Application Guide
Fike copyrights this manual and products it describes. You may not reproduce,
transmit, transcribe, or any part of this manual without express, written
permission from Fike.
This manual contains proprietary information intended for distribution to
authorized persons or companies for the sole purpose of conducting business
with Fike. If you distribute any information contained in this manual to
unauthorized persons, you have violated all distributor agreements and we may
take legal action.
QUALITY Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we
thoroughly test our products and review our documentation to assure the highest
quality in all respects.
WARRANTY Fike provides a one-year limited manufacturer’s warranty on this product. All
warranty returns must be returned from an authorized Fike Distributor. Contact
Fike’s Marketing department for further warranty information.
Fike maintains a repair department that is available to repair and return existing
electronic components or exchange/purchase previously repaired inventory
component (advance replacement). All returns must be approved prior to return.
A Material Return Authorization (MRA) number must be indicated on the box of
the item being returned. Contact the appropriate Regional Sales Manager for
further information regarding product return procedures.
LIMITATIONS OF LIABILITY Installation in accordance with this manual, applicable codes, and the
instructions of the Authority Having Jurisdiction is mandatory. Fike can not be
held liable for any incidental or consequential damages arising from the loss of
property or other damages or losses resulting from the use or misuse of Fike
products beyond the cost of repair or replacement of any defective components.
Fike reserves the right to make product improvements and change product
specifications at any time.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its content, Fike assumes no responsibility for errors or
omissions.
APPLICATION GUIDE
TABLE OF CONTENTS
Section Title Page
Document History .................................................................................................................3
About This Manual................................................................................................................4
Product Support....................................................................................................................4
Safety Information ................................................................................................................4
Terms Used In This Manual .................................................................................................5
1.0 Introduction ...........................................................................................................................6
2.0 What is a Smoke-Control System? .....................................................................................6
3.0 Smoke-Control System Objectives .....................................................................................6
4.0 Smoke-Control Approaches ................................................................................................6
4.1 Compartmentation ..................................................................................................................6
4.2 Smoke Filling ..........................................................................................................................7
4.3 Mechanical Smoke Exhaust....................................................................................................7
4.4 Gravity Smoke Venting ...........................................................................................................7
4.5 Pressurization .........................................................................................................................7
4.5.1 Positive Pressure Systems .....................................................................................................8
4.5.2 Negative Pressure Systems....................................................................................................9
5.0 Factors Affecting Smoke Movement................................................................................ 10
5.1 Stack Effect.......................................................................................................................... 10
5.2 Wind Effect........................................................................................................................... 10
5.3 HVAC Systems .................................................................................................................... 10
5.4 Bouyancy (Temperature Effects) ......................................................................................... 10
5.5 Climate Effects..................................................................................................................... 10
6.0 Equipment Used for Smoke-Control................................................................................ 11
6.1 Dedicated and Non-dedicate Equipment ............................................................................. 11
6.2 Selecting Fans and Ductwork .............................................................................................. 11
6.3 Selecting Dampers............................................................................................................... 11
7.0 System Controls ................................................................................................................ 12
7.1 Automatic Activation ............................................................................................................ 12
7.2 Manual Activation................................................................................................................. 12
7.2.1 Firefighters’ Smoke-Control Station (FSCS)........................................................................ 12
7.3 Manual Fire Alarm Pull Stations .......................................................................................... 12
7.4 Stairwell Pressurization System Controls ............................................................................ 13
7.5 Zoned Smoke-Control System Controls .............................................................................. 13
8.0 Design Considerations...................................................................................................... 13
8.1 Smoke-Control Strategy....................................................................................................... 13
8.2 Coordinating with Other Systems ........................................................................................ 14
8.3 Defining Smoke-Control Zones............................................................................................ 14
9.0 System Response Times................................................................................................... 15
10.0 System Response Sequence............................................................................................ 17
11.0 End-To-End Verification .................................................................................................... 17
12.0 Weekly Self-Test ................................................................................................................ 17
13.0 Operational/Acceptance Testing...................................................................................... 17
14.0 Modifications ...................................................................................................................... 17
LIST OF EXHIBITS
Exhibit 1 Mechanical Smoke Exhaust Approach ...................................................................................7
Exhibit 2 Gravity Smoke Venting Approach...........................................................................................7
Exhibit 3 Air Pressure Containing Smoke..............................................................................................7
Exhibit 4 Positive Pressure System .......................................................................................................8
Exhibit 5 Negative Pressure System .....................................................................................................9
Exhibit 6 Smoke-Control Zone Arrangements .................................................................................... 14
Exhibit 7 Automatic Smoke-Control Command Timing ...................................................................... 15
Exhibit 8 Manual Smoke-Control Command Timing........................................................................... 15
Exhibit 9 Weekly Dedicated Self-Test Command Timing ................................................................... 16
Exhibit 10 Smoke-Control Application Overview .................................................................................. 18
Exhibit 11 CyberCat 1016 Control Panel .............................................................................................. 19
Exhibit 12 Six Zone Smoke-Control Module......................................................................................... 20
Exhibit 13 Input/Output Control Module................................................................................................ 21
Exhibit 14 FSCS Graphic Panel............................................................................................................ 22
Exhibit 15 Relay Module ....................................................................................................................... 23
Exhibit 16 Monitor Module .................................................................................................................... 23
Exhibit 17 Mini Monitor Module............................................................................................................. 23
Exhibit 18 High-Rise Building FSCS Layout (Zone Control) ................................................................ 25
Exhibit 19 High-Rise Building FSCS Layout (Individual Control) ......................................................... 26
Exhibit 20 High-Rise Building Field Device Connections ..................................................................... 27
Exhibit 21 High-Rise Floor Above/Floor Below Pressurization (+) ....................................................... 28
Exhibit 22 Warehouse Building FSCS Layout ...................................................................................... 29
Exhibit 23 Warehouse Building Field Device Connections................................................................... 30
Exhibit 24 Warehouse Building Depressurization (-) ............................................................................ 31
Exhibit 25 Single Story Shopping Mall FSCS Layout ........................................................................... 32
Exhibit 26 Shopping Mall Field Device Connections ............................................................................ 33
Exhibit 27 Shopping Mall – East Commons Area Alarm ...................................................................... 34
Exhibit 28 Shopping Mall – Store 4 Alarm ............................................................................................ 35
DOCUMENT HISTORY
Document Title: Smoke-Control Application Guide
Document Reorder Number: 06-470
4.5 PRESSURIZATION
Pressurization involves the use of mechanical fans
to induce airflows and pressure differences across a
smoke barrier between the zone of fire origin and
adjacent spaces, in order to contain the smoke to
the zone of fire origin. Pressurization is well suited
for use in compartmented buildings with
predominately low-ceiling spaces, such as high-rise
office buildings. Exhibit 3 shows how pressure can
be used to inhibit smoke movement.
6.0 EQUIPMENT USED FOR SMOKE- 6.2 SELECTING FANS AND DUCTWORK
CONTROL
The fans and ductwork used in the smoke-control
All equipment (i.e., fans, ducts, dampers, etc.) that is system must be capable of providing the amount of
to be used for the purpose of smoke-control shall be air pressure required for each smoke-control zone.
suitable for their intended use and the temperatures In a nondedicated system, this may mean that you
that they are likely to experience. Equipment shall need to install fans that have a higher capacity than
be designed or modified to provide the required the HVAC system calls for. The ducts must be
smoke-control operation and shall have the highest capable of handling the pressurization (or the
priority over all other control modes associated with depressurization for the fire zone’s return duct) that
the equipment. the smoke-control system will exert. Both the fans
and ducts should meet the requirements stated in
6.1 DEDICATED AND NON-DEDICATED NFPA 90A, Standard for the Installation of Air
EQUIPMENT Conditioning and Ventilating Systems.
The equipment used for smoke-control shall be System fans must be able to reach their desired
designated as either dedicated or non-dedicated. state or operational mode in 60 seconds from when
Dedicated equipment is used for the sole purpose of the component receives the signal. Each fan must
providing smoke-control, and upon activation, the be equipped with a contact to provide feedback to
equipment operates only to perform the smoke- the smoke-control system to indicate that the fan is
control function. Non-dedicated equipment shares operating correctly.
equipment with other system(s), such as building
HVAC system, and upon activation causes the 6.3 SELECTING DAMPERS
HVAC system to change its mode of operation in
The smoke dampers installed to protect openings in
order to achieve the smoke-control objective. In
smoke barriers or used as safety-related dampers in
most cases, a building will have both dedicated and
engineered smoke-control systems shall meet the
non-dedicated equipment.
requirements of UL 555S, Standard for Smoke
Dedicated equipment is less likely to be modified Dampers. The dampers listed in this standard are
over the life of the building. Operation and control of designed to block the movement of smoke when
dedicated equipment is relatively simple because they are fully closed. Where a combination
they serve only one purpose and do not rely on or fire/smoke damper is used, it must meet the
impact other building systems. However, dedicated requirements of both UL 555S and UL 555 Standard
equipment typically requires additional space, and for Fire Dampers.
problems may go undiscovered between the
Dampers for a smoke-control system must be able
required weekly self-tests or maintenance activities.
to completely close in 75 seconds from when the
Examples of dedicated equipment are stair
component receives the signal. Each damper must
pressurization fans and atrium smoke exhaust fans.
be equipped with two contacts to provide feedback
Non-dedicated equipment is more likely to be to the smoke-control system to indicate the
maintained, and they require less space because open/closed position of the damper.
the equipment serves multiple purposes. However,
the system controls may become quite elaborate,
and any modifications made to the shared HVAC
equipment can affect the smoke-control functionality.
An example of non-dedicated equipment is an air
handler supply fan used to positively pressurize a
smoke-control zone.
SIGNALING
LINE CIRCUIT
SIGNALING
LINE CIRCUIT
NOTES ( ):
1. THE PRIMARY CYBERCAT FIRE ALARM CONTROL
FIRE FIGHTER'S SMOKE PANEL CAN BE EQUIPPED WITH SMOKE-CONTROL
CONTROL STATION (2) MODULES THAT ARE CAPABLE OF PROVIDING STATUS
INDICATION AND OPERATIONAL CONTROLS OVER THE
FIRE-FIGHTER'S COMMAND CENTER SMOKE-CONTROL SYSTEM.
SMOKE CONTROL PANEL 2. THE FIRE FIGHTER'S SMOKE CONTROL STATION
PROVIDES STATUS INDICATION AND OPERATIONAL
CONTROLS OVER THE SMOKE-CONTROL SYSTEM.
EXHA UST AIR S UPPL Y AIR
DAMPER DAMPER
RETURN AIR
OPEN CLOSE DAMPER OPEN C LOSE
E XHAUST
FAN
ON A UTO OFF FA ULT OPEN CLOSE ON A U TO OFF FA ULT
S UP PLY
FAN
3. SMOKE-CONTROL OPERATION(S) CAN BE DISTRIBUTED
E XHAUST DAMPER S UPP LY DAMPER
ON A U TO OFF FA ULT
LARGEST SYSTEM REQUIREMENTS.
BUS 4. FIELD RELAYS ARE INSTALLED AT EACH PIECE OF
E XHAUST DAMPER S UPP LY DAMPER
OFF
AUTO
ON
OFF
AUTO
ON
OFF
AUTO
ON
OFF
AUTO
ON
OFF
AUTO
ON
OFF
AUTO
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON ON ON ON ON ON
-
OFF OFF OFF OFF OFF OFF
provided by the fire alarm system, Firefighters’ AUTO AUTO AUTO AUTO AUTO AUTO
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON ON ON ON ON ON
ON
AUTO
ON
AUTO
ON
AUTO
ON
AUTO
ON
AUTO
ON
dedicated).
OFF OFF OFF OFF OFF OFF
S UP PLY
FAN
customer and the project scope. It consists of a E XHAUST DAMPER S UPP LY DAMPER
lexan viewing window with silk-screened artwork that ON A UTO OFF FA ULT ON A UTO OFF FA ULT
building arrangement, smoke-control systems and ON A UTO OFF FA ULT ON A UTO OFF FA ULT
equipment, and the areas of the building served by E XHAUST DAMPER S UPP LY DAMPER
the equipment. If the graphic layout is too large to fit ON A UTO OFF FA ULT ON A UTO OFF FA ULT
on a single panel, multiple panels may be used. E XHAUST DAMPER S UPP LY DAMPER
LED indicators are used to indicate operational ON A UTO OFF FA ULT ON A UTO OFF FA ULT
equipment. Distinct background colors can be used ON A UTO OFF FA ULT ON A UTO OFF FA ULT ON A UTO OFF FA ULT
O VERRIDE
P OW ER O.K.
E NGAGE
Features
• Communicates on the associated control panel’s
RS485 peripheral bus.
• Local piezo sounds for annunciation of system
status changes.
• Access key switch for lock-out of smoke-control
switches.
• Immediate visual status of smoke-control
components in compact area.
• Bi-directional communication with associated
control panel.
• Integrated LED test switch function.
• 24vdc power input from associated control panel
or battery backed 24VDC, regulated, power-
limited, power supply listed for Fire Protective
Signaling System use.
RED
RED
VIOLET
YELLOW
AUTO AUTO
OFF OFF
FAULT FAULT
DAMPER 6-1
EF 6-1
VAV 6-1 ZONE 6
DAMPER 6-2 VAV PRESSURIZE
BOX AUTO
EXHAUST
FAULT
DAMPER 6-3
SF 6-1
DAMPER 5-1
EF 5-1
VAV 5-1 ZONE 5
PRESSURIZE
DAMPER 5-2 VAV
AUTO
BOX
EXHAUST
FAULT
DAMPER 5-3
SF 5-1
DAMPER 4-1
EF 4-1
ZONE 4
VAV 4-1 PRESSURIZE
DAMPER 4-2 VAV AUTO
BOX EXHAUST
FAULT
DAMPER 4-3
SF 4-1
AUTO AUTO
OFF OFF
FAULT FAULT
EF 6-1
DAMPER 6-1
ON
OPEN DAMPER 6-2 AUTO
AUTO
VAV 6-1
OPEN
OFF OPEN
CLOSE AUTO VAV
FAULT
FAULT CLOSE
BOX AUTO
CLOSE
FAULT
FAULT
AUTO AUTO
CLOSE OFF
FAULT FAULT
EF 5-1
DAMPER 5-1
ON
OPEN DAMPER 5-2 AUTO
AUTO OPEN
VAV 5-1
OFF OPEN
CLOSE AUTO VAV
FAULT
FAULT CLOSE
BOX AUTO
CLOSE
FAULT
FAULT
AUTO AUTO
CLOSE OFF
FAULT FAULT
EF 4-1
DAMPER 4-1
ON
OPEN DAMPER 4-2 AUTO
AUTO OPEN
VAV 4-1
OFF OPEN
CLOSE AUTO VAV
FAULT
FAULT CLOSE
BOX AUTO
CLOSE
FAULT
FAULT
AUTO AUTO
CLOSE OFF
FAULT FAULT
SLC4
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
6TH FLOOR
SF 5-1 EF 5-1 TYP. DAMPERS
5-1, 5-2 & 5-3 VAV
5-1
SLC3
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
5TH FLOOR
SF 4-1 EF 4-1 TYP. DAMPERS
4-1, 4-2 & 4-3 VAV
4-1
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
4TH FLOOR
SF 3-1 EF 3-1 TYP. DAMPERS
3-1, 3-2 & 3-3 VAV
3-1
SLC2
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
3RD FLOOR
SF 2-1 EF 2-1 TYP. DAMPERS
2-1, 2-2 & 2-3 VAV
2-1
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
2ND FLOOR
SF 1-1 EF 1-1 TYP. DAMPERS
1-1, 1-2 & 1-3 VAV
1-1
SLC1
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
1ST FLOOR
FSCS
FIRE-FIGHTER'S SMOKE CONTROL PANEL
RS485
CyberCat 254
or 1016
(+)
SMOKE DETECTOR
TRIGGERS ALARM
(-)
(+)
(+)
(+)
Enter /
Exit
EF-1 Loading
ON Dock 1
AUTO
OFF
FAULT
SF-1 Loading
ON Dock 2
AUTO
OFF
FAULT
Throughway
No Door
EF-2 Loading
ON Dock 3
AUTO
OFF
FAULT
SF-2
Loading
ON
Dock 4
AUTO
OFF
FAULT
Enter /
Exit
SF 2-1 EF 2-1
SLC2
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM
DETECTORS ON OFF ON OFF
South Warehouse Area
SF 1-1 EF 1-1
SLC1
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM
DETECTORS ON OFF ON OFF
North Warehouse Area
FSCS
FIRE-FIGHTER'S SMOKE CONTROL PANEL
Enter /
Ex it
EF-1 Loading
Do ck 1
SF-1 Loading
Do ck 2
Z ON E 1
EF-2 Loading
Do ck 3
SF-2
Loading
Z ON E 2 Do ck 4
Enter /
Ex it
CyberCat 254
or 1016
Enter /
Exit
EF-1 Loading
ON Dock 1
AUTO
(-) (-)
OFF
FAULT
SF-1 Loading
ON Dock 2
AUTO
OFF
FAULT
Throughway
No Door
EF-2 Loading
ON Dock 3
AUTO
OFF
(-) FAULT (-)
SF-2
Loading
ON
Dock 4
AUTO
OFF
FAULT
Enter /
Exit
EAD-7 EAD-8
EF-7 EF-8
Enter / Enter /
Exit ZONE S7 ZONE S8 Exit
PRESSURIZE PRESSURIZE
AUTO AUTO
EXHAUST EXHAUST
Enter / FAULT FAULT
Enter /
Exit SAD-7 SAD-8 Exit
SF-7 SF-8
SF-4 EF-4
SAD-4 EAD-4
SLC 3
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
Typical Stores 4, 5 & 6
SF-1 EF-1
SAD-1 EAD-1
SLC 2
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
Typical Stores 1, 2 & 3
SF-8 EF-8
SAD-8 EAD-8
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
East Commons
SF-7 EF-7
SAD-7 EAD-7
SLC 1
(254 DEVICES MAX.)
SMOKE/HEAT MM RM MM MM RM MM MM RM MM MM RM MM
DETECTORS ON OFF ON OFF OPEN CLOSE OPEN CLOSE
West Commons
FSCS
FIRE-FIGHTER'S SMOKE CONTROL PANEL
RS485
E nter / E nter /
E xit E xit
E nter / E nter /
E xit E xit
CyberCat 254
or 1016
Enter / Enter /
Exit Exit
(-) (-)
Smoke Smoke
Enter / Detector Enter /
Detector
Exit Exit
Enter / Enter /
Exit Exit
(+) (+)
Smoke Smoke
Enter / Detector Detector Enter /
Exit Exit