 RCW-42 42 688 — A-175-1 9.06 230
C-R427-G 7/8 9.44 240
C-485-G 5/8 9.15 232
C-487-G 7/8 9.30 236
C-489-G 1-1/8 FS-480 1 48 787 RPE-48-BD A-685 9.50 241
C-4811-G 1-3/8 9.60 244
C-4813-G 1-5/8 9.60 244
C-967-G 7/8 RCW-48, 14.84 377
C-969-G 1-1/8 RC-4864 15.04 382
FS-960 2 96 1573 RPE-48-BD A-685
C-9611-G 1-3/8 or 15.14 385
C-9613-G 1-5/8 RC-4864-HH 15.14 385
C-1449-G 1-1/8 20.58 523
C-14411-G 1-3/8 FS-1440 3 144 2360 RPE-48-BD A-685 20.68 525
C-14413-G 1-5/8 20.68 525
C-19211-G 1-3/8 26.22 666
FS-19200 4 192 3146 RPE-48-BD A-685
C-19213-G 1-5/8 26.22 666
UL and ULC Listed – Guide SMGT-File No. SA-1756. C-480 through C-1920 Series shells have a 650 psig (44.8 barg) rating.
*Optional Secondary Filter must be purchased separately. O-rings (p/n 621-025) are supplied with each secondary filter, but can be purchased separately. The secondary filter cannot
be used if the shell is installed in the suction line.
Type numbers with G suffix indicate that unit is supplied with 1/4” female pipe connection in the end plate and pipe plug. For liquid line service and angle charging valve for system
charging purposes can be installed in place of the pipe plug. Angle charging and Schrader type access valves are available from your Sporlan Wholesaler.
Filter-Driers CO2
Selection Instructions
The flow capacities are rated at the maximum recommended pressure To reduce the pressure drop through replaceable core shells, substi-
drop for permanent installation. tute cores with filter elements (see page 19) after the system has been
cleaned up. The 6171-5 screen should be discarded when cores are
To ensure the suction line filter-drier has ample contami- replaced with RPE-48-BD elements in RSF shells.
nant removal ability, selection must be based on flow capac-
ity and the amount of desiccant required for system clean-up. For complete description of the suggested system clean-up procedure,
The suction line filter-drier must be large enough to adequately request Bulletin 40-10.
remove acid, moisture and solid contaminants without causing
nuisance plug-ups. Sizing is especially important for sealed type
suction line filter-driers since they should be sized to clean a small
system with one service call.
SEALED TYPE
REPLACEABLE
CORE TYPE
Filter-Driers CO2
8 Outstanding Benefits
1. The See•All Moisture and Liquid Indicator provides a Liquid Indicator has an extra large crystal clear sight glass
true moisture indication for refrigerants. The dark green for viewing the refrigerant. Bubbles indicate a shortage of
indicates dry and a bright yellow indicates wet. The one indicator refrigerants or a restriction in the liquid line.
avoids the confusion found in models with two elements. You 5. Indicator protected from discoloration and dirt. The
cannot pick the wrong element when checking the moisture indicator is protected by a filter pad and screen. This prevents
content of the system. washing of the indicator by the refrigerant and protects it from
2. Reliable and accurately calibrated color change system contamination and turbulence.
points. The See•All Moisture and Liquid Indicator is 6. Replaceable indicator element. The color indicator paper
accurately calibrated in parts per million of moisture for each can be changed on the new fused glass models without removing
refrigerant. All moisture indicators change color on the basis the See•All from the line. Replacement is through the bottom
of relative saturation of the refrigerant. Therefore, liquid line (see SA-14SU below). Request the K-SA-4 kit.
temperature must be considered if an accurate calibration is to be 7. Disassembly of the smaller sizes not required. The
obtained. For easy comparison, a color chart is part of the label. extended steel fittings on solder models in the smaller sizes make
3. Color changes are easily distinguished and reversible. it unneccesary to disassemble for installation since steel conducts
The indicator’s color differs so widely between WET and DRY only one eighth as much heat as copper.
conditions that there is no possibility of confusion between the 8. A double duty plastic cap is supplied to keep the glass free
two. Colors will reverse as often as moisture concentration in the from dust, dirt and grease. It also permits the service engineer to
system changes. use his own discretion concerning instructions to his customers
4. Large full view sight glass. The See•All Moisture and on observing the See•All Moisture and Liquid Indicator.
Specifications - Inches Listed by Underwriters’ Laboratories, Inc. – Guide SEYW – File No. SA3182
FEMALE & MALE MALE FLARE x SWIVEL NUT x FEMALE FLARE x SWIVEL NUT x ODF
CONNEC- MALE FLARE ODF SOLDER
FLARE SWIVEL NUT SWIVEL NUT SWIVEL NUT SOLDER
TION
OVERALL TYPE OVERALL TYPE OVERALL TYPE LENGTH TYPE OVERALL
OVERALL TYPE OVERALL
SIZES TYPE OVERALL
TYPE
Inches NO. LENGTH NO. LENGTH NO. LENGTH NO. NO. LENGTH NO. LENGTH NO. LENGTH
Inches Inches Inches Inches Inches Inches Inches
1/4 SA-12 2.87 SA-12FM 2.56 — — — — — — — — SA-12S
4.62
3/8 SA-13 3.37 SA-13FM 2.97 SA-13U 3.64 SA-13UU 3.95 SA-13FU 3.19 SA-13SU 4.19 SA-13S
1/2 SA-14 3.81 SA-14FM 3.44 SA-14U 4.13 SA-14UU 4.50 SA-14FU 3.75 SA-14SU 4.62 SA-14S
4.87
5/8 SA-15 4.13 — — SA-15U 4.44 SA-15UU 4.75 — — SA-15SU 4.89 SA-15S
7/8 — — — — — — — — — — — — SA-17S
6.31
1-1/8 — — — — — — — — — — — — SA-19S
1-3/8 — — — — — — — — — — — — QSA-211
7.97
1-5/8 — — — — — — — — — — — — QSA-213
mm
FEMALE & MALE MALE FLARE x SWIVEL NUT x FEMALE FLARE x SWIVEL NUT x ODF
CONNEC- MALE FLARE ODF SOLDER
FLARE SWIVEL NUT SWIVEL NUT SWIVEL NUT SOLDER
TION
TYPE OVERALL OVERALL TYPE OVERALL TYPE OVERALL OVERALL TYPE OVERALL
SIZES OVERALL
TYPE TYPE
NO. LENGTH
Inches TYPE NO. LENGTH LENGTH LENGTH LENGTH LENGTH LENGTH
NO. NO. NO. NO. NO.
mm mm mm mm mm mm mm
1/4 SA-12 72.9 SA-12FM 65.0 — — — — — — — — SA-12S
117
3/8 SA-13 85.6 SA-13FM 75.4 SA-13U 92.5 SA-13UU 100 SA-13FU 81 SA-13SU 106 SA-13S
1/2 SA-14 96.8 SA-14FM 87.4 SA-14U 105 SA-14UU 114 SA-14FU 95.3 SA-14SU 117 SA-14S
124
5/8 SA-15 105 — — SA-15U 113 SA-15UU 121 — — SA-15SU 124 SA-15S
7/8 — — — — — — — — — — — — SA-17S
160
1-1/8 — — — — — — — — — — — — SA-19S
1-3/8 — — — — — — — — — — — — QSA-211
202
1-5/8 — — — — — — — — — — — — QSA-213
Maximum Rated Pressure for all models is 650 psig (44.8 barg). Overall width is: 1.31” (33.3 mm) for 1/4” and 3/8” sizes. 1.58” (40.1 mm) for 1/2” and 5/8 sizes, and 1.38” (35.1 mm)
for 7/8” and 1-1/8” sizes. Most solder connections can be used as male fittings as well as female fittings. The 1/4” ODF is 3/8” ODM, the 3/8” ODF is 1/2” ODM, the 1/2” ODF is 5/8”
ODM, and the 5/8” ODF is 3/4” ODM. Models with female flare and/or swivel nut connections are supplied with a copper gasket in the fitting.
Q These models have copper connections and feature a removable element cartridge – for replacement cartridge specify AC-20.
CATALOG 744 — Page 21
Replaceable CO2
The Replaceable Suction Filter shell, used
with RPE-48-BD pleated filter element,
How It’s Used
Sporlan Replaceable Suction Filters are installed in the suction line of
is designed to be installed in the suction refrigeration or air conditioning systems to remove contaminants that
line of new systems to remove circulating may be in the system at startup.
contaminants.
The Replaceable Suction Filter has large fittings permitting the use
Design Benefits RSF-4817-T of a small shell on a system with large line sizes, resulting in consid-
erable economy. The angle construction is suitable of flow in either
■ High flow capacity direction, which results in easy installation even on compact racks.
■ Corrosion resistant coating on shell
The Replaceable Suction Filters should be used with cores for clean-
■ Can be used with desiccant cores ing up a system after a hermetic motor burnout. Select the RC-4864,
for clean-up after burnout RC-4864-HH or RCW-48 replaceable cores. After cleanup, install
RPE-48-BD elements in the shells.
■ Various fitting sizes up to 1-5/8” line size
■ Access valve supplied for pressure drop Selection
measurement or charging The table below gives information for choosing the proper model for
a given system. The filter elements are supplied in hermetically sealed
metal cans. For flow capacity WITH CORES, see page 18.
OVERALL LENGTH
OVERALL LENGTH
CONNECTIONS
CONNECTIONS
Square Inches
FILTER AREA
FILTER AREA
ODF SOLDER
ODF SOLDER
NUMBER OF
EVAPORATOR
NUMBER OF
EVAPORATOR
ELEMENTS
ELEMENTS
TEMPERATURE TEMPERATURE
FILTER
Inches
FILTER
Inches
Inches
cm 2
mm
TYPE 40°F TYPE 5°C
PRESSURE DROP – psi PRESSURE DROP – bar
1 2 3 0.07 0.14 0.20
RSF-487-T 7/8 12.6 18.5 23.2 9.30 RSF-487-T 7/8 43.1 63.4 77.3 236
RSF-489-T 1-1/8 19.8 29.0 36.4 9.37 RSF-489-T 1-1/8 67.6 99.3 121 238
RSF-4811-T 1-3/8 29.2 42.9 53.8 One 9.60 RSF-4811-T 1-3/8 99.7 147 179 One 244
388 2503
RSF-4813-T 1-5/8 36.3 53.4 67.0 RPE-48-BD 9.60 RSF-4813-T 1-5/8 124 183 223 RPE-48-BD 244
RSF-4817-T 2-1/8 48.6 71.4 89.5 9.37 RSF-4817-T 2-1/8 166 244 298 238
RSF-4821-T 2-5/8 64.1 94.2 118 9.75 RSF-4821-T 2-5/8 219 322 393 248
RSF-9611-T 1-3/8 31.3 46.1 57.7 Two 15.14 RSF-9611-T 1-3/8 107 157 192 Two 385
776 5006
RSF-9613-T 1-5/8 41.8 61.4 76.9 RPE-48-BD 15.14 RSF-9613-T 1-5/8 143 210 256 RPE-48-BD 385
Ratings based on 20°F (-5°C) liquid, 25°F (14°C) superheat.
Listed by Underwriters’ Laboratories, Inc. Guide SMGT File No. SA-1756. RSF shells have a 500 psig (34.5 barg) M.R.P. rating.
Note: Ratings are in accordance with ARI Standards 730. Flow capacity (tons/kW) with cores is approximately 40% of the above values.
All Sporlan EEVs are rated for at least 620 psig (42 barg) MRP.
Specifications
VALVE CABLE LENGTH
INLET – Inches OUTLET – Inches CONFIGURATION
TYPE Feet Meters
1/4, 3/8, 1/2 ODF 3/8, 1/2, 5/8 ODF
SEI 0.5, 1, 2, 3.5, 6, 8.5, 11 Angle
1/4, 3/8, 1/2 SAE 1/2 SAE
SEI 30 5/8, 7/8, 1-1/8 ODF 5/8, 7/8, 1-1/8, 1-3/8 ODF Angle
SEI 50* 7/8, 1-1/8, 1-3/8 ODF 7/8, 1-1/8, 1-3/8, 1-5/8 ODF Straight through
SER 1-1/2 3/8, 1/2, 5/8 ODF 3/8, 1/2, 5/8 ODF Angle
SER 6 3/8, 1/2, 5/8 ODF 3/8, 1/2, 5/8, 7/8 ODF Angle 10, 20, 30, 40 3, 6, 9, 12
SER 11 3/8, 1/2, 5/8 ODF 1/2, 5/8, 7/8, 1-1/8 ODF Angle
SER 20 1/2, 5/8, 7/8, 1-1/8 ODF 5/8, 7/8, 1-1/8, 1-3/8 ODF Angle
SERI G 5/8, 7/8 ODF 1/2, 5/8, 7/8, 1-1/8 ODF Angle / Straight through
SERI J 7/8, 1-1/8 ODF 7/8, 1-1/8, 1-3/8 ODF Angle / Straight through
SERI K 1-1/8 ODF 7/8, 1-1/8, 1-3/8, 1-5/8 ODF Angle / Straight through
*Not suitable for bi-directional applications.
Specifications
(Standard Connections and Cable Lengths are in BOLD type.)
CONNECTIONS CABLE LENGTH
TYPE CONFIGURATION CABLE ENDS
ODF SOLDER – Inches Feet Meters
CDS-4 1/2, 5/8, 7/8
CDS-7 Straight Through
5/8, 7/8, 1-1/8, 1-3/8
CDS-9 10 3 S-Stripped and Tinned
CDS-16 1-3/8 Angle
CDS-17 1-3/8, 1-5/8 Straight Through
EVAPORATOR PRESSURE DROP ACROSS VALVE – psi EVAPORATOR PRESSURE DROP ACROSS VALVE – bar
TYPE TYPE
TEMP. °F 0.5 1 3 5 10 TEMP. °C 0.03 0.07 0.20 0.40 0.70
0 2.17 3.05 5.22 6.70 9.40 -20 6.79 10.3 17.2 24.1 31.7
CDS-4 -20 1.83 2.57 4.39 5.64 7.92 CDS-4 -30 5.80 8.79 14.7 20.6 27.1
-40 1.51 2.12 3.62 4.65 6.53 -40 4.88 7.38 12.3 17.3 22.8
0 6.06 8.38 14.0 17.8 24.6 -20 19.1 28.3 46.3 64.1 83.3
CDS-7 -20 5.14 7.11 11.9 15.1 20.9 CDS-7 -30 16.4 24.4 39.8 55.1 71.6
-40 4.27 5.91 9.89 12.6 17.4 -40 13.9 20.6 33.7 46.6 60.6
0 9.07 12.6 21.2 27.1 37.6 -20 28.5 42.6 70.1 97.4 127
CDS-9 -20 7.68 10.7 18.0 22.9 31.8 CDS-9 -30 24.5 36.6 60.2 83.6 109
-40 6.37 8.85 14.9 19.0 26.4 -40 20.7 30.9 50.8 70.6 92.1
0 15.0 20.7 34.6 43.9 60.7 -20 47.2 70.1 114 158 205
CDS-16 -20 12.7 17.6 29.4 37.3 51.5 CDS-16 -30 40.6 60.3 98.4 136 177
-40 10.6 14.6 24.4 31.0 42.9 -40 34.4 51.0 83.3 115 150
0 16.3 22.6 38.2 48.7 67.8 -20 51.0 76.4 126 175 229
CDS-17 -20 13.7 19.1 32.3 41.2 57.4 CDS-17 -30 43.8 65.5 108 151 197
-40 11.4 15.9 26.8 34.2 47.6 -40 36.9 55.3 91.2 127 166
Ratings based on 20°F (-5°C) liquid, 25°F (14°C) superheat.
PRESSURE DROP ACROSS VALVE – psi PRESSURE DROP ACROSS VALVE – bar
TYPE Cv TYPE Kv
0.5 1 3 5 10 0.03 0.07 0.20 0.40 0.70
CDS-4 2.88 9.26 13.0 22.3 28.6 40.1 CDS-4 2.49 29.8 45.1 75.4 106 139
CDS-7 7.28 24.3 33.6 56.2 71.4 98.7 CDS-7 6.30 78.4 117 191 264 343
CDS-9 11.2 37.0 51.5 86.6 110 153 CDS-9 9.72 119 179 294 408 532
CDS-16 17.9 59.9 82.7 138 175 242 CDS-16 15.5 193 287 469 648 841
CDS-17 20.4 66.8 93.0 157 200 279 CDS-17 17.6 216 323 533 741 968
Ratings based on 20°F (-5°C) liquid, -20°F (-30°C) evaporator temperature.
Controller Packages
Sporlan offers a variety of controllers for use in refrigeration and air Cold rooms can be controlled with RCS, which has onboard remote
conditioning systems. Applications include self-contained food ser- communication, and master-slave settings for defrost control. Included
vice equipment, cold rooms and chillers. With over 80 different mod- real time clocks allow defrost initialization times to be set precisely
els, Sporlan can satisfy almost any customer requirement. and relays allow control of fans, solenoids, alarms and compressors.
Many of the controllers can be customized for specific needs, or sup-
Small, standalone controllers include the compact Kelvin II and plied in an enclosure, please contact Product Manager, Electronic
larger Superheat and Refrigeration controllers. All are designed to Products, Sporlan Division.
provide true pressure/temperature superheat control of any system
using Sporlan Electric Expansion Valves (EEVs). Chiller controllers
offer true pressure/temperature superheat control for two Sporlan
EEVs and are available in Fahrenheit/psi or Celsius/Bar versions.