Sei sulla pagina 1di 2

750W PSU/Charger for use with batteries

 Constant monitoring of battery circuit integrity


 Deep discharge protection
 Controls load and charge current independently
 Wide input voltage window tolerance
 Overload, short circuit & reverse polarity protect
 Automatic battery temperature compensation
 High efficiency switch mode design
 No transition switching between PSU & backup
battery
Uninterruptible DC Power Supply &  LED flash codes for precise state indication
battery management system -
batteries supplied separately  Two alarm relay outputs standard
 ISO9001 Design management system
Microprocessor controlled
 Suitable for use with all types of lead acid
batteries (batteries external to power supply)

♦ 24 Month Warranty
SPECIFICATIONS All specifications are typical at nominal input, full load and at 20°C unless otherwise stated.
ELECTRICAL No-Break™ FUNCTIONS AND ALARMS*
Input Voltages Battery Charge See Model Table for default settings.
▪ standard 230V AC: 180V - 264V Current Limit Charge current may be set to maximum PSU
rated current.
▪ optional 110V AC: 88V - 132V
Reverse Polarity Battery reverse connection will open internal
Frequency 45- 65 Hz fuse (and produce alarm)

Fusing / Protection Internal AC input fuse, output battery fuse Battery Monitoring Detects for presence of battery after 1 minute
on start up, then every 60 minutes when
Isolation 3.5KVAC 1 min. input / output, charge current < 200mA
1KV DC input / earth
ELCB Electronic Circuit Breaker operates under the
Efficiency > 85% following conditions:
- battery discharged ELVD (electronic low voltage disconnect)
Inrush current Soft start circuit activates when battery voltage drops to 1.67V/
Output Power cell (adjustable) - auto reset
750W continuous (0 - 50°C)
- overload Allows ~150% load from battery without acting,
Output Voltages 13.8V, 27.6V, 41.4V, 55.2V Operates within 300ms for load > 600%
Other voltages by request. - short circuit Acts within 2ms, backed up by fuse

Voltage adj. range 85 - 105% of Vout Indication LEDs Green: Battery System OK, Power OK
Red: Standby
Temp. Compensation Temperature sensor on 1.7m lead with ad- (refer to page 15 for fault codes)
hesive pad: -4mV / °C / cell ±10%
Alarms • Power OK (Mains/PSU fail, standby mode)
Current Limit Straight line profile –refer model table for • Battery System OK - alarms when battery
values voltage low (on mains fail) , battery missing,
battery circuit wiring faulty, BCT fail
Line Regulation <0.2% over AC input range • Relay contacts C - NO - NC full changeover rated 1A /50V DC,
32VAC
Load Regulation <0.4% open circuit to 100% load
Standby Mode Turns off DC output of PSU & allows load to
Noise <1% run off battery
Drift 0.03% / °C
Hold-up time ENVIRONMENTAL
15 - 20 ms (nom. - max. Vin) without battery
Operating 0 - 50 °C ambient at full load
Thermal Protection Automatic current de-rating if >50°C. Self- temperature De-rate linearly >50 °C to no load @ 70 °C
resetting (see Operating Temperature)
Storage temperature -10 to 85 °C ambient
OVP Over-voltage protection on output
Humidity 0 - 95% relative humidity non-condensing
at ~ 130% of nominal output voltage
Cooling Fan cooled
Battery Overcurrent Electronic circuit breaker (ELCB) allows
Protection max. battery current of 1.5x I PSU continuous STANDARDS
and trips when I load > 6 x IPSU .
EMI to CISPR 22 / EN55022 class A

Safety to IEC950 / EN60950 / AS/NZS3260

Specifications are subject to change without notice due to continual product improvement. No liability accepted for errors or omissions. 32
www.innovative-energies.com
750W PSU/Charger for use with batteries

STANDARD PREFERRED MODEL TABLE

DC Output

MODELS Charge
Output Voltage Max. Recomm.* PSU Rated
Current Limit
(Load & Charger) Load Current Current
(minimum)*2

SR750C12 13.8V 42.0A 12.0A 54.0A

SR750C24 27.6V 19.0A 8.0A 27.0A Temperature Probe

SR750C36 41.4V 12.0A 6.0A 18.0A

SR750C48 55.2V 8.5A 5.0A 13.5A *1 to allow for adequate charging current as load
takes precedence over charging of battery

*2 Default setting may be increased on request

MOUNTING DETAILS / DIMENSIONS PHYSICAL

340 mm AC Input connector IEC320 inlet socket (similar to PCs etc.)

DC Output Connec- M8 brass stud: or 'Phoenix combicon' plug-in


tions style socket & mating screw terminal block:
(max. wire 4mm² / way)

Alarm Connections Plug in screw terminal block (max. 2.5mm²)

Enclosure Powder coated aluminium


Dims: 328 x 225 x 70 mm
120 mm
Weight: 4.3 Kg Weight 4.3kg
225 mm

OPTIONS
19”Rack Mount 2U sub rack available, Code: SR-RM2U
Optional V/I meter, Code: SR-METER

Wall Mount Enclosure PSU may be fitted into enclosure with MCBs
304 mm
and terminals, Code: SEC-SR
318 mm
328 mm
Parallel redundancy Use external output diode, eg +P50

Battery Condition Test Available as an option, please specify


(BCT) duration & frequency.
70mm
77mm

Relay output provided for indication or to


control additional load for testing battery

ACCESSORIES SUPPLIED
Mounting Feet together with screws
AC power cord Standard 1.5m lead with IEC320 socket / local plug
'Phoenix combicon' DC connector for ‘X’ version
Mating screw-terminal plug for alarm outputs
Crimp lugs for stud terminal versions

MODEL CODING AND SELECTION CHART

SR750C 12 T F S L +Int-Meter (with Volt/ Amp Meter) No = blank

230V AC + switch = L 230V AC no switch = blank


Input voltage and front
110V AC + switch = U 110V AC no switch = G
panel standby switch:
110V DC + switch = H 110V DC no switch = J

Output DC Connector type: Stud = S Phoenix combicon (plug in screw terminal block = X

Fan cooled: With fan = F No fan = blank

Temperature Compensation Yes = T No = blank

DC output: Nominal voltage 12, 24, 36, 48V

Function: C = No-Break™

Specifications are subject to change without notice due to continual product improvement. No liability accepted for errors or omissions. 33
www.innovative-energies.com