Sei sulla pagina 1di 2

TD 44-661-1A

Technical Data
January, 2001

GUIDELINES ON BUSHING DRAW LEAD APPLICATION

The following guidelines apply to O Plus C TM bushings manufactured by ABB Power T&D Company Inc. For
draw lead application, the maximum continuous current rating of the bushing is limited to the rating stated on the
bushing nameplate. The maximum current in the draw lead , however, is limited by the size of the cable selected
by the transformer manufacturer as the draw lead is an integral part of the transformer. While choosing the cable
size for the draw lead, care should taken so as not to exceed the rating stated on the bushing nameplate.

Many factors contribute to the temperature rise of the cable e.g. current, cable size, cable paper thickness, top oil
temperature rise and it’s level. This document only gives guidelines and it is the transformer manufacturer’s
responsibility for correct application of the draw lead.

Draw Lead Cable Rating

The following table lists maximum continuous current ratings for different sizes of stranded copper cables for
draw lead application in O Plus C TM bushings. These ratings are based on draw lead temperature rise tests
made on 69 kV to 245 kV bushings.

Bushing Rating Draw Lead Cable Size Maximum Continuous Current


kV MCM mm²* Amps

Up to 72.5 167 84.6 265


250 126.7 350
300 152 400

115 to 145 450 228 440


800 405.4 670
900 456 750
1000 506.7 800

161 to 245 1000 506.7 650


2 x 450 456.0 700

* Equivalent area in mm2

To minimize cable insulation loss of life during overloading of transformer, choose a suitable cable with current
capability of at least 20% above the rated current of the transformer.

The above ratings are based on the following conditions.

1. Maximum ambient air temperature of 40o C, and an average of 30o C over a 24 hour period as per the IEEE
Standard C57.12.00 - 1993
2. Maximum top oil temperature rise of 65o C above ambient air as per the IEEE Standard C57.12.00 - 1993
3. Maximum cable hottest spot temperature rise of 80o C above ambient air.
4. Maximum external bus or cable temperature rise of 30º C above ambient air.
5. Maximum radial insulation (thermally uprated) per side of 0.031 inch or 0.79 mm on the cable.

ABB Power T&D Company Inc.


Components Division ABB
TD 44-661-1A Page 2
Technical Data
January, 2001
Overloading

For calculating the cable hottest spot temperature rise, use Equation (1) of the IEEE standard C57.19.100 -
1995. The use of this equation requires thermal constants. Please contact ABB Alamo or your local ABB
representative for these constants. For limitations and other loading guidelines, refer to C57.12.00 - 1993, C57.91
- 1995, and C57.19.100 - 1995

Short - Time Current Withstand

The short time current withstand of the cable can be calculated by using the method given in Section 7.6 of the
IEC standard 137 - 1995. The maximum short-time hottest spot temperature rise of the cable should be limited
to 180 o C.

Technical Support
If a technical question arises regarding the product detailed in this Technical Product Literature contact:

ABB Power T&D Company Inc.


Components Division
1128 Highway 412 S.
Alamo, TN 38001-3813 USA

Phone: (800) 955-8399


(901) 696-5561
Fax: (901) 696-5269

Comments
ABB Power T&D Company Inc. continually strives to make its instruction literature current, accurate, and easy
to understand. Suggestions to improve this document may be sent to: Literature Coordinator fax (901) 696-
5269 or use the above mailing address. For a reply, please include name, company, phone number, and/or fax
number.

DISCLAIMER OF WARRANTIES
AND LIMITATION OF LIABILITY

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, REPRESENTATIONS, OR WARRANTIES, EX-


PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PAR-
TICULAR PURPOSE OTHER THAN THOSE SPECIFICALLY SET OUT BY AN EXISTING CONTRACT BE-
TWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF SELLER. THE
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXISTING
AGREEMENT, COMMITMENT, OR RELATIONSHIP.

The information, recommendations, description, and safety notations in this document are based on our experi-
ence and judgement. THIS INFORMATION SHOULD NOT BE CONSIDERED TO BE ALL INCLUSIVE OR
COVERING ALL CONTINGENCIES. If further information is required, ABB Power T&D Company Inc. should be
consulted.

NO WARRANTIES, EXPRESSED, OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICU-


LAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR
USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, DESCRIPTIONS
AND SAFETY NOTATIONS CONTAINED HEREIN. In no event will ABB Power T&D Company Inc. be respon-
sible to the user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect,
incidental or consequential damage or loss whatsoever including but not limited to damage to or loss or use of
equipment, plant or power system, cost of capital, loss of profits or revenues, cost of replacement power, addi-
tional expenses in the use of existing power facilities, or claims against the user by its customers resulting from
the use of the information, recommendations, description, and safety notations contained herein.

Potrebbero piacerti anche