Sei sulla pagina 1di 185

FORCED CONVECTION HEAT TRAJISFER TO A

SINGLE AND TWO-PHASE STEAM/WATER

MIXTURE IN A HELICAL COIL WITH

RADIANT HEATING

by

FOAD N. VAFAIE, 3.S. in Farm Mach., M.S. in M.E.

A DISSERTATION

IN

MECHANICAL ENGINEERING

Submitted to the Graduate Faculty


of Texas Tech University in
Partial Fulfillment of
the Requirements for
the Degree of

DOCTOR OF PHILOSGFirf

Approved

December, 1981
73
Iff:I
ry^^ /A ACKNOWLEDGMENTS

I wish to thank and commend Dr. Jerry R. Dunn, chairman of the

advisory committee, for his kindness, patience and outstanding guidance

throughout the supervision of this work. Without his uninterrupted

encouragements, the success of this work would have never been possible.

I am deeply indebted to Dr. Ronald J. Pederson, Dr. Herbert J-

Carper and Dr. Luther D. Clements for their constructive criticism and

support during the preparation of this dissertation. I would also like

to express my appreciation to other members of my committee for their

cooperation as committee members.

Thanks are also extended to Dr. James H. Lawrence, Jr., Chairman

of the Mechanical Engineering Department, for his continuing support

during the period of my study at Texas Tech University.

Special thanks goes to Mrs. Judy Pearce for her beautiful typing

of this manuscript.

Finally, I wish to express my sincere gratitude to my wife, Mehrnaz,

who made my graduate studies possible by her immense sacrifice and moral

support.

11
TABLE OF CONTENTS

ACKNOWLEDGMENTS ii

ABSTRACT v

LIST OF TABLES vii

LIST OF ILLUSTRATIONS viii

NOMENCLATURE xi

I. INTRODUCTION 1

II. LITERATURE SURVEY 13

III. DISCUSSION OF EXPERIMENTAL APPARATUS 22

3.1 Equipment Controlling the Fluid Condition at

the Test Section Inlet 26

3.2 Heat Exchanger 28

3.3 Test Section 29

3.4 Solar Simulator 33

3.5 Condenser 36

3.6 Supporting Instrumentation 41

3.6.1 Flow Measuring Instruments 41

3.6.2 Temperature Sensors 42

3.6.3 Pressure Sensors 42

IV. EXPERIMENTAL PROCEDURE 46

4.1 Introduction 46

4.2 Single-Phase Runs 51

4.3 Two-Phase Runs 52

V. THER14AL ANALYSIS 54

5.1 Calculation of Total Heat Input 56

iii
5.2 Solution to the Problem of Heat Conduction
in Tube Wall 61

5.3 Functions Representing Heat Flux and


Temperature Distributions 67

5.4 Calculation of Local Fluid Properties and

Heat Transfer Coefficients 71

VI. EXPERIMENTAL RESULTS AND DISCUSSION 78

6.1 Single-Phase Heat Transfer Results 78

6.2 Two-Phase Heat Transfer Results 88

6.3 Comparison of Results 112

VII. CONCLUSIONS AND RECOMMENDATIONS 123

REFERENCES 127

APPENDICES

A. Sample Calculation 130

B. Uncertainty Analysis 150

C. Test on Solution Method 161


D. Two-Phase Heat Transfer Data 1^8

IV
ABSTRACT

The purpose of this study has been to perform an analytical and

experimental investigation into the heat transfer characteristics for

a once-through steam generator with a helical flow geometry. The

application is the receiver for a fixed hemispherical mirror solar

concentrator on the Crosbyton Solar Power Project. In this design,

the working fluid, water, goes successively through the single-phase

liquid, two-phase and super-heated vapor regimes in a once-through,

helically wrapped tube bundle subjected to nonuniform, asymmetrical

radiant heating.

Individual segments of the radiation profile for the receiver were

simulated using high intensity, line source quartz lamps providing con-

centrations of up to 240 suns. A segment of the helical coil was

instrumented and mounted in the radiation field. Test section instru-

mentation included inlet fluid flow rate, inlet and exit fluid pressure

and temperature, and 42 type K thermocouples welded to the surface of

the coil. The incident radiation field was mapped using a Gordon type

heat flux transducer calibrated for the quartz lamp spectrum. An up-

stream hot oil heat exchanger provided inlet fluid conditions to the

test section consistent with the segment of the receiver being simulated

e.g., single-phase or two-phase. The range of test conditions included


2
an incident radiation flux of 6,000 to 27,000 Btu/hr-ft , a flow rate

of 100 to 500 Ibm/hr, an inlet pressure of 100 to 500 psia, and an

inlet quality of 0 to 70 percent.

V
A numerical analysis was developed to predict the local internal

heat transfer coefficients and fluid state based on the measurements

obtained in the test procedure discussed above. The analysis included

consideration of the externally applied radiation field, convective

and radiative heat losses, two-dimensional conduction through the tube

wall, and.convection to the internal fluid.

The results show that there is a significant change in the angtilar

variation of the internal heat transfer coefficient at low quality when

compared with values for high quality. At low quality, the highest

internal heat transfer coefficients are obtained on the tube surface

farthest from the axis of the coil. At high qualities, this changes to

yield the highest coefficients on the tube surface closest to the coil

axis. Factors contributing to this phenomena include radial accelera-

tion, induced secondary flow, flow acceleration along the flow axis,

and the onset of film boiling.

The integrated average values of the heat transfer coefficient

for the subcooled liquid and two-phase were correlated against dimension-

less parameters of the flow such as the Reynolds number, Prandtl number,

boiling number and tube-to-coil diameter ratio.

VI
LIST OF TABLES

Table Page

3-1 Equipment Identification 24

3-2 Location and Number of Thermocouples at

Different Stations 32

6-1 Experimental Conditions for Single-Phase Runs 79

6-2 Coefficients of the Correlation Equations 85

6-3 Experimental Conditions for Two-Phase Runs 89

6-4 Coefficients of the Correlation Equation 111

C-1 Temperature Distribution Inside Tube Wall Thickness 166


C-2 Temperature Distribution Inside Tube Wall Thickness 167

Vll
LIST OF ILLUSTRATIONS

Figure Page

1-1 Schematic of Flow Patterns and Heat Transfer

Regions in a Heated Vertical Tube 3

1-2 Location of Dryout for Flow in Helical Coil 7

1-3 Photograph of the Fixed Mirror Distributed


Focus (FMDF) System 9
1-4 Variations of Incident Energy Upon the Receiver

as a Function of Location 12

3-1 Schematic Diagram of the Test Loop 23

3-2.a,b Circumferential Location of Thermocouples 31

3-3.a,b Coiled Tube Test Section and Thermocouple Connections 34

3-4 Schematic Diagram of Lamp Panel Representing the


Cooling Channels 37
3-5.a,b Triangular and Open Position Arrangement of

Lamp Panels 38

3-6 Photograph of Test Facility 40

3-7 Instrument Panel 44

3-8 Radiant Test Facility Plan View Schematic 45

4-1 Photograph of Experimental Flux Plot Configuration 48

4-2 Symmetric Flux Plot 49

4-3 Asymmetric Flux Plot 50

5-1.a,b Heat Flux Distribution for Sjmraietrical and

Asymmetrical Heating 58

5-2 General Form of Heat Flux Function 60

5-3 Tube Cross Section Representing Boundary Conditions 62


5-4 Tube Wall Discretized Model 65

Vlll
5-5.a,b Cosine and Circular Incident Flux Distributions 69

5-6 Relative Locations of Pressure and Temperature


Measurement Points at the Inlet and Exit to the Coil 75

6-1 Axial Distribution of Heat Transfer Coefficients,


Run 93 80

6-2 Axial Distribution of Heat Transfer Coefficients,


Run 8 81

6-3 Circumferential Distribution of Nusselt Number,


Run 93 83

6-4 Circumferential Distribution of Nusselt Number,


Run 8 84

6-5 Comparison Between the Experimental and the Computed


Data, Subcooled Liquid Runs 86

6-6 Comparison Between the Experimental and the Computed


Data, Subcooled Liquid Runs 87

6-7 Axial Distribution of Heat Transfer Coefficients,


Run 105 92

6-8 Circumferential Distribution of Nusselt Number,


Run 105 93

6-9 Axial Distribution of Heat Transfer Coefficients,


Run 104 94

6-10 Circumferential Distribution of Nusselt Number,


Run 104 95

6-11 Axial Distribution of Heat Transfer Coefficients,


Run 102 96

6-12 Circumferential Distribution of Nusselt Number,


Run 102 97

6-13 Axial Distribution of Heat Transfer Coefficients,


Run 98 99

6-14 Circumferential Distribution of Nusselt Number,


Run 98 100

6-15 Model Representing the Variation of Heat Transfer


Coefficients 103

IX
6-16 Axial Distribution of Heat Transfer Coefficients,
Run 100 105

6-17 Axial Distribution of Heat Transfer Coefficients,


Run 6 107

6-18 Axial Distribution of Heat Transfer Coefficients,


Run 71 108

6-19 Axial Distribution of Heat Transfer Coefficients,


Run 50 109

6-20 Axial Distribution of Heat Transfer Coefficients,


Run 78 110

6-21 Comparison Between the Experimental and Computed


Data, Two-Phase Runs 113

6-22 Comparison Between Experimental Data and Seban-


McLaughlin, Single-Phase Runs 115

6-23 Comparison Between Local Values of Nusselt Number,


Station 1, Run 9, (Single-Phase) 117

6-24 Averaged Values of Nusselt Number, Run 9, (Single-


Phase) 119

6-25 Comparison of Two-Phase Results with Results of


Owhadi and Crain 121

A-1 Junction of Fluid Streams at the Test Section Inlet 133

A-2 Condenser 138

A-3 Boundary Condition Designator 145

B-1 Experimental Results, Run 51 159

B-2 Experimental Results, Run 71 160


NOMENCLATURE

A area, ft 2

BO boiling number, = q/(G H^ ) , dimensionless

C heat capacity, Btu/lbm-^R

d tube diameter, ft

dr differential element in radial direction, ft

dz differential element in axial direction, ft

D coil diameter, ft
2

D dimensionless flow parameter = Re(d/D)

DNB Departure From Nucleate Boiling

f friction factor, dimensionless


2
G mass velocity, Ibjjj/hr-ft
2
h heat transfer coefficient, Btu/hr-ft -"F
— 2

h circumferential average heat transfer coefficient, Btu/hr-ft -°F

H fluid enthalpy, Btu/lb^

k thermal conductivity, Btu/hr-ft-^'F

m mass flow rate, Ib^/hr

N number of differential elements in axial direction

Nu Nusselt number, dimensionless

Nu circumferential average Nusselt number

P pressure, psia
P, heated perimeter, ft
h
Pr Prandtl number, dimensionless
2
q heat flux, Btu/hr-ft

XI
— 2

q integrated average wall heat flux, Btu/hr-ft

Q total absorbed heat, Btu/hr

r tube radius, ft

R tube radius, ft

RA radial acceleration, dimensionless

Re Reynolds number, dimensionless

S standard deviation

T temperature, °F

T integrated average wall temperature


3

V specific volume, ft /lb

V velocity, ft/hr

X quality, dimensionless
h_^^0.9.vf]0.5r..^0.1
^yf^
X Lockhart-Martinelli parameter, dimensionless
yg

axial direction

Subscripts (except as noted above)

AMB ambient

B bulk fluid properties

C critical

c coil

calc calculated

conv convective losses

cr critical or transition

d bubble departure

ex exit

Xll
f saturated liquid properties

flux incident flux

g saturated vapor properties

hom homogeneous model

i coil inlet

i tube inner surface

inc incident

i liquid

m average

o tube wall outer surface

rad radiative losses

S straight pipe

sat saturated

sb significant boiling length

TP two-phase

w wall

z axial location z

Greek Symbols

e emissivity

Tj viscosity

p density

a Stephen-Boltzman constant

9 circumferential direction

Xlll
CHAPTER I

INTRODUCTION

Recent advances in engineering technology have attracted the

interest of scientists around the world working in different fields

related to atomic energy, jet propulsion, space exploration, electric

power generation (including solar electric power generation), and others

to many specialized topics of heat transfer. One of the main areas of

interest, however, has been boiling heat transfer and two-phase flow.

This subject provides the scientist a broad and interesting field of

study as it involves the combined transport of mass, heat, and momentum

between the different phases present.

Pressure drop of a two-phase flow through a pipeline was the subject

of study of early investigators in this field. These studies usually in-

volved the consideration of momentum transfer between the phases. Later,

heat transfer in two-phase flow received more attention as it was

noticed that boiling is an extremely efficient mode of heat transfer [15].'

The state of the art is still far from being established and very few

general correlations are available in the literature, but it is realized

that in the process of convective boiling, which can be defined as the

addition of heat to a flowing liquid and generation of vapor, the hydro-

dynamic and heat transfer mechanisms are very closely related, and have

a much more profound effect on each other than in a single-phase flow.

The pressure drop in two-phase flow depends upon the flow pattern

or topology of the flow, which is in turn affected by the variations in

*Numbers in [ ] refer to list of references


the amount and distribution of each phase. This is in turn a function

of the amount of heat being added to or removed from the flow. The

changes in flow pattern will also cause variations in local heat trans-

fer coefficient.

Because of this coupling effect between the hydrodynamic and thermal

properties of a convective boiling system, the situation at any axial

location in the channel can never become either thermally or hydrody-

namically fully developed. These, along with the effect of time varying

properties that one may encounter, make the problem very difficult if

not intractable to solve analytically, which explains why the subject

to date is largely empirical [10].

To gain a better knowledge of how the addition of heat will change

the flow pattern in a two-phase flow system, consider a vertical tube

heated uniformly over its entire length with a low heat flux. Subcooled

liquid is pumped from the bottom of the tube at such a rate that the

effluent is entirely steam. Figure 1-1 is a schematic diagram of such

a system. As the figure represents, a wide range of local conditions

and different flow regimes exist along the heated channel.

In the entrance region of the tube, both tube wall and liquid

temperature increase, but they are still below the value required for

nucleation. In this region, heat transfer is entirely by single-phase

forced convection. At point B the wall temperature has reached a value

high enough to start the nucleation process, after which the wall temper-

ature begins to decrease. At this point the bulk liquid temperature is

still well below the local saturation temperature and, therefore, the

bubbles collapse as they separate from the wall. This is the subcooled
"^i^'i^'a^ii^

Single-phase Convective heat


vapor transfer to vapor

Drop Liquid
flow deficient region

Forced
Annular convective heat
flow transfer through liquid
film

i;
Slug
flow
Saturated
nucleate
boiling
Bubbly
9*
•*
«C
• flow
I
Subcooled boiling
B
Single-phase Convective
liquid heat transfer
to liquid

Temperature tSubcooled Liquid

Figure 1-1 Schematic of Flow Patterns and Heat


Transfer Regimes in a Heated Verti-
cal Tube [6,9,10]
boiling region. Farther along the channel, the bulk fluid temperature

reaches a value which, though still below the saturation temperature,

is high enough to prevent the bubbles from collapsing. The bulk fluid

temperature increases until it reaches the local saturation temperature,

and from this point on it decreases gradually corresponding to the

decreasing pressure. The tube wall temperature also decreases gradually,

but it always stays a few degrees above the bulk liquid temperature.

Now the tube is filled with a bubbly flow, and coalescence of these

bubbles leads to slug flow and annular flow farther downstream.

From point C to E, the process of heat transfer is saturated

nucleate boiling. In the annular flow region, from point E to G, the


{
process of boiling is replaced by evaporation as the thickness of the

thin liquid film attaching to the inner tube wall is such that the heat I

is carried away to the liquid-vapor interface by conduction through

liquid and causes evaporation of liquid film at this interface. This

region is the so-called two-phase forced convective region.

Finally, liquid deficiency occurs as the thin liquid film evaporates.

As a result of this, there will be a sudden decrease in heat transfer

coefficient with a corresponding rise in wall temperature. This is

known as "dry out" and the region between this and the dry saturated

vapor is the liquid deficient region.

The dry out point represents the effective limit on the amount of

evaporation in a boiler tube and its specification is a very important

part of the design of evaporator tubes.

Note that the gradual decrease in AT , the difference between the


o w
wall temperature and the bulk fluid temperature from point B to G,
represents an increase in heat transfer coefficient over this range.

The definitions of a few terms that will be used later during the

course of this study are worth mentioning here. These are the pre-

viously mentioned term "dry out" and the term "departure from nucleate

boiling" (DNB).

Consider the uniformly heated tube of Figure 1-1 again. If the

heat flux imposed on the tube surface is increased gradually, the posi-

tion of the point where complete evaporation of liquid film occurs (the

dry out point) will move downward along the tube. As long as this point «

is located after an annular flow pattern section in the tube, it is

called the dry out point. But if the imposed heat flux is increased

such that the complete evaporation of the liquid film on the wall occurs

when the process of heat transfer in the tube is nucleate boiling, then

it is called "departure from nucleate boiling." That is, by increasing

the heat flux, the bubble population on the wall increases so much that

these bubbles form a thin blanket of vapor on the wall, preventing the

liquid from wetting the wall. This will change the mechanism of heat

transfer to film boiling. It can occur either in the subcooled or

saturated nucleate boiling region. In any event, the pressure of DNB

or dry out will cause a sudden decrease in heat transfer coefficient

and a corresponding increase in wall temperature.

Boiling in a helically coiled tube, which is the subject of this

study, offers advantages over that in a straight tube especially where

the effluent is to be saturated or superheated steam. Helical coil

evaporators have been used in a variety of systems such as nuclear steam


generators, cryogenic evaporators, and are currently being evaluated

for use in solar power generators.

In the flow in a helical coil, due to the large radial accelera-

tions induced by the helical path, there will be a secondary flow

present which at lower pressures causes the liquid at the center of each

tube cross section to be driven outward (farther from the coil axis) in

the center section of the tube and toward the center of curvature along

its outer walls. Figure 1-2 illustrates the effect of pressure and

mass velocity on the flow pattern and the location of dry out in two-

phase, helical coil flow. It has been shown that at high pressures of I

13 I
more than 160 atm, mass velocity will be the major factor affecting the
Iti B f.
location of dry out and local flow pattern [6]^ At low mass velocity,

the liquid will be flowing in the bottom of the tube due to the effect

of gravity, while at higher mass velocities the liquid will move radi-

ally outward attaching to the wall of the tube farthest from the center

of the curvature. At lower pressure, the secondary flow takes over.

This effect is especially important in the annular flow regime, where

secondary flow in the gas core causes a circulation in the liquid film.

Liquid film is carried with the gas flow from the channel wall close to

the center of curvature across the tube center and is deposited on the

opposite wall some distance downstream. The liquid is then returned to

the wall close to the center of curvature due to the circulation in the

liquid film further downstream. This peripheral circulation of liquid

film and separation of liquid droplets from the gas core due to centri-

fugal force maintains the inner tube wall wet up to very high qualities,

causing the critical heat flux to be higher in coils than in straight


Burnout

CO
E
CO

O
Q.
iJ
Low mass velocity
Q.

J-l

OJ
5-1

GO
•H
PS
Burnout

L High mass velocity

0)
00
u
03

O
Q.

Q.

0)
Burnout
u
3

0)
u
PL,
o
t-1
Axis of
helix

Figure 1-2 Location of Dryout for Flow


in Helical Coil [6]
8

tubes. That is, the transition to the liquid deficient condition

occurs at higher average steam quality and, therefore, it can be said

that at the same conditions an evaporator tube using a helical coiled

tube will be more efficient than one with a straight tube.

This concept is being used in the Crosbyton Solar Power Project.

The system consists of a solar radiation collector with a large fixed

spherical mirror which focuses the incident solar energy on a linear

receiver. The receiver consists of a cylinder with tube bundles heli-

cally coiled around it. This receiver functions as a linear, once-

through boiler, converting the compressed liquid to saturated or super-

heated steam, by transferring the energy from the solar flux incident

upon its outer surface to the working fluid (water/steam). The effluent

steam is then taken to the power plant for the generation of electricity,

To efficiently convert this thermal energy into electrical energy in a

Rankine thermodynamic cycle, the output of the receiver must be a high

temperature, high pressure steam.

Figure 1-3 is a picture of the system currently being tested using

this concept. The receiver system is supported from the top and is

built such that it is always aligned in the direction of the radiation

from the sun. At or near solar noon and zero incidence angle for the

dish collector, the receiver will be located such that at any specified

axial location, any differential area around its periphery can see the

same amount of mirror surface. Thus, the flux distribution around the

circumference of the receiver will be uniform, although it varies along

the length.
\

Figure 1-3 Photograph of the rixed Mirror


Distributed Focus (FMDF) System
10

At times other than solar noon, however, differential areas, around

the circumference of the receiver at a given axial location, will see

different amounts of mirror surfaces and, thus, the flux distribution

around the periphery of the receiver will not be uniform.

It is obvious that the heat transfer characteristics of the above

mentioned helical receiver are an important aspect in the operation of

the system. The knowledge and understanding of the behaviour of this

receiver under the actual working condition will be helpful in develop-

ing a final evaluation of the performance of the system as a whole.

After a careful examination of the literature, it was noticed that

most of the existing correlations for forced convective boiling are

valid for flow in channels with direct, uniform heating, while the

receiver in the model under investigation is subjected to a radiant

asymmetrical heat flux.

•Thus, it was felt that a series of tests on a receiver system sub-

jected to a radiant heat flux would not only be helpful in understanding

the behaviour of this specific receiver system, but the information so

obtained could also be useful in the design of other once-through steam

generators that use the same concept.

However, in order to simulate the actual conditions that system

experiences, one would need to have a long coil and some means of pro-

viding the incident radiation for the whole length of the receiver coil.

This radiation facility should be such that it would reproduce the

variations of the incident radiation on the actual receiver.

Such a test facility would be a very complicated and costly appara-

tus. Therefore, as it will be discussed in more detail in later chapters.


'*•» ^m'm'm

11

it was decided that a test facility be built that could be used to test

different segments of the receiver. Using this method, it would be

possible to investigate individual regions of the receiver, for example

the liquid heating region, the boiling region, the superheated region,

and even the transition region.

This test facility should also have the characteristic that would

allow the testing of the performance of the receiver under the conditions

of asymmetrical heating. This is of considerable interest as a great

deal of the actual performance of the system will be under such

conditions.

Figure 1-4 represents a typical variation of incident energy on the

receiver in terms of the number of suns as a function of axial location

along the receiver at solar noon and zero degree incidence angle, where )

mirror surfaces are assumed to have a perfect reflectivity of 1.0. This


I
figure also shows how the incident flux is subdivided into small segments, !

to be reproduced individually in the test facility. Under the conditions

of these tests, the best that could possibly be done was to average the

flux requirement for each subsection.


12

No. of segments

4 5 6 7
700

600

500

C
3
CO 400
c
o
CO
•u
c
a; 300
•J
c
o
o

i
200

100

X/R (Length along Receiver)

Figure 1-4 Variations of Incident Energy Upon


Receiver vs. Location [37]
CHAPTER II

LITERATURE SURVEY

Due to the ever increasing use of the concept of the evaporator

tubes in different applications in the industry in recent years,

boiling inside conduits under natural or forced circulation has been

the subject of the study of many investigators. Although these studies

have been mostly related to boiling inside the straight tubes, their

results have been very helpful in understanding the flow patterns and

heat transfer characteristics of flow in other tube configurations such

as orifices, bends, spirals, and helical coils.

Following is a brief review of a few of the papers and articles

published in this field. This is by no means a complete listing of

these papers, but these are the major works that are relevant to the

present study.

One of the most important of these studies is that of Lockhart-

Martinelli [18]. These authors correlated the pressure drop and liquid

hold up (the volume fraction of the flow conduit which is occupied by

the liquid phase) in isothermal two-phase, two component flow in pipes.

They obtained their data for simultaneous flow of air and liquids,

including benzene, kerosene, water, and oil at atmospheric pressure in

pipes with diameters ranging from 0.0586 to 1.017 inches. They concluded

that, depending on whether each phase is laminar or turbulent, four types

of flow exist. The two-phase pressure drop for each of these four flow

types was correlated by means of a parameter X, where X is the square

root of the ratio of the single phase pressure drop in the pipe if the

liquid was flowing alone to the single phase pressure drop if the gas

13
14

was flowing by itself. Liquid holdup was also correlated for all of

these four flow regimes by means of the parameter X.

Later, Martinelli, Nelson, and Schenectady [19] studied the effect

of boiling on two-phase pressure drop in pipes. They developed some

curves by means of which the pressure drop during boiling can be esti-

mated once the exit quality, the boiling pressure, and the pressure drop

for 100 percent total liquid flow are known.

Chen [9] obtained a correlation for boiling heat transfer to satu-

rated fluids in convective flow. He assumed that convective boiling

heat transfer is an additive mechanism of micro- and macroconvective

heat transfer. An effective two-phase Reynolds number function F was

calculated as a function of the Martinelli parameter X. A bubble

supression function S was obtained as an empirical function of the two-

phase Reynolds number. Then using these two functions, he was able to

calculate a heat transfer coefficient which when compared to experimental

results (over 600 data points) showed an average deviation of ±12 percent.

There are also a number of studies in which the effect of tube

curvature on single phase flow is the main concern of the authors.

The effect of pipe curvature on pressure drop in turbulent, single-

phase flow was the subject of an investigation by Ito [16]. His experi-

mental data were obtained from measurements of the pressure drop for

turbulent flow through curved pipes of different pipe diameters and

radius of curvatures. Based on these data points, Ito proposed empirical

correlations for calculating pressure drop for turbulent flow of single-

phase fluids in curved tubes.


15

Seban and McLaughlin [33] presented the results of their experi-

ments on friction factor and heat transfer for the laminar flow of oil

and the turbulent flow of water in tube coils having ratios of coil to

tube diameter of 17 and 104. The ranges of Reynolds numbers varied from

12 to 65000. They concluded that their results for the friction factors

for laminar and turbulent flow are predictable by Ito's correlations

when for non-isothermal flow the properties are evaluated at the mean

film temperature. Circumferential average heat transfer coefficients

for both laminar and turbulent flow were correlated with the Reynolds

number.

Experimental results for forced convection heat transfer and the

friction factor for turbulent flow of water through steam heated, coiled

tubes is reported by Rogers and Mayhew [30]. Three coils with ratios

of coil to tube diameters of 10.8, 13.3, and 20.12 were constructed from

0.5 inch O.D. copper tubing. The range of Reynolds numbers covered was

3 X 10 to 5 X 10^. The results of their experiments are compared to

the existing correlations and heat transfer coefficients were correlated

against Reynolds numbers.

Mori and Nakayama conducted a theoretical and experimental study of

forced convective heat transfer in curved pipes with laminar [22] and

turbulent [23] flow under the condition of uniform heat flux. They

obtained the resistance coefficient (friction factor) and heat transfer

coefficient in fully-developed regions of the flow. Their theoretical

and experimental results showed good agreement. Their results for

Nusselt numbers in both laminar and turbulent flow were correlated

against Dean number and Reynolds number. They also studied the effect
16

of replacing the condition of uniform heat flux with uniform wall

temperature [24]. They showed that in the first order approximation,

the Nusselt number for heat transfer in a curved pipe does not differ

for uniform wall temperature or uniform heat flux.

The effect of coil diameter, pitch, and the diameter of the tubing

used on the friction loss for Newtonian fluids flowing through helical

coils was studied by Mishra and Gupta [21]. A wide range of variables

were included. Pressure drop data in the laminar and turbulent region

for flow through 60 different helical coils was reported and correlations

representing their data in these flow regimes were obtained.

Srinivasan, et al [35] have examined the various published correla-

tions for pressure drop and heat transfer for the flow of fluids in coils

with a constant curvature (helices) and in those with a variable curvature

(spirals). The curvature is defined as the ratio of the tube diameter to

the diameter of the circle into which the tubing is bent. They also

reviewed the existing correlation for critical Reynolds number and pro-

posed new equations for critical Reynolds number in coils.

Two-phase flow inside coils has very interesting features, as it

combines the effect of the secondary flow due to self-induced radial

acceleration with the various aspects of the interactions between the

two phases.

Davidson, et al [13] studied the heat transfer and pressure drop in

spirally coiled steam generating tubes at pressures from 500 to 3300 PSI.

The tubes were exposed to furnace heat and were heated on only one side

of the spiral. The influence of variations of steam-water ratio and of

tube dimensions on heat transfer and pressure drop was investigated.


17

The effect of tube curvature on departure from nucleate boiling

was the subject of a study by Carver, et al [7]. Their experiments

were performed with water boiling in helical coils at 2600 PSI. Two

helical coils with ratios of coil to tube diameter of 16 and 65 were

constructed from 0.42 inch I.D. stainless steel tubing and were heated

uniformly by using them as resistance elements in an electric circuit.

The results of their experiments were stated as:

I. DNB in coiled tube occurs at different steam qualities for

different position around the circumference of the tubes; whereas, for

a straight vertical tube, DNB occurs around the complete circumference

of the tube at one steam quality.

II. Coiled tubes have higher average DNB steam qualities than do
)
i
straight vertical tubes.

III. Surface temperature fluctuations at the DNB point are much

lower than those in a straight vertical tube.

IV. In the coil with the smaller coil to tube diameter ratio, DNB

occurs at higher steam qualities than in the coil with the larger ratio

of coil to tube diameter.

V. Increase in mass velocity increases the steam quality at DNB.

Rippel, et al [29] measured the pressure drop, holdup, and liquid

phase axial mixing in coils constructed by winding 0.5 inch I.D. tubing

around a cylinder 8 inches in diameter. Measurements were made for

concurrent flow of air-water, helium-water, Freon 12-water, and air-

2 propanol. Liquid holdup was measured by both the tracer method and

trapping method. They concluded that the pressure drop in two-phase


18

flow can be predicted with reasonable accuracy by a two-phase flow

correlation derived for straight horizontal pipe.

In a number of experiments by Owhadi, et al [4,25,26,27], the

circumferential average and local heat transfer coefficient for forced

convective boiling inside helically coiled tubes at near atmospheric

pressure was correlated against the Lockhart-Martinelli parameter. Two

coils of 9.86 and 20.5 inches in diameter with tube inside diameter of

0.492 inches were uniformly heated by an electric current. Flow rate


4 5
ranges of 5.83 x 10 to 2.32 x 10 lb /(hr-sq ft) were investigated.
The exit conditions ranged from 1.4 percent quality mixture to SO^F \
\
superheated steam. !

Following the above experiments by Owhadi, Crain, et al [11,12]

correlated the local heat transfer coefficient against the Lockhart- i

Martinelli parameter for higher qualities, using almost the same experi- ,

mental set up. The range of the pressure in these experiments was

0-35 PSI.

The results of the above experiments are quite similar in nature

and indicate that the effect of the secondary flow in distributing

liquid to the surface of the tube is very important and due to this,

heat transfer coefficients at all circumferential locations remains high

up to qualities of approximately 90 percent, after which the heat trans-

fer coefficient at points other than the stagnation points of the

secondary flow decreases sharply. At qualities slightly above 90 per-

cent, the heat transfer coefficient at the location on the tube farthest

from the axis of the helix decreases, but it essentially remains high at
19

the location closest to the axis of the helix even up to qualities close

to 100 percent.

Crain also conducted visual flow observations by wrapping 5/8-inch

O.D. X 1/2-inch I.D, Tygon tubing around a mandrel. This experiment

confirmed the existence of the secondary flow and its effect on distri-

buting the liquid on the tube wall.

Banerjee, et al [2] investigated the effect of the tube and coil

diameter, helix angle and liquid viscosity on flow pattern, pressure

drop and holdup for concurrent gas liquid flow in helical coils. Nine

helical coils with coil diameters of 6, 9, and 12 inches and helix angles

of 2, 5, and 8 degrees were constructed from 5/8-inch I.D. vinyl tubing.

To investigate the effect of tube diameter on pressure drop and holdup,

four other coils were constructed from stainless steel tubes of diameters

up to 2 inches. Air-water and air-oil mixtures were run through these

coils. They found that small helix angles had no effect on pressure drop

and holdup in coiled tubes and both pressure drop and holdup could be

adequately correlated using modified Lockhart-Martinelli parameters.

Bianchi and Cumo [5] reported the results of their study on heat

transfer and pressure drop in once through steam generators. A straight

vertical test section (11 m long, 12 mm in inside diameter) and a helical

coil (83 cm coil diameter, 15 mm tube inside diameter, heated over 62.8

m ) , both uniformly heated by electric current were used. They reported

that no correlation has been found that accurately correlates their heat

transfer data, but Thom's correlation gives the best result. They found

that pressure drop in a coil can be calculated by the homogeneous model


20

with a correction factor. Using this approach, the authors were able to

predict their experimental pressure drop results to within ± 10 percent.

In another experiment on once through boilers, Campolunghi, et al

[8] constructed a helical coil with 0.836 m coil diameter from 0.0155 m

I.D. tubing. Subcooled liquid water entered the tube at the bottom and

superheated steam exited at the top. Ranges of pressure and mass velocity
2
covered were 80-170 bar and 1000-2500 kg/m -sec, respectively. They

found that for the ratios of heat transfer to mass velocities of less

than 0.13 KJ/kg, no DNB occurs and, thus, one may consider a boiling

length extended up to 100 percent quality for this range. A mean boiling

heat transfer coefficient for the entire length is suggested by the

authors which predicts their results within a ± 30 percent error margin.

From this brief review of the available pertinent literature, it

becomes evident that most of the work done so far has been related to

flow inside straight conduits or helical coils where the test section

was heated uniformly by using it as a resistance in an electric current


i
circuit. At present the only study that the author is aware of in which

indirect radiant heating has been used is due to Davidson, et al [13]

which was done on flow in spirals heated by flame in a furnace, which

was reported in 1943.

Although the bulk of data and correlations obtained from these

studies are very helpful in understanding the general behaviour of the

system under investigation, it is felt that in order to be able to

accurately analyze the effects of asymmetry of the flux field around

the circumference of the tube cross section (as well as around the
21

periphery of the coil itself in some cases) on the thermodynamic and heat

transfer characteristics of the receiver system, a new set of experiments

is needed.

These experiments could include the effect of heat flux variations

around the circumference of the tube cross section, as well as the change

in parameters such as mass velocity, pressure, temperature and the quality

of the working fluid. A flow loop, designed to simulate these conditions

will be described in detail in the next chapter.

I
CHAPTER III

DISCUSSION OF EXPERIMENTAL APPARATUS

As it was mentioned earlier, in order to simulate the actual

working conditions of the receiver system in the FMDF Solar Thermal

Power system, it was decided to construct a test section, a helically

coiled tube, similar to the actual receiver. Then by changing the

incident flux and the state of the working fluid at the test section

inlet, one would be able to test the performance of different segments

of the receiver under various conditions of symmetrical or asymmetrical

heating. The flow loop must have the ability to provide the test section

with a working fluid ranging from subcooled liquid to a water-steam

mixture with different qualities, or superheated steam, corresponding to

the pressure at the inlet to the test section. The radiant testing

facility used in this study was designed to perform these functions.

A schematic diagram of the flow loop is presented in Figure 3-1.

It can be divided into the following major subsections, which will be

explained individually later in this chapter:

1. Equipment controlling the fluid conditions at the test

section inlet.

2. Heat exchanger.

3. Test section.

4. Solar simulator.

5. Condenser

6. Supporting instrumentation.

A summary of the major instruments used in this investigation along

with their stated accuracy are tabulated in table 3-1.

22
23

Test Section

i.Lt-i.
—@H-
C.V c.v
Condenser
©-<T) (P><T)
Hot O i l
Heater

©- H.X.
Pump

.-O ®-<T)
Cooling
Water

P.R.V. Pressure Relief Valve


P.D. Pulsation Dampener
H.X. Heat Exchanger
C.V. Check Valve V.8
V Valve
T
P
Temperature Sensor
Pressure Sensor 'Discharge i
'•>X V •^x m Flow Rate Monitor

Circuits By-Pass Line


(B) (A)
Water Supply
Tank

P.D. JT"" I

V.3 P.R.V.

Strainer

Figure 3-1 Schematic Diagram of the Test Loop


24
B^
in
r>« CO
• -H

o S^ ^s &«5 B«« o u fe
o
cd • in m O un
u 1)
U u Q)
u < o o iH o o Q)
> Q)
CC in <:
3
CJ
• • • • • •
2 o o O o fe Xi U «N
q +1 +1 +1 +1 0 O 60 +1
< O -H
• 4=
•<r >
+1

T3 <v Q iH
0) oo cn 1 -d-
<d
CM
iH 3 1 Q #t CM
iH Cd cu U ^ 1
•H
A V.I
o
iH iH Pi^ o r-i iH 0)
.c
4-1 ON
in
:s
<r1 0)
M
1
M
1
iH
•p d) (U a -H a\ CO
o CO 13 -o iH 0
H 3 P£S 0^ •H (U O o ^ ^
ft, CO H
M
TS PM O S S CO rH rH
cn = 0) (U
u (U
0) iH C iH iH A n A A C» • H X3 0 TD
S-i (U Cd (U (U &0 00 CO CO •->^ r H 0 4-1 0
TS M XI T3 •H •H +J 4-1 S S
3 '-' -9 Cd
u O H o O CO
Pu
CO
o a 6 a n
o s S S Pu 3 3 « Q)
*^ • H
cfl
:s n
T3 XI • CO • T3 •
4-1 «\ o A
O o O 0 0
• iH
o a CO
C M
c
3 • • O o U M
PL.
c <c
M M
C
l-H
C a fe o o O o P-i
C cd c c c iH iH (U cu OJ
o Is M <U l-l M 1 1 M o u •> t H M
U A

•H c O o (U
c a) 00 Oi 00 3 00
•u «4J ^ •H 0i
.< a cd o C 3 4J C 4J c
cfl >^.0 >. >^ A A 3 4J 3 •H O 0 T\ Cd •H
a iH ao M3 00 t>0 (U (U T3
CO
O XI
CO
V4
OJ
a Q)
o C
!-i $-1
<U
^
(U
•H (U o
iH H
o
iH
o
iH
00 00 3
rH CU
<u x:
M-l 13 3 3 C C 0) e 0C a (U 0
I •H O o o o Cd cd cd QJ cd
c cu
u c e c u
•H 0 • H 0) •H •H
JJ
s c A
c c o o u Pd >-i
fcc 4:: CO 00 H 00 5
x; J2 H H
o s
C J=
(U 4.) tu H •H C CO
0) H o o $-1
iH
C
rH c
iH 0) fe <u 0) M-l 0) O O w ^ c w Cd w ?^
H H H O rH o U3 O
CO «\ u (U CO Cd CO cd 4J .i«5 Cd 4-1 cd J-l ]
H > vO 5 5 o CO (U •H <u 0 0 cd 0 00 •H 0 0 cd
c o H 1 o O .c M iH M rH 0) (U • H 0) 0 0 (U 4->
<u iH rH i-H CO d) 0) Cd (U ^ 3
6 CA; 6 •H s 0
6 P"4CL, ^ [x^ < :s CJ) > CJ 0
o- 0 0 0 pu
p.
•H
3
cr
w
/-N 0
p.. CO
<
^w/
1 #\
U-)
P^
u j-i
H
A
0 /—s $-1 X
ro 4-1 0) <1-
4J <u •H
Cd •S /-\
0 a
3
Hn
c #\ /-^ 3
:s ro
CM in r>. X) XI
00
QJ CD H
x:
0
.H •B PH a< CO
CO n 4->
CO /"-N A A A
3 C
cd CN •H
OJ rH CN <r vD cd 3
S-i
0 f-i 1 1 pL. PH
u H 5
1 rH rH #1 A
H ^ H M CO
•6 0 rH
C ro 'B
v-^
CO
PH
rH
(U 14-J (U 5-1 5-1
0 PH
v,^
H 0 0
• H (U >«-' M U ^^-^
•P M S-4 }-l 3 !-i 3 4-1 4-1
CD 0 CO U Cd
cd 3 0 0 M V4
CO 4-1 CD 0 0
a
a 00 !-i u 4-1 0
4J
0
4-1 (U Cd (U CO •H
<u
0 -H 0 cd Cd
r-{ T3
^(U
a 5-1 pi
HJ C^ 4-1 0 Cd Cd v^
PH (U CO
•H ^H •H 0 a 3 PH
CO M
3
<^ c •H XI
c
0
X3 XI •H
XI -0 r-\ 0 ^ cu
0 c Mc Cd B •cd (U CU rH
c
0 s M
Mc Hu •H H
cu 4J 5-1 5-1 O.
•H 0) (U 0) 4-1 Q 3 3 3
4-1 4-» 4J 4-1 (U (U C C 4J 4-1 0
0 cd Cd Cd }-i 5-1 (U J-i (U Cd Cd 0
(3 P^ pts (ii 3 3 ^ (U 5-1 U / ^ 5-1 0
•H (U 0) r^
3 CD CO cu cu e
5-1
1
r-l
5
0
rH
5
0
rH
CO
0)
l-l
CD
0)
>-i
14-1
l4-(
•rl
U
U
cd
14-^
U-i
•H
P-
6
cu
H
•>
vo
a
6
cu
cu
f=M fe fe PH PH 0 0 0 H H H ^
25
(U
(U
>% i H
4-» a g
;>> 3 4J
o ^ u O U a
cd tH
• < < < < <: <: < <3 <3
o o o cu
14H 0 14-1
u O • • • • • e
3 • • • • 6 cu
O +1 z 3 Z z z z z Z Z PH 5-1 6>5 5^
o 0 (U r H 3

0.0
leas
1.5
<
•M

+1 ts^ +1 B

X j-i
O crt
CD 4-> g >.
•U •H 5^ 5-1 4-1
rH :$ CU <U •H cu
>
O CO

>%
g j - \
rH •P
cd
O
CO
P.
r-{
.Q

U 5.4
o cd
53
& 5-1 cu B
o cd 4-1 « a
4J cu C 5-1 Cd
4-J cu O 5.4
o
in
o
psJ rH
o
CJ J3 e
3 •P 00
CX3 3 3 6 cd o
M cs r-\ PH < (U H •H r-{ 5-1
CU O 1 M >< 3 5-1 PH
5-1 rH A
O 3 X3 Cd o
3
T-^
CU CM 4J C S e
3 p A

4-* X3 1-^ c
o in Cd cd a cd <t
a O CU •H o 5.4 ,C o r-{ vP
cd S X3 4-1 1 CU rH 4-1 <: 3 o B
(4-1 O cd EH P. rH •H •H 00 CM CU
3 A
S u ^ B CU 15 CO o cu 1 P
d • o cu X fl4
o Pi Q CD
C p. rH H CO O • dn >i
cd O A


o cu P. CO
XI
O
•H s CJ
u Xcu m
CO o
vP
5-1 rH
P. o I O #t
o o 5-4
CU 3
(U 4-1 oa o 5^ u o in • o 3 O
3 cd •H O
s in
o rH T-ll r-\ CD CJ 3 X) o
o CJ CU CD •H O 'H
Mc
rH M rH CU
•H •H CU 4-1 Cd «k CO X I 4-> X3 cu CD <4-l S P
4J cu CU •H •H
>4H Ti a r-^ B 5-1 o Cd 0 5-1
3 •H o cu O 5-1 CU •H •1
S s P-. > 3 " CD
O 4-1 rH 5.4 (U 4J 5.1 S T-\ 3 CU "H
s 43
W
g P3cdcu PH «v
A
3 4J <U Cd 5-1 M Cd cd 3 3
a cu CO > ffi •H cr
c Pu CU
a a p.
XI c O 1 00 B o E e 1 rH O
P rH C 3 -^ 3 3 >^ 5-1 5-1 < :
O U o1 • PH CU
I CO o
X) Cd cd (i4 PH cu
p
cu
4-J Cd
CO P' CU 4-1 • H ^ 4-> . 3
o .i»i
C B > ^ 3 C CD o 4-1 P p •H 5-1 CD P
cu
i
Pu
•H
CO
o
1-4 Pt^
3 rH cu
PH
3
CJ ^
Cd M-l
CJ 0
cd
CJ
cd
CJ § cd
PH
Cd
P4
Cd
o
cd •H
H 3
cr
w

5-1
O
P
cd cu
C rH
00
•H O
CD
p
u PS
CU .P PH
O rH a 3 /—V N»^
1 p O
Q
3 CO •H a
Ive

P-i
O 5
• H CU CO o
4-t 5-1 •H
M p 5-1 cd
cd 3
O 00 M O cd CU >
O -H CU 4-1 S 3
CU M-l
HJ PU 4-1 CJ o
p U P. CU
^
r-i
cu 3 CU B •H
^a 3 p
B
CU < 00 cd rH
3
o rH CO 3 Q CU CU 5-1
5-1 5-1 cd Cu Pi > CU
o o CU .3 B 3 r-li 5-1 00
•H > 5-1 CU
O CU Cd O 00
p CU P P o 3
P cd •H 5-1 > CD
o
o r-^ cd
cu ^
PH P 3 3 hJ
3 Cd 9J cu CO
3 p 6 33 DS 5-1 Cd ^ cu
p p CU CD CO o XI cd
Pu •H
p
00 j - ^ rH :-^ cd P j-i cu cu 3
•H 0 •H •H cu cd 3 5-1 -3 O Cd
Q > O X IS PU PH CJ O O
o
26

3.1 Equipment Controlling the Fluid Condition

at the Test Section Inlet

Deionized water stored in a water supply tank was drawn by a

positive displacement pump through a strainer. The pump was a Cat

pump model 330 which was capable of delivering 4.0 GPM at 1000 psi. This

pump provides a relatively uniform flow, but to insure that even these

minor pump pulsations will not result in any kind of flow instability

in the system, two pulsation dampeners or accumulators with different

amounts of charges were installed. It was determined experimentally

that one of these would dampen any pressure fluctuations when the pump

discharge pressure was below 300 psi and the other which had a higher

charge pressure would dampen the fluctuations for pressures above 300

psi. Both of these accumulators had a maximum working pressure of 1000

psi and a safety factor of 4 to 1.

An adjustable pressure relief valve was installed after the pulsa-

tion dampeners to keep the pump and the other components of the flow

loop below a safe pressure.

In order to adjust the total mass flow rate to a desired level, a

bypass line was provided. This line would return the excess deionized

water back to the supply tank. The flow then passed through one of the

two flow rate monitors with different ranges of flow measuring capability.

The smaller one had a range of 0.05 to 0.5 GPM, while the larger one had

a range of 0.5 to 4.5 GPM.

After measuring the total mass flow rate, temperature and pressure

of the fluid, it was delivered to one of the two lines which hereon will

be called the superheated vapor line (line A) and the subcooled liquid
27

line (line B). Each line was equipped with a micrometer needle valve.

The amount of fluid flowing through the subcooled liquid line was

measured by another flow meter with a range of 0.25 to 2.5 GPM. The

difference between the total flow rate and the flow rate through the

subcooled liquid line represents the flow rate through the superheated

vapor line.

The fluid passing through the superheated vapor line was passed

through a shell and tube heat exchanger where it was converted to super-

heated steam.

During the course of the experiments, it was noticed that after

the system was shut down, the steam or hot water in the heat exchanger

tends to flow backward through the system. As this would possibly result

in damage to the pump, a check valve was installed before the heat

exchanger.

After the temperature and pressure of the steam leaving the heat

exchanger was measured, the subcooled and the superheated vapor flows

were combined. Each of the lines were provided with a check valve before

this connection was made, as the higher pressure in any one of these

lines might force the fluid in the other line to flow in the reverse

direction or probably would tend to stop the flow in the other line.

The temperature and pressure of the mixture was measured after

this junction. Using these measured quantities, i.e., the total flow

rate, the subcooled liquid flow rate and pressures and temperatures

measured at three different locations before and after the connection

was made, and by a simple energy balance on the system, the enthalpy of

the mixture at the inlet to the coil was calculated. If the state of
28

the system at this point was saturated, the quality would also have to

be calculated.

By changing the total flow rate, subcooled liquid flow rate and

the pressure and the temperature of the discharge steam from the heat

exchanger, a mixture of steam and water with different qualities as

desired was obtained. It was also possible to send the fluid through

only one of the lines, to get a superheated steam or subcooled liquid

with different temperatures corresponding to the pressure at the inlet

to the coil.

3.2 Heat Exchanger

To be able to simulate the actual working conditions of individual

sections of the main receiver system in the FMDF system, the test ^
i
facility must be able to provide the test section with a working fluid
I
ranging in temperature from a compressed liquid to a two-phase mixture i

of steam and water or superheated vapor.

A gas-fired oil heater with an oil to water shell and tube heat

exchanger provided the thermal energy necessary to meet these ranges of

conditions. The heat transfer oil (Exxon Calora HT43) in the system was

heated by a Fulton's "Fultemp" gas-fired oil heater up to a desired

temperature with an upper limit of 650°F, which is the maximum tempera-

ture that this oil can stand without being degraded. The oil heater was

equipped with an automatic temperature controller, a Fenwel series 550,

which would shut off the flow of gas to the oil heater as soon as the oil

temperature was within a few degrees of a preset value, while the oil was

continuously being recirculated through the heat exchanger.


29

The heat exchanger was a Cust-0-Fab, Inc. shell and tube heat

exchanger with a counter flow, one-shell pass, one-tube pass design with

18 rows of 3/4-inch O.D. tubing. It had a design temperature of 600*'F

on the tube side.

3.3 Test Section

The helically coiled tube test section used in these experiments

was made from 14.7 feet of type 304 seamless stainless steel tubing with

a 3/8-inch outside diameter and 0.049-inch wall thickness. The coil was

made by wrapping the tubing around a cylindrical mandrel in such a manner

that consecutive turns of the coil were in close contact as was dictated

by the design of the receiver in the FMDF system. The diameter of the

coil, from tube center to center, was 2.74 inches and the coil had a

total number of 20 turns. No measurable flattening of the tube during

this process was noticed.

In order to measure the variations of tube wall temperature along

the axis of the tube as well as its circumferential direction, a total

number of 42 type K (Chromel-Alumel), 20-guage thermocouples were located

on the outside surface of the tube in a special arrangement such that

there was one thermocouple station at each 1 1/3 turns of the coil. At

each thermocouple station, either two or four thermocouples were arc

welded or silver soldered to the tube surface. At the stations with

two thermocouples, one was arc welded on the location of the tube wall

farthest from the coil axis (location A, 6 = 0 ° ) and one was silver

soldered on the location nearest to the coil axis (location C, 9 = ISO**).

At the stations with four thermocouples, two more thermocouples were


30

silver soldered at 90-degree angles from locations A and C mentioned

above (locations B and D counterclockwise). A schematic diagram of

thermocouple arrangements around the circumference of the tube cross

section is shown in Figures 3-2.a and 3-2.b.

Arranged in this manner, the coil as a whole had three rows of

thermocouples along the axis of the coil located 120 degrees apart.

There were a total number of 15 thermocouple stations along the coiled

tubing, located at intervals of approximately 0.98 feet. This arrange-

ment would allow the measurement of the temperature variation around the

circumference of the tubing, as well as in the axial and circumferential

directions of the coil itself.

The lead wires of all of these thermocouples were connected to a

data logger for readout and recording of the temperatures at each thermo-

couple location on the coil. This data acquisition system scanned and

recorded all of the temperatures and. flow rates measured along the flow

loop. It was an Esterline Angus model PD-2064 which was programmable

with 64-channel recording capability.

Thermocouple station numbers, number of thermocouples at each

station, and the distance between each thermocouple station and the coil

inlet are given in Table 3-2.

After the thermocouples were connected, the coil surface was wire

brushed and then coated with Tempil Corporation "Pyromark 2500" flat

black paint. This special paint is reported [371 to have a high absorp-

tance in the solar spectrum (a = 0.90) and to be able to withstand

temperatures up to 2500**F when properly applied, cured, and vitrified.


31

^^' ^'

-x-'y^

Ci(^

Coil Axis

Figure 3-2.a Figure 3-2.b

Figure 3-2 Circumferential Location of Thermocouples;


3-2.a: Stations with two thermocouples
3-2.b: Stations with four thermocouples
32

Table 3-2

Location and Number of Thermocouples


at Each Station

Distance
Station Number of
from
Number Thermocouples
Coil Inlet
(inches)
1 2 4.4

2 4 16.2

3 2 27.9

4 2 39.7

5 2 51.5

6 4 63.3

7 2 75.0

8 2 86.8

9 2 98.6

10 4 110.3

11 2 122.1

12 2 133.9

13 2 145.6

14 4 157.4

15 2 169.2
33

After the paint was dry, it was cured in the oven for one hour at 480''F

and for one hour at 1000**F,

Figures 3-3.a and 3-3.b show pictures of the coil and the thermo-

couple wires before the coil surface was painted.

The pressure drop across the coil was measured by a Celesco model

P-3D differential pressure transducer which was capable of measuring

differential pressures in the range of ± 0.1 to ± 5000 psi at high line

pressures by the use of interchangeable diaphragms. This transducer

operates in combination with a Celesco model CD-10 carrier-demodulator

with 10 volts DC output. The output of this demodulator was connected

to a Simpson model 2850 DC digital voltmeter through a rotary selector

switch.

There were also two precision type pressure gauges, Ashcroft 0-1000

psig oil filled gauges, placed at the inlet and exit to the coil. The

combination of the test gauge at the inlet to the coil and the differ-

ential pressure transducer across the coil provided the pressure at the

test section exit with the second pressure gauge at the exit giving a

check on the performance of the differential pressure transducer and also

acting as a back-up system during the tests.

3.4 Solar Simulator

As it was mentioned earlier, in order to investigate the performance

of the receiver coil, it was necessary to simulate the intensity of the

incident radiation along the actual receiver in a segment by segment

fashion. The radiative fluxes that this solar simulator must provide

were defined by previous analyses performed by both Texas Tech University


34

Figure 3-3.a Close-up view of the thermocouple


j u n c t i o n s on the c o i l

</

&j^^

Figure 3-3.b Coiled tube test section before


it was painted
35

and E-Systems Corporation [36,37]. For example, at solar noon and a

zero degree incidence angle, assuming a perfect reflectivity of 1.0 for

the mirror surfaces, the incident flux upon the receiver ranges from

30 suns at the bottom of the receiver to 650 suns at the top. Each sun

is generally defined as the amount of incident flux upon the surface of

the earth on a clear day and is taken to be 1000 w/m^. The distribution

of the incident flux at solar noon was presented earlier in Figure 1-4.

This figure also shows how the axial length of the receiver was sub-

divided into nine different segments. The average incident flux for

some of these segments was reproduced by using a solar simulator

described below. Asymmetrical incident flux distribution at times

other than solar noon is given in reference [36].

Sandia Laboratories had fabricated a series of infrared lamp panels

for use in solar receiver testing. These panels were made available to

Texas Tech University for the period of these experiments.

The panels had a polished aluminum reflector and were designed to

hold up to 17 pairs of T-3 quartz lamps with a distance of 0.5 inches

between the center of the lamps. The panels were approximately 18 inches

square and were composed of a main reflecting panel and two electrical

busbars. Each of these three components had a separate water cooling

jacket as it was required to keep the panel temperature below 160°F

during the period when the lamps were on. To achieve this, a cooling

water system was designed to deliver approximately 3.0 GPM of water to

the reflecting panel and 0.5 GPM to each of the busbars. During each

experiment, water flowed continuously through the cooling jackets. A


36

schematic diagram of one of the panels is reproduced from [34] in

Figure 3-4.

In order to be able to approximate a uniform circumferential

radiant flux incident upon the test section, three of these panels were

arranged in a triangular fashion. These panels were mounted on a frame

in such a manner that the panel in the bottom was fixed and the two side

panels were hinged at the bottom. This arrangement allowed the repro-

duction of the symmetrical flux distributions when the two side panels

were brought together, with the simulation of asymmetrical flux distri-

bution possible by opening the two side panels.

The electric power required for the lamp panels was provided by a

300 KVA, 400 A, three phase dry transformer.

Figure 3-5.a represents a typical triangular arrangement of the

lamp panels and the location of the test section at the center of the

triangle, while Figure 3-5.b shows a typical lamp panel arrangement when

the side panels are open.

3.5 Condenser

In cases where the pressure and temperature of the effluent frc:om

the test section indicates that saturation conditions exist at the out-

let, the quality of the mixture must be determined.

One of the methods of calculating this exit quality is to condense

this two-phase mixture into a subcooled liquid and measure the amount of

heat released during this process. A simple energy balance on the system

will then reveal the exit quality.


37

Panel Cooling
Serpentine Reflective Back
Panel
ih 'I !! 'i !i ii It!! lull i! i| iM iinN n n i li i li ji ii ii / •rv^
«>~'i /

o r
/

I
I
I
/ » (.--. i /
i f
/

' I 1
I 1 I

i!«
I
I

I I

1 1 '
I I .

/ >«.
--^ u

"!! :i !| :! i| ^i il 11 'I '!lii ! !! |l i: 'I ii zM


Electrical Teflon
Busbars Instilator

nnOinJ]J!y]rtnOr^^^ Busbar Cooling Channel


• • ,

TET
i :
nu \ r
Teflon Insulator

1 r Cooling
Cooling Water
Water

Figure 3-4 Schematic Diagram of Lamp Panel


Representing the Cooling Channels
38

Figure 3-5.a Triangular Position of Lamp Panels

^^jj^^j^^^^^J^^Jj^^^^^^^y^ln^y,

Figure 3-5.b Open Position of Lamp Panels


39

Therefore, a condenser unit was placed in the flow loop after the

test section. The unit provided was a compact heat exchanger made of a

helically coiled annulus. The outer tube which carried the cooling

water was copper, while the inner passage was made of stainless steel

tubing to withstand the higher pressures. The unit was capable of

removing 400,000 Btu/hr at 7 GPM of cooling water flow. The condenser

was tightly wrapped in several layers of insulating material and was

then placed in an insulated box to minimize the heat loss.

The cooling water flow rate was measured by an in-line turbine

flow transducer with a flow measuring range of 5 to 60 GPM. The pressure

and temperature of the cooling water at the inlet and exit of the con-

denser and the temperature and pressure of the working fluid at the exit

from the condenser were also measured. Assuming that all of the heat

being removed from the working fluid during the condensation process

was transferred to the cooling water, the quality of the mixture entering

the condenser (leaving the test section) was calculated by an energy

balance on the condenser. In cases where the entering fluid was not

saturated, the enthalpy of the fluid calculated in this manner provided

a measure of accuracy for the measured temperature and pressure at the

exit of the test section, as well as the amount of incident flux upon

the test section.

Figure 3-6 is a photograph of the test facility which shows the

arrangement of the lamp panel cooling water lines, the condenser unit,

and the lamp panels in their open position.


40

Figure 3-6 Photograph of the


Test Facility
41

3.6 Supporting Instrumentation

The instruments that were used to measure any one of the different

quantities during this experiment comprise a major part of the equipment

used. Although some of these instruments were mentioned briefly in pre-

vious sections while describing other major components of the flow loop,

it is thought that a more precise description of some of the more impor-

tant ones under a separate heading would serve the purpose better. These

instruments can be classified as follows.

3.6.1 Flow Measuring Instruments

Four flow rate monitor units with different ranges of flow measuring

capabilities were used. These units were each composed of a Flow

Technology, Inc. standard line, turbine flow transducer, and an econo-

line indicator.

Flow through the turbine-type flow transducer produces electrical

pulses which are transmitted to the econo-line indicators. These

indicators have an analog readout device which represents the flow rate

as the percentage of the maximum flow. The indicators also provide an

analog output of 0-10 VDC. This voltage output was connected to a

digital voltmeter via a rotary switch for instantaneous readout and also

to the data logger for recording of the flow rates during each run.

These flow meters were calibrated in the factory at the time of

the purchase and were also frequently checked against each other or re-

calibrated using a graduated container to measure the effluent liquid

during a certain time interval.


42

3.6.2 Temperature Sensors

The temperature of the fluid flowing through the flow loop was

measured at eight different locations by placing type K, sheathed thermo-

couples in the direction of the flow. The output of these thermocouples

was connected to a digital temperature indicator via a rotary switch and

also to the data logger. This procedure proved to be very helpful as it

was very easy to check the fluid temperature at any desired location

along the flow loop, while other variables were changing.

Another thermocouple was used to measure the temperature of the

lamp panel cooling water. If the temperature of the cooling water after

circulating through the cooling jacket on the panels rose above a pre-

scribed limit, an automatic switch would be activated to cut off the

electric power to the lamps. The sound of a buzzer and an indicator

light on the instrument panel would inform the operator of the problem

in the system.

3.6.3 Pressure Sensors

The pressure of the fluid flowing through the test section was

controlled by a valve located after the condenser unit. Pressure was

monitored at seven different locations along the flow loop. Precision

type pressure gauges with a range of 0 to 1000 psi and 5 psi graduations

were used.

At the heat exchanger exit and inlet and at the exit of the test

section, the gauges were oil filled to further increase the accuracy of

the measurements. Pressure drop across the coil was also measured by a

differential pressure transducer and compared with the gauge readings.


43

An automatic pressure monitoring device was placed at the exit

from the test section. If the pressure in the system due to any mal-

functioning of the instruments or human error rose above the preset

value, this device would automatically turn the pump off and inform

the operator by the sound of a buzzer and the indicator light on the

instrument panel. Figure 3-7 is a picture of the instrument panel.

The radiant test facility, composed of the lamp panels and the

frame structure, the test section, and the flow lines, was located in

an area surrounded by a 12-foot high concrete block wall. This pre-

caution was taken to avoid any personal injury due to exposure to high

pressure steam leaks or high heat fluxes. Figure 3-8 shows the relative

location of different components of the test facility.


44

Figure 3-7 Instrument Panel


45

1.
.y

>s u cu
U (U
a B u
u U 3
< a a OJ u
> U4
•^ o
^ CO
C r-t
c
C8 •H O s
o M U C 0)
o
cn e- VM CJ "a
O CO
CN r-t
^ S3 3
5.1 0)
<U
1/ / / / / / / / / / / / / / / / / 7 CO
c c
CO ns
rr 1-1
^ U
X

/ / ctj
(U

u u
<v
Su p
0 CC
iJ / 3 CD
31 c I
r-l
W4 o
•H
E ^
.p^ O C
CO CU C8
CO •art
5-1
Cd 4_i
f-i OJ
o a
cn H
00
I
CO

/ cu
1/ 5-1
3
/ / / / / / / / / / / // / / 00
•H
CHAPTER IV

EXPERIMENTAL PROCEDURE

4.1 Introduction

Instruments installed in the test facility were chosen based on

the desired measurement range, application, and accuracy requirements.

On-site calibration was also performed on all flow meters, pressure

gauges, and selected thermocouples before installation in the test loop.

Pressure gauges were checked against dead weight tester and, in

all cases, showed no more than ± 2 psi deviation. On the flow meters,

the turbine flow transducers were checked for cleanliness and free

rotation of the turbine rotor.

The instruments were then placed in the flow loop. At places

where the temperature of the flowing fluid was to be measured, a sheathed

thermocouple probe type K, 1/8 inch in diameter was inserted against the

flow direction in an effort to measure the bulk temperature of the fluid

as close as possible. The flow meter transducers were placed in horizon-

tal sections of the flow loop, upstream of any flow control valves and

bypasses. The calibration of these flow meters were checked several

times during the period of the tests by collecting the effluent of the

system in a graduated container.

For each series of test runs that were executed, the main variable

could be considered to be the heat flux intensity which was set to a

predetermined level by arranging the lamps in the lamp panel into a

specific configuration. These lamp configurations were determined by a

previous investigation [34] so as to reproduce the average radiation

46
47

intensity at successive segments of the receiver. The average intensity

of radiation for different segments of the receiver for the case of

solar noon at a zero degree angle of incidence was shown in Figure 1-4.

At this time of the day the distribution of radiant flux around the

circumference of the receiver is symmetrical, but in the early morning

and late afternoon the receiver will be subjected to both axially and

circumferentially asymmetric radiant fluxes.

Both symmetric and asymmetric radiant fields were mapped [34] by

manipulating lamp and panel configurations to most closely simulate the

actual radiant conditions the receiver would encounter in the field.

In order to measure the intensity of radiation from the lamps, a

fluxmeter was constructed consisting of a Gordon gauge calorimeter

placed in a replacement receiver. This calorimeter was calibrated by

the manufacturer using quartz filters in an effort to accurately repro-


•i
duce the radiant spectrum of the T-3 quartz lamps. l

Using this approach, symmetric flux plots of intensities ranging

from 24.2 to 156 suns and ass3rmmetric flux plots of intensities ranging

from 15 to 220 suns at the peak were mapped. Figure 4-1 is a photograph

of the fluxmeter in the test section. Figures 4-2 and 4-3 are two

examples of the symmetrical and asymmetrical incident fluxes that were

mapped by using this fluxmeter [34].

At the beginning of each series of tests, the magnitude of the

heat flux for those tests was chosen and the lamps were placed in the

lamp panels according to the lamp panel configuration corresponding to

the desired heat flux level. The oil heater was then ignited and the
48

Figure 4-1 Photograph of Experimental Flux Plot Configuration


49

160-
1501
140-
CN 130-
^ 120-
•J

"^^ 110.
c:
0
100-
u
CO
5a 90-
4J
80-
o
c 70-
CJ
u 60j
cu
3 50-
0
A4
4J 40.
c.•3
-H
30-
5J
06
20-
101
0
-r
—r 90 120 150 130 210 240 270 300 330 360
0 30 60
Caloriineter P o l a r P o s i t i o n (")
Figure 4-2 Symmetric Flux Plot
50

rM

I
5. 13C4

120 ii
UO
u 100
u
3
90'
80 •
70-
60 .
50.
40,

30-
20-
10 -

0 30 60 90 120 130 180 210 240 270 300 230 360

Calcriaecar Polar Position ('')


Figure 4-3 Asymmetric Flux Plot
51

flow of the working fluid through the coiled tube test section was

started.

When the temperature of the steam at the heat exchanger exit was

about 500**F, the flow of the cooling water through the condenser and the

lamp panel was started.

The total flow rate and the subcooled liquid flow rate was then

adjusted to give the desired flow rate through the heat exchanger. At

this point the power line to the quartz lamps was connected. The temper-

ature of the fluid entering the test section was always a good indicator

of when the existing conditions were close to steady state, as otherwise

temperature fluctuations were noticed.

4.2 Single-Phase Runs

Experimental runs during which only single phase fluid was flowing

through the test section was performed for both subcooled liquid and

superheated vapor states.

The subcooled liquid runs were usually the first experiments that

were performed during each day that the system was operated. A few runs

with the liquid at the temperature of the supply tank, but with various

flow rates and different inlet pressures, were performed first. The oil

heater was then ignited and the process of heating the fluid through the

heat exchanger was started. At any point during this process, fluids

with different degrees of subcooling were obtained by keeping the inlet

pressure above the saturation pressure for the existing temperature.

The superheated vapor runs were executed in the same manner as the

subcooled liquid runs, except that the inlet pressure was kept below the
52

saturation value. By increasing the flow rate through the superheated

vapor line, steam with different degrees of superheat was obtained.

4.3 Two-Phase Runs

For tests involving two-phase conditions, it was necessary to mix

two streams of fluid, one superheated steam and the other subcooled

liquid, both with known pressure, temperature, and flow rate. Having

these measured properties, one could easily calculate the enthalpy and

hence the quality and other properties of the mixture by a simple energy

balance at the junction of the two inlet streams of fluid. A sample

calculation will be presented in the appendix.

After the desired mixture of liquid and vapor at the test section

inlet was reached and it was assured that the conditions were such that

the assumption of steady state condition was applicable, a set of data

was taken. The next step then was to either change the pressure or the

flow rates in an effort to establish a two-phase mixture.

Initially, the superheated vapor flow rate was slightly decreased

while the subcooled liquid flow was gradually increased such that the

total flow rate would stay constant. In this manner, at a given total

flow rate, the state of the fluid entering the test section would vary

from a high quality mixture to one with a low quality. Then, the total

flow rate was either increased or decreased and the same process was

repeated in a reverse fashion, such that the compressed liquid flow rate

was decreased and the superheated vapor flow rate was increased while

the total flow rate was constant.


53

It should be mentioned here that in some cases when the two-phase

runs were being executed, at special combinations of mass flow rates

instability in the system was noticed. Rapid fluctuations in the

pressure and temperature of the fluid at the inlet and exit to the test

section were an indication of the unstable condition present. The range

of temperature fluctuations were sometimes in the order of ± 30*'F in

less than 30 seconds. Parallel channel instabilities are thought to be

the cause of these unstable conditions. No special instrument for

recording of these fluctuations was considered and, thus, no data were

taken. A change in the pressure at the coil inlet or change in the mass

flow rate combination was found to resolve the problem.


CHAPTER V

THERMAL ANALYSIS

In previous chapters, it was mentioned that in the process of

convective boiling, the hydrodynamic and heat transfer mechanisms are

very closely interrelated. The existence of the complex flow patterns,

the unknown slip ratio (ratio of the gas phase velocity to the liquid

phase velocity) between the phases and the uncertainty about the local

conditions existing at any point in the channel render the problem very

difficult to be solved analytically.

For flow of a two-phase mixture in a coiled tube, in addition to

the above mentioned difficulties, one encounters the effects of the

secondary flow in the vapor core which constantly exerts a drag on the

liquid droplets in the flow, causing them to move outward from the

center section of the tube to the outer wall and then circulating along

the tube wall back to the wall closest to the center of the curvature.

In the problem under investigation, the combination of the factors

mentioned above, along with the fact that the incident flux around the

circumference of the tube is asymmetrical, causes the problem to be very

difficult, if not impossible, to be solved analytically, thus necessi-

tating this experiment.

The succeeding will present the development of an analysis for the

heat transfer characteristics in two-phase helical flow for the case of

both symmetric and assjnranetric radiant heating of the helical coil.

Results will be presented in Chapter VI from the experimental test

program for the case of symmetrical heating for a range of flow rates,

54
55

heat transfer rates, and inlet thermodynamic conditions to the test

section.

The quantities necessary for the calculation of the heat transfer

coefficient at the inner surface of the tube are:

q^ = Heat flux at the inner surface of the tube,

Btu/ft^-hr.

T^ = Wall temperature at the inner surface of the tube,

Tg = Bulk temperature of the fluid at the axial loca-

tion considered, "F.

In this chapter, the method of calculation of each of these

quantities is described. In section 5.1, total heat absorbed at the

outer surface of the tube is calculated. Radiative and convective heat

losses from the coil to the ambient air are also considered. In sections

5.2 and 5.3, the general form of the functions representing the circum-

ferential temperature and heat flux distribution of the outer tube sur-

face are discussed. Using these boundary conditions, the heat conduction

equation is solved in the interior of the tube wall. As the final result

of this solution, the heat flux and temperature distribution around the

periphery of the inner wall of the tube cross section is found. Deter-

mination of the bulk temperature of the fluid at the specified axial

location is the objective of section 5.4.

When all of the necessary quantities for any given axial location

are calculated, the local values of heat transfer coefficient are found

according to:
56

^'R.,9
i'
(R^.e) T^ - T
R.,e ^
1

5.1 Calculation of Total Heat Input

Previously, it was explained that the lamp panels were mounted on

a frame such that the two side panels were hinged at the bottom edge.

When these two side panels were brought together, the three panels would

form an equilateral triangular prism. This arrangement of the panels

with the coiled tube test section in the center was used for the cases

where heat flux around the circumference of the coil was symmetrically

distributed. With this arrangement, the case of asymmetrical distribu-

tion of incident flux could also be tested by moving the coil off-center

or by opening the side panels to form a three-sided rectangular prism.

Considering the geometry of the helically coiled test section and

the variations of the incident flux around it, the problem of the calcu-

lation of the heat input into the test section can be divided into two

general catagories: one with symmetrical heating over the outer surface

of the coil and one with asymmetrical heating. Now, since only half of

the perimeter of the coiled tube can see the radiation source, there

will always be a variation of incident flux around the circumference of

the tube, regardless of whether the distribution of flux around the

periphery of the coil is symmetrical or asymmetrical.

If a portion of the coiled tube test section equal in length to

one turn of the coil under actual working conditions could be unwrapped,

it would be noticed that when the incident flux around the coil is
57

symmetrical, there would be a uniform incident flux along the axis of

the tube section while there is a non-uniform distribution around the

circumference of the tube. On the other hand, when the flux around the

coil is asymmetrically distributed, there is a non-uniform flux along

the axis as well as along the periphery of the tube section. These two

types of incident flux distribution are shown in Figure 5-1.

As it was mentioned in previous chapters, the variations of

incident flux around the circumference of the coil for special lamp

configurations were previously measured and reported [34]. This distri-

bution of flux is the same as that shown along the axis of the tube

section in Figure 5-1. Based on this for both symmetrical or asymmetri-

cal cases, a function q. (6) can be found to represent the circumferen-


mc

tial variation of incident flux around the tube cross section at each

specific axial location. The form of this function will be discussed

in more detail in a later section.

The heat losses from the outer surface of the coil are due to con-

vection and radiation to the outside environment. These heat losses will

also be a function of the circumferential position around the tube cross

section, as the tube surface temperature is not uniform. These heat

losses are represented by q ^^^O) fo^ convective losses and q^^^C©) for

radiative losses.

If the heat conduction to the adjacent tube and central support is

neglected, the net heat absorbed by the tube surface at any specific

axial location along the coil and at angular position 0 is given by:
q (6) = q. (6) - q (6) - q ,(9) (5.1)
^o ^inc ^conv rad
58

V.

Figure 5-1.a
Symmetrical Heating: Uniform in axial direction,
non-uniform in circumfer-
ential direction

Figure 5-1.b
Asymmetrical Heating: Non-uniform in axial and
circumferential directions
59

where:
2
q. (9) - incident heat flux, Btu/ft -hr
inc
2
qconv (9) = convective heat loss, Btu/ft -hr

2
q ,(9) = radiative heat loss, Btu/ft -hr

= a£{[TQ(9) + 460]^ - [T^^^ + 460]^}

The form of the function representing T-j(9) will be discussed in

section 5.3.

Consider the problem in a general form that would include both

cases of symmetrical and asymmetrical flux distribution. Assume that

the distribution of flux in the axial direction of the tube section in

Figure 5-1 is given by a function, f(z). At a point z along the axis

of the tube, let f (z^.) = b-

If the shape of the function representing the distribution of the

flux around the circumference of the tube cross section is known, then

q. (9) for each angular position can be calculated. If T^(9) is known,


inc ^ ' ° u
the convective and radiative losses can also be found. Then, the general

form of the function qQ(9) representing the net absorbed heat flux can

be evaluated.

The total heat input up to any axial location z is then calculated

by dividing z into small differential elements with equal length Az and

then integrating qA^) around the circumference of the tube, multiplying

by Az and summing these integral values. Assuming steady-state condi-

tions, this also represents the total heat added to the fluid up to this

axial location.
60

If the amplitude of qQ(9) in each differential element with length

/Az is taken as the average value of f(z) in that interval, then:

N '2TT
Qn(z) = S {[ qQ(9)d9]Az} (5.2)
i=l >'0

where N, the number of elements of length Az in z is given by

N = Az (5.3)

In the special case of uniform distribution of incident flux

around the coil circumference, f(z) = b, for all points along the tube

axis.
The general form of the function f(z) is shown in Figure 5-2.

length of one turn of the coil

Figure 5-2 General Form of Heat Flux Function


61

5.2 Solution to the Problem of Heat Conduction

in Tube Wall

In the cases of both symmetrical and asymmetrical flux distribu-

tion described in the previous section, the temperature gradient around

the circumference of the tube cross section is larger than that in the

axial direction and, therefore, the effect of axial heat conduction in

the tube wall can be neglected. The problem at hand thus reduces to a

two-dimensional heat conduction problem in cylindrical coordinates with

the appropriate differential equation stated as:

Considering the tube cross section in Figure 5-1 or 5-2, it is

seen that the distribution of flux around the circumference of the tube

is symmetrical with respect to a vertical line through the center of

the tube. Therefore, the solution to only one-half of the tube cross

section is needed. The boundary conditions necessary for solving the

above partial differential equation are obtained by the following

procedure.

Consider the left half of the cross section of the tube as shown

in Figure 5-3.

Due to the symmetry of the problem, there is no heat transfer

across the sides, 1 and 2. On the outer surface of the tube at r = R^,

two functions representing heat flux and temperature distribution are

known. The function representing heat flux is the function qQ(9)

represented by equation 5.1. The other function representing the


62

l9 = 0 ^^ 1
T^(0) and q^(e) ^
known at 3

9T ^ ^
33 = 0 at 2

Figure 5-3 Tube Cross Section Representing


Boundary Conditions

temperature distribution as a function of angular position is obtained

by a curve fit through the experimentally measured temperatures at three

different peripheral locations (9 = 0, Tr/2, TT) . The precise form of

these functions will be discussed in a later section.

Thus, the boundary conditions are

= 0 (5.5)
99
9=0

= 0 (5.6)
9=TT

k^ = q^O) (5.7)
^9r
r=R,0

(5.8)
^ lr=RQ = ^0^^>
63

At this point the problem is to determine the solution to a

second order partial differential equation, equation 5.4, subject to

boundary conditions 5.5 through 5.8. It is noted that both boundary

conditions on r are at the outer surface, r=R_^. Using a procedure

utilized by references [8] and [28], a finite difference method was

used to determine the temperature distribution through the tube wall

and, subsequently, the heat flux at r=R..

To evaluate the accuracy and uniqueness of this procedure, two

arbitrary temperature distributions for the outer surface and the inner

surface of the tube was assumed and the temperature distribution inside

the tube wall thickness was calculated. Based on this temperature pro-

file, the heat flux at both surfaces was found. Then, the same tempera-

ture distribution and the calculated heat flux, both at the outer surface,

were used to once again solve for the temperature distribution inside the

tube wall thickness and also the heat flux at the inner surface. The

results of one such calculation is 'shown in appendix C.

Using different arbitrary temperature distributions, this procedure

was repeated several times and the results were compared. The average

standard deviation of the differences in nodal temperatures at the inner

surface of the tube, for these test runs was 0.19. Standard deviation

was calculated according to:

M
r Z (T,-TT)^1/2
J=l ^ ^
S =
M
where:

T = flcalculated - Tassumed)
1
^noae i
64

M = Number of nodal points around the circumference of the

tube cross section.

After the P.D.E. and the related boundary conditions were deter-

mined, the finite difference method was used to solve for the temperature

distribution in the tube wall thickness. The domain of the problem was

subdivided into a number of small elements with nodal points at the

center of each element. An initial temperature distribution throughout

the domain was assumed and the thermal conductivity for each node at its

corresponding temperature was calculated. At the boundaries, equations

5-5 through 5-8 were applied.

Starting from the outer surface of the tube, the steady-state

energy balance equation was written for each node. Since, at the out-

side surface of the tube, the nodal temperatures and also the incoming

flux are known, the temperatures of the nodes on the second ring from the

outer surface can be calculated from these equations. Then, the energy

balance equations for the nodes on the second row are written. Again,

since the temperature of the nodes on the first and second row are known,

the temperatures of the nodes on the third row are calculated. Continu-

ing this process, the temperature distribution throughout the solution

region will be found.

After completion of this first iteration, new values of thermal

conductivity for each node at its new temperature are calculated and in

a second iteration a new set of nodal temperatures is found. At the

end of this iteration, the rate of convergence is calculated and the

process is terminated if the absolute value of the difference between

the new and old temperature at each node is less than 1 percent of the
65

present value of the nodal temperature.. Otherwise, a new iteration is

started and at the end of each iteration, the convergence of the solution

is checked.

When the converged solution is found, the energy balance for the

inner surface nodes is used to calculate the local rate of heat transfer

to the fluid at each specific angular location.

Figure 5-4 represents a section of the tube wall with nodal points

and corresponding elements. The energy balance for node (i,j) on the

outside surface of the tube following the sign convention that heat

added to this element is positive is written as follows:

i,j-l

dr

i,j-l

•d9

Figure 5-4 Tube Wall Discretized Model


66

NiJ)(i,j-l) * fT(i,j-l)-T(i,j)] *C1

^Ni,j)(i,j+1) * tT(i,j+l)-T(i,j)] *C1

^Ni.J)(i+l,j) * tT(i+l,j)-T(i,j)] *C2

+ Qo = 0 (5.9)
where

^ , (dr/2) * dz
o
C2 = (Rn-dr/2)^* de * dz ^^^^^^

dz = depth of each element

Q = net heat transfer at R=R , Btu/hr


o o
= q R d9dz
^o o

Since all of the quantities, except T(i+l,j), in the above equation

are known, this nodal temperature can be easily calculated.

For the nodes in the interior of the domain, the term representing

Q in the above equation is replaced by another term corresponding to J

conduction from the node on the previous ring. In this manner, all of

the nodal temperatures are calculated.

The energy balance for the nodes on the interior surface of the

tube wall is written as:

- Q. = 0 (5.12)
67

where

_„ (dr/2) * dz
^^ = R. * d9 (5.13)
1
n,. - (Ri+cir/2) * d9 * dz .^ ^,.
C4 -^ (5.14)

Q. = net heat transfer at R=R., Btu/hr


1 1

= q.R.d9dz
^1 1

The heat flux to the fluid at this location is thus given by:

q.(9) = Q./R.d9dz
1 1 1

In addition to equation 5-2, another way of calculating the total

heat input to the fluid along the length of the heated coil is to sum

up all of the values of the Q. for each and every node at the interior

surface of the tube cross section and repeat the process at different

sections of the tube with equal length dz. Then,

N M
Q , = Z Z Q. (5.15)
^total . , . , ^1
1=1 J=l
where M is the number of nodal points in the circumference of the tube

cross section and N is the number of increments with length dz along

the axis of the tube. This total heat input, considering the steady

state assumption of the problem, must equal the quantity calculated in

section 5.1.

5.3 Functions Representing Heat Flux and

Temperature Distributions

The last two boundary conditions, equations (5.7) and (5.8) in the

previous section, and also the equations for calculation of total heat
68

flux in section 5.1, all require a function representing either the heat

flux or the temperature distribution on the outer surface of the tube.

From the geometry of the helically coiled test section, it is

obvious that only one-half of the perimeter of each tube cross section

receives the incident radiation and the other half remains in the

shadow and will not see the radiation source.

Two different types of heat flux distribution on the outside sur-

face of the tube were considered. The first method was to assume that

the distribution of the heat flux can be represented by a cosine func-

tion. For this case, nodal elements on the tube outer surface receive

an amount of heat input proportional to the projected area of their

exposed surface. This function is given by:

q. (9) = b cos 9 for -TT/2 < 9 < TT/2 (5.16)

mc — — '

where b is the quantity described earlier as the value of f(z ) = b in

section 5.1 and shown in Figure 5-2.

The second choice was to assume that equal segments of the tube

perimeter on the side of the tube that can see the radiation source will

receive the same amount of radiation. This is the so-called circular

distribution of the flux which is represented by:


q. (9) = b for -7T/2 < 9 < TT/2 (5.17)
inc — ~

In either case, for the back side of the tube, where the tube wall

is in the dark, it is assumed that the tube wall is insulated.

These two types of flux distribution are shown in Figures 5-5.a and

5-5.b.
69

TT/2 -TT/2

-TT/2

Figure 5-5.a Figure 5-5.b


Cosine D i s t r i b u t i o n Circular Distribution
of Flux of Flux

In order to evaluate which of these two proposed types of flux

distribution would more closely simulate the actual condition of flux

distribution upon the tube external surfaces, a number of test runs

were executed in which the entering fluid was a compressed liquid. The

amount of heat that was theoretically added to this fluid was calculated

by using the two above models by integrating the function representing

q (9) around the tube perimeter and multiplying by the appropriate area

(projected area of the exposed tube surface in case of cosine distribu-

tion and the total exposed surface in case of circular distribution of

flux). This procedure is the same as using equation 5.2 described

earlier.

The total amount of heat that was actually added to the fluid was

also calculated by an energy balance on the test section. That is, by


70

measuring the temperature and pressure of the subcooled liquid at the

inlet or exit to the coil and thereby calculating the fluid inlet and

exit enthalpy, the total heat added to the fluid is found from:

Q ^ , ., = m(H -H. ) (5.18)

actual, coil ex in

The actual heat added to the fluid was then compared with the

results of the theoretical calculations for the two flux distribution

models. The circular distribution model was found to be within 5-12

percent of the actual heat as compared to 10-20 percent for the cosine

distribution.

Obviously, one would think that the part of the tube surface which

is closer to the radiation source must receive more radiation flux than

the parts ± 90 degrees apart from this location. But considering that

the tube radius is only 0.1875 inches, it seems like this dimension

compared to the distance between the tube center and the radiation

source is just too small to have any significant effect. In addition

to this, part of the reflected radiation from adjacent tubes will also

be absorbed by the tube surface which will render the distribution of

incident flux around the tube cross section more uniform. In fact, it

is thought that the radiation intensity remains constant over an angle

of about 75 to 80 degrees from the point closest to the radiation source

and then reduces sharply from this point to a very small intensity at

90 degrees, resembling a circular distribution profile.

For each experimental run, the actual and theoretical heat trans-

ferred to the fluid were calculated and compared as a measure of accuracy

of the test measurements.


71

As for the temperature distribution on the outer surface of the

tube, the necessary function was obtained by a curve fit through the

measured temperatures at two or four peripheral locations around the

tube cross section at each thermocouple station. The function which

would best fit the existing data was found to have the general form:

T(9) = a + b cos 9 (5.19)

where

a = (T^+T^)/2

b = (V^C^/^
with points A and C as shown in Figure 5-3.

5.4 Calculation of Local Fluid Properties

and Heat Transfer Coefficients

The method of calculation for local heat flux and temperature at

the inner surface of the tube was discussed in previous sections of this

chapter. Having these quantities, the local internal heat transfer

coefficient at any peripheral and axial location can be calculated once

the fluid bulk temperature at any axial location is found.

Fluid bulk temperature at any axial location in the test section

can be specified if two independent properties at that location are

known. Normally, pressure is chosen as one of these properties.

Local pressure at any axial location was calculated by using the

assumptions of the so-called "homogeneous model" [10]. Since this

model was not consistently predicting the total experimentally measured

pressure drop across the test section, the local values so calculated
72

were corrected for the difference between the experimentally measured

and the theoretically calculated exit pressure. This procedure is

described in more detail in the sample calculation of appendix A.

Enthalpy of the fluid was chosen as the second required property.

Local values of enthalpy along the length of the heated tube were found

by calculating the total heat added to the fluid up to the specific

location desired and by an energy balance on that segment of the coil

as:
Q. . 1 V.2 V ^
H =H. ^ ^ + _ t £ t a l + 1 ^ ^ (5.20)
local inlet m Zg

where

H^ , = local value of enthalpy in Btu/lb^


local
H = enthalpy of the fluid at the coil inlet in Btu/lbm
inlet ^^

mii = total mass flow rate in lb m /hr


0 , = absorbed heat by the fluid in Btu/hr
^total
V , V = mean flow velocities in ft/hr
i e

Having these two local properties (pressure and enthalpy), the local

bulk temperature is found by referring to steam tables. The local in-

ternal heat transfer coefficient at this axial location is then calculated

from:
q,(e)
h. "• - (5.21)
1 z,9
A T,(9)-T
1 B

where

h = heat transfer coefficient at axial location z, and


z.e 2 o
angular position 9, in Btu/hr-ft - F
73

q^O) local value of heat flux at the inner surface of


2
tube in Btu/hr-ft

T^(9) local value of wall temperature in °F

B bulk temperature at axial location z in °F

The circumferential average heat transfer coefficient and Nusselt

number at any axial location were then calculated by evaluating the

integrated average wall temperature:

2TT
T.(9)d9 (5.22)
^i 2TT 1
0

and the integrated average wall heat flux:

'2TT
qi(9)d9 (5.23)
^i = 2^
0

and utilizing the equations

h. = (5.24)
1
^i-^B

and

h.d
Nu = 1
(5.25)

This method was used in all cases of different flow conditions

except when the situation in the channel was such that the deviation

from thermodynamic equilibrium was thought to be significant. In such

instances, a different method proposed by Ahmad [1] was used in which

the axial bulk temperature distribution is given by:

,^ -(c,z*-K:^z*^/^)
AT'' = e (5.26)
74

in which

AT* = AT/ATJ
d
AT = subcooling at axial location z, = T - T^
sat B
AT^ = subcooling at the onset of bubble detachment,

= T ^ - T,
sat d
T^ = bulk temperature at the onset of detachment

h„P Z
C = heat transfer parameter, = -rr-r—p—
f P

_ K H- Z ,
n J ^• ^ 2 f g sb
CT = condensation parameter, = — „ , „
2 ^ ' 3 G A^ C
f P

If the effect of post-detachment bubble condensation is negligible,

the above equation reduces to:


*
AT* = e ^1^ (5.27)

The pressure and temperature before and after the test section were

not measured exactly at the start and the end point of the coiled tube

itself. Therefore, these values had to be corrected for the straight

pipe sections between the measurement points and the test section inlet

or exit.

At the inlet side of the test section, temperature was measured at

19.5 inches before the start of the coil and pressure was measured at

11.75 inches before the coiled section starts. At the exit side,

pressure was measured at 12.125 inches and temperature at 17.75 inches

after the coil ends. Figure 5-6 is a schematic diagram of the test

section, representing the corresponding locations of pressure and temper-

ature measurements.
75

©
©
f-11.75"
19.5"

Figure 5-6 Relative Locations of Pressure and


Temperature Measurement Points at
the Inlet and Exit to the Coil

The corrections were made by the following procedure:

The pressure at the site of temperature measurement was calculated.

If this pressure was close to saturation pressure corresponding to the

indicated temperature, it was set equal to the saturation pressure value.

Using this value of local pressure, the actual pressure at the coil inlet

or exit was calculated. The bulk fluid temperature at the test section

inlet or exit was then taken as the saturation temperature for the cal-

culated pressure.

If the calculated pressure at the site of temperature measurement

was not close enough to saturation pressure at this point to justify the

assumption of saturation state, then the value of enthalpy at this loca-

tion was found. Minor errors that might have occurred during pressure

measurements will not have a significant effect on this value of enthalpy.

Since the straight pipe sections before and after the test section were

thoroughly insulated, the calculated enthalpy will actually be equal to


76

the enthalpy at the inlet or exit to the test section. The test section

inlet or exit pressure was then calculated.

Pressure drop in straight pipe section before or after the test

section was calculated by single-phase or two-phase pressure drop equa-

tions as follows.

1 - Single-phase Flow: The frictional pressure drop for flow in

a straight pipe is related to the friction factor by:

where for laminar flow

f^ = 16/Re (5.29)

and for turbulent flow, from Blasius equation:

f = 0.0791(Re)-°-" (5.30)

2 - Two-Phase Flow: The frictional pressure drop for adiabatic

two-phase flow in a straight pipe is calculated from the following

equation, derived by utilizing the assumptions of the homogeneous model

[10].
2f G^LV. V^
^o = — ^ tl + X ^ ] (5.31)
S D V^
where the two-phase friction factor is given by

-1-0.25
GD (5.32)
f^„, = 0.0791
TPS
_^TP-

and the two-phase viscosity is defined by:

"^ + i ^ (5.33)
^TP ^g ^f
77

Frictional pressure drop in the helical coil was calculated from

equations (5.28) and (5.31) where in both of these equations the fric-

tion factor for the straight pipe was replaced by the corresponding

friction factors for the flow in coils.

For the single-phase laminar flow, the following equation derived

by Mori and Nakayama [20] was used:


0.5
.,^0.5
a
1^ = 0.1080 Re (5.34)
fs
For the single-phase turbulent flow, the effect of curvature was

accounted for by Ito's relation [15]:

f^(d^/D)"°*5 = 0.316[Re(d/D)2]"°-^ (5.35)

which holds true for

Re(d/D)^ > 6

The increase in the friction factor for two-phase flow in coil

was allowed for by the following equation [10]:

^TPC^^TPS = [Re(d/D)^]°-°^ (5.36)

for

Re(d/D)^ > 6

in which fT,^^, the two-phase friction factor for straight pipe flow,

was estimated from equation (5.32).

The sample calculation presented in Appendix A will clarify the

calculation procedure discussed in this chapter.


CHAPTER VI

EXPERIMENTAL RESULTS AND DISCUSSION

This chapter will present the results from the experimental test

program and data analysis discussed in previous chapters. These results

correspond to circumf erentially uniform heat flux.

A total number of 77 experimental runs, composed of the single-

phase and two-phase states, were completed. For all of the two-phase

runs and all but three of the single-phase runs, the estimated

Reynolds number, based on the assumption that only liquid was flowing

in the test section, was larger than the transition or critical

Reynolds number for flow in helical coils. The transition Reynolds

number is given by Ito [16] as:

0.32
(Re)
cr = 2 X 10^(DJ
[^ (6.1)

The critical Reynolds number for the test section under study

is 9606.

6.1 Subcooled Liquid Heat Transfer Results

Twelve of the experimental runs were made with only subcooled

liquid flowing in the coil. Although the total liquid flow rate and

incident heat flux were adjusted such that the possibility of subcooled

liquid boiling in the test section was remote, Ahmad's method [1] was

also used as a check on the validity of the assumptions.

A summary of the experimental conditions for the single-phase

runs is presented in Table 6-1. Local heat transfer coefficient results

for runs 8 and 93 are shown in Figures 6-1 and 6-2. The variation of

78
79

bu jj -3- r~ ^ o r^ 00 • * -3- in in in
0 •H CN po I-H CN 00 •<r O in O
1 X
•—" in m -3- in CN CO ro r-4 ro ro
-3-
ro
u IK m
1

•kJ

«^
3 i-l
u (U fn CN r^ ro CN O ro O
OQ 1—1 (N CO CO
^- ro l-H
CN
r~ CN
^^ in
in
cn CN o
ro >3-
•<r
CN ro CN
00
CN
-3-
CN rM
1^ c < •

4-1 -H o- vO OO p~ CT\ r^ ro -3- in .—1 r~


•H a> 00 n f^ l-H in ro
X CN CN rH <r
CM CN rvl CN
l-H
CN
,—1
--. o
01
1—1
,_, , M

^^
0

H
u
01 CO r-1 cr ro O 1—1 m r^ ro ro ro ro
vO t» O in f-H cr ~3- cr cr a^ cr
— CN ^
CN CSI CN l-H ^H
cT^ ^^
CO

^J in NC c» O r^ r-» -3- • ^ cr a\ o m
r~ CN r^ -3- -3- ro in
.X-^ s^ ^ CN ^ <• ro •3- CO m
CO
cu ^-N 0) ^^
r7
CO
cd '^v.'

CU 4.J
I 1) CN
-- CN ro ^- 00 \D vO
^- ^- ro cr
CU r~ OO CO r~ va- •<T in in
^c^ o
l-H CN
• ^

ro
<• ro
m
ro
.H •H
1—t
<r
00
3
•H r~ cn <r cr in in r» < • in
u CJ\ ON O m in 00 CN -3- \C CM r—
r-.
•H CN -3- CN 1— 00 00 O ^H
5-1 X ^ ^^ <r ^-
I O 01
— l-H ro l-H
•^ f—t 1—1
'^ ro ro -3- ~T
SO

CO
a.
CU
rH 3 4.1 -a- m 00 -3- CN in in OO rM vO cr in
O OJ <^ ro -3- o o ro O CM
»— -3- in <£!
CO •H CN 00 vT OO OO 00 00 00
'2 cn O cr r^
H 4-1 •H — — m .H CO '"' CM <T ~3- ~3- -3-
•H •"•

c
o
a 4J r-.
O
m CN
00
CO
in
in
CN
-3-
r^
r~
r^
OO <

cr
• vO
-3-
in <r
vC
•H
m •^ CN O cr O 00
• ^

O r~» <•
r~- ro
X
r~
<r OO o u-l CO o
M3 o C3V -3-
0) cr
vO cr
ro vD CO CN ^^
cd CX> — •— — —
4-> 0)
3 a:
cu 4-1 -3- in o in ro o O P~ r^ p~. 00 00
B a < • r~. CJN r- vO CM r^ CO in
^ r^ o
r~ in r^ ~3 -3- 00 00 in
•H
c
CO o
CN ro r** in o
00
1 —

-3- 1— cr rM
5-1 •H
<JN
r» v£)
^-
ro cr CN
CU in
a ^
X
w >^
4-1
•H l-l
O ro
0
T CTv vD CO
CN
r-«
in
CJV -3-
\D
CO
00
vC
CN
00 vO
-3-
C
i-H CSI ON in F —
cr <r c
OJ CN -3- r~ r-^ CN CN vO O 00 ~3- in
4J o CN \D in in P-.
> 14-1 -3- in vO
in vO ^-^ in «
l-H
1 ^
I-H ^H o in in
^

e3>
m
1 —

-3- -3- cc 00 ro
o
\0 r-» CTv
w
U) "^e
Xi r-^ l-H
cr cr 1—^
(0
^^
S

u
X SI
3 1 f-^ OO
<r 00
tL.
CM
4J
o ^ CO
ID
CN CN C
i-l
^3.^ 3
n
OJ 4-J
0^
CO

* * *
Run

::5j^ , 1 CN 00 cr \D CN r-' <r CO <r in vC


in vC CTv 3^ 0^ o^
^
80

0 6=0''
t> e = 180

250 •

o
I
c>4
4-1
14-
I
U
220

pa

CD
190
Mass Velocity 315143 Ib^/(hr-sq.ft)
Pressure 351-349 psia
Temperature 93-134°F
Incident Heat Flux 24.2 Suns
160
CO

CO
cu
3:

130

100
6 7 8 9 10 11 12 13
Station Number

Figure 6-1 Axial Distribution of Heat Transfer


Coefficients at 0 = 0° and 9 = 180°,
Run 93
81

O e = 0'
360

V e = 180

330

o
I

T 300

CQ

270

240
D
X

!-
210
<U
PS

180
Temperature 89-136°F
Incident Heat Flux 89.8 Suns

150
6 7 8 9 10 11 12 13 14 15
Station Number

Figure 6-2 Axial Distribution of Heat Transfer


Coefficient at 9 = 0° and 9 = 180°,
Run 8
82

the local Nusselt number around the periphery of the tube cross section

at three thermocouple stations (stations 2, 7 and 14) for these runs

is shown in Figures 6-3 and 6-4. These stations along the coil are

chosen such that each figure represents the circumferential variation

of Nusselt number as the flow progresses through the test section from

inlet to exit.

As is seen from these figures, the heat transfer coefficient at

location A (6 = 0*') is higher than that of location C (6 = 180°)

throughout the coil. Location A corresponds to the side of the tube

cross section which is directly subjected to radiant flux, while

location C receives heat only by conduction through the wall. As the

bulk fluid temperature gradually increases and as fluid properties

approach the saturated liquid values, the heat transfer coefficient

at both locations steadily increases.

The circumferential average heat transfer coefficient at each

thermocouple station along the coil was calculated according to the

procedure outlined in Chapter 5. The average Nusselt number so calcu-

lated was correlated against dimensionless parameters of the flow.

For three of the subcooled liquid runs, the calculated Reynolds

number at the test section inlet was less than the critical Reynolds

number. Only one run was completely laminar throughout the coil and

for the other two, the Reynolds number at the coil exit was greater

than the critical value.

Two correlations were derived for the average Nusselt number for

the subcooled liquid runs. For the first correlation, all of the

laminar and turbulent data were used. The second correlation was
83

17 Station 2
Station 7 /
\
16
Station 14

15

14

Nu

6
Mass Velocity 315143 Ib^/(hr-sq.ft)
5 . Pressure 351-349 psia
Temperature 93-134°F
4 Incident Heat Flux 24.2 Suns
3 X
0 90 180 270 360
9 (Degrees)

Figure 6-3 Circumferential Distribution


of Nusselt Number, Run 93
84

Nu

11
Mass Velocity 956169 ibm/(hr-sq.ft)
10 Pressure 282-278 psia
Temperature 89-136°F
9
Incident Heat Flux 89.8 Suns
8

7
0 90 180 270 360
0 (Degrees)

Figure 6-4 Circumferential Distribution


of Nusselt Number, Run 8
85

derived using the turbulent data only. The correlating equation for

both cases has the general form:

Nu = a(Re)^(Pr)^ T P
(Dn) (6.2)
T-J lp
The coefficients of the above equation for the two previously

mentioned cases are given in Table 6-2. In Figures 6-5 and 6-6, the

predictions of the above models are compared with the results of the

analytical calculations. In both figures, the data points correspond-

ing to laminar runs are specified. Although the equation for Figure

6-6 was derived for turbulent data only, it is used to predict the

results of laminar runs for comparison.

Table 6-2 Coefficients of the Correlation Equations

Laminar and Turbulent Data Turbulent Data Only

a = 5.6484 a = 1247.46

b = 0.80 b = 0.8

c = 4.004 c = 6.7493

d = 4.6213 d = 8.3782

e = 0.06126 e = 0.1452

f = -0.5941 f = -0.8644

The properties required for the evaluation of the Reynolds number,

Prandtl number, and the average Nusselt number in the above equation

were estimated at the local values of pressure and bulk temperature.


86

CN

'o 5

(i4

^ 4
C>4
4-1
«4-l
I
u
Xi
3
4J
PQ
3 -
CO
4J
3
cu
6
•H
5-1
CU Equation Based on All Data
3.
X
W
O Re > Recritical
.^. T
1^ 2
Re < Re .^. ,
critical

-2
h, Calculated (Btu/hr-ft -''F) * 10

Figure 6-5 Comparison Between the Experimental and


the Computed Data, Subcooled Liquid Runs
87

Equation Based on Turbulent Data

O Re > Re
CM critical
'o 5
Re < Re critical

O
I
CM
4->
<4-l
I
5-1
,C
3
4-1

Cd
4->
3
cu
e
•H
5-1
CU
a
X
w

-2
h. Calculated (Btu/hr-ft -''F) * 10

Figure 6-6 Comparison Between the Experimental and


the Computed Data, Subcooled Liquid Runs
88

6.2 Two-Phase Heat Transfer Results

Sixty-five two-phase runs were completed. These runs were com-

posed of cases where an established two-phase mixture entered the coil.

In all cases, the effluent from the coil was also a two-phase mixture.

During these tests, inlet quality was varied from 2.3 to 65 per-

cent, while exit qualities varied from 6 to 70 percent. The range of

mass flow rates investigated were from 125 to 500 lb /hr, while coil
m

inlet pressure was varied from 60 to 525 psia. Incident heat flux

ranged from 6300 to 26600 Btu/(ft^-hr).

Because of the large number of two-phase runs made, presentation

of all of the results is not feasible. Therefore, a number of runs

which are thought to be representative of the heat transfer behavior

of the model are chosen. The experimental conditions for these selected

runs are given in Table 6-3. The results of the experiments for these

runs are presented in Figures 6-7 through 20. The experimental condi-

tions for all of the two-phase runs are given in appendix D.

Figures 6-7 through 14 correspond to a series of runs for which

the incident flux was kept at a fairly low value of 6300 Btu/(sq.ft-hr) ,

corresponding to 24.2 suns of incident radiation upon the receiver in

the FMDF system. This low heat flux was chosen in an effort to allow

all of the regions of the flow and heat transfer to develop.

For each run included in this group, the axial variation of the

internal heat transfer coefficient at two locations ( 0 = 0 ° and 0 =

180°), as well as the variation of the local Nusselt number around the

periphery of the tube cross section at three thermocouple stations

(stations 2, 7 and 14) along the tube axis, are presented.


89

/—\
CO
^
60
>w' 4-1 iH >3- a\ O
•H CX3 rH <f
o o o O o
r^ rH o o o in 00
3 CX> so a\ o r-i
o «^ ,-^
^ iH 00 00 CM CO
o
•H m rH o
f-i r-{ o> r-i rH
4_l
Cd
ler

cu
CJ

<o 4J
CU O m f^ 1-i CTi .00 r^ in o
iH tH a\ CTi in CM 00 O •<r CJ\ SO
Cd 3 O p>. O O CO cs) CO
•H IH m iH CN SO
<

in

r-^
T3 <r CO
Cd
PH

CO
3
3 o
Exit

CN 00 O CO ^ CO C3^ CO
(^
<U
CSI o vO r^ in in in in <r
CN CO <3- vO in in 1-i CM CO
ity

CO
cd
x: iH 4-1 O in SO p^ so un CO
I Cd CU o <r
3 iH CTv sC CN CN CO r^
o CD^ 3 iH CN SO o
in
r^
<!•
CN
r-{ CM
M <r
5-1
m O
I /—\ in
vO Cd 4-J O CO r-{ SO so SO SO •
CO •H •H CT\ C3^ in c^^ r-{ so in
CU 3 CO CN CN CM
r^
r-i
o
CM CO
<r r-i
I—I O X
<-i
x>
cu w
H
CO cu
u
d 3 4-)
o CO CU O vO O o\ o 00 o r^ T-i
a CO I-H iH CN CN
o o Csl so o CM
3 CO CO CO CO in r-i CN
c-u
5 1 h-l ro
CO flH
XJ
3
CU
/—s
e 5-1
•H >< x:
5-1 3 1
CU rH CN CTi C^ cTi C3^ a^ r^ «d- <t- 00
fe 4-» 00 00 00 00 00 O so SO 00
a U-(
v^ on CO CO CO CO
r^ so SO CO
4-1 vO vD vO so so CO so so so
Cd ">«.» CN CM CN
cu 3
X 4-»

>.
4-1 /—\
•H CM
O 4->
M-4 00 CT> \0 CM CM in CN O SO
o
1-i 1 CN CO CN O o\ O
CU 5-1 VO <t <r
CO vt
<

00
! •

in o r^
> X a\ O <r
in CO 00 00 in o in
s^ in 00 r^ so in so so
o
so »3-
in in in in in r-H vO
CO • — ^

rH
<r <r
CO B
iS x>
rH
S
3 in <r CNJ 00 o SO rH o 00
3 =ite CT. r-> in r>.
Pd o
rH o
rH o
iH o
r-\
90

Since the flow patterns and the regimes of the heat transfer for

the asymmetrically heated coil under the experimental conditions in-

vestigated are unknown, the discussion concerning the heat transfer

characteristics of the system given here should merely be considered

as the opinion of the author, based on the experimental results and

not proven facts.

At relatively low mass flow rate and low qualities, the two phases

occupying the tube cross section are flowing at relatively low

velocities and, as a result, the generated secondary flow will not be

strong enough to remove all of the vapor bubbles from the tube wall as

they are formed. Therefore, if the incident heat flux is high enough

to generate any vapor bubble, it will remain attached to the tube wall

until its size becomes large enough that it is swept away from the

wall by the main flow. Since location A (0 = 0°) on the tube wall is

exposed to the incident radiation, it is assumed that the first vapor

bubbles will be formed on the tube wall at this position. If the

bubble population at this point is large enough, it will form a local

vapor blanket, resulting in a lower heat transfer coefficient and

higher wall temperatures. At the same time, the departure of the

bubbles from the hot tube wall will result in agitation of the liquid

especially close to the wall, and this will tend to lower the tube

wall temperature and, as a result, increase the heat transfer coeffi-

cient. The result of these two counter acting occurances at location

A (0 = 0°) is such that although the heat transfer coefficient at A,

h , continues to increase, h^ approaches h^ and will eventually become

greater than h^.


91

Figures 6-7 and 6-8 represent a situation corresponding to this

phenomena. In the beginning h > h , continuing the trend from the

subcooled liquid region as was seen from Figures 6-1 and 6-2. In

this low quality region, h and h are both increasing, but probably

due to the effect of the local vapor blanketing at A, h approaches

h^ as the flow approaches the coil exit. The radial acceleration for

this run ranges from 590 to 880 g's, representing a very weak secondary

flow in the coiled tube cross section.

Figures 6-9 and 6-10 correspond to run number 104 for which radial

acceleration ranges from 1093 to 1674 g's. As the radial acceleration

increases, both the stronger secondary flow and increased "g" force

will remove the vapor bubbles from the outer tube wall probably as fast

as they are formed. As a result of this process, the slope of the line

representing h becomes greater than that of h , such that close to the

end of the coil the Nusselt number variation around the circumference

of the tube is represented by a straight line. At still higher quali-

ties (outside the quality range of this run), h will assume values

greater than h .

Figures 6-11 and 6-12 show the results for run number 102 for

which radial acceleration increases from 2757 to 5119 g's and the mass

quality ranges from 42.5 to 46.8 percent. Close to the test section

inlet, h is greater than h^. The flow pattern in this region is


A ^
probably an annular flow, with liquid forming a thin layer on the tube

wall, possibly much thicker at location C (0 = 180°) than at A (0 =

0°), such that except for the liquid droplets that are carried by the

secondary flow from the core section of the tube to the location A,
92

Quality (%)

Figure 6-7 Axial Distribution of Heat Transfer


Coefficient at 0 = 0° and 0 = 180°,
Run 105
93

- — " — - ^
* ^ II _ ^ * — ^

40

Mass Velocity 559628 lb /(hr-sq.


39 m
Pressure 310-290 psia
38 Quality 19-22%
Radial Acceleration (590-881) g's
37 .
Incident Heat Flux 24.2 Suns
36

35 -

34 •

Nu
33 "" ^ -. ^ — -
•^ ^^ ^ "^
*^
^ ^ ^ ^
32

31

•^0

29

€^4-^4--:^^ o ^v
28
Station 7
27
Station 14
26
0 90 180 270 360
0 (Degrees)

Figure 6-8 Circumferential Distribution


of Nusselt Number, Run 105
94

0 0 = 0'

[> Q = 180"
700

Uu
o

Csl
14.H
I
i-l 650 •
3
4-1
pa

3
<U
•ri
u 600

(U

CO
550
5-1

CO
OJ
X

Mass Velocity 580439 lb /(hr-sq.ft)


500 m
Pressure
326-293 psia
Radial Acceleration
(1093-1674) g's
Incident Heat Flux
24.2 Suns
450
26.6 27.2 27.8 28.4 29.0 29.6 30.2
Quality (%)

Figure 6-9 Axial Distribution of Heat Transfer


Coefficient at 9 = 0° and 9 = 180°,
Run 104
95

42

41

40
Station 2
39 Station 7

38

37 -

36
Nu
35

34

33

32

31 Lss Velocity 580439 I b ^ (hr-sq. ft)


Pressure 326-293 psia
30
Quality 26.6-30.2%
29 Radial Acceleration (1093-1674) g's
Incident Heat Flux 24.2 Suns
28
0 90 180 270 360
0 (Degrees)

Figure 6-10 Circumferential Variation


of Nusselt Number, Run 104
96

O 0 = 0°

> 0 = 180°
650 •

o
I
CN
4-1
>4-H
I
5-1 600 •
X.

4-i
P3

3
CU
•H
u 550 •

cu
o
a
(U

CO
3
CO 500 •
!-i
H

CO

•^—O Mass Velocity 573408 lb^/(hr-sq.ft)


450 Pressure 320-251 psia
Radial Acceleration (2757-5119) g's
Incident Heat Flux 24.2 Suns

400
42.5 43.5 44.5 45.5 46.5
Quality (%)

Figure 6-11 Axial Distribution of Heat Transfer


Coefficient at 9 = 0° and 9 = 180°,
Run 102
97

40

39

38

37
Station 2
36 Station 7
•- Station 14
35

34
Nu
33

32

31
Mass Velocity 573408 lb /(hr-sq.ft)
30 m
Pressure 320-251 psia
29 Quality 42.5-46.8%
Radial Acceleration (2757-5119) g's
28 Incident Heat Flux 24.2 Suns
27

26
0 90 180 270 360
9 (Degrees)

Figure 6-12 Circumferential Distribution


of Nusselt Number, Run 102
98

the heat transfer at this position is mainly to saturated vapor.

Because of the higher heat fluxes at this location, the liquid drop-

lets evaporate as soon as they reach this location. The result of

this combined process of evaporation of the liquid droplets and heat

transfer to saturated vapor is such that h^ is still increasing, but

with a smaller slope than h^, which is transferring heat through

evaporation at the liquid vapor interface. Soon after this, as the

quality still increases, the transition to dryout at location A will

take place, after which h will rapidly decrease.

Figures 6-13 and 6-14 correspond to run number 98, for which the

quality ranges from 62.3 to 67.1. Due to the dryout at 9 = 0°, h

has dropped to a low value, possibly corresponding to heat transfer to

saturated vapor. At 0 = 180°, h^ increases to its highest value at a

quality around 64.5 percent, at which point it will experience a rapid

drop, possibly because of the complete evaporation of the liquid film

and transition to dryout at this location.

If the effect of the coil geometry on the flow and, as a result,

the secondary flow pattern in the tube cross section is momentarily

neglected, one would expect h and h to follow the same pattern as

the heat transfer coefficient for a two-phase flow in a uniformly

heated straight pipe.

In a qualitative description of the progressive variation of the

local heat transfer coefficient along the length of a uniformly heated

vertical tube. Collier [10] suggests that for a given heat flux, the

forced convective heat transfer coefficient will experience the


99

650 •

600 •

o
I
CN
4-1
y-i
I
S-i
550 •

PQ

3
lU
500 B /
•rH 0 9 = 0° \

CU
[> 9 = 180° n^"''^^\0'''''^—^
o
450 •
u
cu
M-H
cn
3
CO
5-1
H
400 »
CO
CU
3:

/Mass Velocity 563930 lb /(hr-sq. ft) \


/ m \
350 0 Pressure 309-176 psia \
Radial Acceleration (6021-18940) g's \
Incident Heat Flux 24.2 Suns ^
300
62.2 63.0 64.0 65.0 66.0 67.0
Q u a l i t y (%)

Figure 6-13 Axial Distribution of Heat Transfer


Coefficient at 9 = 0° and 9 = 180°,
Run 98
100

station 2

•- Station 7

40 Station 14 / s

35

30
Nu

25

20
Mass Velocity 563930 Ib^i/(hr-sq. ft)
Pressure 309-176 psia
Quality 62.6-67%
Radial Acceleration (6021-18940) g's
Incident Heat Flux 24.2 Suns
15
0 90 180 270 360
9 (Degrees)

Figure 6-14 Circumferential Distribution


of Nusselt Number, Run 98
101

following changes as the flow passes through the subcooled liquid,

mixed phase and the superheated vapor region.

a - In the highly subcooled region, where heat transfer is due to

convection to single-phase liquid only, the heat transfer coefficient

experiences a slight increase due to the effect of the increase in bulk

temperature on the liquid physical properties.

b - In the subcooled nucleate boiling region, the heat transfer

coefficient increases linearly with length as the bulk fluid temperature

approaches the wall temperature.

c - In the saturated nucleate boiling region, the heat transfer

coefficient remains constant as the total heat flux is utilized in the

formation of vapor.

d - In the two-phase force convective region, heat transfer from

the tube wall is by conduction through the liquid layer at the wall

(flow regime in this region is primarily annular flow) and subsequently

by evaporation of liquid at the liquid-vapor interface. As a result,

the heat transfer coefficient increases as the liquid layer thickness

decreases or, in other words, as the quality increases.

e - At the dryout point, where the liquid layer on the wall is

completely evaporated, the heat transfer coefficient will suddenly

decrease to a low value corresponding to the heat transfer to dry

saturated vapor at the local conditions. From then on as the vapor

velocity increases, h will also gradually increase to the value cor-

responding to the heat transfer to a single-phase vapor.

For an asymmetrically heated pipe, where one side of the tube is

receiving a higher heat flux than the other, one would expect that the
102

heat transfer coefficients at both sides of the tube would follow the

pattern previously explained, with the heat transfer coefficient at

the back side (location C) being less than that at the front side

(location A), This model is shown in Figure 6-15.

As is seen from this figure, in subcooled and part of the nucleate

boiling region, h at any axial location is greater than h„ until some-


A C

where in the two-phase region at high quality, at dryout point, h

decreases sharply. Soon afterwards at still higher qualities, h will

experience this sudden drop. Later on, heat transfer at both locations

will gradually recover, but since at location A the tube wall is

exposed to the incident radiation, the tube wall temperature at this

location will be higher than that of location C (AT at A will be


sat
greater than AT at C) and, as a result, the heat transfer coeffi-
S Ol U

cient at C will become larger.

Although this model does not consider the effect of the secondary

flow, the experimental results indicate that in most cases the trends

of this model are close to the actual behavior of the system under

study. The principle differences between the model and the behavior

of the results can be attributed to the fluid dynamic and heat trans-

fer effects associated with the radial acceleration and secondary

flow in the coiled tube. These effects are expected to be small at

low mass velocities, large coil diameters and high pressures. However,

as mass velocity increases and coil diameter and pressure decrease,

the strength of the secondary flow would be expected to increase with

the result that the model of Figure 6-15 would tend to shift to the

right and increase the quality at which dryout occurs.


103

cu
CO 5H 3
O
CU O •H
X CO 0
a
00
5-1 CO CU cu O
cu > 33 0 0
3- Pi
^
3 CU
cy3 X II
4J
CD
14-4
0 -o
3
CO CO
3
Q 0
•H O
4-1
CO 11
•H
i-l CD
CO
> 4-1
CO
cu CU
CO X cn
CO •u 4-1
3
X O 3
00 CU
•H
00 3 •H
PH • H CJ
cu 4-) • H
3 <4-l
CU cu 14-1
cn CU
cu o
u CJ
a
cu
PS
5-1
CU
M-l
r-^ CO
CU 3
TJ CO
O U
S H

in
I
sO
TD
CU T3 c CU
rH •H
c
•H
S-I
3
o 3
00 00
0 cr
CJ • H (V
Xi X PC
3
C/2
104

As the heat flux increases, the lines representing h and h in

Figure 6-15 will shift to the left, resulting in an earlier transition

to dryout. Very high incident heat fluxes may result in burnout even

in the low quality regions of the flow. Under special circumstances

of low radial acceleration and high radiation intensities, the flow

may not be able to remove the local, low quality vapor blanketing

described earlier corresponding to Figures 6-7 and 6-9. As the heat

transfer coefficient as a result of this phenomena decreases, the tube

wall temperature will rise, causing a steeper decrease in the heat

transfer coefficient. This cyclic effect may finally result in

burnout.

Increase in pressure and decrease in mass flow rate will have a

similar effect as that of increasing the incident flux. This is at

least partly because both increasing the pressure and decreasing the

mass flow rate will reduce the strength of the radial acceleration.

At relatively high pressures as p^ approaches p , the radial accelera-

tion will effectively lose its importance in the flow in the coiled

tube.

Figure 6-16 represents the results of the experiment for run 100.

The behavior of the heat transfer coefficients at 0 = 0° and 0 = 180°

is quite similar to run 98 (Figure 6-13), except that the sudden drop

in h at 9 = 180° occurs at a lower value of quality. For this run,

the mass velocity was lower than that of run 98 while the exit pressure

was slightly higher, both contributing to earlier transition to dryout

at the 0 = 180° location.


105

650 • O 0 = 0

600
tlH
o
I
CN

I
X 550

3
CU

500
CU

5-1
0)
14-4
cn
3
CO
5-1 450
e-H

CO Mass Velocity 558403 lb^/(hr-ft^)


CU
X Pressure 300-202 psia
Radial Acceleration (4098-10000) g's
400
Incident Heat Flux 24.2 Suns

50.4 51.1 51.8 52.5 53.2 53.9 54.6 55.3

Quality (%)

Figure 6-16 Axial Distribution of Heat Transfer


Coefficient at 0 = 0° and 0 = 180°,
Run 100
106

Figure 6-17 shows the location of transition to dryout at 0 = 180°

for run 6. For this run heat flux, pressure, and mass valocity have

much higher values than in runs 98 and 100. Increase in heat flux and

pressure will tend to decrease the quality at dryout point while in-

crease in mass velocity will result in a delay in transition to dryout.

The effect of the combination of these three factors on flow is such

that the transition to dryout at 0 = 180° occurs at about 52 percent

quality.

In run 71, because of the effect of the local vapor blanketing

at 0 = 0 ° , h^ has values lower than that of h , but as the quality

and, as a result, radial acceleration increases, h approaches h . At

higher qualities in run 50, h will become larger than h . Results for
A C

these two runs are shown in Figures 6-18 and 6-19, respectively. The

same type of behavior was noticed in run 78 where as is shown in

Figure 6-20, as a result of increase in mass velocity, the change over

between h. and h„ takes place at a higher quality than in run 50.

Along with the local values of heat transfer coefficient around

the periphery of the tube cross section, circumferential average values

for each thermocouple station were also calculated. These average

values for all two-phase runs were correlated against different para-

meters of the flow.

Previous investigations on the subject of single-phase heat trans-

fer in coils have revealed that the Nusselt number for this type of

flow can be correlated as a function of dimensionless parameters of

the flow such as Reynolds number, Prandtl number, and tube to coil

diameter ratio.
107

0 0 = 0
700
^ 0 = 180

650
o
I
CN

I
5-1
X
600
pa

3
lU

CM
CU
550
o
c^J
5-1
CU

X
C
CO
S-I
H 500
CO
cu
X 1168845 lbm /(hr-ft )
Mass Velocity
Pressure 528-316 psia
450 Radial Acceleration (5408-18100) g's
Incident Heat Flux 89.8 Suns

47.7 78.7 49.8 50.8 51.9 53.0 54.0 55.1


Quality (%)

Figure 6-17 Axial Distribution of Heat Transfer


Coefficient at 0 = 0° and 0 = 180°,
Run 6
108

550

500
o
I
CN

I
5-1
X

450
pq

3
CU

<4-t
cu 400 •
o
CJ
5-1
CU

cn
3
CO
i-l
H
350 Mass Velocity 465592 lb /(hr-ft )
m
CO
X
(U Pressure 60-46 psia
Radial Acceleration (347-9000) g's
Incident Heat Flux 101 Suns
300

X li

3.6 5.28 6.96 8.64 10.32 12.0 13.68 15.36


Quality (%)

Figure 6-18 Axial Distribution of Heat Transfer


Coefficient at 0 = 0° and 0 = 180°,
Run 71
109

550

iii
o
I 500
CN
4-)
M-l
I
5-1
X
3
4J
pa
450
3
CU

ij-i
u-
0)
o
u 400
5-1
CU
<4-l
cn
3 Mass Velocity 460000 Ib^/(hr-ft )
CO
S-I
H
Pressure 107-66 psia
4-t
CO
<U
350
X Radial Acceleration (1295-12450) g's

Incident Heat Flux 101 Suns

300

12.5 14.4 16.3 18.2 20.2 22.1 24.0 25.9


Quality (%)

Figure 6-19 Axial Distribution of Heat Transfer


Coefficient at 0 = 0° and 0 = 180°,
Run 50
110

550 • Mass Velocity 645706 lb /(hr-ft^)


m ^
Pressure
213-120 psia
Radial Acceleration
(3360-13180) g's
500 . Incident Heat Flux
o 24.2 Suns
I
CM
4-1
14-1
I
5-1
X
3
4J 450
pa o-^
3
cu
•H

CU 400
o
CJ
S-I
<u
14-1
cn
3
CO
U
H
4-1
350
CO
(U
X

O 0 = 0°
300
> 0 = 180'

27.8 28.6 29.4 30.2 31.0 31.8 32.6 33.4


Quality (%)

Figure 6-20 Axial Distribution of Heat Transfer


Coefficient at = 0° and 0 = 180'
Run 78
Ill

Schrock and Grossman [32] in their study of boiling heat transfer

in a straight tube suggested that the Nusselt number can be expressed

by a functional relationship of the form:

Nu = f(Re,Pr,X^^,B0)

tt

In correlating the results of the two-phase runs for this study,

a combination of the dimensionless groups mentioned above seemed to

be the appropriate choice. Also because of the profound effect of the

local pressure on the behavior of the heat transfer coefficient as was

evident from the results of the analytical model, it was decided to


p
include a pressure term, namely — in the model.
c

In the model proposed, the circumferential average Nusselt number

is correlated against different dimensionless groups in an equation of

the form: . ,^b e


Nu (6.3)
T, 0.8^Pr 0.4 = a X.
Re tt

Coefficients of this model obtained through a stepwise multiple

regression on the data of the two-phase runs are given in Table 6-4.

Table 6-4 Coefficients of the Correlation Equation

a ^ 4.1128

b = 5386 * 10-=

c = 10917 * 10"^

d = -794 * 10-3

e = 27855 * 10"^
112

In the above model, the properties necessary for the evaluation of

the different dimensionless groups are taken as the saturated liquid

values at the local pressure in the channel.

A comparison between the average values of the heat transfer co-

efficient as predicted by the above model and the analytical results

of the study is made in Figure 6-21. As this figure shows, the devi-

ation limits of ± 30 percent covers most of the experimental results.

The discrepancies mostly occur in the region corresponding to low levels

of incident heat flux, where a minor error in measurement of these

fluxes or the surface temperatures will result in a higher percentage

of error as compared to the higher heat flux regions.

6.3 Comparison of Results

In comparing the heat transfer results of the present analysis to

the available analytical and experimental data in the literature, three

important facts will become evident. First of all, no experimental

results for flow in coils with small diameters and tightly wrapped turns

are available. Secondly, the available correlations for flow in coils

were mainly derived for single-phase flow of liquids or gases in coils

with diameters and coil pitches several times that of the test section

used in this study. Thirdly, all of these studies were done on uni-

formly heated coils, and results for non-uniformly heated coils do not

exist.

To separate the effects of coiling and asymmetrical heating on the

results of the present work, it is suitable to compare these results


113

CM
I
o

/-\
o
I
CM
4J
14H
I
u
X
3
4J
pa

cd
4J
3
cu
e
•H
U
CU

1.^

3 4 5 6 7 8 9 10
h . Calculated ( B t u / h r - f t ^ - ° F ) x lO"^

Figure 6-21 Comparison Between the Experimental and


the Computed Data, Two-Phase Runs
114
with the available data for flow in uniformly heated coils and also with

the available analytical results for flow in asymmetrically heated

straight pipes.

In Figure 6-22 the experimental results for single-phase runs have

been plotted as N^ vs. (Re * Pr°*^). Also shown in this figure is the

line representing the Seban-McLaughlin correlation [33] for turbulent

flows of water in uniformly heated coils:

1^=0.023 Re°-«Pr°-^Re(f)2]0-05 (6.4)

Required properties for calculation of Re and Pr in Figure 6-22

are evaluated at the local film temperature.

As is noted from this figure, the experimental results fall sub-

stantially below those predicted by Seban-McLaughlin.

In Figure 6-22, results have also been compared to those for single-

phase flow of fluids in asymmetrically heated straight pipes. Available

analytical solutions by Gartner, et al and Reynolds [14,28] predict the

variations in the Nusselt number around the periphery of the tube for a

given heat flux distribution around the tube circumference. In both of

these methods, the convective turbulent energy equation for flow of a

single-phase fluid in a circular tube subjected to an arbitrary wall

heat flux is solved. The flow is assumed to be hydrodynamically and

thermally fully developed. In solving this equation, Reynolds makes

the assumption that the diffusivities for heat in the radial and cir-

cumferential directions are identical, while Gartner, et al take into

account the anisotropy of the turbulent energy transport. The resulting

solution in both cases gives Nu(0) in the form of a series solution.


115

100
1 1 r
9
O Reynolds
8 O -
^ Gartner
7
D Experiment
Seban-McLaughlin
Correlation

Nu 3

a
A D° °
a ° n°
1
D D
O

10 L J L
8 9 10
.^ 0.85^ 0.4. . T^-3
(Re Pr ) * 10

Figure 6-22 Comparison Between Experimental


Data and Seban-McLaughlin [33],
Single-Phase Runs
116

with the coefficients of the series tabulated as a function of Reynolds

number and Prandtl number.

Both methods have been shown to yield expected results for laminar

or turbulent flow for the special case of constant heat flux around the

periphery of the tube. Gartner, et al also compare the predicted results

from their method to that of Reynolds and also to the available experi-

mental data. For the cases shown, the agreement is satisfactory.

For the purpose of this comparison, a Fourier series was fitted

through the discrete heat flux values at the interior surface of the

tube at each thermocouple station. The function so obtained was then

used as an input to the solution methods given by both Reynolds and

Gartner, et al. Using the appropriate coefficients for the series

solution given, the Nusselt number at different peripheral locations

was found.

Figure 6-23 is a comparison between the local values of Nusselt

number obtained from the experiment and those calculated from the above

mentioned methods. As is seen from this figure, the effect of circum-

ferentially varying heat flux on Nusselt number for flow in straight

pipe is much more pronounced than in coiled tubes. Reynolds' method

predicts values as high as 369 at one angular location and values as

low as -130 at another. Predictions from the method by Gartner, et al

ranges from -587 at one angular position to 150 at another. Values of

the Nusselt number for flow in the coil, however, do not change drasti-

cally around the tube circumference. It appears that the effects of

the secondary flow in the tube cross section are such that it effectively

smooths these local values to a level close to an average value for the
117

O Reynolds
369 O
A Gartner
• Experiment
160
O Dittus-Boelter (Nu = 0.023 Re Pr * )
140 - (Dark symbols represent averaged values)

120 h

100
I

80-
X
60- 6 ^
^
40-
Nu(0)
20- A • a-
O D
0 D

-20

-40

-60

-80

-100

-120 O -130
-587 A • -383^
-J J—
-140 112.5 135 157.5 180
0 22.5 45 67.5 90

0 (Deg.)

Figure 6-23 Comparison Between Local Values of


Nusselt Number, Station 1, Run 9,
(Single-Phase)
118

the cross section. In Figure 6-23, the arithmatic average values of

the Nusselt number for each method, as well as the predicted value from

the Dittus-Boelter equation, are also given. Reynolds' method predicts

an average value which is much closer to the experimental result than

the method of Gartner, et al. The value predicted by the Dittus-Boelter

equation is much higher than the experimental results and predicted

values from the other two methods.

Average heat transfer coefficient results for run number 9, as

obtained from the experiment as well as those calculated from Reynolds'

and also Gartner's method, are compared in Figure 6-24. The method by

Reynolds predicts values which are close to the experimental results

near the coil inlet, but deviates from them as the flow approaches the

test section exit. The reverse is true for Gartner's method as it

approaches the experimental results as the flow progresses in the test

section. For most other experimental runs, the values predicted by

Gartner, et al become greater than the experimental results somewhere

along the coil.

It should be noted, however, that as was shown in Figure 6-23, the

local values of Nusselt number calculated from Gartner's method are

usually higher than the experimental results and, in most cases, com-

patible with predictions of Reynolds. But, at two angular positions,

0 = 135° and 0 = 180°, the values predicted by these two models are

usually very much apart from the rest of the local values such that,

depending on their sign, the local values at these two angular positions

can bring the average Nusselt number down to a negative value. The

reason for predicting such large values of local Nusselt numbers at


119

1 1 1 r "I T 1 1 r

P < _ m

CT>

3
CO

D CN cu
<3

3
i
5S
D <
CU
D
i2 CO
CO

5-1
CU
S
D as
•n3
z CO
D < - 00 cu
3 3
O
•H cd
D 4J >
Cd
4J
CU
00
C vO
cd
u
cu
D < - in
5
CO D <1 CN

3 SO
CO cu
T5 D CO
^ e < CU
rH CU •H U
o 3 M 3
3 4J CU 00
>, i-l a D csl •H
CU CO <
X (ii
0£i O Cd

O < D D <

_L _L JL
O O o o o o o o O o o
so
CN
o so CN <r vo
00 I I I

^
2
120

these two locations is that both models predict very small wall to

fluid temperature difference at these angular positions.

In summary, the experimentally predicted single-phase heat trans-

fer results are much lower than the values predicted by either the

Seban-McLaughlin equation for flow in helical coils or by the available

methods for flow in asymmetrically heated straight pipe. The compari-

sons show that part of the reason for having low values of heat transfer

coefficient are due to the effect of circumferentially varying heat

flux. They also show that although the local values of Nusselt number

at some peripheral locations in an asymmetrically heated straight pipe

can be quite large, and as a result contribute to a higher average

Nusselt number for the cross section, the secondary flow present in

coils will have a dampening effect on these values.

As for the comparison of the two-phase heat transfer results,

because of the unavailability of any asymmetrically heated two-phase

correlations, the only possibility is to compare the experimentally

determined heat transfer coefficients to that of previous works on

coils with uniform heating. From the bulk of results available, those

of Owhadi [27] and Crain [2] were chosen for comparison. Figure 6-25

presents this comparison. In this figure, the ratio of the circumfer-

entially averaged two-phase heat transfer coefficient, h^^, to that

predicted by Seban-McLaughlin for single-phase flow, h^^, is shown as

a function of 1/X^^. In calculating h^^ by the Seban-McLaughlin

equation, the Reynolds number was based on superficial liquid velocity

[G(l-x)v ]. The present experimental results have values much lower

than those measured for uniformly heated coils.


121

100.0 T I 1 — I I 1 II I T 1—I I II I T 1 — I — I I I 11:

6^o
oo-
o ^ ^<) Ooo 8
10.0 ocoo

T.P.

ilc

1.0

Data of Owhadi [27]

O Data of Crain [11]


A Experimental Results'

0.1 I f I I I II11 I 1 — I I I III i I I I I I I iJ


10 100 1000

1/X
tt

Figure 6-25 Comparison of Results with Data


of Owhadi and Crain
122

If the conclusions derived from comparing the single-phase heat

transfer results to that of the literature is extended to the two-phase

results, one could propose that, here again because of the effect of

asymmetry in heat flux, local values of Nusselt number at different

angular locations around the tube cross section, except at a few points,

are usually lower than those for a uniformly heated tube. In addition

to this, the secondary flow in the tube cross section causes all of

these local values to remain in the neighborhood of some average value.

One point that is worth mentioning here is that the heat flux

values for these experiments, especially considering that only half of

the tube cross section is heated, are much lower than values used in

most of the previous investigations related to this investigation. The

effect of heat flux on the heat transfer coefficient has also been noted

by other investigators such as Schrock and Grossman [32] who have

included heat flux in their correlation. Crain [11] also reports that

there appears to be an effect of heat flux on the heat transfer coeffi-

cients, which indicates a decrease in measured heat transfer coefficients

as heat flux is decreased.


CHAPTER VII

CONCLUSIONS AND RECOMMENDATIONS

Local values of heat transfer coefficient and Nusselt number were

calculated for single-phase or two-phase flow of water/steam in a

coiled tube subjected to asymmetrical radiant heating. The integrated

average values of heat transfer coefficient for all subcooled liquid

data and two-phase data were correlated for a wide range of heat flux,

pressure, mass velocity, and quality by equations (6.2) and (6.3).

These equations were derived for flow through a 2.74-inch diameter

coil constructed of 0.277-inch I.D. stainless steel tubing subjected

to the radiant heating from T-3 quartz lamps. The experimental set up

was designed to simulate the performance of the receiver in the Fixed

Mirror Distributed Focus (FMDF) concentrating solar thermal system.

Measured heat transfer coefficients were found to be much lower

than the predicted values for the uniformly heated coils. A part of

the reason for having low values of heat transfer coefficient are

believed to be due to the effect of circumferentially varying heat

flux. It was also found that due to the dampening effect of the pre-

sent secondary flow in the tube cross section, local values of Nusselt

number at different angular locations do not vary drastically from the

average value for the cross section, while in a non-uniformly heated

straight pipe the local values at some angular positions can take on

very large positive or negative values. The very small coil diameter

of the test section (as compared to other investigators' test appara-

tus) is also believed to have had some adverse effect on heat transfer

results, although this apparently contradicts many earlier works.

123
124

Pressure and mass velocity were found to be two of the major con-

trolling factors in defining the location of transition to dryout.

Increase in pressure, decrease in mass velocity, and increase in heat

flux were all found to decrease the quality at which transition to

dryout occurs, while as pressure decreases, mass velocity increases

and heat flux decreases, the quality at transition point increases.

The effects of pressure and mass velocity on the behavior of the

system can be attributed to their effect on the radial acceleration

in the coiled tube which in turn defines the strength of the secondary

flow in the tube cross section. As the secondary flow becomes

stronger, the generated bubbles at the tube wall are removed faster,

reducing the possibility of local vapor blanketing in the subcooled

boiling and low quality nucleate boiling regions. In high quality

regions, the secondary flow removes the entrained liquid droplets from

the channel core distributing the liquid to the tube surface.

The local fluid pressure through the coiled test section was

estimated using results from a homogeneous flow model derived for

straight pipe flow [10]. While this procedure has been successfully

used by prior investigators [5,29] for helical flow with large coil

to tube diameter ratios, the conditions of this investigation required

a linear correction procedure to be applied to the pressure drop

predictions.

Further studies are recommended to define the effects of (1)

indirect heating and (2) asymmetrical heating on pressure drop in both

straight and helical pipe flows. Such a study could result in much
125

better understanding of the processes involved, if it is coupled with

flow regime studies.

Another aspect of the flow which requires additional studies is

that of the effect of the hydrodynamic and thermal entrance regions on

the flows. Although for straight pipe flow it is believed that

entrance effects can lead to flow patterns that may take considerable

lengths to reach equilibrium [3], for flow in coiled tubes the effects

of entrance region is considered to be very small [22,23,24]. But,

of course, again these might be true for uniformly heated channels,

while asymmetry in heating could result in non-equilibrium conditions

at the channel entrance.

As it was mentioned earlier, the experimental set up for the

present study was designed to simulate the receiver operation in a

FMDF system. The T-3 quartz lamps provided can only be used in a hori-

zontal position, as the high temperature attained by the resistance

filament in the lamps will result in melting of the filament if posi-

tioned vertically. As a result, it was decided to position the coil

in a horizontal direction, whereas the receiver in FMDF system is

usually in near vertical position.

It is recommended that the system be redesigned such that although

the lamps are still in a horizontal position, the coil itself could be

positioned vertically. This could be achieved by constructing a tri-

angular prism with the three available lamp panels in such a way that

the triangular surfaces of the prism are placed in a horizontal position

and the lamp panels are placed on the sides in such a manner that the
126

lamps are in a horizontal position also. At present, one of the lamp

panels forms the base of the triangular prism.

Coiled tubes are used extensively in different forms of heat

exchangers. With the advent of high concentrating solar power systems,

the use of asymmetrically heated coiled tubes is increasing. Under-

standing of the thermal and flow characteristics of this component of

the system will definitely have an impact on successful design of the

overall system.
REFERENCES

1. Ahmad, S.Y., "Axial Distribution of Bulk Temperature and Void


Fraction in a Heated Channel with Inlet Subcooling," Trans.
ASME, J. Heat Transfer, 595-606, November 1970.

2. Banerjee, S., E.A. Rhodes and D.S. Scott, "Studies on Concurrent


Gas-Liquid Flow in Helically Coiled Tubes," Can. J. Chem. Engr.,
47, 445-453, 1969.

3. Banerjee, S., "Experimental Techniques in Two-Phase Flow,"


Stanford University, Dept. of Chemical Engr., Two-Phase Short
Course Notes, Summer 1980.

4. Bell, K.J. and A. Owhadi, "Local Heat Transfer Measurements


During Forced Convection Boiling in a Helically Coiled Tube,"
Proceedings, Symposium on Fluid Mechanics and Measurements
in Two-Phase Flow Systems, Vol. 184, Pt. 3C, 1969-70.

5. Bianchi, G. and M. Cummo, "Heat Transfer and Pressure Drop in


Once-Through Steam Generators," Int. J. Heat Mass Transfer, 15,
120-133.

6. Butterworth, D. and G.F. Hewitt, "Two-Phase Flow and Heat


Transfer," Oxford University Press, 1977.

7. Carver, J.R., C R . Kakarala and J.S. Slotnik, "Heat Transfer


in Coiled Tubes with Two-Phase Flow," Atomic Energy Commission
Document T1D20983, 1964.

8. Campolunghi, F., et al., "Full-Scale Tests and Thermal Design


Correlation for Coiled Once-Through Steam Generators," AICHE
Symposium Series, Solar and Nuclear Heat Transfer, 73(164),
215-222.

9. Chen, J . C , "Correlation for Boiling Heat Transfer to Saturated


Fluids," I&EC Process Design and Development, 5(3), 322-329,
1966.

10. Collier, J.G., "Convective Boiling and Condensation," McGraw-


Hill, London, 1972.

11. Crain, B., Jr. and K.J. Bell, "Forced Convection Heat Transfer
to a Two-Phase Mixture of Water and Steam in a Helical Coil,"
AICHE Symposium Series, 69(131), 30-36, 1973.

12. Crain, B., Jr., "Forced Convection Heat Transfer to^a Two-
Phase Mixture of Water and Steam in a Helical Coil," Ph.D.
Thesis, Oklahoma State University, Stillwater, 1973.

127
128

13. Davidson, W.F., et al., "Studies of Heat Transmission Through


Boiler Tubing at Pressures From 500 to 3300 Pounds," Trans.
ASME, 65, 553-591, 1943.

14. Gartner, D., K. Johannsen and H. Ramm, "Turbulent Heat Transfer


in a Circular Tube with Circumferentially Varying Thermal Boundary
Conditions," Int. J. Heat Mass Transfer, 17, 1003-1018, 1974.

15. Hsu, Y.Y. and R.W. Graham, "Transport Processes in Boiling and
Two-Phase Systems," McGraw-Hill, 1976.

16. Ito, H., "Friction Factor for Turbulent Flow in Curved Pipes,"
J. Basic Engr., Trans. ASME, D, 81, 123-134, 1959.

17. Kline, S.J. and F.A. McClintock, "Describing Uncertainties in


Single-Sample Experiments," Mech. Engr., 3, January 1953.

18. Lockhart, R.W, and R.C. Martinelli, "Proposed Correlation of


Data for Isothermal Two-Phase, Two-Component Flow in Pipes,"
Chem. Engr. Prog., 45, 39-48, 1949.

19. Martinelli, R . C , D.B. Nelson and N.Y. Schenectady, "Prediction


of Pressure Drop During Forced Circulation Boiling of Water,"
Trans. ASME, 70, 795-702, 1948.

20. Meyers, C.A., R.B. McClintock, G.J. Silvestri and R.C. Spencer,
Jr., "Thermodynamic and Transport Properties of Steam," Pre-
pared for the American Society of Mechanical Engineers, 1967.

21. Mishra, P. and N. Gupta, "Momentum Transfer in Curved Pipes.


1-Newtonian Fluids," Ind. Engr. Chem. Process Des. Dev., 18
(1), 130-137, 1979.

22. Mori, Y. and W. Nakayama, "Study on Forced Convection Heat


Transfer in Curved Pipes, 1st Report, Laminar Region," Int.
J. Heat Mass Transfer, 8, 67-82, 1965.

23. Mori, Y. and W. Nakayama, "Study on Forced Convective Heat


Transfer in Curved Pipes, 2nd Report, Turbulent Region," Int.
J. Heat Mass Transfer, 10, 37-59, 1967.

24. Mori, Y. and W. Nakayama, "Study on Forced Convective Heat


Transfer in Curved Pipes, 3rd Report, Theoretical Analysis
Under the Condition of Uniform Wall Temperature and Practical
Formula," Int. J. Heat Mass Transfer, 10, 681-695, 1967.

25. Owhadi, A. and K.J. Bell, "Forced Convection Boiling Inside


Helically Coiled Tubes," Int. J. Heat Mass Transfer, 10, 397-
401, 1967.
129

26. Owhadi, A., K.J. Bell and B. Crain, Jr., "Forced Convection
Boiling Inside Helically Coiled Tubes," Int. J. Heat Mass
Transfer, 11, 1779-1792, 1968.

27. Owhadi, A., "Boiling in Self-Induced Radial Acceleration


Fields," Ph.D. Thesis, Oklahoma State University, Stillwater,
1966.

28. Reynolds, W . C , "Turbulent Heat Transfer in a Circular Tube


with Variable Circumferential Heat Flux," Int. J. Heat Mass
Transfer, 6, 445-454, 1963.

29. Rippel, G.R., C M . Edit, Jr. and H.B. Jordan, Jr., "Two-Phase
Flow in a Coiled Tube," I&EC Process Design and Development,
5(1), 32-39, 1966.

30. Rogers, G.F.C and Y.R. Mayhew, "Heat Transfer and Pressure
Loss in Helically Coiled Tubes with Turbulent Flow," Int.
J. Heat Mass Transfer, 7, 1207-1216, 1964.

31. Schmidt, R.R. and E.M. Sparrow, "Turbulent Flow of Water in


a Tube with Circumferentially Nonuniform Heating, with or
without Buoyancy," ASME Journal of Heat Transfer, Vol. 100,
403-409, 1978.

32. Schrock, V.E. and L.M. Grossman, "Forced Convection Boiling


in Tubes," Nuclear Science and Engineering, 12, 474-481,
1962.

33. Seban, R.A. and E.F. McLaughlin, "Heat Transfer in Tube Coils
with Laminar and Turbulent Flow," Int. J. Heat Mass Transfer,
6, 387-395, 1963.

34. Shinn, K.E., "An Experimental Simulation of Asymmetric Radiant


Heating for the FMDF Receiver," M.S. Thesis, Texas Tech Univer-
sity, Lubbock, 1978.

35. Srinivasan, P.S., S.S. Nandapurkar and F.A. Holland, "Pressure


Drop and Heat Transfer in Coils," The Chemical Engineer, No.
218, 113-119, 1968.

36. Texas Tech University, "Optical-Thermal-Fluid Analysis and


Experiments," Appendix A to Technical Report of Work Accom-
plished (Phase 1), The Crosbyton Solar Power Project, February
1978.

37. Yakel, D.E., "Solar Simulator Tests of an FMDF Receiver,"


Supplementary Report F to Technical Report ETC/78TR-01, E-
Systems, Inc., Dallas, February 1978.
APPENDIX A

130
131

SAMPLE CALCULATION

All of the data taken during the experiment were reduced on a

digital computer. Different properties of water and/or steam were

calculated by using a special subroutine named WATER which is capable

of taking any two of the properties T, P, H, S, and X as the known

values and calculating the rest. If the fluid is not saturated, C


P

is calculated instead of quality.

The sample calculation presented in this section is provided as

an example to show how different quantities were calculated. These

calculations will be performed for thermocouple station 9 of run number

77.

Data For Run No. 77

Symmetrical Incident Flux

Radiation intensity =24.2 suns

Total mass flow rate = 270.2 lb /hr


m

Subcooled liquid mass flow rate = 152.9 Ib^/hr

Cooling water flow rate = 2832.2 Ib^/hr

Pressure (psia) Temperature (°F)

Pump exit 271 89.6

H.X. exit 232 548.9

Subcooled liquid 260 89.6

Test section inlet 222 391.3

Test section exit 112 335.3

Condensed fluid 14.0 94.1


132

Cooling water inlet 38.0 70.5

Cooling water exit 38.0 123.1

Tube surface temperature at station 9: T = 385.2°F


A
T^ = 371.5°F

Referring to Figure 5-6, it is seen that the inlet pressure is

measured at 11.75 inches before the start of the coil and 17.75 inches

after the location where the inlet temperature is measured.

Measured inlet temperature is 391.28°F for which the saturation

pressure is 223.64 psia. The measured inlet pressure is 222 psia.

Thus,

percent^ deviation
, . ^. = 223.64-222
j^ _ ^ percent
= 0.7

Assuming that the fluid flowing in this location is a two-phase

mixture, the pressure at the temperature measurement location is found.

G D-°-^^
f^p = 0.0791
^P

1 _ _x_ 1-x

At the measured inlet temperature of 391.28,

y^ = 0.3244 Ib^j/ft-hr

y = 0.03781 Ibnj/ft-hr

Quality at the location of temperature measurement is calculated

from an energy balance on the junction of the superheated vapor and

subcooled liquid lines. This junction is shown in Figure A-1.


133

Superheated
vapor
© Two-phase

© mixture to
test section
Subcooled
liquid
2
© inlet

©
Figure A-1 Junction of Fluid Streams at
the Test Section Inlet

2 2 2
^1 ^2 ^3
^^«i ^ Ii;) ^ ™2<»2 -^ Ii;) = *3^«3 ^ Ii;)
or
V ^ V 2
\^\ ^ Ii~^ "^ '^2^"2 + if")
H„ =
m. 2g,

^^l^JlV^_ ^ 2
m..H^ + tii-H^ m^ 3
m. 2g,

where

m m V
\ = Pl*l*l =^ 'l = ^ = -A^

m- ™2'^2
"2 = ^2*2*2 =' '2 = - ^ ° ^

•"3 '°3''3
"3 = P 3 V 3 =^ '3 ' P3A3 A3
134

In the above equations v^ and v« are known and, thus, V^ and V„


1 z 1 2

can be calculated. But, if the state at 3 is saturated, in order to

find v^, quality is needed. An iterative procedure is followed in

which, for the first iteration, changes in kinetic energy is neglected

Thus,
m,H, + m„H,
, _ 11 2 2
3=
H: m_

For the given conditions for run 77:

m. = 270.223 - 152.985 = 117.238 lb /hr


1 m
T^ = 548.96°F 1 H2 = 58.395 Btu/lbn^

P^ = 232 psia J V2 = 0.01608 ft^/lb^j

and for the first iteration:

, _ 117.238 * 1292.3274 + 152.985 * 58.39


3=
H: 270.22

= 593.744 Btu/lbm

First estimate of quality at point 3 is then;

H3 - H^
x^ =
'3 H.
fg

593.744 - 365.719
834.99

= 0.2731

First estimate of v^ is then calculated from:

V3 = Vf + X3 * v^g

= 0.018516 + 0.2731 * 2.0402

= 0.5756 ft-^/lb
m
135

The second iteration, which will take the changes in kinetic energy

into consideration can now be started.

Velocities are calculated as:

V - ""l""! - 117.238 * 2.4746 ,,-.„ , , .^


^1 - A ^ = 693257.3 ft/hr
^ ^^
1 TT ro.277^^
4 12

m„v^
V^ = —— = 5879.82 ft/hr
A2

m V
V = -^-^ = 371713.86 ft/hr
•^ ^3

Enthalpy at 3 is then:

"I'^l + •°2'^2 2
m J
Ho = H H
3 3 2g^

where H' is the first estimate of H_ calculated in the first iteration.

Thus,

117.238*(693257.3)^ + 152.985*(5879.82)^ /Q^T-,-, o oc^^


970 990 (.J/1/lJ.Ob)
H = 593.744 + £AJ^.Z£3
^ 2 * 32.174 * 778 * (3600)
= 593.744 + 0.1084 = 593.852 Btu/lbj^

• u 593.852 - 593.744 ^ ^^
percent change m H„ = CQ^ y, , =0.01 percent.

If the change in enthalpy is greater than 1 percent, the iteration

will be repeated. For the sample problem at hand, iteration will be

terminated at this point. Thus:

H3 = 593.852 Btu/lbni

X3 = 0.2732

v, = 0.5759 ft /Ibm
136
and

1 _ 0.2732 . 1 - 0.2732
yTP 0.03781 0.3244

= 9.46604 (Ibm/ft-hr)-1

-0.25
f^p = 0.0792 GD
y,TP

where

r - 270.223
A 2
645706.83 lbm /ft^-hr
T^fo.277^
H 12 J
Thus,

0.2771-0.25
= 0.0791 645706.83 * 12
TP 1/9.46604

= 0.0040813

The pressure drop between the location of measurement of tempera-

ture and pressure is then calculated by:

2 * f G LV V
AP = ^D ^[1 + X -^^]
^f

2 X 0.004813 * (645706.83) * 7.75 * 0.018516


0.277

[1 + 0.2732 * ^^;?Q2?^] *
0.018516^ 32.174 * (3600)^

= 155.08 Ibf/ft

= 1.077 Ib^/in^

Pressure at the location of temperature measurement is then:

P = 222 + 1.077 = 223.077 Ib^/in^

derivation of P^ from saturation pressure at this point is:


137

"/A • *.- 223.64 - 223.077 ^ _„


/o deviation = 223 Q77 ^ 0.25%

Thus the pressure at this point is set equal to the saturation

pressure.

Pressure at the start of heated section of the coiled tube is

then calculated from equation 5.31 as:

2.0 * 0.004813 * (645706.83)^ * 19.5 * 0.018516 ^


^ 0.277

[1.0 + 0.2732 * -rrj^^] * 9


0.018516 32 -L7^ ^ (3600)^
= 390.22 Ibf/ft^

= 2.71 Ibf/in^

Thus the pressure at the inlet to the coiled tube is:

p. = P ^) - AP
^m sat'3

= 223.64 - 2.71 = 220.93 Ib^/in^

Bulk temperature at the inlet to the coil is then taken as the

saturation temperature at P. . Thus,

T. = 390.23°F
m
«

Since inlet enthalpy is the same as H3 calculated before, the

inlet quality is calculated as:


«3-«f
Xo =
3 H^
fg
where H^ and H^ are evaluated at T as:
f fg i'^
H^
f = 365.3 Btu/lb^
m

H. = 835.36 Btu/lb
fg ^
Thus,
138

^ 593.852 - 365.3 _ ^ .y-^A


""3 835T36 °-^^^^

The same procedure is followed for the calculation of the coiled

tube exit pressure. From Figure 5-6, the locations of temperature and

pressure measurements are at 17.75 and 12.125 inches after the end of

the coiled section, respectively.

Measured exit temperature is 335.3°F for which the saturation

pressure is 110.91 psia. The measured exit pressure is 112 psia. Thus,

% deviation = '^"'"^ 112"^^'^"'" " °*^^^

Assuming that this deviation is small enough to justify the assump-

tion of the saturation state at this point, the enthalpy and the quality

at this location are calculated.

The fluid leaving the test section passes through the condenser.

The enthalpy of the fluid before entering the condenser is calculated

by an energy balance on the condenser as shown in Figure A-2.

Cooling water - out

Two-phase
mixture leaving ^
the test
section © Condensed
Fluid

©
OT©
Cooling water - in

Figure A-2 Condenser


139
Assuming that the heat loss from the insulated condenser is
negligible, one can write:
v/ V 2 V 2 ^2
»4(»4 + 2i-) + "6(«6 -^ 2r> = "4»5 + I T ^ * ^e^^y + 2r>
c c °c °c
or rearranging:
2 o 9 9
"^6 ™fi ^7 - ^A ^q - ^/
^ = ^ » 5 ^ /"4
< »'7 - V-^ ^ /'"(4 2.
^§c )^ 2g^ '
The state of the cooling water at both inlet and outlet to the

condenser is compressed liquid. Therefore, its specific volume and,

as a result, its velocity from inlet to the outlet of the condenser

will not change significantly. Thus with reasonable accuracy, the

second term in the above equation representing the change in kinetic

energy of the compressed liquid is neglected.

As a result,

H, = [H^ +z^(H^ - H J ] + ^ ^
4 ^ 5 m,/"7 "6^^ 2g^

where
™4^4
\ = P4\^ =" ^ = -AT

m V
*4 = P5S^5 =^ ^5 = ^

To calculate v,, quality at point 4 is needed. Again an iterative

procedure is used in which, for the first estimate of H,, the change

in kinetic energy is neglected. Thus,

1 ™fi
H4 = «5 + S7<»7 - V
4
For the given conditions:
140

m,
4 = 270.223 lb m/hr
T^ = 335.3°F

P, = 112 psia

T^ = 94.1°F ] "5 = 62.1997 Btu/lb


m
P^ = 14.0 psia J 3,,.
v^ = 0.0161105 ft^/lb
m

riig = 2832.221 Ibm/hr

T^ = 70.52°F
' H^ = 38.728 Btu/lbni
P,
6 = 38.0 psia
^ )

T = 123.08°F 1
j- H = 91.1687
P^ = 38.0 psia J

and for the first iteration

HJ = 62.1997 + ^270*223 (91.1687 - 38.728)

= 611.833 Btu/lb
m
First estimate of quality at 4 is then:

»4-»f
"^4 ~ H^
fg

^ 611.833 - 306.3838
883.26

= 0.3458

First estimate of v, is then


4
4 f 4 fg
= 0.017819 + 0.3458 * 3.8176

= 1.338 ft-^/lb
m
141

The second iteration can now be performed. Velocities are

calculated as:

'4 = ^^T^^fTTiltP = ^ ° — - / -

Enthalpy at 4 is then:
2 2
1 ^5 - ^
H, = H, + - ^ ^
4 4 2g^
= 611.833 - (^Q9955.95)^ - (4936.17)^
2*32.174*(3600)^*778

= 611.833 - 0.25 = 611.583 Btu/lb


m
percent. change
u m' V! = 611.833 - 611.583 = 0.04%
H, ^ ^,„,

Assuming that this change is small enough, the iteration will be

stopped here. Thus,

H. = 611.583 Btu/lb
4 m
X, = 0.3455
4
V, = 1.337 ft^/lb
4 m
The pressure at the location of temperature measurement is now

calculated.
1-0.25
"GD
f^„ = 0.0791
TP
^TP

where:

X 1-x
^P ^g ^i
and

y^ = 0.38666 lb /ft-hr
r m
142

y„ = 0.0352233 lb /ft-hr
g m
Therefore:

0.3461 _!_ 1 - .3461


y^p 0,0352233 0.38666

= 11.517 (Ibm/ft-hr)^

-0.25
0.277
f^p = 0.0791 645706.83 * 12
1/11.517

= 0.003886

The pressure drop between the location of measurement of tempera-

ture and pressure is calculated as:

. ^ 2.0 * 0.003886 * (645706.83)^ * 5.625 * 0.017819 ^


0.277

[1 + 0.3461 * _ M i Z 6 _ i * ^
0.017819^ 32.174 * (3600)^

= 211.32 Ib^/ft^

= 1.467 Ib^/in^

Pressure at the location of temperature measurement is then:

P^ = 112 - 1.467 = 110.53 Ibj/in^

deviation of P, from saturation pressure at this point is:


4
c ^ . -• 110.91 - 110.53 _ ^ ^,„
% deviation = ,-.Q ^3 = O.J4/i

The pressure at this location is thus set equal to the saturation

pressure. Pressure drop between the coiled tube end point and the

location of temperature measurement is:

_ 2.0 * 0.003886 * (645706.83)^ * 17.75 * 0.017819 ^


^^ ~~^ OTITT

[1.0 + 0.3461 * Jk^.llL] *


0.017819 32.174 * (3600)^
143
2
= 666.84 Ib^/ft

= 4.63 Ib^/in^

The coil exit pressure is thus:

P^^ = 110.91 + 4.63 = 115.54 Ib^/in^

Bulk temperature at the exit from the coil is now taken as the

saturation temperature at P . Thus:


ex
Tex = 338.43°F

and the exit quality is calculated as:

»4-^f
""4 " H^
fg
where at 338.43°F:

H^, = 309.62 Btu/lb


f m
H- = 880.13 Btu/lb
fg m
and

611.583 - 309.62 „ ., .,
^4 = 88033 ^'^""^^

The local pressure at any axial location is calculated by evalu-

ating the pressure drop between the coil inlet and the specified axial

location through appropriate equations as were given in section (5.4).

At each thermocouple station, pressure and enthalpy and, as a

result, other required properties such as bulk temperature, specific

volume and quality are calculated. At the end of this stepwise pro-

cedure the calculated and the experimentally measured test section

exit pressures are compared. If the difference between the two is

less than 1 percent of the measured value, the calculated properties

are accepted.
144

However, if the deviation of the calculated exit pressure from

the experimentally measured value is large, the local pressures, as

were calculated in previous steps, are corrected based on the assump-

tion that the pressure drop model will consistently overestimate or

underestimate the pressure drop in such a manner that the difference

between the actual and the predicted value is a linear function of the

axial position along the tube.

Therefore, if:

DP = P . - P X
ex) ex)
exp calc
Then, at thermocouple station 9:

in which P is the pressure at this thermocouple station as calcu-


U J 11 will

lated from the homogeneous model and L^ and L are the total length
i q "^

of the coiled tube and tube length up to station 9, respectively.

Once the corrected local pressure and enthalpy at each thermo-

couple station is found, other properties are evaluated.

For the example run under study, the calculated exit pressure

from the homogeneous model is found to be 132.81 psia. Thus,

DP = 115.54 - 132.81 = -17.27 Ib^/in^

Pressure at station 9, calculated in a stepwise fashion by the

homogeneous model is 171.14 psia. The corrected local pressure at

this station is then:


PQ = 171.14 + Cll'llr, * 98.58) = 161.5 Ib./in^

Enthalpy at this station is calculated by an energy balance on

the heated portion of the coil, between inlet and this axial location.
145

In this energy balance both the radiative and convective losses are

accounted for. The total heat absorbed by the fluid in this portion

of the coil as computed by the computer program is:

Qg = 1965.06 Btu/hr

Enthalpy at this station is found from:

U _ U J. £
9 in Total Flow Rate

= 593.852 + 1965.06
270.223

= 601.124 Btu/lb
m
Two independent properties at this station are calculated. Other

properties can easily be foimd.

Tg = 364.3°F

Xg = 0.307

In order to calculate the heat transfer coefficient, tube wall

temperature and heat flux should be found. The method outlined in

section (5.2) is used. The necessary boundary conditions are given

as:
T (9) = a + b cos (6)
o
where:

a= (T^+ V / 2
= (385.22 + 371.53)/2

= 378.375°F

b = (T^ - T^)/2

= (385.22 - 371.53)/2
Figure A-3
= 6.845°F Boundary Conditions
Designator
146
q^ce) = p - j l ^ l j

=0 I< 9 < f
where P is the absorbed heat per unit area and time. In calculation

of P, heat losses are also included.

Thus:

P = Incident flux - Radiative loss - Convective loss


4 4
= Incident flux - ae(T - T.-„) - h (T - T,,^)
o AMB o o AMB
where:

o = Stephen-Boltzman constant

e = emissivity of flat black paint

T = wall temperature at the specific angular position (°R)

T.>^ = ambient temperature (°R)


AMB
h = convective heat transfer coefficient for the outside
o
2
surface of the coil (Btu/hr-ft -°R)

Using these boundary conditions along with other necessary infor-

mation, the inside surface temperatures and heat fluxes at different

angular positions are found. The results for three angular positions

are given below.

T
Angular Heat Flux w
position (Btu/hr-ft^) ("F)

9 = 0 6899.53 382.36

9 = Tr/2 4374.27 376.69

9 = TT 1869.04 371.03

Once these quantities are evaluated, heat transfer coefficients

for different angular positions is calculated.


147

''e = 0 = 3 8 2 ! 3 r i i 6 4 . 3 ' ^^^.OS B t u / f t ^ - h r - ^ F

4374 27 9
''e=Tt/2 = 376.69 - 364.3 = ^53.04 B t u / f t - h r - ° F

^9 = ^ = 3 7 l ! o f : ° 3 6 4 . 3 = " 7 . 7 1 Btu/f t ^ - h r - ' F

Nusselt number i s c a l c u l a t e d by:

Nu = -r—

where d = inside diameter of the tube


k = thermal conductivity of saturated liquid

ot- A - n M 382.03 * 0.277


at 9 - 0, Nug ^ Q = 0.3896 * 12

= 22.635

Average values of heat transfer coefficient and Nusselt number

were calculated by finding a mean value for inside surface wall tem-

perature and heat flux for each thermocouple station as:

r2TT
1
T. = T(9)d9
1 ' 2TT
J 0

<2TT
1
q(9)d9
' ^ ' • " 2TT
0

Then the average heat transfer coefficient is calculated from;

F—^L_
(T^ - Tg)

and the average Nusselt number by:

Nu = ^j—
k
148
Using these relations:

h = 352.53 Btu/hr-ft^-°F

Nu = 20.89

Reynolds number at this axial location is calculated from:

?d
Re _ pvd _ A ^ Gd

where G = —mA is the mass velocity in lbm /ft2-hr.

Thus:

G = ^^^-^^^^ = 645706.8 lb /ft^-hr


TT 0.277
4 12
.0.277
_ 645706.8 * ^ 12 ^ , _._. _
^^ Osli = "^2331.7

Radial acceleration in terms of the number of g's is given by

V^
R.
A = R ^.. g
coil^

where

V m = pA
-^ = Gv ft/hr

V, the specific volume is easily calculated and can be shown to

be:

V = 0.88765 ft-^/lb
m
Thus:
^ 645706.8 * 0.88059/3600.0)^
(1.37 * 32.174/12.0)

= 6791.55 g's

Calculations shown here were repeated for all thermocouple

stations. This stepwise procedure will result in calculation of total


149

heat input into the coil which for this example run is calculated to

be 4853.65 Btu/hr.

On the other hand, total heat added to the fluid is also calcu-

lated from:

Q = m(H - H. )
^ ex in
which for this run:

Q = 270.223(611.583 - 593.852)

= 4791.65 Btu/hr

with a percent deviation of:

4853.65 - 4791.65
= 1.29%
4791.65
APPENDIX B

150
151

UNCERTAINTY ANALYSIS

Whenever measurements are made, errors are made. Because no

measurement is free from error, steps must be taken to evaluate the

accuracy and precision of the measurement.

Although the equipment and instruments used were selected with

care and although the measurements were made as accurately as possible,

but as in any experimental work, there is some degree of uncertainty

inherent in the final results, thus necessitating this section on

error analysis.

One of the available methods for estimating uncertainty in experi-

mental results is that of Kline and McClintock [17]. According to this

method, if R is a function of n independent variables, each of which

is normally distributed, then the relation between the uncertainty in

the variables W. and the uncertainty for the result W_ is given by:
1 1^

TT r/9R ^2 ^ M N2 . . /8R „ >»2il/2 f^ . .


\^^dz;^i) -^ ^9^^2) "• '•' ^ ^-^T^n) ^ ^^-^)
1 2 n
where R = R(x-^,X2, •. . ,x^)

This method will be used to estimate the uncertainty involved in

the calculation of the heat transfer coefficient. Calculations will

be performed for the data of sample calculation of Appendix A.

Heat transfer coefficient at any position along the coiled tube

test section is calculated according to the equation:

h =^ ^ ^ (B-2)
w B

where T and T are the tube inside surface wall temperature and the
w B
fluid bulk temperature at the specified location.
152

According to the Kline-McClintoch method, the uncertainty in

calculating h is given by:

w - [f^^ TT ^2 . /9li TT x2 ^ ,8h „ N2I1/2 ,„ ^.


\ - ^^T(Q7AT ^ Q ) -^ < 9 ^ ^T^) + (-8T- ^T ) ^ <^-3)
w ^ B B
where from equation B-2,

8h 1 1
= 0.0289
9(Q/A) T^
w - T^
o = 385.22 - 350.6

9ti _
.__- Q/A _ 6388.8 ^ ._
=5.33 ._ ..
(B-4)
w (T - T^) (385.22 - 350.6)
W D

9ti _ Q/A _

and where W-^, W_ , and W_ are the uncertainties in the measurement

of heat flux, wall temperature and bulk fluid temperature, respectively.

The type of equipment used in these measurements, along with their

stated accuracy, were summarized in Table 3-1.

The uncertainty in the calculation of Q/A at the inner surface

of the tube is due to uncertainties in the measurement of variables

such as:

a - incident flux from the lamp panels upon the test section

b - temperature of the outer surface of the tube

c - ambient temperature surrounding the coil

Incident flux from the lamps were measured and mapped [31] using

a calorimeter with a stated accuracy of ± 3 percent. Both the outside

tube wall temperature and ambient temperature were measured by type

K, sheathed thermocouples with an accuracy of ± 4.0°F or 0.75 percent

of the readings, whichever is larger.


153
The amount of heat absorbed by the test section per unit area
and time is given b y :

''abs = '^Incident " "^K ' ^P^'> " '•,„„^(t„ - t ^ ) (B-5)

According to Kline-McClintock,

^Q, =^^W^\ )'^^^^T)'^<S^^T )'l'^' ^'"'^


"^abs ^^inc ^inc ^ \ \ ^^AMB ^AMB
where
9Q ,
^abs
9Q.m c " ^

^abs , „3
9T = -4aeTW - hconv (B-7)
w
9Q T-
abs , 3
•^ = 4aeT.-^ + h
^^AMB ^"^ ^ ° ^ ^
or
9Q
^ — = -4.0 * 0.1714 * 10 ^ * 0.9 * (385.22 + 460)"^ - 2.0
w
= -5.7258 Btu/hr-ft^°F

^^abs -4 -^
^^ = 4.0 * 0.1714 * 10 ^ * 0.9 * (350.6 + 460)"^ + 2.0
^^AMB
= 5.2865 Btu/hr-ft^-°F
W = 6388.8 * 0.03 = 191.664 Btu/hr-ft^
inc

The uncertainty in measurement of tube wall temperature and

ambient temperature is calculated from:

W = (—) W
T ^9E''^ EMF

where:
W = [(W )^ + (W )'^]'^^^
EMF thermocouple data logger
154

EMF corresponding to T^ = 385.22°F is 7.981 milivolts. Thus:

^EMF = f(0-089)2 + (0.033)2]^/2 ^ ^ ^^3 ^^^^

where 0.089 and 0.033 are the values of EMF corresponding to the un-

certainty of the thermocouple wires and data logger.


9T

"BE^T ^^ ^^^ ^"^^^^ °^ ^^® "^ ^^- ^ ^ ^^^^^ f°^ type K thermocouple
at the measured wall temperature. It is found from thermocouple tables
as:
9T. ^ AT. 386 - 384
9 E ) T ^ AE>385.22 ^ 8.003 - 7.959 = ^5.454°F/M.V.

Thus for T :
w
W
= 45.459 * .095 = 4.315°F
w
Following the same procedure W is found as:
^AMB
W^ = 4.28°F
^AMB
From equation B-6:
1 4. f-i^ 7 9 * /. '3it;\2 1 /c OQ/- 4, /. « o v 2 , l / 2
W = [(1.0 * 191.664)^ + (-5.72 * 4.315)^ + (5.286 * 4.28)"^]
^abs
= 194.57 Btu/hr-ft (B-8)

From equation B-5:

^abs " ^388.8 - 0.1714 * lO"^ * 0.9 * [(385.22 + 460)"^ -

(350.6 + 460)^] - 2.0 * (385.22 - 350.6)

= 6198.28 Btu/hr-ft^

W as calculated above is the uncertainty involved in the


^abs
calculation of the absorbed heat flux at the exterior surface of the

tube. In calculating the temperature and heat flux at the interior

surface of the tube Q , is used. It is assumed that any additional


^abs -^
uncertainties generated as a result of these calculations are

negligible and thus W^ will also represent the uncertainties of q


^abs ^
at the inner surface of the tube.
155

In calculating bulk fluid properties at station 9 of the sample

run under consideration, since the fluid is saturated, bulk temperature

will be the saturation temperature at the local pressure which is

calculated from:

8
^sat = \ Ai[^n(10P)]^ 0.2 < P < 450 (B-9)
1=0
where:

^) = 35.15789

*i = 24.592
2.118
*2 =

*3 = -0.34144

^ = 0.1574

s =-0.0313
*6 = 0.00386
0.00025
*7 =
08 X lO"''
*8 =

According to Kline-McClintock,

9T ^
Tj =
r
rf
/ sat (B-10)
sat
where, from equation (B-9):

9T
sat
9P = ^{J/if^"<^°''^i'}
8 iA. i-l
= Z -pi [£n(10P)]
i=0

substituting for P^ = 161.5, psia and A^ as given above:

9T
sat = 0.3255287 (B-11)
9P
156

Local pressure is calculated by evaluating the pressure drop

through using the homogeneous model and is corrected for the deviation

of the calculated from experimentally measured exit pressure (sample

calculation. Appendix A ) .

Thus:
- P ,
ex) ex) T
exp calc
PQ
9
= P. - AP,
in homo
+ (-
*S^
If for simplicity, it is assumed that the uncertainty in calcu-

lation of P_ is a direct consequence of the uncertainty with which

the inlet and exit pressures are measured, then:

apg 2 ^^9 ^2,1/2


W,
V = [<3P;-"P. > + ( ^ p — ex)
9 m m ex)exp exp
where:
Wp = Wp = ± 2 Ibj/in'
in ex
and

. 2 (B-12)
Wp = ^(2)2 + (^imij * 2)2]l/2 ^ 2.29 Ib^/in
9

substituting B-11 and B-12 into equation B-10:

W = 0.3255287 * 2.29 = 0.745°F (B-13)


sat
where in equation (B-3):

W = W = 0.745°F
B sat
Thus from equation (B-3), we have:
2^1/2
W = [(0.0289 * 194.57)^ + (5.33 * 4.315)^ + (5.33 * 0.745) ]
h
2 o.
= 24.0 Btu/hr-ft -°F

Converting this to the percentage of the calculated value of the


157

heat transfer coefficient at this specific location:

^ 24.0 * 100 ^
h 382.03 •^'^

That is, there is a 6.3 percent uncertainty in the calculated

results based on the stated accuracy of the equipment used.

Of course, this percentage is valid only for the sample calcula-

tion presented in previous chapters. For runs with higher incident

flux, the rate of uncertainty will be slightly higher while in some

other cases it will be lower.

Repeatability of an experiment is also a measure of the accuracy

with which the data are taken. In order for a set of data to be

valid, the experimentor must be able to reproduce his data if necessary.

During the course of this study, a few runs were selected randomly,

and it was tried to reproduce the inlet condition to the coil as close

as possible. Although the inlet condition in most cases is a function

of several variables such as pressure, temperature and quality of the

mixture, and it is almost impossible to exactly reproduce a given con-

dition at the inlet, but the final results were very close to each

other and certainly within the bounds of the error limit set above.

In Table B-1, the conditions for two such runs are reproduced.

The experimental results for the heat transfer coefficients at 9 = 0°

and 9 = 180°, as well as the bulk fluid temperature along the test

section, are shown in Figure B-1 and B-2.


158

TABLE B-1

Experimental- Conditions for Runs 51 and 71

Run #51 Run #71

Mass Velocity, Ib^/(hr-sq.ft) 459189 464592

Pressure, psia 62.6-43.2 67.0-44.5

Temperature, °F 295.5-271.95 300.0-273.7

Radial Acceleration, g's 241-9200 184-8665

Incident Heat Flux, Suns 101 101


159

650

600

400 - 550

350

300

O Heat transfer coefficient, 9 = 0 ° , Btu/hr-ft -°F


2
_ ^ Heat transfer coefficient, 9 = 180°, Btu/hr-ft -°F
250

<> Bulk fluid temperature, °F


I I •I I J.
6.62 8.38 10.14 11.9 13.66 15.42
3.1 4.86
Quality (%)

Figure B-1 Experimental Results, Run 51


160

650

600

400 550

350 -

300

O Heat transfer coefficient, 9 = 0 ° , Btu/hr-ft -°F

250 ^ ^ Heat transfer coefficient, 9 = 180°, Btu/hr-ft^-°F

<> Bulk fluid temperature, °F

2.8 4.57 6.34 8.11 9.88 11.65 13.42 15.19


Quality (%)

Figure B-2 Experimental Results, Run 71


APPENDIX C

161
162

TEST ON SOLUTION METHOD

The heat conduction equation in the form presented by equation

(5.4) is an elliptic partial differential equation in two dimensions,

which essentially requires specified boundary conditions on the closed

boundary.

If, on the other hand, the heat conduction equation is written in

terms of heat flux values, for the case of steady-state, two dimension,

this equation becomes:

^(rq,) + ^ ( q g ) = 0 (C-1)

where:

9T (C-2)
^r = - k r 9r

9T (C-3)
^9 = • r 99

presented in this form, the above equations are hyperbolic equations.

The given boundary conditions for these sets of simultaneous equations

are:

T(r = R^,9) = 0(9) (C-4)

q (r = R ,9) = ^(9) (C-5)


^r o

The procedure for solving these equations can be stated as follows:

1 - substituting (C-4) into (C-3):

k
= - -?- ^ (C-6)
^9 r=R R d9
o
o
163

2 - using (C-6) in (C-1), at r = R :


o
_9_ _^ di
IF^^^r) ^ ^ 99*^ R d9^ "
r=R o
o
or:

(C-7)
97^^\> r=R
R 99^ 9 d9''
o
o

The above equation written in finite difference form becomes

(rq^) - (rq^)
r=R R -Ar
o
Ar R 99'''^9 d9''
o

or:
R
o Ar 9 (k ^ )
\r) R (R -Ar) 99' 9 d9
R -Ar • ("^o-^ o o
o

R H'(9)
o Ar 9 d^. (C-8)
(R -Ar) R (R -Ar) 99' 9 d9
o o o

3 - Equation (C-2) at r = R - dr

_9T
= -kr 9r
R -dr R -dr
o o
or:

_9T
9r
R -dr
ir^r R -dr
o o

substituting (C-8) into the above equation:

, R ^(9)
9T = _ _L{_2—;^_^ " R_(R^-Ar) 99'"9 d9 ""' A(K t)}
9r k (R -Ar) o o
R -dr r o
o
164

or, in finite difference form:

- T
R R -Ar , R ^(8)
O ^ 1 r O Ar
Ar —(k ^)}
k^'(R^-Ar) R^(R^-Ar) 99^*^9 d9

and finally:

Ar
R -Ar —(k ^)} (C-9)
o r o Ro (Ro-Ar)
^ 99^*^9 d9

Therefore, by using the above set of equations, temperature and

heat flux at the nodal points on a ring of radius R -Ar are found. By

repeating the steps outlined above, the temperature distribution through-

out the tube wall thickness is found. The solution method as outlined

above is a non-iterative procedure, except for the fact that the material

thermal conductivity is temperature dependent.

In order to prove that the above procedure will actually result in

a unique solution, a test on the method was performed. Initially, two

arbitrary functions representing the tube wall temperature at r = R and

r = R were chosen. The functions selected for this sample problem were:
i
T +T T -T„
T^(9) = - ^ ^ + - i ^ * cos(9) (C-IO)

T +T T -T
T.(9) = ^ 2 - ^ + ^ 2 " ^ * cos(9) (C-11)

where:

T, = 281.0 °F

T^ = 266.0 °F

T^ = 255.0 °F

T, = 240.2 °F
165

The tube wall was subdivided into four divisions in the radial and

eight divisions in the circumferential directions. Nodal temperatures

as well as the heat flux at the boundary nodes were then calculated.

The results of this part of the calculations are shown in Table C-1.

Once the nodal heat flux values on the exterior surface were found,

these along with equation (C-10) were used as the boundary conditions

expressed by equations (C-4) and (C-5) and the procedure outlined pre-

viously was used to once again calculate the temperature distribution

and the nodal heat fluxes on the interior surface. The results of these

calculations are shown in Table C-2, which compares very favorably with

Table C-1.
166

TABLE C-1

TEMPERATURE D I S T R I B U T I O N INSIDE TUBE WALL THICKNESS

GIVEN BOUNDARY CONDITIONS:

TEMPEATURE D I S T R I B U T I O N ON THE OUTSIDE SURFACE

TEMPERATURE CISTRIBUTION ON THE INSIDE SURFACE

ANGLE(OEG) 0 45 90 135 180

RADIUS(IN. )

0.1875 281.00 273.80 273.50 268.20 266.CO


0.1753 275.17 273.13 268.19 263.25 261.21
0.1630 268.95 267.05 2 62.4 8 257.91 256.C2
0.1508 262.25 260.51 256.31 252.12 250.38
0.1385 255.00 253.42 2 49.6 0 245.78 244.20

f-EAT FLUX AT THE EXTERIOR SURFACE < B T U / F T * F T*HR)

53 8 0 3 . 3 6 52314.01 48730.27 45163.02 43690.25

TOTAL HEAT INPUT AT THE EXTERIOR SURFACE (BTU/HR.)= 0.239245D 04

HEAT FLUXT AT INTERIOR SURFACE (BTU/FT*FT*HR)

71215.21 69678.08 65975.99 62286.69 60762.28

TOTAL HEAT INPUT AT THE INTERIOR SURFACE (BTU/HR.) = 0.239247C 04


167

TABLE C-2

TEMPERATURE D I S T R I B U T I O N INSIDE TUBE WALL THICKNESS

GIVEN BOUNDARY CONDITIONS:

HEAT FLUX ON THE OUTSIDE SURFACE

TEMPERATURE DISTRIBUTION ON THE OUTSIDE SURFACE

ANGLE(DEG) 0 45 90 135 180

RAOIUSCIN.)

0.1875 281.00 278.80 2 73 . 5 0 268.20 266.CO


0.1753 275.17 273.13 2 68.19 263.25 261.21
0.1630 268.95 267.05 262.48 257.91 2 5 6 . C2
0.1508 262-25 260.51 2 56.31 2 5 2 . 12 250.38
0.1385 255.00 253.42 2 49 . 6 0 245.78 244.20

HEAT FLUX AT THE INTERIOR SURFACE (BTU/FT*FT*HR.)

71216.77 69678.67 65975.30 62284.30 60759.95

TOTAL HEAT INPUT AT THE INTERIPOR SURFACE ( B T U / H R ) = 0.239245C 04


APPENDIX D

TWO-PHASE HEAT TRANSFER DATA

168
169

522

534
exit

548

540
566

464

459

548

542

510
546
UO

441

490
485

500
464

493

496
519
0 00
~a
CN
U
r-f

JZ
^^
3 4-1
410

403
Inle

413

388

406

338

340
312
359

430

422

393

390

390

393

430

431
402
395
kiyl
OQ

4J ro so o UO ro NO r^ 0\ r^ o CO 00 NO ro l-H p^ p~ -a
/—\ •H ON ON
8«« x: CN NO UO NO ro NO O 00 NO NO o NO o O ON o CN fNl vO NO
1-H CN UO iH CN
a vO ro -a ro -a- -a NO r^ ~a ^H CN -a P^ CN

4J
iH
T—^

4J
« lU ro UO O -a- r^
3 NO • ^ 00 00 UO CM -a 00 r^ NO -a -a P^ -a -a
I-H
cr C UO 00 r>. o >a NO Ov NO o\ 00 ro _ -a CN O CM <r UO 00 NO
TH 1—1 NO CSI CN CN CO CO
•a- r^4 1-H ND NO ro 1-H NO l-H

4J ro f^ NO ro <JN <r 00 ON <JN (y-. NO 00 p~ ro NO -a ro -a- NO ^


TH l-H f-^ l-H 00 NO l-H 00 UO NO ON p^ CO CN p— CN
ro
l-H
o NO -a o
X CN ro ro f—I I-H CN CN ro CN rsi CN l-H CN ro I-H
^•v
OJ
(0
psi

N—*'

CU 4-1
lU 00 -3- 1^ ^H CJN r^ NO P^ CN UO r^ ro -a ON -a
.-H ON UO CN CN r— ON o
NO
UO O CN Pv ON
CN
UO
00
(N ON ^H r^
vO
,-^
c 1—'
ro UO UO CO CM 1-H 1-H
-a -a -a -a -a r- CN ro
^-
UO
^H
CM
•H ^

4J -a- O o c 00 •a- ro NO ro -a- UO -a UO -a ro CN 00 CJN CN 00


iH -a- -a o UO CM CN NO NO -a- -a ro ro r~ UO O 00 00 CM o ON
o
• X rsi -T l-H CNJ iH OO 00 u-1 Ol UO CN CJN -a r~ l-H ro UO NO C^N p—
o OJ UO oc r^ rvi 00 NO NO o NO ON o <r ON -a CN o ON
ON
f-H r-j l-H 1-H 1-H CN « ro -a
^ rM -H
< ^^ ""^ '"
CO
•H
T) 4-1
CO Oi •J- r~ ON ro p^ CN 00 r» -a UO ^H CM NO CM UO ro 00 ON P^
Oi >-H r^ «
o O UO X. <r o ro NC P^ NO <r ro r^ O -a ON NO
C UO ^—
O -a 00 NO p^ ro ON O o
^-
OO o UO r^ O CO UO
•H CN UO 00 CN CN ro CM -a
^- -a
^-
-a
NO
CO p^ l-H
-a
t—1

4-1 -a- NO CN NO -a 00 00 00 NO 00 ro ro r-j NO ON CSI CJN CN 00


UO UO 00 CO UO l-H ON CN
•W -a 00 O -a- ~a <T O o -a o o o
X -a- 00 O 00 ro I-H <7N o 00 •<r 00 l-H 00 r~ r» <?1 UO o
(U <r -a- ,—1 CN u-i O NO NO ^
uO NO r-> 00 o o 00 O 00 ro o UO
i-» 00 ON ON NO ro ro CN F-H
o O o CJN OO 00 ND NO r^ -a -a
(U

4J p^ i—H ^_ -a- ro ON ro CNl •a- <r ro CO 00 CN vO UO ,— UO NO 00


<u ON NO o Ov CM -a ON 00 T—\
O CNI O r~ >o r-« O ro ON o ^H
r- C7N 00 l-H UO P^ 00 CN NO -a CN NO P~ ro o r^ CJN
I-H
c
UO
I-H f-H CN •a- CO
1—I

l-H o p~ r^ ON O
^-
^H CJN 00 r~ p^ ro -a o
•H 00
<•
CJN o o r^ ro -a ro 1-H 1—1 CN O o> ON NO r- 00 -a UO
f-H - l-H

>.
4-1
TH IH
O 1 ON CO UO ON r^ o sD NO UO r- NO -a o NO rM ro ON ON .— UO
r—^ NO I-H CN CN 00 UO NO NO ON ^H ON
o CN ND ON ^ 00 o o NC
-a
4J r«^ <t CN NO o I-H UO 00 ro ON -a 00 -a o CN
f-H
00 NO 1-H
CN UO ^ UO CN CO 00 00 UO P—
> Vb- CO ro
<T^
00
NO
CO
00
r-
uo
ro
00
CN
ON
-a-
P-. O
NO
l-H O
O
O
ro
O ON ^H NC UO UO -a CN
00 ON
CO ^H CJN UO UO -a rO -a -a -a CN CM CjN ON r^ P--
f-H
^H 1-H 1-H l-H ^H ^^
rH
CO
l-H
^H ^H 1—1
^
IB
s

)H
X x:
3 1 t~-
r—1 CN o
U. 4-1
ro
4J "o.^ CN
(0 3
4-1
01
a: la
Run

ON UO NO ON CN r-
=»= -a UO NO r-. O I-H CN UO OO
CN CN CN CN r^ r^ ro ro
f—' 1-H
1-H

sun^ 3SBqd-oMi.
170

Cb 4-1 x> l-H O p~ UO (JN rH •<r NO ro UO r^ P-. ON m o NO vO 00 CN


o •H
*-" 1-H P^ UO O c^ r^ l-H
o 00 OO ~T CN ON O p^ UO -a l-H CM
X UO UO -a -a- UO -a -a ro ro <r m UO -a -a -a- Ul
CN <• •^ ^ -a
u QJ
r-f

j=
-^
3» 4-1
4-1 OJ 00 <JN 00 r^ ro f-^ CJN vO UO cn ^H O NO r^ O r-- ro r^^ ro P^
0 l-H cn ON p~ -a l-H UO O 00 NO >a ON CJN p-- -a- (n o 00 r^ UO ~T
-a CO m ro -a ro ro ro ro CN cn m c^ -a ro m ro -a
c <^ -3-
•H

4-1 UO ^H ro NO 00 CJN O NO ON ro -a NO UO 00 CN OO OO UO NO
/r-S HH
9>e X ON UO ro O CN ro cn ro
o
NO -H
o NO
in CN NO
NO UO
CN
UO
UO
r^
cn
l-H
CN
ON CN ON
rH
ro
^~' OJ -a ro vr -a- I-H
-a ^ ro l-H -a
4J
HH
1-H
-J
^
3 OJ 00 ~a nH r». ro 1^ CN UO -a r>- r»
C 1—1
o 1—1 00 CO vD CN CM P^* p^

c ON -H UO ro 00 ro r-» CO cn CN ro i-H UO o CJN fn CM O -a -a


•-H
ro UO CN CSI -a -a ro CN m ro CM ro
1
<•
^^ <—t

UO
4-1 00 O CN OO NO ro • -T OO NO UO 00 •£> UO <T XI -a P>. p^» UO
-H X -a UO -a O O 00 l-H ON -a- ^H p~ ON rr 00 NO
X rM l-H <T
NO
-
l-a
H -^
CN rH
NO
f-H CN
.^s 11
I—f
-^ ^^ f-^

^- f—1

CO
HH
7)

^^
BU i-l in
V OO UO ON CN ro ON CN P-. ON r^ 00 CN UO OO
CN 1—1 —
o

ON CO ON r«. r^^
r—1
NO ^- ON r— NO ON x>
I-. OO CN o
-a-
— -o <a CN o
CN o NO
rM rH 1-H
ro m CN r-{
-a-
NO ^H
^^
1-^
•rH

.J •••O rM ON C-M 00 UO o <m o ON p-» r~- <r O O ro rM


• •rH CO —1
o NO 1—1 UO -a UO r~. UO CN ro •x 30 00 <r m vO UO vO
o X •a- CO ^H P-» OO rM UO r~ -a CM UO ON 00 ON \0 ro OO NO 00
y u LlO uO r»
o
UO ro ON CN ON •XI <T cn CO rH
r^ -a rM
^ r^ o
CN ^^ CM o NO CN
< ^" "* ^^ ^^ '""' ' ' ' ' '^ ^* '"'
1
! '^
-J
' — 11 -a- -a- -H 00 CN O ON UO CM M 00 r^ ro O ^O m UO
1 ^ cn
NO
-a —
vO 00 UO UO CN ON ON ON ON O «
ro CN ^T NO O
1 ^ ^
p~- -M
00
-a- CN P~. 00 ON r^ CN CM r-» CN -a CN CN o -a CN
•rH ^ ro <r CN CSI o -a- (n 1—1 •^
-a CN ro ro CN o
^ (^

iJ ON «T p^~ ON o CJN NO 00 ro CN ON r-* CN O -T 00 CN


UO ON -a UO CN I— ro NO CN ON -a UO CN •XI
•^
X
XI CM
"J o
CO
•a'
•JS
cn r~ CM CO <r —4 sO ro o
CM UO -a UO ro UO UO o
ro
V O 3 r^ r~ <r M vO ^H UO sO -a ON UO MJ
JO
UO
UO
00 VT
CN ro ^
CN o
CN CN CN ^4 —
CM m m ro UO UO in <a <r r-»
<•
QJ
1 °^
LJ CO 00 _^ ^ -a CN UO -a CM UO 00 UO l-H O M CN •<r 00 ro <r
V 00 00 p-* rM ro 00 —4 OO UO CN uO OO p-- CN 1—1 00 CN UO CJN -a
l-H vO NO NO CN rr ON
I p^^ ro ro 00 r^ •JS -a <r ro cn O -^ m
~a -o -a OO CN I-H r-< P^ m ro UO CN ro UO CJN in
^ sD CN
cn CM CM ro ro CN CN <r
^-
-a ro vO ND —*
vD uO -T 00
-^ UO NO UO ^

>^
U
•rH u
Veloc

1 •J- L/-1 30 CJN CN <r ro ON CO -a •o ro ON UO o ^ vO O c; -a-


757031

CN UO UO ro XI X)
rM
u X> ON Ol
UO o O C^J CN ro -a -a X O X "iZ
728;

OH 1— ON ON ON
o I-H o ON CN UO ^4 •J- ON ro ON
^
-O UO P~ ^o U-1 ON Ol x> CO I-H O
•J) ^~'= r~- o UO -a- -a
CN -a -a -a <• UO UO UO p^ 00 OO 00 30 o
•n J3~ UO
n l-H
X.

u
3
CN
T f-~ -a
lit l-l
o
ro vO
4-1 , f-J CN
03 3
4-1
ii ca

5 -a •o p~ ON O -o <r 00 CJN o in
-a UO
UO UO
p>.
UO
X
u-\
ON
UO X X X
vT u-1 UO
ro ro m cn <r -a' <r <r

sun-a a s B t i d - o " !
171

CJN ON r^~ ON CN CN 00 NO vO (^ rM rt r^ rH CN ^
^ CN sO CN rH ON CN O P^ 00 CN r^ ro rH ^7- rH ro
o -a -a -a CM <• -a CN ro CN cn cn ro ro ro cn ^
II

I
u
J:

3
4J 3J o CM NO UO o -a -a- 00 CN CN CN —« CN NO ON 00 CJN
CX3 i ^ 00 rH CN o UO UO v3- CN r^ rH X) 00 ro 00
c -a- cn m CN m ON
CN CN CN CN CN CN
NO
CN o
CM
CN ro ^ ro m

CJN ro O ON rH P^ —1 rr

X 00 UO -a -a -3- m ON NO UO -a CON
ro -a -a-
9) ro ro m UO rM ro CN cn rM fM NO NO

-a UO NO m UO ON

00
CN d 00
CN CN
P^
CN
m OO
-a
-a
CN
CM CN
ro
CJN
r-i
O 00 UO r— ^« CM
NO
CJN
UO

CM NO r- NO UO — r^ cn r- UO f^ NO ro
-a 00 O r-i ~a ro 30 O CN P^~ O
CM CN t-l .—1 CM

•n

V o o ON CN P^~ CN CN CM r- <JN -a CM O CN UO (JN


00 cn NO CM CM NO NO UO P^* NO -a ON O NO NO ON O
m CM CN CN ro CN ro ro m

r-. -a ro CN ON O »
CJN
O
O
X
O CM
P~ o
uO
O
CO
vO
O
OO
r^ ON ^^
UO
NO
NO
1-4
(JN -a -a- in r~ -a UO
•J O ON o CJN r-
<r ro -a 00 CM ro NO CM O CJN CM
^ x:
o
ON -a- ro
1—1
r^ <a r^ o
—N ro l-H
o •—' 00 -a UO OO ro
<

UO 3 ro -a vO CJN CJN UO r-i r-


_
r-«
-r
X
OO
UO
r~*
UO X
NO
CM <r NO CN 00 r» CJN ON -a CN ON
ON O ^
ro UO cn r^ in CN CM -a UO CN r- NO UO ON C5 CN
CM ro ro ro UO m cn CN m CM CN o UO

m CM m ON UO ON p~
o ON O
ro r-~ 30 ^ UO O 30 CM CM
X
CN
X> vO o
C7N P-.
—- ND P-. 00 CJN CN r» UO —
-a 00 UO Ol UO CM cn CN 30
•£>
NO
ON
cn o
cn uO -^
UO m X UO 1— NO 00 r^ ro

in JO <T r~ CN M « UO CN r— t-~ r^ • ^
o -a UO o o
ON p~
I ^
X X 30 m CJN ON cn O CM in NO P-- UO ^4
— ^
o
X X JO r-< CN X 00 CN r- O -^ •<T
-a CN r->
m o
cn
m
X
m
r^
rr^
CM o
ro
UO
-a
3
<r
m
ro
CN
NO
»
UO
CN
-a ^
r»-
P^~
X
UO
30
O
00
X
sO
o
30 <r -a

CJ CN UO CN ^4
X CN X X ^ _ X P-. CM O ON ON UO
O X UO UO UO X CN ro 1— r-
-a
o
ON o r-- O O o
30 r"^ ON -a- X ON -a -a- •^ ^ <r
V ro
UO
uo O o
r^ O UO (ON ON -r
-a r~ X
^ ^^
r^
UO
~a -a
ON
-a
<r
ON ON m CM -a -a UO p- X
>
CN
O
vO
-a -a sO
00
P-. p^ P— ON ON ^
c: vO X5
o o — '^ ^'
cn
cn
rj

- I -a X
— C-J X X
X ro
NO
X
-J • ^ CN
-3 "
1) -J
32

vO r-- NO r^ ON 0 CN ro X! r-* X 0 X ON
— ^^
2: XJ —~
p~ 1— P-- »
p-« P-- X -^
X X W
<T
X X X X ON —
ON ON ON
^o

sun-^ 3SBq^-ortX
172

CJN CN p^ rH NO
ON UO X X
UO -a
NO o
p~ NO NO
^o

I
u

3
4-1 >a NO cn l-H ON rH
cn X CM UO CJN P*.
OQ <r -a- ^ -a ^ -a
IX

m NO UO O CN
N.r' UO ro CN
UO -a- cn

o ON CN —1 NO ON
UO -a *a" ro CN r^

CM M r-l ro cn o
O CM UO ON ON CJN
CN CN CM CN CM CN

CO
•H
cn

3 NO O UO NO O
(3 CN CM
m
o
cn
m
ro ro •—<
m m

o X ON ^ - a r~
3 rr
m p-»
CJ
^-i

o X r—^ rH X) ^^
X
r^ UO CN X
<
-J
o -^

-o
X.
o o r-»
CON ON
X
UO
p-»
ON
o
o
o ro CM CJN
-a UO

— ON CN \0 X p^
UO ON r^ p~. ON p>.
ON X CN X rt UO
X o CM CM - a CM
ro <r -a- -a -a
u
ac:

ro vT O UO r-.
m o ro r-» -a
X UO vO rt CN
CN ro -a -a uo ro
-a -a -a- -a <T -a

rt u
0 T CM X3 X
CM
r-^ ON X
CN
rt CN C-3 ro ro ro
QJ iJ CM ro NO
<
X
r P-* -a
UO ro
-
O
a- Ol
> '-^ UO •X p^ X) X UO
•J) i UO UO UO UO UO UO
•n -D
CO -^

X —
3 I
— CM X
X

03 3
1) 4J
3: ca

O •—' CN UO
3 CD O
~a O
o

suny ssBqd-ortj.

Potrebbero piacerti anche