♦ 24 Month Warranty
SPECIFICATIONS All specifications are typical at nominal input, full load and at 20°C unless otherwise stated.
ELECTRICAL No-Break™ FUNCTIONS AND ALARMS*
Input Voltages Battery Charge See Model Table for default settings.
▪ standard 230V AC: 180V - 264V Current Limit Charge current may be set to maximum PSU
rated current.
▪ optional 110V AC: 88V - 132V
Reverse Polarity Battery reverse connection will open internal
Frequency 45- 65 Hz fuse (and produce alarm)
Fusing / Protection Internal AC input fuse, output battery fuse Battery Monitoring Detects for presence of battery after 1 minute
on start up, then every 60 minutes when
Isolation 3.5KVAC 1 min. input / output, charge current < 200mA
1KV DC input / earth
ELCB Electronic Circuit Breaker operates under the
Efficiency > 85% following conditions:
- battery discharged ELVD (electronic low voltage disconnect)
Inrush current Soft start circuit activates when battery voltage drops to 1.67V/
Output Power cell (adjustable) - auto reset
750W continuous (0 - 50°C)
- overload Allows ~150% load from battery without acting,
Output Voltages 13.8V, 27.6V, 41.4V, 55.2V Operates within 300ms for load > 600%
Other voltages by request. - short circuit Acts within 2ms, backed up by fuse
Voltage adj. range 85 - 105% of Vout Indication LEDs Green: Battery System OK, Power OK
Red: Standby
Temp. Compensation Temperature sensor on 1.7m lead with ad- (refer to page 15 for fault codes)
hesive pad: -4mV / °C / cell ±10%
Alarms • Power OK (Mains/PSU fail, standby mode)
Current Limit Straight line profile –refer model table for • Battery System OK - alarms when battery
values voltage low (on mains fail) , battery missing,
battery circuit wiring faulty, BCT fail
Line Regulation <0.2% over AC input range • Relay contacts C - NO - NC full changeover rated 1A /50V DC,
32VAC
Load Regulation <0.4% open circuit to 100% load
Standby Mode Turns off DC output of PSU & allows load to
Noise <1% run off battery
Drift 0.03% / °C
Hold-up time ENVIRONMENTAL
15 - 20 ms (nom. - max. Vin) without battery
Operating 0 - 50 °C ambient at full load
Thermal Protection Automatic current de-rating if >50°C. Self- temperature De-rate linearly >50 °C to no load @ 70 °C
resetting (see Operating Temperature)
Storage temperature -10 to 85 °C ambient
OVP Over-voltage protection on output
Humidity 0 - 95% relative humidity non-condensing
at ~ 130% of nominal output voltage
Cooling Fan cooled
Battery Overcurrent Electronic circuit breaker (ELCB) allows
Protection max. battery current of 1.5x I PSU continuous STANDARDS
and trips when I load > 6 x IPSU .
EMI to CISPR 22 / EN55022 class A
Specifications are subject to change without notice due to continual product improvement. No liability accepted for errors or omissions. 32
www.innovative-energies.com
750W PSU/Charger for use with batteries
DC Output
MODELS Charge
Output Voltage Max. Recomm.* PSU Rated
Current Limit
(Load & Charger) Load Current Current
(minimum)*2
SR750C48 55.2V 8.5A 5.0A 13.5A *1 to allow for adequate charging current as load
takes precedence over charging of battery
OPTIONS
19”Rack Mount 2U sub rack available, Code: SR-RM2U
Optional V/I meter, Code: SR-METER
Wall Mount Enclosure PSU may be fitted into enclosure with MCBs
304 mm
and terminals, Code: SEC-SR
318 mm
328 mm
Parallel redundancy Use external output diode, eg +P50
ACCESSORIES SUPPLIED
Mounting Feet together with screws
AC power cord Standard 1.5m lead with IEC320 socket / local plug
'Phoenix combicon' DC connector for ‘X’ version
Mating screw-terminal plug for alarm outputs
Crimp lugs for stud terminal versions
Output DC Connector type: Stud = S Phoenix combicon (plug in screw terminal block = X
Function: C = No-Break™
Specifications are subject to change without notice due to continual product improvement. No liability accepted for errors or omissions. 33