Sei sulla pagina 1di 2

Customer Services for Transformers

SITRAM · Avoidance of major costs due to

Multisense 5
failures or outages
· Cost savings thanks to scheduled and
efficient transformer maintenance
· Easy mounting on a transformer
Monitoring and Diagnostics valve (installation without interrupt-
ing operation)
· Uses advanced software (the unit
and via PC)

Scope of work
Introduction · Easy to understand due to simple
· Configuration and administration of
In their average lifetime of 40 years, setup
each individual Multisense unit
transformers endure various forms of · Compact, robust design (IP55)
· Data and configuration read-out of
stresses that can contribute to a multi-
· High accuracy enabling comprehen- Multisense units
plicity of failures (electrical, thermal, sive early warning
chemical or mechanical). Transformer · Processing and visualization of data
· Various communication options
failures may cause e.g. costly damage · Read-out (trend or table)
to primary and secondary equipment, · Optional high- and low-voltage bush-
· Online functions (online sensors,
outages, environmental cleanup ing sensors for bushing monitoring
extraction status and process flow)
charges and a loss of reputation. applications from Siemens via com-
munication interface · Diagnostics functions
DGA (Dissolved Gas Analysis) monitor- (Duval triangle)
· Optional: 5 digital outputs, 5 digital
ing with SITRAM Multisense 5 helps optocoupler outputs, 5 analog out- · Further processing of the processed
utilities to avoid transformer failures. puts, 10 analog inputs data (Excel, CSV, clipboard and
printing)
SITRAM Multisense 5 indicates devia- · Monitoring functions:
tions and imminent faults by analyzing · Storage of the processed data and
o Voltage and current monitoring
the concentration of four dissolved key unit configuration
(via voltage and current trans-
gases in transformer insulating oil, and formers / transducer) · Automatic data read-out and alerting
moisture. This helps to predict and by e-mail
prevent four major fault types: o Temperature monitoring: lower
and upper oil temperature, ambi-
Overheated oil (monitoring C2H4) ent temperature (via additional
Partial discharge (monitoring H2) temperature sensors)
Overheated cellulose (monitoring CO) o Cooling stage / tap changer posi-
Arcing in oil (monitoring C2H2 ) tion monitoring (e.g. via current
transducer)
Features o Free configuration of analog in-
· Robust, NDIR measurement technol- puts, free allocation to any addi-
ogy without moving parts or refer- tional sensor
ence gas o Calculation of hot-spot (acc. to
· Easy installation directly at trans- IEC 60076), loss-of-life, ageing
former rate
Benefits
· Display and keypad enabling com-
prehensive configuration and setup · Monitoring of key gases inside the
without additional computer transformer oil, enabling recognition
of all potential failure types

siemens.com/td-services
· Standard electrical and mechanical
connection kit, individual mechanical Range Accuracy
connection kit on request
H2 0 - 2000 ppm ± 5% or ±LDL (whichever is greater)
· Installation flange (different ventila-
tion sizes available)
C2H2 0 - 2000 ppm ± 5% or ±LDL (whichever is greater)
· Turnkey installation and communica-
tions services (optional)
CO 0 - 5000 ppm ± 5% or ±LDL (whichever is greater)
· On-site training courses for operation
and maintenance for our systems C2H4 0 - 2000 ppm ± 5% or ±LDL (whichever is greater)
· Expert analysis of monitoring data
and customer support (optional) H20 0 - 100% ± 3 % or ±LDL (whichever is greater)

Technical Details * Accuracy quoted is the accuracy of the detectors during calibration
Operation Principle
· Miniaturized gas sample production · Power consumption: max. 350 VA
based on headspace principle · Housing: aluminum, W 263 x H 263 x Fault gas measurement
· No membrane, negative pressure D 327.5 mm SITRAM Multisense 5 is executed in
proofed · Weight: approx. 13.5 kg two steps: gas extraction (headspace
technique) and gas detection (non-
· Patent on oil sampling system (EP 1 · Operating temperature (ambient):
dispersive infrared radiation method).
950 560 A1) -55°C - +55°C (below -10°C display It measures the concentration of
· Near-infrared gas sensor unit for CO, function locked)
dissolved gases in the oil.
C2H2 and C2H4 · Oil temperature (inside transformer):
· Micro-electronic gas sensor for H2 -20°C - +90°C Discover Siemens comprehensive
transformer monitoring and sensor
· Thin-film capacitive moisture sensor · Storage temperature (ambient):
portfolio. For more information about
H2O -20°C - +65°C
Siemens comprehensive monitoring
· Temperature sensors (for oil and gas · Oil pressure: up to 800 kpa (negative package for transformers, please con-
temperature) pressure allowed) tact your local partner or our Customer
· Optional nominal voltages of auxilia- · Connection to valve: G 1½" DIN ISO Support Center.
ry supply: 120 V AC 50/60 Hz or 230 228-1 or 1½" NPT ANSI B 1.20.1
V AC 50/60 Hz or 120 V DC or 230 V · Safety: CE certified, Isolation protec-
DC tion: IEC 61010-1:2010/IEC 61010-2-
081, Degree of protection: IP-55

All rights reserved. Trademarks cited in


this document are the property of Sie-
mens AG, its affiliates, or their respective
owners in the scope of
registration.

Subject to change without prior notice.


The information in this document contains
general descriptions of the technical
options available, which may not apply in
all cases.

Siemens AG
Energy Management
Humboldtstr. 59
90459 Nuremberg, Germany
Customer Support Center
Phone: +49 (911) 433 78 78
E-mail: support.energy@siemens.com
© Siemens AG, 01.2018, V 1.0

Potrebbero piacerti anche