Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
REVISION STATUS
Description of
Issue Date Created Reviewed Approved
Changes
Morten
A 08/11/2018 David Walsh Lindegaard Pierre Girodet First version
Santiago Parent
Update to add
additional safety
recommendations
B 14/06/2019 David Walsh Pierre Girodet Pierre Girodet
+ update of
weight for
transportation
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 3 of 118
T AB L E O F C O N T E N T S
1. Introduction ........................................................................................................... 11
1.1. Intent of this Manual....................................................................................................11
1.2. Disclaimer Statement ..................................................................................................11
1.3. Proprietary Rights Statement ......................................................................................12
2. Health & Safety ..................................................................................................... 13
2.1. Safety Instructions ......................................................................................................13
2.2. Operator Care .............................................................................................................14
2.3. Personal Protective Equipment ...................................................................................15
2.4. Safety Notes - Following Installation ...........................................................................16
2.4.1. Electrical ..............................................................................................................16
2.4.2. Water ...................................................................................................................16
2.4.3. Chemicals ............................................................................................................17
2.4.4. Fire ......................................................................................................................17
2.4.5. Natural disasters ..................................................................................................17
2.5. Safety Notes - Daily Operation ....................................................................................17
2.5.1. Electrical ..............................................................................................................17
2.5.2. Water ...................................................................................................................18
2.5.3. Performance ........................................................................................................18
3. Actiflo Turbo ACP2 MK2 Process and Components Description..................... 19
3.1. Actiflo Turbo Process general description ...................................................................19
3.2. ACP2 MK2 Range: Description and Specificities ........................................................20
3.3. Parts description .........................................................................................................21
3.3.1. Tank ....................................................................................................................21
3.3.2. Mixers ..................................................................................................................22
3.3.3. Scraper ................................................................................................................22
3.3.4. Lamellas ..............................................................................................................24
3.3.5. Recirculation pumps ............................................................................................25
3.3.6. Hydrocyclones .....................................................................................................26
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 4 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 5 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 6 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 7 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 8 of 118
LIST OF FIGURES
Figure 1: ACTIFLO Process description ....................................................................................19
Figure 2: ACP2-60 scraper .......................................................................................................23
Figure 3: Motorisation of the ACP2-40 scraper..........................................................................24
Figure 4: Lamellas and outlet troughs during assembly in a workshop ......................................25
Figure 5: MA hydrocyclones from MA80 to MA1 .......................................................................26
Figure 6: Lifting lugs of the Actiflo .............................................................................................33
Figure 7: Installation of the scraper shaft...................................................................................39
Figure 8: Connection of the scraper shaft for large Actiflos .......................................................39
Figure 9: Coagulant injection recommended .............................................................................44
Figure 10: Sand pot Calculate the sludge concentration with the formula:.................................64
Figure 11: Start-up Screen ........................................................................................................71
Figure 12: Home Screen ...........................................................................................................72
Figure 13: Home Screen with Available Sub-Screens ...............................................................73
Figure 14: Login Screen - Empty ...............................................................................................74
Figure 15: Login Screen - Engineer Login Active ......................................................................75
Figure 16: Alarm Screen ...........................................................................................................76
Figure 17: Alarm History Screen ...............................................................................................77
Figure 18: Overview Schematic Screen ....................................................................................78
Figure 19: Overview Schematic Screen - with Engineer Override .............................................79
Figure 20: Mixer Pop-up Screen ...............................................................................................80
Figure 21 Dosing Screen ..........................................................................................................82
Figure 22: Starting Conditions Screen .......................................................................................83
Figure 23: Counters Screen ......................................................................................................84
Figure 24: Contact Screen ........................................................................................................86
Figure 25: Digital Inputs Screens ..............................................................................................87
Figure 26: Digital Outputs Screens............................................................................................89
Figure 27: Analogue Inputs Screen with Override .....................................................................90
Figure 28: Analogue Output Screen ..........................................................................................91
Figure 29: Options Screen ........................................................................................................92
Figure 30: System Information Screen ......................................................................................95
Figure 31: Timers Screen - Production ......................................................................................96
Figure 32: Settings Screen ........................................................................................................97
Figure 33: Dosing screen 1 .......................................................................................................98
Figure 34: Dosing screen 2 .......................................................................................................98
Figure 35: Instrument Limits Screen..........................................................................................99
Figure 36 Equipment Timer Limits Screen 1 ...........................................................................100
Figure 37 Equipment Timer Limits Screen 2 ...........................................................................100
Figure 38: Components maintenance guidelines.....................................................................103
Figure 39: Suggested material for lamella cleaning .................................................................105
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 9 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 10 of 118
L I S T O F T AB L E S
Table 1: Actiflo Tank dimensions, prepared for transport, with control panel .............................30
Table 2: Actiflo Tank dimensions, prepared for transport, with junction boxes ...........................30
Table 3: Disassembled components prepared for transport, with Control panel ........................30
Table 4: Disassembled components prepared for transport, without control panel ....................31
Table 5: Tightening torque for lifting lug bolts ............................................................................33
Table 6: Factor for initial micro-sand load calculation ................................................................50
Table 7: Coagulant type and dosing rates for Waste water applications ....................................58
Table 8: Coagulant type and dosing rates for drinking or process water applications ................59
Table 9: Flocculant type and dosing rates for Waste water applications ....................................60
Table 10: Flocculant type and dosing rates for drinking or process water applications ..............61
Table 11: Micro-sand specifications ..........................................................................................62
Table 12: Micro-sand concentration recommended ranges for Actiflo Turbo used in waste water
applications ...............................................................................................................................63
Table 13: Micro-sand concentration recommended ranges for Actiflo Turbo used in drinking
water or Process water applications ..........................................................................................63
Table 14: User Access Overview ..............................................................................................75
Table 15: System Options .........................................................................................................92
Table 16: Daily inspection tasks ..............................................................................................102
Table 17: Environmental conditions ........................................................................................110
Table 18: Feed water requirements.........................................................................................110
Table 19: Actiflo typical performance levels for treatment of ground or surface water (Drinking or
Process water applications) ....................................................................................................111
Table 20: Actiflo typical performance levels for treatment of Waste water (Municipal or Industrial
applications) ............................................................................................................................111
Table 21: Actiflo ACP2 MK2 process data...............................................................................111
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 11 of 118
1. INTRODUCTION
The Actiflo® Package Plant is manufactured and supplied by Veolia Water Technologies. This
equipment of proven design will ensure decades of trouble-free operation. However, in order to
reach and maintain peak efficiency and performance of the system, it is imperative to take into
consideration all guidelines described in this manual and also in the components manuals.
This manual may include original manufacturer’s literature. These manuals should provide
complete and accurate information to meet your operating and/or service requirements based
on the information available at the time of publication. However, Veolia Water Technologies
assumes no responsibility for the technical content of original manufacturer’s component
literature.
The information in these manuals may not cover all operating details or variations or provide for
all conditions in connection with installation, operation, and maintenance. Should questions
arise which are not answered specifically in this manual, contact the Veolia Water Technologies’
Service Department.
Veolia Water Technologies reserves the right to make engineering refinements that may not be
reflected in these manuals. The material in these manuals is for informational purposes and is
subject to change without notice.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 12 of 118
In the event the content of this manual is altered or section/items are omitted during a
reproduction, in whole or in part, and instructions or definitions within the reproduction result in
personal injury to those who follow the altered instructions, the burden of responsibility for
personal injury falls solely on the party who affects the reproduction.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 13 of 118
The safety instructions listed in this document must be read carefully and strictly adhered to in
order to reduce possible health hazards and to avoid dangerous situations.
In this chapter you will find general safety instructions that draw attention to hazards in the
handling of the system as well as unavoidable residual risks.
The “Safety” chapter is fundamentally important and must be read carefully and adhered to. It is
the only way to ensure that all operations and work on the system can be carried out safely and
correctly.
Not adhering to the safety instructions can result in danger to persons and material damages to
the system.
Please keep this Operator Manual & these safety instructions close to the unit so that they are
available for reference by the operators at all times.
To the Operator:
It is your responsibility to read & become familiar with the instructions in this manual.
If in doubt, seek guidance before carrying out an operation / procedure with this equipment.
are shown at various points in this manual for your protection - please take note of them.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 14 of 118
The plant / unit has been designed and manufactured to applicable harmonized standards and
technical specifications and with the greatest possible safety in all operating modes.
The safety of the plant / unit operation can only be achieved if all of the following points are
adhered too.
The plant / unit are operated only when in good functional condition. All safety devices
should be checked regularly to ensure proper functioning.
Personnel Protection Equipment (PPE) is available in good condition and used when
required.
The operating instructions are complete, readable and available on site for use on the plant /
unit.
Only trained, qualified and authorised personnel are permitted to operate, maintain and
repair the plant / unit.
Those personnel are instructed with regard to safe working practices and environmental
protection, and know the contents of the operating instructions and any safety notes.
All safety and warning labels on the plant / unit are visible, readable and are not removed.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 15 of 118
To minimise safety hazards, personal protective equipment has to be worn correctly during
operation of the plant.
Please respect any additional signs regarding personal protective equipment which are installed
in the plant area.
Protective clothing
Protective clothing is tightly fitted and resistant to tearing, with tight sleeves
and no external parts. It is mainly used to protect against being grasped by
moving machinery.
Do not wear rings, necklaces or other jewellery.
Safety gloves
Used to protect the hands from hot or cold surfaces and from contact with
hazardous substances.
Safety boots
Used to protect the feet from falling parts and slipping on slick surfaces.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 16 of 118
2.4.1. Electrical
Fire Risk!
The unit should not be installed near flammable liquids or gases.
Danger
Maintenance
Isolate / switch off the mains power supply before carrying out electrical work
on the control enclosure.
Only qualified personnel should carry out electrical work.
Warning On completing maintenance work close & lock the control enclosure.
2.4.2. Water
Where water ingress is possible / expected, ensure that measures are taken
to allow water to exit the electrical enclosure and / or provide a water leakage
sensor and alarm system.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 17 of 118
2.4.3. Chemicals
2.4.4. Fire
Fire Risk!
The unit should not be installed near flammable liquids or gases.
Lamellas are made in Polystyrene that is highly flammable. Submerge with
water as soon as possible after installation. Don’t perform any welding or
action that could ignite a flame next to the lamellas.
Hydrocyclones are made in Polyurethane that is flammable. It must not be put
Danger
in contact with direct flame.
Attention
2.5.1. Electrical
Make sure your hands and the place where you are standing is dry before
touching any live electrical components.
When working on electrical equipment make sure that the mains power has
been isolated / switched off.
Danger
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 18 of 118
Attention
2.5.2. Water
Ensure that all electrical enclosures are sealed & / or locked during operation
of the equipment.
Attention
2.5.3. Performance
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 19 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 20 of 118
In wastewater treatment, the ACTIFLO® process is appropriate for use in any application that
would benefit from physical-chemical treatment including coagulation, flocculation and settling. It
can be applied to primary and tertiary wastewater treatment where either better performance or
cost reduction is desired. It is ideally suited for storm water treatment including CSO, SSO or
other overflows due to its high performance, small footprint, and extremely short start-up time. It
is also suited for clarification after fixed-film processes. It can also be used for the treatment of
Biofilter and Sand filter backwash water treatment. The process consistently displays efficient
removals of TSS, BOD, Total P, COD, metals, fecal coliform, and other typical wastewater
contaminants, which can be removed by physical-chemical processes.
In drinking water treatment and process water treatment, the ACTIFLO® process is appropriate
for use in any application that would benefit from physical-chemical treatment including
coagulation, flocculation and settling. It can be applied to both ground water and surface waters
where either better performance or cost reduction is desired. It is ideally suited for difficult to
treat waters such as rapidly fluctuating sources or extreme raw water conditions. The process
consistently displays efficient removals from raw waters containing Turbidity (high and low),
Color, TOC, algae, particle counts, Cryptosporidium, iron, manganese, arsenic and other typical
undesirable water contaminants.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 21 of 118
The complete tank with the 5 compartments has a cuboid shape. The models ACP2-15 to
ACP2-40 are slightly different from the 5 other models as the 3 reaction compartments are
elevated with an empty space below for the installation of recirculation pumps
Operators can access the top of the tank using a dedicated ladder. The Actiflo Turbo Pack
standard design includes ladder access although it can sometimes be modified to allow for the
installation of stairs. The top of the tank is covered with composite gratings and surrounded by
handrails in coated steel.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 22 of 118
All models, except ACP2-15, have the treated water section, including a part above the lamellas
that is not covered with gratings.
3.3.2. Mixers
Each ACP2 mk2 unit comes with 2 mixers in the standard model (coagulation mixer and
flocculation mixer) and one optional mixer (extended coagulation). They are hanging mixers,
supported by a plate in coated carbon steel, which is bolted to support beams that are bolted to
the tank walls.
They are composed of a motor reducer flanged to a shaft with a3 blade impeller bolted to the
shaft. Standard wetted materials are in SS304L but can be changed to alternative materials in a
non-standard design.
The extended coagulation mixer (when included) pumps upward and rotates clockwise.
The coagulation mixer pumps downward and rotates counter-clockwise.
The flocculation mixer pumps downward and rotates clockwise.
The flocculation mixer is VFD driven and is normally designed to work optimally at 45 Hz. At
start-up, the flocculation mixer rotates at 50 Hz for a short period to ensure that all of the micro-
sand that may have settled in the flocculation compartment is put back in suspension for
creating new ballasted flocs. In certain specific cases, flocculation performance can be
improved by adjusting the frequency between 40Hz and 50 Hz.
For more information on mixers, please refer to the specific supplier manual.
3.3.3. Scraper
The ACP2 mk2 scraper rotates in the settling compartment, with arms that scrap the circular
bottom of the compartment. The scraper moves the micro-sand that has settled at the bottom of
the hopper to its centre where a collector captures the accumulated sludge.
The hydraulic part consists of a vertical shaft bolted to 2 arms. Each arm is retained to the shaft
with radial support plates (ACP2-15 to ACP2-55) or with radial tenders (ACP2-60 to ACP2-75).
All these hydraulic parts are in SS304L in the standard version. In order to cover any issue with
dimensional tolerances that could have occurred during fabrication, the vertical shaft is design in
2 sections that are bolted, with the possibility to insert adjustment disks between the flanges to
increase the length of the shaft. There can be up to 3 disks inserted between the 2 parts of the
vertical shaft of the scraper.
2 sets of rubber pads (EPDM) are installed on each arm. These pads are adjusted to scrape the
bottom of the settling hopper.
There are 2 different reducer designs:
- ACP2-15 and ACP2-30 scrapers are designed with a solid shaft that is connected to a
hollow shaft reducer with helical gears.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 23 of 118
- ACP2-40 to ACP2-75 scrapers are designed with a hollow shaft separated into 2 flanged
parts. They are flanged on top to a planetary reducer. The planetary reducer (called
MECTAN) is then connected to a reducer (helical gear type) using a keyed connection
(on reducer side) inside an hollow sprocket (on Mectan side)
In both cases, the gear reducer is connected to a motor–reducer. Also, to ensure the scraper is
not rotating while there is an abnormal torque, there is a speed controller between the gear
reducer and the motor-reducer. In case of scraper blockage (for example if a tool falls down in
the settler and prevents the scraper from rotating normally), the speed controller sends a signal
above a certain torque. With the standard control panel, this signal initiates an emergency stop.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 24 of 118
For more information on the motor-reducer, the speed monitor or the gear reducer, please refer
to the specific supplier manuals.
3.3.4. Lamellas
The ACP2 mk2 proposes two types of lamellas: for drinking/process water and for wastewater.
They are both made of plastic plates welded together to create tubes that have a honeycomb
shape. The main difference between them is the size of the tube (hydraulic diameter) that is
bigger for the waste water version.
In certain specific waste water treatment applications (for example for phosphorous removal in
tertiary treatment), the drinking/process water lamella can be used to enhance treatment
efficiency.
Lamellas are assembled in blocks of several lamellas and several blocks are installed on top of
the settler to cover the entire surface. The lamellas are supported by stainless steel shaped
bars on the bottom and are installed below adjustable anti-floating bars that are connected to
the outlet troughs.
WARNING: Lamellas are made of HIPS (High Impact Polystyrene) that is highly
flammable. Submerge in water as soon as possible after installation. Don’t
perform any welding or action that could ignite a flame next to the
lamellas.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 25 of 118
The motor of the pump is connected to the shaft using a belt and pulley transmission system
that is inside a metallic protective casing. The shaft is connected to the impeller using a dry
gland system that doesn’t require water lubrication as long as the shaft is perfectly adjusted.
The impeller is also lined with rubber.
WARNING: Don’t operate the pump when the metallic protective casing is not
installed. There is a serious risk of injury if you do so.
For more information on the recirculation pumps, please refer to the specific supplier manuals.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 26 of 118
3.3.6. Hydrocyclones
Hydrocyclones are polyurethane devices used to separate sludge from sand. The sand is sent
to the bottom of the hydrocyclone in order to re-inject it inside the flocculation compartment. The
sludge is sent to the top of the hydrocyclone in order to extract it for possible further treatment
outside of the Actiflo.
There can be one or 2 hydrocyclones per Actiflo according to configuration selected.
The specificity of the Hydrocyclone used by Veolia is the possibility to use service water to wash
the micro-sand before it is re-injected into the system. In certain cases, it can improve the global
efficiency of the Actiflo. In the standard model, there is no pipework installed for service water
but this can be added as a modification or directly on site. This is particularly useful for high
concentrations of sludge or to control possible bacterial growth.
For more information on the hydrocyclones, please refer to the specific manual from Veolia.
3.3.8. Instruments
In the base scope of supply, the Actiflo is equipped with a:
- Treated water pH meter
- Treated water turbidity meter
- High level switch
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 27 of 118
The raw water pH meter and turbidity meter are supplied separately along with an insertion ball
valve and must be installed on site before the Actiflo, directly on raw water inlet pipework.
The flow meters used are electromagnetic. The inlet flow meter is supplied separately and must
also be installed on site before the Actiflo, with the metering part flanged on the raw water
pipework and the transmitter installed nearby (distance limited by cable length as defined in
instrument schedules).
The transmitters in the recirculation flowmeters are integrated in the metering part.
For more information on the instruments, please refer to the specific supplier manuals.
3.3.9. Valves
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 28 of 118
As an option, a control valve can be supplied for inlet flow control. It is a motorized butterfly
valve with a body in coated cast iron and closing device in SS316. It is supplied separately and
must be installed on site upstream from the Actiflo, directly on the raw water inlet pipework
For more information on valves, please refer to the specific supplier manuals.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 29 of 118
After testing in the workshop and before transportation, most components are disassembled
from the Actiflo tank. The tank itself is covered by a tarpaulin on top. The scraper hydraulic part,
the lamellas and the gratings are kept in/on the tank during transport. For the ACP2-15, ACP2-
30 and ACP2-40, the recirculation pump(s) and some pieces of pipework are kept assembled
for transport.
Disassembled components are packed into wooden crates that are suitable for transport inside
general purpose containers which are transported inside covered trucks.
The control panel or the junction boxes (depending on option selected) that is/are attached to
the Actiflo wall is/are kept installed on the Actiflo wall except if requested otherwise by the client.
They are covered by waterproof plastic, which protects them from moderate rainfall for a short
period of time. The panel/junction boxes packings are not suitable for storage outdoor.
It is the responsibility of the company contracting the transport/carrier company to plan for any
extra packing required. Depending on contracts, it may be another company than Veolia that is
managing transport. The extra packing can usually be done in the Veolia workshop at an extra-
cost.
When there is the possibility of roads being salted, it is advised to completely cover the tank
walls with plastic to avoid premature corrosion. Additionally, if the wooden crates are
transported uncovered or stored outside, it is advised to provide extra-protection against
rain/water on top of the wooden crates.
Dimensional information hereafter is preliminary and provided for informational purposes only.
For each order, the real order-specific packing list would be provided by Veolia Water
Technologies.
Each Actiflo tank, prepared for transport, has different dimensions as listed in the tables
hereafter. The ACP2-15 can be transported inside an open top container but for all other
models, transport shall be done with flat rack container or a low bed truck.
For the ACP2-75, if you need to transport by sea, it is better to consider dismantling the control
panel for transport. By doing this, you would have a total length of 11.8m that fits in most 40ft
FR containers (depending on container manufacturing site). Please refer to the outline and
connection drawings for precise dimensions of the ACP2-75 tank.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 30 of 118
Table 1: Actiflo Tank dimensions, prepared for transport, with control panel
Table 2: Actiflo Tank dimensions, prepared for transport, with junction boxes
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 31 of 118
The condition of all delivered components must be verified by the responsible party upon
delivery (usually EXW or DAP depending on contracts). Verification that all equipment has been
delivered as per contract must also be done upon arrival at the site. Notification of missing or
damaged items must be sent to VWT within 2 weeks after reception of the equipment.
If items are damaged during transport the impact must be discussed with VWT to ensure that
installation is possible without incurring significant risks.
VWT is not responsible for the replacement of any items found to be missing or damaged at the
time of installation and start-up of the supplied equipment. It is the responsibility of the party
receiving the equipment to ensure that all packaging is opened at the time of receipt and to
identify and document any and all damage which must be reported to the freight company and
VWT. Photographs and written documentation should be provided concerning all damaged
equipment.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 32 of 118
- Two operators in charge of assisting lifting which includes positioning hooks, avoiding rotation
of the tank, helping the crane operator to position the tank, etc.
- One supervisor in charge of checking that materials are suitable before starting the lifting
operation, of checking that the operation is doable (space, loads,…) and safe, and that all
persons involved are trained and protected with suitable equipment,…
They should be able to communicate using a walky-talky (or equivalent).
Before starting the lifting, make sure there is no water in the tank. Verify that there are no loads
other than the tank, the scraper and, if applicable, the control panel (+ the pump(s) for the
ACP2-15, ACP2-30 and ACP2-40) are applied while lifting the Actiflo tank. Other elements such
as handrails, ladder, motors, etc. must not be installed while lifting the tank. Before lifting,
inspect carefully to ensure that there are no damaged or loose items that could cause injury or
damage the equipment.
WARNING : The Actiflo tank must be lifted using the 4 removable lifting lugs. Don’t
use the welded lugs that are on the corners of the tank (that are only used
during tank fabrication). Lifting related tasks such as unloading should
only be performed by qualified staff
In the figure hereafter, 2 of the 4 lifting lugs that must be used are circled in green. The 4 lugs
crossed in red must not be used for lifting the Actilo tank (on both sides of the Actiflo tank).
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 33 of 118
The 4 removable lifting lugs must be bolted with the protective rubber pad placed between the
tank and the lugs. (to avoid scratching the coating of the tank). The lugs must be oriented
toward the tank as per Figure 6. The torque of the lifting lug bolts must be tightened as per the
following table. It is mandatory to use carbon steel 10.9 class bolts or above, never below. If
these guidelines are not respected, significant damage can occur on the tank and could lead to
hazardous situation for the operators.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 34 of 118
Slings or chains, designed to withstand the weight of the tank, must be used. A minimum length
of slings/chains must be used to ensure there will always be an angle of at least 60° between
the surface of the tank and each sling/chain, as indicated on Figure 6. In case of height
limitations restricting the possibility of having an angle of at least 60°, one or two suitable
spreaders should be used. If these guidelines are not respected, significant damage can occur
on the tank and could lead to hazardous situation for the operators.
The length of each sling/chain must be adjusted to ensure that the tank will remain stable and
upright during the lifting operation. If required, an additional suitable device must be used to
avoid rotation of the tank.
If it is not possible to directly unload the tank to its final location, suitable equipment shall be
used for transportation of the tank between the unloading area and the final installation position.
Ensure that the means used to transport the tank will not jeopardize the mechanical integrity of
the tank, damage the coating or damage the control panel.
4.3. STORAGE
The following instructions outline the duties and responsibilities of the responsible party for
equipment storage. The responsible party shall assume responsibility for the equipment upon
arrival at the project site. These instructions shall define the minimum expectations for storage
of all equipment.
While this storage specification takes into account common environmental issues that may
affect the system during storage, common sense should be the overriding factor in determining
the best method to ensure the integrity and proper storage of the VWT equipment. In any case,
all drain valves should be kept open during storage to avoid any issue in case of flooding.
Should it be necessary to delay installation and subsequent operation of a unit for more than
one month from date of shipment, special precautions must be taken. If possible, all equipment
should be stored indoors in a dry and sheltered environment having a relatively constant
temperature (especially for gear reducers, motors, bearings, etc.).
Air may contain excessive moisture, pollutants, microorganisms, and other particulates that
accelerate the deterioration of some materials. Humidity and pollutants can produce an
aggressive atmosphere.
The storage environment into which a system is placed can have a dramatic effect on the long-
term usefulness of some spare parts. Key environmental factors are:
1) Temperature
2) Relative Humidity
3) Pollutants
The environmental indoor conditions should not exceed the following ranges:
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 35 of 118
For mixers, scrapers and recirculation pumps, long term storage methods (including complete
lubricant filling) must be applied to the equipment. Protect machined surfaces and rotate shafts
periodically (every month). Five complete rotations of the output shafts are recommended each
time.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 36 of 118
Periodic checks should be made to ensure that no rusting or other damage has occurred.
Should such be noted, corrective action should be quickly initiated. Prior to putting unit into
service, drain lubricant and refill to proper level as determined by the mounting position. Refer to
manufacturer documentation.
All motors must be removed and stored indoors (in a heated and ventilated area). All motors
must be run every 3 months to prevent corrosion.
It is recommended that tanks and pumps be stored indoors and on a raised surface to avoid
flood damage, however if this cannot be done, they must be placed on secure, high ground and
meet all other specifications provided in this document. The responsible party must be sure to
elevate the equipment off of the ground.
If the equipment is stored outdoors it must be kept on high ground not susceptible to flooding
and elevated at least 250 mm off the ground. If there is reason known to the responsible party
that more than 250 mm of elevation is required, appropriate measures should be taken.
Completely cover the equipment with a tarp or similar protective shield to prevent direct
exposure to the elements (dust, rain, snow, etc.). The tarp should fit tightly around the
equipment to prevent any type of accumulation beneath tarp. Equipment must be checked on a
weekly basis to ensure tarp integrity and absence of any accumulation.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 37 of 118
Load and foundation drawings can be provided by Veolia for the tank, the control panel (if
applicable) and the recirculation pump (if applicable). Ensure that the concrete slab that will
support the Actiflo is designed to withstand the load, especially the ring that is below the settler.
It is advised to install the tank directly on concrete.
Make sure the concrete is dry and clean before placing the Actiflo tank. The concrete slab below
the tank must be sufficiently level. It shall be levelled within +/- 3mm every 3m in any direction
and within +/- 10mm on all the surfaces that will be covered by the tank baseplate. These
guidelines are mandatory to avoid any mechanical damage to the tank during operation, due to
stress on steel plates and tubes caused by an unlevelled surface.
When the Actiflo tank is positioned properly, seal the gap between the tank baseplate perimeter
and the concrete. The use of a dedicated product, such as polyurethane sealant (example
Sikaflex 11FC) is mandatory. This seal is required to avoid possible water infiltration that could
lead to corrosion of the tank. No anchor bolts are required with the standard design. In specific
cases with special design requirements which are adapted for local seismic or cyclonic
constraints, a different design with anchor bolts might be considered. Please refer to order-
specific drawings in this case.
Inspect all coating to ensure there is no damage. If scratches are identified, touch up must be
performed by qualified personnel wearing suitable personal protective equipment, as indicated
on the coating supplier documentation.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 38 of 118
Check that the 4 top lifting lugs have been unbolted and removed before starting assembly.
Then, follow the steps listed below.
5.2.2. Mixers
The mixers are delivered separately. On site, the contractor must attach the impellers to the
shaft hub and the shaft to the gear box flange.
Install the motor on the appropriate tank mixer following the instructions given in the supplier’s
equipment manual. You might need to temporarily remove some of the grating plates while
doing so.
Verify the mixer blade installation and orientation (as described in chapter 3.3.2)
Verify that the set screws which secure the hub onto the shaft are well tightened.
Follow manufacturer recommendations for oil check and fill up procedure (supplier manual).
5.2.3. Scraper
In order to install the scraper motor reducer, you will need to consider the following sub-steps:
1. Connect the shaft top eyebolt to a suitable lifting device
2. Remove the transportation plate from the rake assembly.
3. Lower the shaft of the rake using the eyebolt. Be careful to do it slowly to avoid any
damage to the coating at the bottom of the tank.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 39 of 118
5. Ensure that there is no contact between the rake arm and the bottom of the hopper. The
height of the rubber pads can be adjusted. Also, if the arm is too short, extra-disks can
be inserted in the central connection of the shaft. The inside of the settler can be
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 40 of 118
accessed using the internal manhole located between the flocculation tank and the
settler.
5.2.5. Gratings
Reinstall all gratings as they were at delivery and ensure that the plates are bolted tightly
together so as to avoid any movement. Install gratings properly to avoid any risk of falling. There
must be at least 4 clips per grating.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 41 of 118
complete recirculation line, install the blind flange on the second branch of the Y
connection
- Connect the outlet of the pump(s) to the hydrocyclone(s) using the different HDPE pipe
spools, attaching them to the tank wall using dedicated pipe supports.
- If applicable, install the recirculation line flow meter(s) (optional item).
- Install the pressure gauge(s) and the pressure transmitter(s) with their dedicated
isolation valves.
- Install the last piece of HDPE pipe at the outlet of the hydrocyclone (top part).
- Install the sand pot and connect it to the recirculation pipe(s), using the small diameter
pipe spools available and associated valves. Thread the bottom valve of the sand pot.
At every step, it must be ensured that all required supports are properly bolted and installed.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 42 of 118
5.4.3. Drains
All drain valves (TP05, TP06 and TP07) shall be connected to a common drain collector. The
drain collector must be self-supported and should not apply significant stress on the drain
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 43 of 118
valves. It is usually recommended to have the drain collector connected to a trench drain.
Ensure that there is no counter pressure on this drain so as to be able to empty the Actiflo tank
when required. Suitable seals (not in Actiflo scope of supply) must be used to avoid any leaks.
Ensure bolts are installed in the proper order (following the shape of a star) with suitable torque.
In certain exceptional cases, service water can be also used on the hydrocyclones (for specific
applications such as Actiflo Carb or when there is the need to have a very low return of sludge
from the hydrocyclone). In such cases, when required, connect the dedicated hydrocyclone
nipple to the service water with the required flow and pressure control devices. For more
information, refer to the hydrocyclone manual.
5.4.6. Chemicals
A proper use of chemicals is mandatory to ensure the performance levels of the Actiflo.
Coagulant must always be injected into the raw water inlet pipework, upstream from the Actiflo.
A suitable connection from the coagulant dosing pump(s) to this pipe should be installed. It is
recommended to use specific devices such as injection quills or static mixers to ensure that the
chemical is evenly dispersed in the raw water before entering the Actiflo tank. This last
recommendation is advised for all applications except waste water primary treatment where
there could be clogging of the static mixer.
In any case, it is recommended to inject the coagulant near the center of the raw water pipe as
per the Figure 9. If a simple T branch on top is used, the liquid will spread mainly at the surface
of the water in the main pipe, leading to poor dispersion and possibly corrosion.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 44 of 118
Certain types of coagulant require dilution before injection (concentrated PolyDADMAC and
polyamine e.g. above 20-30% of active product). In this case, ensure that the dilution point is
placed so that there is less than 5s contact time to the injection point.
In some cases, it is also necessary to adjust the pH of the raw water in order to improve
coagulation and/or flocculation. Inject the suitable pH adjustment chemicals downstream from
the raw water pH meter and upstream from the coagulant dosing point. Usual pH adjustment
chemicals such as Acid or Soda have a contact time in raw water of 10 seconds before the
coagulation dosing point. Some others, such as lime, used in specific applications need a longer
contact time in raw water (around 2 minutes) and in some cases, mixing is required before the
coagulation dosing point. It is recommended to have a pressure loss of at least 0.3 m between
the pH injection point and the coagulant injection point to ensure good preliminary dispersion. It
is also recommended to install the pH adjustment chemicals in the same way as the coagulant
injection chemicals in order to prevent corrosion issues.
The use of polymer is always required in the Actiflo process. It is always necessary to dilute
polymer 3 to 10 times the capacity of the metering pump. The diluted polymer inlet pipe must be
connected to the dedicated connection TP04. A significant head loss between this connection
point and the dilution water injection point must be taken into account. Therefore, in some
cases, it is required to install a static mixer. Ensure that the pipework used to transport the
polymer before and after dilution has a large enough diameter to avoid clogging. Verify that the
metering pump selected is suitable for the pressure losses expected in the pipework and that
dilution water with enough pressure is available.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 45 of 118
It is highly recommended to use only powdered polymer. More detailed information is available
in chapter 8.4.
The only exception is for storm water applications. During storms, it is usually necessary to dose
much more polymer than during standard operation, but enough time is needed to dissolve and
maturate the polymer (1 to 2 hours). Therefore, emulsion type polymer can be used for the first
2 hours, until enough flow from HYDREX powdered polymer is available.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 46 of 118
6. ELECTRICAL INSTALLATION
Electrical installation must be done by qualified electricians who are employed by a qualified
sub-contractor, in accordance with local laws and regulations. Only authorized personnel, using
suitable Personnel Protection Equipment, shall be able to access the Actiflo Area during
electrical installation, until the person in charge of safety determines that access is safe.
6.1. GROUNDING
Grounding must be done on relevant components in accordance with local regulations.
Wiring for all components that are installed on the tank or recirculation lines is done in the
Veolia workshop before FAT. As most components are disassembled before shipping,
connections to motors, instruments and emergency stop shall be made again on site. All the
cables related to these components installed on the tank are pre-installed in cable trays. Refer
to wiring diagrams to ensure that all connections have been made correctly.
If optional instruments or an inlet control valve are installed on the raw water inlet pipework,
cable trays and wiring must be installed made between these components and the junction box
or control panel.
During this step, Ensure that all electrical connections are properly tightened.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 47 of 118
WARNING : At this stage, verify that all handrails, gratings and related safety
equipment is now properly installed and tightened.
A complete check list for pre-commissioning (dry tests), commissioning (wet tests) and start-up
(process performance tests) is in ANNEX A. It is recommended to take pictures of all of the
components at these 3 steps (maintaining the same level of light as much as possible). This
check list must be filled in and a record kept throughout the warranty period (at minimum), as it
will be required in case of malfunction.
The minimum number of points, to verify before commissioning, are listed below. Use your good
judgement to determine if there are any other points to verify. Any additional verification
required according to project, site or local regulations must be also made.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 48 of 118
only, ensure that the scraper torque switch is properly installed and set-up as per the
supplier manual. Take special care to verify that the high level switch is working
properly. The pH and turbidity meters are normally calibrated in the factory but for
certain orders or for instruments that are not in the Actiflo scope of supply, calibration
must be done on site before commissioning. Check the FAT report of the Actiflo to
ensure that instrument calibration has been done and that the parameters used are
appropriate for your site.
14. Check that the graduations have been put on the sand pot and verify that they are
accurate.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 49 of 118
A complete check list for pre-commissioning (dry tests), commissioning (wet tests) and start-up
(process performance tests) is in ANNEX A.
It is recommended to take pictures of all of the components at these 3 steps. This check list
must be filled in and a record kept, throughout the entire warranty period (at minimum) as it will
be required in case of malfunction.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 50 of 118
continuous micro-sand dosing system is installed on your site, review the storage and
dosing systems compliance with dedicated checklists. This task must be performed by
qualified personnel, using the suitable Personnel Protection Equipment such as
protection against heavy loads (helmet, safety shoes, etc) and protection against sand
and dust (Dust masks, respirators, etc).
9. For special applications such as Actiflo Soft and Actiflo Carb, check the related
equipment utilities (dosing screw, dilution water, etc.)
At start-up or after full drainage, load the appropriate amount of micro-sand taking into account:
The targeted concentration in the flocculation tank (usually between 3 g/l and 15 g/l,
depending on the application
Sand losses that always occur during start-up
Flocculation adjustments.
This value must be calculated multiplying the factor below by the targeted sand concentration,
as per the Table 6 hereafter.
For example, the initial loading of sand should be 1 355 kg for an ACP2-45 with a targeted
microsand concentration of 5g/l in the flocculation tank. In certain cases, when particular issues
are encountered during start-up, it might be necessary to use more than this calculated weight.
It is usually recommended to have at least twice the recommended weight stored on site, in
case of such an occurrence.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 51 of 118
Check that the treated water pipe is not routing the outlet water to production during start-up (it
should go back to the inlet of the treatment plant, back to the inlet of the Actiflo or go directly to
the drain).
Verify that the sludge outlet collector lets the sludge drain freely. If required to avoid damage to
sludge treatment, route the outlet to the drain.
You can then let the raw water flow into the Actiflo. Stop the raw water immediately if you detect
any possible leakage and determine how to solve the leakage issue. Stop the unit, empty it as
required, clean it as required, inspect it and repair or reinstall any item responsible for the leaks.
These tasks must be performed by personnel using suitable Personnel Protection Equipment at
every step.
When the tank is completely filled and not leaking, follow these steps:
1. Check that all the VFDs have been configured with a suitable and safe ramp up
2. Start the mixers one after the other to ensure there is no abnormal vibration. It is normal
to have significant vibration at start-up of the coagulation mixer(s) but this should be less
than few mm after 2 minutes.
3. Run the scraper for a complete rotation at minimum to ensure there is nothing
preventing it from rotating freely.
4. Run the recirculation pump(s) and check that there is no leakage from the gland. At
start-up, there may be a few drops from the dry gland but after few minutes, there
shouldn’t be any more. If there are any leaks or any other problems such significant
noise or abnormal vibrations, stop the pump(s), close the pump’s inlet gate valve(s) and
follow the instructions in the pump supplier manual.
5. When the recirculation pump is running properly, record the pressure indicated in each
recirculation pipework pressure gauge. Then compare them with the value indicated by
the pressure transmitters. If they differ significantly, recalibrate the pressure transmitter
following the supplier manual. Compare these values with the guidelines available in the
hydrocyclone manual to ensure that the pressure measured is in the normal working
range of the cyclone
6. Review the water level at the outlet troughs. The water should flow inside the outlet
troughs equally in each V-notch all along the outlet trough but should also be divided
equally between each different trough. To ensure this is the case, measure the level of
water in each trough and adjust the position of each trough until you have the same
height of water in each trough (+/-2mm), and good flow distribution along the V-notches
of each trough.
7. When all this is done, start the polymer maturation in the preparation unit during a
minimum of 1h, preferably 1h30.
8. When the polymer is ready to be used, open the valve VM80-02 (if you have 2
recirculation lines, also open the valve VM82-02) and ensure you have a flexible pipe
going to the hydrocyclone underflow. Start the metering pump and check that polymer is
flowing into the Actiflo.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 52 of 118
9. You can then also start the coagulation dosing pump (and pH adjustment pump if
applicable). Ensure that the chemicals are flowing to the raw water inlet pipes.
10. Review the values of each instrument to be sure there are no calibration issues.
When you are sure that automation is working as planned, you can proceed with process start-
up. Start-up should only be done by trained staff who must have a good knowledge of the Actiflo
Process.
Firstly, setup the chemical dosing rates as per JAR tests results. Then start the Actiflo, the
chemical dosing sets, ensure that polymer maturation has been done for at least one hour and
begin to load the microsand. To reduce sand loss, you can usually double the polymer dosing
rate for the first few hours.
Before starting to load the microsand, Make sure you have the required personal protection
equipment:
mask and goggles to prevent microsand inhalation or contact with the eyes.
safety shoes and a helmet to avoid injuries if sand bags fall
hearing protection as you will be exposed to motor noise for a long period of time.
After 30 minutes, you should measure the sand concentration in the maturation tank. Take a
sample of water in the section that is between the flocculation tank and the settler. Be careful to
wear proper personal protection equipment if you need to remove some gratings to access this
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 53 of 118
part of the water. If the microsand concentration is below the value defined during the JAR tests,
you should check that there is not significant leakage of micro-sand in the sludge outlet.
If you find out that there is significant leakage in the sludge outlet, it might mean that the
hydrocyclone is clogged or blocked with a foreign object. In this case, you should stop the
Actiflo, dismantle the hydrocyclone and open it for inspection. Follow the hydrocyclone manual
to perform this task, while wearing personal protection equipment (especially safety shoes and
helmets for all personnel working around the Actiflo).
If there was no significant leakage, then you can add up to 10% more micro-sand compared to
initial loading that you calculated, using the same filling method as previously. After 30 minutes,
measure the microsand concentration again in the maturation tank. If you don’t detect a micro-
sand concentration increase in the flocculation tank, there might be an issue with chemical
dosing (not enough polymer), maturation mixer speed (must be between 45Hz and 50 Hz) or
the hydrocyclone duty point (a too high recirculation flow that induces microsand loss). If you
notice an increase in microsand but concentration remains below the value defined during JAR
tests, you can repeat this refilling with up to 10% additional sand until you reach the targeted
microsand concentration.
When the optimized microsand concentration is reached, the recirculation flow rate must be
adjusted.
The optimum recirculation flow rate is normally defined by Veolia experts during the design
phase.
It is usually defined to maximize the sludge outlet concentration, taking into account the treated
water quality expected.
Firstly, adjust the frequency of each recirculation pump until the calculated optimum
recirculation flow rate is reached. If there are 2 recirculation lines in duty, ensure they are set-up
at the same frequency.
Secondly, it is recommended (but not mandatory) to adjust the recirculation flowrate to reach a
concentration of sand + sludge of 150 g/l at the inlet of the hydrocyclone. In certain cases with
highly loaded waste water, it is not possible to reach 150 g/l because of limitations in sludge
outlet concentration. When setting up the recirculation flow, always ensure that the sludge
concentration at the hydrocyclone outlet stays below 10-15 g/l. It is not recommended to exceed
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 54 of 118
these values to avoid clogging of the recirculation line and/or losses of microsand in the sludge
outlet. Always take into account the most limiting factor when defining the optimum recirculation
flowrate.
To do so, with the pump(s) adjusted at the calculated optimum flow rate, measure the sand +
sludge concentration at the hydrocyclone inlet and sludge concentration. This can be done
using the sand pot as defined at the end of chapter 8.5.
Determine which factor is the limiting one and then adjust the frequency of the pump(s) to be at
the value defined in the paragraph above.
For example, if you measure a sand+sludge concentration of 130 g/l and a sludge concentration
of 8g/l, the most limiting factor is the sand + sludge concentration (130/150=87%) compared to
the sludge concentration (8/15=53%). In this case, it is recommended to decrease the flow rate
by a factor of 1.15 (100/87), but only if the targeted flow remains in the hydrocyclone normal
operating range.
When you have reached this optimum recirculation flow rate, wait 30 minutes and then use the
sand pot to check that there is no significant quantity of microsand in the sludge.
If there is a significant amount of microsand in the hydrocyclone sludge outlet (more than
1/1000 of recirculation sand mass load), then the recirculation flow rate might need to be
reduced or increased.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 55 of 118
If the Actiflo has been delivered with the standard control panel, shutdown can be initiated on
the HMI or remotely through the PLC Ethernet connection.
The key element of shutdown is that the recirculation pump will run for a certain time that must
be adjusted to ensure it will remove all of the sand that is in the settler.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 56 of 118
For exceptional maintenance activities on the scraper, it is necessary to fully drain the settler.
To do so, first perform a normal shutdown procedure. Then, run the recirculation pump(s) until
the settler is nearly empty. It is normal to have a small part of the water recirculated that will
come back to the settler (around 10-20%). To avoid losing time, you can run the pump(s) with
the VFD set at 50 Hz. Be careful to stop the recirculation pump(s) before the settler is
completely empty or there could be significant damage done to the recirculation pump(s) glands
in only few minutes of dry-running. Ensure that 2 to 5 cm of water remains inside the settler.
After waiting 5 minutes, you can perform start up as described in the chapter 8.2.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 57 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 58 of 118
Table 7: Coagulant type and dosing rates for Waste water applications
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 59 of 118
Table 8: Coagulant type and dosing rates for drinking or process water applications
Turbidity and colour Hydrex 3250/ Hydrex 3255/ HYDREX 3240/ HYDREX 3240/
(T<6°C) prefer Al 3ppm/mg DOC* + 1ppm 3ppm/mg DOC + 1ppm 1.5ppm/mg DOC + 1ppm 1.5ppm/mg DOC +
< 1000 <5 < 20
coagulant when Fe/50NTU Fe/50NTU Al/50 NTU 1ppm Al/50 NTU
water is cold (expressed as Fe°) (expressed as Fe°) (expressed as Al°) (expressed as Al°)
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 60 of 118
Table 9: Flocculant type and dosing rates for Waste water applications
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 61 of 118
Table 10: Flocculant type and dosing rates for drinking or process water applications
Turbidity and colour - Powder: Hydrex 3511 DR, 3621 Powder: Hydrex 3511 DI, 3621
HYDREX 3841 ,3842/
Total hardness < 50ppm < 1000 <5 DR, 3631 DR, 3552 (DR) DI, 3631 DI, 3552 (DI)
0,5-1 ppm
CaCO3 0,1-0,2 ppm 0,1-0,2 ppm
Turbidity and colour - Powder form : Hydrex 3521 DR, Powder form : Hydrex 3521 DI,
HYDREX 3841 ,3842/
Total hardness > 50 and < < 1000 <5 3523 DR 3523 DI
0,5-1 ppm
80ppm CaCO3 0,1-0,2 ppm 0,1-0,2 ppm
Turbidity and colour - Powder form: Hydrex 3531 DR, Powder form: Hydrex 3531 DI,
HYDREX 3841 ,3842/
Total hardness > 80 and < < 1000 <5 3554 DR 3554 DI
0,5-1 ppm
200 ppm CaCO3 0,1-0,2 ppm 0,1-0,2 ppm
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 62 of 118
Drinking water /
Waste water (Type II)
Process water (Type I)
Type (Rolled or Crushed) Crushed Crushed
Silica concentration (SiO2) >95% >95%
Effective size (d10) 85-100 µm 130-150 µm
Uniformity coefficient (d60/d10) <1.7 <1.7
Minimum size (2/3*d10) 60 µm 80 µm
Maximum size (2*d10) 200 µm 300 µm
Real density 2650 kg/m3 2650 kg/m3
Loss on combustion Less than 0.1% Less than 0.1%
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 63 of 118
Table 12: Micro-sand concentration recommended ranges for Actiflo Turbo used in waste water applications
Table 13: Micro-sand concentration recommended ranges for Actiflo Turbo used in drinking water or Process
water applications
You must ensure that the sand concentration remains stable by regularly measuring the sand
concentration at different points (as indicated in chapter 8.7). A small quantity is continuously
lost in the treated water and in the sludge outlet.
The easiest way is to use the sand pot to measure the sand concentration in the recirculation
lines and then to calculate the sand concentration in the flocculation tank.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 64 of 118
V1
V2
Figure 10: Sand pot Calculate the sludge concentration with the formula:
Then, to calculate the sand concentration, record the raw water inlet flow rate Q1 and total
recirculation flow rate Q2 (to be estimated with hydrocyclone pressure curve if you don’t have a
flowmeter). If you have 2 recirculation lines working in duty 2x50%, you should double the
measured/calculated unit recirculation flow rate. You can finally apply the formula
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 65 of 118
clogging, only add one 25kg sand bag per minute. Always verify that there is no more than 10%
of sand lost between 2 top ups.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 66 of 118
- Use a different dose of polymer in each beaker. The polymer doses must be defined to
cover the complete recommended concentration range from Hydrex chemicals.
- Test the treated water and define the optimum polymer doses as per the beaker that has
the best quality of treated water.
3. Definition of optimum pH
- Pour the exact same volume of raw water into several beakers. Ensure that the raw water
is properly mixed before pouring so that the water quality will be the same in each beaker.
- Apply a different pH to each beaker (these different pH values must be in the
recommended range of use for the coagulant type used).
- Dose the optimum volume of coagulant as defined in step 1 into each beaker
- Put the same quantity of microsand, (that must be in the recommended concentration
range), into each beaker.
- Dose the optimum volume of polymer as defined in step 2 into each beaker
- Test the treated water and define the optimum pH as per the beaker that has the best
quality of treated water.
This test can be repeated several times using different coagulants and polymers to define the
best Hydrex Chemicals to use to reach the required performance levels in terms of target
pollutant removal.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 67 of 118
Coagulant Acid or base for pH and alkalinity adjustment (NaOH, aluminates, HCl,
H2SO4, lime, carbonate, bicarbonate, CO2, or equivalent)
Turbidimeter (Hach 2100AN or equivalent)
pH-meter (serial Hach EC or equivalent) and calibration solutions (pH=4, pH=7 and
pH=10)
Chronometer or stopwatch
Micro pipettes 5 ml-1000 ml
Disposable syringes 1 ml-5 ml
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 68 of 118
1. Record the settled and raw water parameter values at the plant (turbidity, colour,
dissolved aluminium, etc.)
2. Fill up the beakers with raw water.
3. Set the beakers on the bench.
4. Make sure that the raw water temperature corresponds to the desired temperature.
5. Set the paddle between 0.5 and 1.0 cm from the bottom of the beaker.
6. Start mixing and adjust the rotation speed to 150 rpm.
7. If needed, add acid, base or equivalent to all of the beakers to adjust the pH.
8. Add coagulant simultaneously to all of the beakers using micro-syringes.
9. “A” minutes after adding coagulant (“A” corresponding to full-scale plant retention time in
coagulation tank(s) at the desired flow), add all of the microsand and the quantity of polymer
rapidly, using a syringe. If you have an extended coagulation mixer installed, ensure that time A
is doubled as required reflecting the real conditions.
10. After a flocculation time of “B” minutes (“B” corresponding to full-scale plant retention
time in maturation at the desired flow), stop stirring and allow the water to settle for the next 3
minutes.
11. Sample the settled water from 5 to 10 cm below the supernatant surface using a 100 ml
syringe. Proceed slowly. Make the required analyses.
8.6.4. Analysis
Analysis of the treated water should be defined according to the treatment target of the Actiflo.
Typically, you should measure:
1. Turbidity (NTU)
2. Apparent colour (ACU) using a spectrometer (mainly for drinking/process water)
3. pH
4. Any other relevant parameters for your project such as phosphate, metallic ions, algae,
etc.
It is recommended that the operators record the following parameters, if suitable devices are
available:
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 69 of 118
- On an hourly basis:
o turbidity, raw water
o color and/or DOC, raw water (drinking/process water only)
o pH, raw water
o turbidity, clarified water
o color and/or DOC, clarified water (drinking/process water only)
o pH, clarified water
- On a daily basis
o total quantity of clarified water
o flocculation mixers speed
o electric current drawn by the motors
o pumps VFD frequency and pressure in recirculation pipework
o other parameters of interest regarding the applications: dissolved iron and
manganese, total organic carbon...
o average raw water flow
o microsand concentration in the sludge outlet
o microsand concentration in the flocculation tank
- On a weekly basis
o flow rate, hydrocyclone underflow
o sand concentration, hydrocyclone underflow
o proper distribution of water in the outlet troughs (along all V-notches and same
level of water in each trough)
o proper distribution of water in the outlet troughs (along all V-notches and same
level of water in each trough)
WARNING : Check on a daily basis that anchoring, ladder, stairs, handrails and
gratings are stable and tightened. Also, check that there are no abnormal
vibrations that could loosen devices related to safety
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 70 of 118
Note: Although the HMI screen is fairly robust, it is advisable to operate the screen
with clean, grease-free hands. Normal finger pressure is sufficient to make
selections on the HMI.
Important: Do not use sharp or pointed items such at pen lids or pen / pencil tips on the
HMI screen. These will cause damage and shorten screen life.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 71 of 118
During this process the unit remains in Shutdown mode (pump off) and will not begin a start up
until after the delay timer (35 secs) has expired.
For this reason there is no HMI function to stop the unit. In an emergency use the E-Stop.
Once the start-up delay timer has expired the Home screen is displayed - see next.
Note: There will likely be active alarms associated with the mixer (AG20-02) and the pump(s)
(PC30-01 & PC32-01) on initial start-up / start up following a power failure or E-Stop
shut down. In this case it will be necessary to clear the alarm on the pump VFD unit –
press the VFD reset button (tick button) twice, then clear the alarms on the HMI
“Alarms” screen – see later.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 72 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 73 of 118
Start button - manually start the unit (Operator access) - go to Standby sequence -
depending on water demand and equipment set up the process will access Internal
Recycle & then Service, or External Recycle, or Standby.
Veolia Icon -> go to Schematic Overview screen displaying an overview of the Actiflo
system - see later.
Production Data -> shows two further sub-menus: Volumes, Trends
About -> shows a pop-up screen with local Veolia contact information
IO -> shows 4 further sub-menus: DI, DO, AI, AO
Options -> go to Options screen (see later) - this displays the software and mechanical
options available & selected on the Actiflo
System Information -> go to System Information screen (see later) - details the last & the
next service visit due (update by Engineer) - displays system time and date (update by
Operator).
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 74 of 118
Process -> shows four further sub-menus: Steps, Settings, Instrum., Equip.
Use the "Log On" / "Log Off" buttons to enter the required pass code to access the various HMI
functions.
Note: The red “Alarms” button indicates there are active alarms.
Pressing "Log On" and then entering the Engineer pass word (see next table) will change the
display to the following:
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 75 of 118
The word "Engineer" appears on the left hand side on the screen indicating the level of access.
The screen shows the access time (in minutes) without HMI interaction before the access is
cancelled.
With the exception of screen navigation, all other settings / functions require a login to make
changes - see table below:
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 76 of 118
The login will remain active for as long as the HMI is being used. Any screen access / viewing
operations using the HMI will maintain the login authority.
With no HMI input the access will expire after the "Logoff time". Any subsequent HMI actions or
modifications to settings will require the relevant access code to be re-entered.
See Appendix for access details to various HMI functions.
Note: The AG20-02 fault may require a reset of the mixer VFD before the alarm can be reset
and cleared from the above screen. This may also be true for other self-contained
instruments.
Press the "back" button to return to the previous screen.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 77 of 118
Note: The red “Alarms” button indicates that there are active alarms.
Historical alarms with additional detail are available to view. There is a scrollbar on the right
hand side of the screen to allow the user to move up / down through the alarm messages.
The "Clear All" button (Engineer access) will permanently remove all alarm history without
warning. This is useful following on-site installation / commissioning to clear faults raised during
the initial setting up process.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 78 of 118
Important: "AVY" indicates availability of the mixer / valve for automatic operation. If
“AVY” is missing from any components the unit will not be available for
automatic operation, i.e. can't be started. In this case operation is only by
manual override inputs from the user (with Engineer access). All items of
equipment will require manual control.
Additional peripheral functions at the bottom of the screen:
"Water Demand" button - Engineer function forcing a Water Demand signal - this
overrides the normal water demand input. This can be used in conjunction with manual
adjustment (override) of AIT70-01 (Engineer access) to force water to service when
there is no demand and / or when water quality is poor.
Warning: Forcing a water demand can result in over-filling the DI water tank.
The manual Water Demand request overrides the digital input status. The status of the "Water
Demand" button is shown as follows:
- Grey button = inactive - no water demand
- Orange button = manual override to force Water Demand on the HMI
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 79 of 118
- Green button = Active Water Demand input based on low DI Water Tank level
- Orange Text AND Green button = Forced Water Demand and an Active Water Demand
input
If the final water Turbidity (AIT20-01) is modified (Engineer access), this is shown on the HMI by
a yellow “O” next to instrument ID and yellow text for the new value and its units - this indicates
an Override input to the user, as is seen in the screen shot below:
The same logic is used to override all the signals (Engineer access).
Since the pump(s) and mixers are all still available ("AVY") this unit can still be run
automatically.
In normal / automatic operation the various icons are activated:
green = on / open
grey = off / closed
red = alarm / fault / low level (air or water tank)
The operating mode / step is shown in the top left hand corner of the screen.
Press the "back" button to return to the previous screen.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 80 of 118
A yellow “O” next to instrument ID and yellow text for the new value and its units indicates an
Override input is in operation.
Pump operation can be set to:
H = Hand or manual operation
O = Off
A = Automatic - normal operation
For the pump - the speed can be manually set - select "H" and the pump speed & the pump will
start.
When the operation has been completed select "O" or "A" - this will set the pump speed at zero.
Select "A" to return the pump to automatic mode for normal operation.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 81 of 118
The "Reset" button (Engineer access) resets the "Next Maintenance" time to the maximum
setting.
Use the "X" in the top right hand corner of the pop-up to close the screen.
Note: It is important to return the pump to its original settings once the reason for the change
has been completed. They will not reset on their own, except in the case of a power
failure / or power off operation when the default settings and standard inputs are
applied.
For the instrument pop-ups:
There is a toggle / "Override" button to set a Manual Value in place of the instrument input.
Of course with the valves these can only be either open or closed. Note that manual overrides
will affect all valves served by the same control solenoid (see Appendix for linked valves).
When the operation has been completed reset the value and toggle the "Override" back to "Off".
Valves can be set to:
H = Hand or manual operation
O = Off
A = Automatic - normal operation
Note: It is important to return the instrument / valve to its original settings once the reason for
the change has been completed. They will not reset on their own, except in the case of
a power failure / or power off operation when the default settings and standard inputs are
applied.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 82 of 118
Indications on the chemical levels are also displayed so that when a low level is reached in one
of the chemical tanks, it can be visualised on this screen by a red circle.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 83 of 118
For Production (service) the following signals are required - all must be green:
Water Demand - if there is no demand (grey) the unit will operate in Standby / Mixing in
line with the software setup.
No Fatal Alarm - alarms (grey) need to be reset before going into production
Unit in Standby - must go through Standby mode to reach Production
Inlet Water Valve Available – the valve is in automatic mode - if grey then go to
Schematic Overview screen and reset. The same logic applies for all the other
equipment.
9.10.1. Volumes
Provides access to the following data, if the inlet flow meter is fitted:
Daily, Monthly, Yearly and Total Volume Produced
Estimated Sand loss.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 84 of 118
Note: A Notification is displayed when the estimated sand loss exceeds the "Max Sand loss"
set point.
Screen details:
The zeros column indicates how many times the particular operation has been started.
The "0 h" is the time in operation - this is adjustable with Engineer access.
The "Reset" button returns the relevant volume / regen counter figures to zero -
Engineer access.
Right hand side info (only available if an inlet flow meter is installed):
Day Volume – is the daily volume of water that entered the Actiflo. It is reset every day
but can be reset manually at any time.
Month Volume – is the monthly volume of water that entered the Actiflo. It is reset every
month but can be reset manually at any time.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 85 of 118
Year Volume – is the yearly volume of water that entered the Actiflo. It is reset every
year but can be reset manually at any time.
Total Volume - this is the total volume of water that entered the Actiflo. It can be reset
manually at any time.
Estimated sand loss – is the calculation of the sand loss during operation of the Actiflo. It
can be used to keep track of the sand used in the process.
Trends from the following instruments can be displayed on this screen (depending on options
selected).
There will always be monitoring of:
- Outlet Turbidity (AIT20-01)
- Outlet pH (20-02)
The other optional instruments that can be monitored in the trends screen are:
Inlet Flow (FIT11-01)
Inlet Turbidity (AIT11-01)
Inlet pH (AIT11-02)
Recirculation line 1 flow (FIT31-01)
Recirculation line 2 flow (FIT33-01)
The current instrument readings are shown at the bottom of the screen. A slider bar at the far
right of the screen can be moved to reveal the other instrument data.
An SD card (memory card) can be fitted to store running data (3 days). This allows the time
span on the screen to be expanded / reduced (see icons on the screen) without loss of data.
When the card is full the oldest data is overwritten.
If no SD card is fitted then no data is stored (on power loss) & only current trend information is
available to be shown on the screen. 1 hour worth of data is available for display (PLC
temporary memory) - the user can zoom in and out without loss of data.
The trend screen is a useful tool in helping engineers to identify faults and issues with plant
operation.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 86 of 118
Provides details of the local Veolia company or agent. This has to be updated during
commissioning.
9.12. IO SCREENS
Accessed from the Home screen these screens display:
Display the status of the Digital Inputs / Outputs
the Current Value and Scaling of analogue signals
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 87 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 88 of 118
Format:
Green button = active
Grey button = inactive
For example, in Figure 25, the coagulation mixer is failing; the emergency stop is activated, etc.
This screen is used for monitoring only - no digital inputs can be adjusted.
Notes:
KC 20-01 is the designation for the Actiflo control panel.
The 3 "Free" slots are for future use (& are already wired up).
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 89 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 90 of 118
Screen detail:
Min = value represented by 4mA signal
Max = value represented by 20mA signal
Raw = Analogue to Digital conversion (not adjustable)
Real = translation of the Raw 4-20mA input to the Min - Max range given
Use the toggle sliders towards the right hand side of the screen to override the instrument input
with the Override input (Engineer access). Typically the Overview screen is used to do this, but
for set up and testing purposes this screen can also be used.
Notes:
It is important to cancel / clear any Override settings (Engineer access) once the reason
for the change has been completed. They will not reset on their own, except in the case
of a power failure / or power off operation when the default settings and standard inputs
are applied.
It is also possible to override the instrument inputs on the Schematic Overview and
Regeneration Overview screens. This screen is mainly designed for testing purposes.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 91 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 92 of 118
The screen is split into two parts - the left side details the purely software based options /
configurations, the right side details those that have additional mechanical components
associated with them.
Table 15: System Options
Hydrocyclone Entering the size of the MA sets the default values for
Size some instruments
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 93 of 118
Inlet Turbidity Not Fitted / Fitted Not Fitted: this instrument is not fitted on the Actiflo
Fitted: this instrument is fitted on the Actiflo
Inlet pH Not Fitted / Fitted Not Fitted: this instrument is not fitted on the Actiflo
Fitted: this instrument is fitted on the Actiflo
Inlet Valve Not Fitted / Fitted Not Fitted: this instrument is not fitted on the Actiflo
Fitted: this instrument is fitted on the Actiflo
Inline Mixer Not Fitted / Fitted Not Fitted: this mixer is not fitted on the Actiflo
Fitted: this mixer is fitted on the Actiflo
Pre Not Fitted / Fitted Not Fitted: this mixer is not fitted on the Actiflo
Coagulation Fitted: this mixer is fitted on the Actiflo
Mixer
Micro-sand Not Fitted / Fitted Not Fitted: this instrument is not fitted on the Actiflo
pump Flow(s) Fitted: this instrument is fitted on the Actiflo
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 94 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 95 of 118
Screen details:
The access level is shown on the left hand side; in this case Engineer access is active.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 96 of 118
Date Next Service Visit - automatically set based on the last service visit date and the
service frequency.
The system time and date settings can be updated with Operator access.
The timers are set up during the factory test and may require some adjustment on site.
To re-set step timers requires Engineer access (on the above screen the access level is shown
on the far left hand side below the instrument readings.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 97 of 118
Select the timer to be modified and enter a new time within the range given. This overwrites the
original value.
Caution: Before modifying any of the above timers please refer to Veolia Water.
Changes may harm the equipment or disrupt the process.
Screen details:
Note: All adjustments to the settings on this screen require Engineer access. Select the
setting to change - a key pad appears - enter the new setting and press enter to accept.
Valve (VA11-01) PID and flow rate settings are factory set. They should not require
adjustment. These settings control the smooth starting / stopping of the valve & set the
flow targets for each mode of operation.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 98 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 99 of 118
This screen details the instrument set points. Set points are as shown except for:
The toggle switches (I/O) are used to enable / disable the related alarm (Engineer
access) - not all potential alarms are active / required.
The Low value in seconds is the time it takes to activate a low or low low alarm when the
conditions are met. The high is the equivalent for high and high high alarms.
Note: Instrument details are only shown if the related option is fitted.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 100 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 101 of 118
Screen details:
The Alarm column indicates the time delay between a fault being raised and the alarm
being activated. This helps avoid nuisance alarms. These alarm delay times should not
require modification.
Maint. is a countdown timer representing the recommended interval until the next
scheduled maintenance, in this case 6 months. They can be updated on this screen or
via the pop-up screens on the Overview and Regeneration Schematic screens.
Note: All adjustments to the settings on this screen require Engineer access. Select the
setting to change - a key pad appears - enter the new setting and press enter to accept.
The columns 2 Starts and Start/Stop should not be used unless specified by SSP.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 102 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 103 of 118
required. In addition, always take into account suppliers recommendations that are found in the
specific supplier’s manuals.
Equipment and spare parts should be maintained as shown below. Depending on site
conditions (SS load, temperature and humidity, flow rate, etc.), the advised frequency might
need to be increased. To optimize maintenance costs, many of these tasks can be done at the
same time during yearly maintenance visits.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 104 of 118
The frequencies shown in the table above give a rough idea of component life-spans /
replacement periods and shouldn’t be taken as a guarantee of component life-span. The table
above is completed by the spare-parts list that is in ANNEX C.
The tank coating can last up to 15 years before complete refurbishment is required (in the best
case scenario). Depending on environmental conditions, water composition and temperature,
refurbishment could be required every 5 years. In any case, yearly inspection is mandatory and
spot repairs must be performed in case of damage to ensure the maximum life span of the
coating.
Repair procedures must be done according to supplier’s requirements, and the required
personal protection equipment must be worn during this process.
For inspection and repairs inside the tank, ensure you are wearing suitable Personnel
Protection Equipment and follow local requirements for work in confined space.
To maintain Actiflo performance levels, the lamellas should be cleaned regularly. Some factors
which influence fouling are:
the nature of the raw water,
the quality of the clarified water produced,
the flow rates handled
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 105 of 118
Water used for cleaning must not be pressurized to avoid damaging the lamellas. In order to
ensure that the entire surface of the lamella can be cleaned without the risk of the personnel
falling,, use a PVC pipe fitted with a hose connector and elbow on one end and a nozzle or
sprayer on the other end to direct water or air along the inclined axis of the lamellas. The length
of PVC pipe should be sufficient for it to be handled from the top of the Actiflo unit while allowing
access to the bottom of the modules.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 106 of 118
5. When turning on the water, direct the jet on the wall of the decanter to avoid damaging
the lamellas;
6. Clean the lamellas with a low pressure water jet (less than 2 bars) using a cleaning tool
(refer to previous figure) while the unit is emptying. Repeat the process to clean every
lamella tube. The water jet should be directed parallel to the lamella axis to clean the
entire length;
7. Close the partial drain as soon as the level of water is below the bottom of the lamellas
8. With the aid of a high intensity beam of light, verify the quality of the cleaning. When the
lamellas are properly cleaned, it is possible to see through them;
9. Once completed, when turning off the water, direct the jet on the wall of the decanter to
prevent damaging the lamellas;
10. Finally, return the Actiflo unit to service, to the sewer or to production depending on the
quality of clarified water to be produced.
For the ACP2-15 that is fully covered with gratings, it is required to dismantle the gratings to
perform an efficient lamella cleaning. IN such case, ensure that required Personnel Protection
equipment for work at height is used.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 107 of 118
10.3. TROUBLESHOOTING
10.3.1. Clarified water turbidity increase
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 108 of 118
10.3.2. Clarified water true color or UV 254 increase (Dissolved Organic Carbon)
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 109 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 110 of 118
It is not advised to install the Actiflo pack in locations with higher temperatures, higher humidity
or a more aggressive environmental category or you may have:
- Premature corrosion
- Unexpected failures
- Abnormal maintenance requirements
- Shorter life span of parts and spare parts
However, the ACP2 mk2 standard design can be modified according to local requirements. In
any case, it is recommended not to operate the Actiflo in a condensing humidity.
For lower temperatures, it is necessary to properly insulate after installation (especially the
recirculation pipework and pump) and the Actiflo must be fully drained when not running.
In addition, the risk of corrosion due to contact with water must be assessed according to water
pH and temperature and the level of chloride. Several parts inside the Actiflo are in SS304L and
the internal coating has some limitations which are dependant upon the above parameters. In
case of non-compatibility, alternative, non-standard materials/coating can be considered
(SS316L, Super-Duplex, thicker/different coating, rubber lining, FRP tank…).
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 111 of 118
Typical ACTIFLO TURBO performance levels have been established by VEOLIA but can
fluctuate according to raw water characteristics, the model of ACP2 mk2 selected, the
concentration of micro-sand and the chemical type and dosage.
To define optimal performance levels, it is mandatory to perform JAR tests (see section 8.6).
Ensure that micro-sand concentration as well chemical dosages, (defined as optimal during JAR
tests), are adjusted for the full scale unit during commissioning and then respected.
Normally, in optimal conditions and for a unit sized properly following Veolia Technical
Department guidelines, performance levels are:
Table 19: Actiflo typical performance levels for treatment of ground or surface water (Drinking or Process
water applications)
Table 20: Actiflo typical performance levels for treatment of Waste water (Municipal or Industrial
applications)
These values above are only indicative and may not be applicable for certain types of water
(cold temperatures or removal of special algae for example) or for very low concentrations. Also,
certain pollutants (COD, BOD, Heavy metals, oil and grease…) can have many forms that are
not always settable. Finally, the dosing of chemicals must be maintained and adjusted
according to inlet water characteristics.
In any case, if you don’t achieve these removal rates, don’t hesitate to contact your local Veolia
Water Technologies subsidiary for a process review.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 112 of 118
Hydrocyclone model small line(s) MA5 MA5 MA10 MA10 MA20 MA20 MA40 MA40
Hydrocyclone model large line(s) MA10 MA10 MA20 MA20 MA40 MA40 MA40 MA40
3
Flocculation tank volume (m ) 4,58 8,34 12,79 17,28 25,82 34,24 52,18 61,35
2
Lamellas mirror surface (m ) 1,04 2,21 3,69 4,14 6,29 9,95 12,59 14,41
(1): Maximum flowrate in each specific case must be defined according to inlet water quality and
removal efficiency required. This value is the hydraulic maximum flowrate.
(2): For specific requirements, recirculation flowrate can be adjusted at a lower flowrate in a
non-standard configuration.
(3): Limitations are defined by the hydrocyclone flow ranges and the max acceptable flow
velocity in the recirculation pipework. Curves are available in the Hydrocyclone manual.
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 113 of 118
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
Page 114 of 118
12. ANNEXES
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
WATER TECHNOLOGIES
DOMAAI202482
ACTIFLO TURBO ACP2 MK2 Issue B
IOM MANUAL 14 June 2019
ANNEX D: COMPONENTS
SUPPLIERS MANUALS
WATER TECHNOLOGIES